HomeMy WebLinkAboutEVALUATION REPORTENGINEER EVALUATE EVALUATION REPORT Polyglass USA, Inc. 1111 West Newport Center Drive Deerfield Beach, FL 33442 (954)233-1230 SCANNED BY St. Lucie County TEST CONSULT NEMO I etc. CerWcate of Authorkatlon 432455 353 Christian Street, Unit #13 Oxford, CT 06478 (203) 262-9245 CERTIFY Evaluation Report P12060.02.09-1124 FL5259-R28 Date of Issuance:02/24/2009 Revision 24: 01/24/2018 SCOPE: This Evaluation Report is issued under Rule 61620-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code sections noted herein. DEscRiPrloN: Polygiass Roof Underlayments LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the product(s), the Quality Assurance or the production facility location(s). NEMO Ietc. requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMOletc. Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPEcrION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for Inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 14. Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59266, Florida DCA ANE1983 The facsimile seal appearing was authorized by Robert Nleminen, P.E. on 01/24/2018. This does not serve as an electronically signed document. CERTIFICATION OF INDEPENDENCE: 1. NEMO Ietc. does not have, nor does It intend to acquire or will It acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. NEMOI etc. is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial Interest In any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial Interest in any other entity involved in the approval process of the product. S. This is a building code evaluation. Neither NEMO I etc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. ONEMOletc. ROOFING COMPONENT EVALUATION: 1. SCOPE: Product Category: Roofing Sub -Category: Underlayment Compliance Statement: Roof Underlayments, as produced by Polyglass USA, Inc., have demonstrated compliance with the following sections of the 6'" Edition (2017) Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Prone Standard Year 1504.3.1 Wind Uplift FM 4474 2011 1504.3.1 Wind Uplift UL1897 2012 1507.2.3/ 1507.1.1 Physical Properties ASTM D226 2009 1507.2.4/ 1507.1.1,1507.2.9.2 Physical Properties ASTM D1970 2015 1507.3.3 Physical Properties FRSA/TRI April 2012 2012 1507.11.2 Physical Properties ASTM D6164 2011 1507.11.2 Physical Properties ASTM D6222 2012 TAS 130 Accelerated Weathering ASTM D4798 2011 3. REFERENCES: Enti Examination Reference Date FM Approvals (TST 1867) Wind Uplift 3004091 01/12/2000 PRI (TST 5878) Physical Properties PRIO1111 04/08/2002 PRI (TST 5878) Physical Properties PUSA-005-02-01 01/31/2002 PRI (TST 5878) Physical Properties. PUSA-013-02-01 12/23/2002 PRI (TST 5878) Physical Properties PUSA-013-02-02 12/23/2002 PRI (TST 5878) Physical Properties PUSA-013-02-03 12/23/2002 PRI (TST 5878) Physical Properties PUSA-018-02-01 07/14/2003 PRI (TST 5878) Physical Properties PUSA-028-02-01 07/13/2005 PRI (TST 5878) Physical Properties PUSA-033-02-01 02/12/2006 PRI (TST 5878) Physical Properties PUSA-035-02-01 09/29/2006 PRI (TST 5878) Physical Properties PUSA-055-02-02 22/10/2007 PRI (TST 5878) Physical Properties PUSA-061-02-02 01/28/2008 PRI (TST 5878) Physical Properties PUSA-076-02-01 02/22/2008 PRI (TST 5878) Physical Properties PUSA-083-02-01 04/14/2008 PRI (TST 5878) Physical Properties PUSA-088.02-01 07/29/2009 MTI (TST 2508) Physical Properties 1X20147A 04/01/2008 MTI (TST 2508) Physical Properties RX14E8A 01/29/2009 ERD (TST 6049) Physical Properties 11752.09.99-1 02/08/2000 ERD (TST 6049) Wind Uplift 11757.08.01-1 08/13/2001 ERD (TST 6049) Wind Uplift 11776.06.02 01/16/2003 ERD (TST 6049) Physical Properties 02200.07.03 07/14/2003 ERD (TST 6049) Wind Uplift P1740.01.07 01/04/2007 ERD (TST 6049) Physical Properties P5130.04.07-1 04/21/2007 ERD (TST 6049) Wind Uplift P9260.03.08 03/21/2009 ERD (TSr 6049) Physical Properties P13450.08.09 08/13/2009 ERD M6049) Wind Uplift P30540.11.09-R1 11/30/2009 ERD(TSr 6049) Physical Properties P13030.11.09-1 11/30/2009 ERD (TST 6049) Wind Uplift P11030.11.09-2 11/30/2009 ERD (TST 6049) .Physical Properties P31030.11.09-3 11/30/2009 ERD (TST 6049) Physical Properties P33360.06.30 06/25/2010 ERD (TST 6049) Physical Properties P33370.03.11 03/02/2012 ERD (TST 6049) Physical Properties P33370.04.11 04/26/2011 ERD (TST 6049) Physical Properties P37300.10.11 10/19/2011 NEMO ETC, LLC. Evaluation Report P12060.02A9-R24 Certpwlt ofAur4mhuMn P32455 e EDITION (20171 F13C NON-HVH2 EVALUATION FLS259•R2a Revision 24: 01/24/2019 Polyglass Roof Undedaymemsl (954) 233-1230 Page 2 of 14 OMEMO I etc. Enti Examination Reference Date ERD (TST 6049) Physical Properties P40390.08.12-1 08/06/2012 ERD (TST 6049) Physical Properties P40390.08.12-2 08/07/2012 ERD (TST 6049) Physical Properties C41420.09.12-3 09/11/2012 ERD(T5T 6049) Wind Uplift P39580.03.13 03/04/2013 ERD (TST 6049) Physical Properties P45370.04.13 04/26/2013 ERD (TST 6049) Wind Uplift P1738.02.07-R2 04/29/2013 ERD (TST 6049) Wind Uplift 11757.04.01-1-R1 04/30/2013 ERD (TST 6049) Wind Uplift P41630.08.13 08/06/2013 ERD (TST 6049) Wind Uplift P31751.05.03-R3 11/26/2013 ERD (TST 6049) Wind Uplift P11781.11.03-R1 11/26/2013 ERD (TST 6049) Physical Properties P45270.05.14 05/12/2014 ERD (TST 6049) Physical Properties 6020.(Y7.14-1 09/08/2014 ERD W 6049) Physical Properties 6020.09.14-2 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-3 09/08/2014 ERD (TST 6049) Physical Properties 5020.09.14-4 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-5 09/08/2014 ERD W 6D49) Physical Properties 6020.09,14-6 09/08/2014 ERD (TST 6049) Physical Properties P46520.10.14 10/03/2014 ERD (TST 6049) Physical Properties P43290.10.14 10/17/2014 ERD (TST 6049) Physical Properties PLYG-SC7550.03.15 03/24/2015 ERD (TST 6049) Physical Properties P40390.D4.15 04/03/2015 ERD (TST 6049) Physical Properties P44360.30.14-R3 05/18/2015 ERD (TST 6049) Physical Properties PLYG-SC80BO.05.15-1 05/20/2015 ERD (TST 6049) Wind Uplift PLYG-SC8905.05.16.1 05/17/2016 ERD (TST 6049) Physical Properties PLYG-SCSOBO.07.16 07/16/2016 ERD (TST 6049) Wind Uplift PLYG-SC12025.10.16 10/12/2016 ERD (TST 6049) Physical Properties PLYG-SC13040.12.16 12/27/2016 ERD (TST 6049) Physical Properties PLYG-SC11900.03.17 03/10/2017 ERD (TST 6049) Physical Properties -PLYG-SC32115.08.17 08/08/2017 ICC-ES (EVL 2396) IBC Compliance ESR-1697 11/02/2014 Miami -Dade (CER 1592) HVHZ Compliance NOA 14-073.7.08 01/22/2015 Polyglass USA Manufacturing Affidavit Products Current 02/18/2009 Polyglass USA P/L Affidavit Mule -Hide Cross Ltg 03/01/2008 Polyglass USA Materials Affidavit Polystick SA Compound 08/18/2011 UL, LLC (QUA9625) Quality Control Service Confirmation Exp. 10/05/2018 4. PRODUCr DESCRIPTION: 4.1.1 Elastobase is a fiberglass reinforced, SBS modified bitumen base sheet. 4.1.2 Elastobase P is a polyester -reinforced, SBS modified bitumen base sheet. 4.1.3 Polyglass G2 Base is afiberglass-reinforced, asphaltic base sheet. 4.1.4 Polyglass APP Base is a fiberglass -reinforced, APP modified bitumen base sheet. d$RF' ♦ !n g6.%tyh,.n 4F��'&i-A�l(1Ct���-�,i(tltiP�OtS yPr4-Vb&3vik2.Y, 5c'n? r;I t:, ' �hSn`.{u�'U�.L"?kF('k/S* .0 +�npaoiFf>k:ItOTS oyN�,P,olyst�iYk MT$�P,LUSysra;n-omitnaln60>mil thi�ckruhtierizetiiasp�hAltwaterpriiofingisbrne, glass fiberreltiorced,�siirfaced with pofyglefiriic.flin surF ce;`meets FRSP_RIAptI1�2012�.,IHF77F,,k,.'-�t 4.2.2 Polystick IR-Xe is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with an aggregate surface; meets ASTM D1970. 4.2.3 Polystick TU Plus is a nominal SG -mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. NEMO ETC, LLC. Evaluation Report P12060.02.09-R24 [ertflc 4fnumorimnan N32455 eR EDITION (2017) FBC NON.HVHZ EVALUATION FL5259-R28 Polyglass Roof Underiayments, (954)'233.1230 Revislon 24: 01/24/2018 Page 3 of 14 S. ONEMOletc. 4.2.4 Polystick TU P is a nominal 13D-mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester reinforced, with a granular surface; meets FRSA/TRI April 2012. 4.2.5 Polystick TU Max Is a nominal 60-mil thick rubberized asphalt waterproofing membrane with a 190 g/m2 polyester fabricsurface; meetsASTM D1970 and FRSA/TRI April 2012. 4.2.6 Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR) are polyester reinforced, APP modified bitumen cap sheets; meet FRSA/TRI April 2012. 4.2.7 Polystick Dual Prom Is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced; with a polyester fabric surface; meets ASTM D1970. 4.2.8 Palystick Tile Prom is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. 4.2.9 Polystick MU-X is a nominal 54-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polypropylene film surface; meets AC188 and physical requirements of ASTM D1970 (See Section 5.8). 4.3.1 Elastoflex G TU is a polyester reinforced, modified bitumen tile underlayment composed of a sand -surfaced SBS modified bitumen back -side and granule -surfaced APP modified bitumen top -side. Elastoflex G TU Is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from'FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or Hot Asphalt applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. 4.3.2 Elastoflex 56 G and Elastoflex 56 G FR are polyester reinforced, SBS modified bitumen cap sheets; meet ASTM D6164. Elastoflex S6 G and Elastafex S6 G FR are for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. Elastoflex S6 G is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered file roof systems. Elastoflex S6 G FR is for use as an alternate to Hot Asphalt applied "Cap Sheet' in the "Two Ply System" from FRSA/TRI April 2012 (04-22) beneath mechanically fastened tile roof systems. 4.3.3 Polyflex G and Polyflex G FR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222. PolyflexG is for use as an alternate to Heat Applied "Cap Sheet" In the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Polyflex G FR is for use as an alternate to Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. LiNaTATloNs: 5.1 This is a building code evaluation. Neither NEMOIetc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in the HVHZ. 5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire ratings of this product. 5.4 Polyglass Roof Underlayments may be used with any prepared roof cover where the product Is specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering. NEMO ETC, LLC. Evaluation Report P12060.02.09-R24 certfone ofAuthalz"tl"n n32455 e EDITION (20171 FBC NON41IVHZ EVALUATION FLW39-RZB Polyglass Roof Undedayments; (954) 233-IMO Revision 24:01/24/2018 Page 4 of 14 ONEMOjetc. 5.5 Allowable Roof Covers: Underlayment Asphalt Shingles Nall -On Tile Foam -On The Metal wood Shakes &shingles Slate Elastobase Yes Yes Yes Yes Yes Yes (Base Sheetln2-plysy#em) (Base Sheetln2-plysysrem) Elastobase P Yes Yes Yes Yes Yes Yes (aasesheetin2-p11'sy#em) (aamsheetln2.plysysrem) Polyglass G2 Base No Yes Yes No No No (Base Sheet In bPiy system) (BasesheetlnbPlyaystem) Polyglass APP Base No Yes Yes No No No (8asesheet1n2.P1ysystem) (Base sheet In 2-ply system) -".0n .s" }P6lystickMTSo6iMTSPCUS+'�.%, tte:pq^eWe59Fu^"T^I i"*•` -"`"Yes ^-rn� h•r,, "C,.,,.,,,,,, No 40_11*(RAR4 i Yes Yes PolysticklR-Xe Yes No Na 'No" Polystick TUP No Yes Yes (See 5.5.1) No. No No Polystick TU Plus Yes Yes Yes (See 5.5.1) Yes Yes Yes Polystick TU Max No Yes Yes (See 5.5.1) Yes No No ' PolWick Dual Pro Yes No No Yes Yes Yes Polystick Tile Pro Yes Yes Yes (See S.5.1) Yes Yes Yes Polystick MU-X Yes No No Yes Yes Yes Elastoflex SGG Yes Yes Yes (See5.5.1) No Yes Yes Elastoflex S5 G FR Yes Yes No No Yes Yes Elastoflex G TU Yes Yes Yes (See 5.5.1) No Yes Yes PolynexG Yes Yes Yes (See 5.5.1) No Yes Yes PolyRex G FR Yes Yes No No Yes Yes Polyflex SAP or SAP FR Yes Yes Yes (See 5.5.1) No Yes Yes Mule -Hide SA-APP Cap Sheet Yes Yes Yes (See 5.5.1) No Yes Yes or SA-APP Cap Sheet (FR) 5.5.1 "Foam -On Tile" is limited to use of the following Approved the adhesives / underlayment combinations. _;. ! J d'C i a.....'_5 ,. Y 1,.., 0 1 A uJ +tl /b bN?'i rA LLt' J�r % l :: �, ^.'': E9lVE+{{iNPE,�7LYIMEIiTt'.O BINAItdNS .�. ,JC...t.a. ... •... ,.;: Adhesive Florida Product Underlayments Approval DAP Foam Touch'n Seal Stormaond Roof FL14506 Polystick TU Plus, PolystickTU Max Tile Adhesive Dow TileBondTM FL22525 Polystick TU P, Polystick TU Plus, Polyflex SAP or The Pro Polystick TU P, Polystick TU Plus, PolysUck TU Max, Polystick Tile Pro, ICP Adhesives Polyset• AH-160 FL6332 Elastoflex G TU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR, Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro, ICP Adhesives Polyset° RTA-1 FL6276 Elastoflex G TU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) t Refer to Tile Manufacturer's orAdhesive Manufacturer's Florida Product ApprovaiJor Overturning Moment Resistance Performance. NEMO ETC, U.C. Evaluatlan Report P32060.02.09-R24 C.Mflmte oM.th.# H..#32455 6r"EDITION 12017)FBC NON-HVHZ EVALUATION FL52SM28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 5 of 14 ONEMOletc. 5.6 Allowable Substrates: 5.6.1 Direct -Bond to Deck: Polystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: ➢ New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing plywood; New or existing, unprimed OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed Southern Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods 'ZIP System" Panels (designed and installed to meet wind loads for project). Note: Polyglass does not require priming of new or existing plywood or OSB sheathing. New or existing plywood or OSB sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ ASTM D41 primed structural concrete. Polyflex G or Polyflex G FR torch -applied to: ➢ ASTM D41 primed structural concrete. 5.6.2 Bond -to -Insulation: Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: ➢ ASTM C1289, Type 11, Class 1 polyisotyanurate or Type V polyisocyanurate-composite insulation; Dens Deck DuraGuard; Dens Deck Prime; or SECUROCK Gypsum -Fiber Roof Board. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. Polyflex G or Polyflex G FR torch -applied to: ➢ ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on tile systems, insulation attachment shall be designed by a qualified design professional and installed based on testing of the insulation/underlayment system In accordance with FBC Section 15134.3.1. 5.6.3 Bond to Mechanically Attached Base Laver: Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or Tile Pro self -adhered to: D ASTM D226, Type I or 11 felt; Elastobase; Elastobase P or Mule -Hide Nall Base. Elastoflex G TU, Elastoflex 56 G or Elastoflex S6 G FR In hot asphalt to: D ASTM D226, Type I or II felt; Elastobase; Elastobase P, Mule -Hide Nail Base or Polyglass G2 Base. Polyflex G or Polyflex G FR torch -applied to: ➢ Elastobase; Elastobase P, Mule -Hide Nail Base, Polyglass G2 Base or Polyglass APP Base. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum coded requirements. For Installations under foam -on tile systems, base layer shall be attached per minimum requirements of FRSA/TRI April 2022 (04-12), Appendix A, Table 1, or as listed In Section 5.6.4 herein, or as tested in accordance with FBC Section 1504.3.1. NENIO ETC, U t Evaluation Report P32060.02.09-R24 artlji oirAurhDd xan F32455 eEDITION (2017)FBC NON-HVHZ EVALUATION FL5259-RZB Polyglass Roof Underlayments; (954) 233-1230 Revision 24:01/24/2019 Page 6 of 14 ONEIVIOletc. SAA Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/iRI April 2012 (04-12) does, not address wind uplift resistance of all underlayment systems beneath foam -on the systems, where the underlayment forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not addressed in FRSA/fRI April 2012 (0442) and are used in foam -on tile applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2022 (04- 12), Appendix A, Table 1A or FBC 1609 for determination of design wind loads. #1 Maximum Design Pressure = -90 psf: Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: None Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #2 Maximum Design Pressure =-97.5 psf: Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG300 or ASTM D41 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back-nalled within the selvedge -edge side laps using 12 ga. x 1%"'Ong shank nails through 32 ga.,1-5/8" diameter tin caps spaced 12-inch o.c. #3 Maximum Design Pressure = -105 DsU. Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: WB-3000 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x W ring shank nails through 32 ga., 1-518" diameter tin caps spaced 12-inch o.c. #4 Maximum Design Pressure= 435 psf: Deck: Min. 15/324nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: (Optional) PG100 or ASTM D41 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Joints: Min. 4-Inch wide strips of Elastoflex SA-V over all plywood Joints. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR,.Mule-Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #5 Maximum Design Pressure =-325 is Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU. Max, Tile Pro, Polyflex SAP, Polyflex SAP FR. Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #6 Maximum Design Pressure = -622.5 psf: Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #7 Maximum Design Pressure =-30.0 osf Deck: Min. 15/32-inch OSB to meet project requirements to satisfaction of Authority Havinglurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 1.25-Inch long x 1-inch head diameter round metal cap nails Spacing: 6-Inch o.c. at the 3-inch wide side laps and 64nch c.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. NEMO ETC, LLC. Evaluation Report P12060.02.09-R24 CeruawteofA"th#rlmtbn#32455 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlaymems; (954) 233-1230 Revision 24: 01/24/2018 Page 7 of 14 NEM0 etc. #8 Maximum Design .Pressure =-37.5osf*: Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 1.25-Inch long x 1-Inch head diameter round metal cap nails Spacing: 6-inch o.c. at the 3-Inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet(FR), self -adhered. #9 Maximum Design Press ure=-37.5 psf*: Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: One (1) or two (2) layers ASTM D225, Type 11 felt Fasteners: 11 Be. x 1.25-Inch long 1-inch head diameter round metal cap nails Spacing: 6-inch o:c at the 3-Inch wide side laps and 12-Inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex 6 TU or Elastoll" S5 G, applied in full mopping of hot asphalt. #10 Maximum Design Pressure =-45 psfh Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: One (1) layer ASTM D226, Type II felt Fasteners: 11 Be. x 1.25-Inch x 3/8-Inch head diameter annular ring shank roofing nails at 1-5/8-Inch diametertin raps Spacing: flinch o.c. at the 2-Inch wide side laps and 4-Inch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional; for use with selfadhering underlaymem only) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule-HideSA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU; applied in full mopping of hot asphalt. #11 Maximum Design Pressure=AS Psf Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Two (2) layers ASTM D226, Type II felt Fasteners: 11ga. x 1.25-inch long x3/8-Inch head diameter annular ring shank roofing nails at 1-5/8-Inch diametertincaps Spacing: 94nch o.c. at the 24nch wide side laps and 94nch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional; for use with self -adhering underlaymem only) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP,.Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU or Elasroflex S6 G, applied In full mopping of hot asphalt. #12 Maximunn Design Pressure=-45osf: Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hat -asphalt or torch -applied cap or poly -film surface fortorchapplied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 94nch o.c. at the 2-Inch wide side laps and 18-Inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #13 Maximum Design 'Pressure=-52.5psf•. Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 9-Inch o.c at the 2-Inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #14 Maximum Design Pressure =-52.5 psf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: Simplex Original Cap Nails Spacing: 6-Inch o.c. at the 3-Inch wide side laps and 6-inch o.c. atfour (4) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. NEMO ETC, LLC. Evaluation Report P32060.02.09-R24 certylmte OfAuthonmtka a32455 6TM EDMON (2M7) FBC NON-HVHZ EVALUATION FL5259-R28 Polyglaa Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 8 of 14 ONEMOletc. #15 Maximum Design Pressure =-52.5 0sf: Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex Original Cap Nails Spacing: 6-Inch ox at the 3-Inch wide side laps and 6-Inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or Polyflex G, torch -applied. #16 MaximumDesignPressure =-60Psf: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: 11 ga. x 1.25-inch long x 3/8-Inch head diameter annularring shank roofing nails at 1-5/84nch diameter tin caps Spacing: 8-Inch o.c. at the 44nch wide side laps and 8-inch o.c. at three (3) equally spaced staggered center rows. Undedayment: Elastaflex G TU or Elastoflex S6 G, applied in full mopping of hat asphalt or Polyflex G, torchapplled. #17 Maximum Design Pressure=-60 osf:. Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: OMG #12 Standard Roofgrip with OMG Flat Bottom Metal Plates Spacing: 12-Inch o.c. at the 4-Inch wide side laps and 12-Inch o.c. at two (2) equally spaced staggered center rows. Underlaymem: Elastaflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #18 Maximum Design Pressure = -67.5 0sf: Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment) Fasteners: 12 ga, x 1.25-Inch long 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-Inch diameter tin caps Spacing: 8-inch o.c. at the 4-Inch wide side laps and 8-Inch o.c. at four (4) equally spaced staggered tender rows. Undedayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #19 Maximum Design Pressure=-75 osf: Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment) Fasteners: Uekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG 3"Galvalume Steel Plates, OMG Roofgrip #14 with OMG Flat Bottom Plates (AccuTrec), Trufast HD with Trufast 3-Inch Insulation Plates or Simplex MAXX Cap Fasteners Spacing: 10-Inch o.c. atthe flinch wide side laps and 10-Inch o.c. atthree (3) equally spaced staggered center rows. Undedayment: Elastoflex G TU or Elastaflex 56 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #20 Maximum Design Pressure=-900sf: Deck: Min. 15/32-Inch plywood to meet project requiremems to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hat -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-inch o.c, at the 2-Inch wide side laps and 6-Inch o.c. at two (2) equally. spaced staggered center rows. Undedayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #21 Maximum Design Pressure = -90 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hotasphalt or torch -applied cap or poly -film surface for torch -applied mp) Fasteners: OMG #12 Standard Roofgrip or OMG #24 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal Plates Spacing: 6-Inch o.c. at the flinch wide side laps and &inch o.c, at three (3) equally spaced staggered center rows. Undedayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #22 Maximum Design Pressure =-900sf: Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Rase Sheet: Elastobase (sanded top surface) Fasteners: Trufast #12 DP or Trofast #14 HD with Trufast 3" Metal Insulation Plates Spacing: 6-Inch o.c. at the 4-Inch wide side laps and 6-inch o.c. at three (3) equally spaced staggeredcenter rows. Undedayment: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hat asphalt. NEMO ER, LLC. Evaluation Report P32060.02.09-R24 cerwww ofAuftawVon 032455 6TM EcirnoN(20171 FBC NON-NVHZ EVADIATION FL5259.R28 Polyglass Roof Underlayments; (954) Z33-1230 Revision 24:02/24/2018 Page 9 of 24 NNEMO I etc. #23 Maximum Design Pressure = -90 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch-appliedunderlayment) Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG 3" Galvalume Steel Plates, OMG Rpofgrip #14 with OMG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-Inch Insulation Plates or Simplex MAXX Cap Fasteners Spacing: 9-Inch o.c. at the 4-inch wide side laps and 9-Inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #24 Maximum Design Pressure=-97.5osf: Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nall Base (poly -film top surface) Fasteners: 11 ga. x 1.25-inch x 3/8-Inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 4-Inch o.c. at the 4-Inch wide side laps and 4-Inch o.c, at four (4) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, PoWu SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #25 Maximum Design Pressure =-205 psf Deck: MIn.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-inch a.c. at the 2-inch wide side laps and 64nch o.c. at three (3) equally spaced staggered center rows. Undedayment: Elastoflex G TU or Elastoflex 56 G, applied In full mopping of hot asphalt or Polyflex G, torch -applied. #26 Maximum Design Pressure=-112.5 osf: Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Havinglurlsdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x1.25-inchx3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diametertinraps Spacing: 6-Inch o.c. at the 4-inch wide side laps and 6-Inch o.c. at four (4) equally spaced staggered center rows. Primer: PG200 or ASTM D41 primer at all tin -caps Base Ply: Polystick MTS or Polystick MTS PLUS, self -adhered Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, PolyflmSAP FR, Muie-Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #27 Maximum Design Pressure=-3.20 psi: Deck: Min. 15/324rich plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal Plates Spacing: 6-Inch o.c. at the 4-inch wide side laps and 6-inch ma at five (5) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastcfiex S6 G, applied In full mopping of hot asphalt or Polyflex G, torch -applied. #28 Maximum Design Pressure=-120 osf: Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface) Fasteners: Trufast#12 DP orTrufast#14 HD with Trufast 3" Metal Insulation Plates Spacing: 6-Inch o.c. at the 4-Inch wide side laps and 6-inch o.c, at five (5) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt 5.6.4.1 All other direct -deck, adhered Polyglass underlayment systems beneath foam -on the systems carry a Maximum Design Pressure of -45 psi. NEMO ETG LLC. Evaluation Report P12060.02.09-R24 rprtlfimte of Audwr&uWnA32455 67 EDIt10N(2017)FBCNON-HVHZEVALUA71ON FL`259-RZB Polyglass Roof Underiayments; (954) 233-1230 Revision 24:01/24/2028 Page 10 of 14 ONEMOletc. 5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A. Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD3, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. 5.7 Exposure Limitations: Elastobase, Elastobase P, Polyglass G2 Base or Polyglass APP Base shall not be left exposed for longer than 30-days after installation. Polystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 90-days after installation. Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Dual Pro, Tile Pro or Elastoflex G TU shall not be left exposed for longer than 180-days after installation. Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure limitation, unless the prepared roof covering is to be adhesive -set tile, in which case the maximum exposure is 30 days. Elastoflex 56 G or Elastoflex S6 G FR or Polyflex G or Polyflex G FR does not have an exposure limitation, unless the prepared roof covering is to be adhesive -set tile (Elastoflex S6 G or Polyflex 6 only), in which case the maximum exposure is 180 days. 5.8 Polystick MU-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226 roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as set forth in Section 4.3, Note 1 of ASTM D1970-15, should be established as to slip resistance. 5.9 Tile Slippage Limitations (FRSA/FRI April 2012 (04-1211; When loading roof tiles on the underlayment In direct -deck file assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. -..�.rit,.Syr,{„rv.'.":��'.�U(9G�".15DCE?�L)�C,A6E����YT,).QNSW,,,�\01�6,TTDECIY,q'iLLEtIIaSiAl7A'f;10�15zrdn{,fa:'�?kJ154:,FaEx9~�°ru`:� "!K 4X S LL3 6T 'l- -0! 4 't iY 4 M1 fe t ,a..s.°f Underlayment Tile Profile Staging Method Matdmum Slope Elastoflex G TU Flat 30-tile stack 7:12 Lugged 8-tile stack (6 over 2) 6:12 Elastoflex S6 G or S6 G FR Flat or Lugged 6-tile stack (4 over 2) 4:12 Polystick MTS or MTS PLUS Flat 6-tile stack (4 over 2) 5:12 Lugged 6-tile stack (4 over 2) 4:12 Polystick Tile Pro Flat or Lugged 6-tile stack (4 over 2) 7:12 Polystick TU Max Flat 6-tile stack (4 over 2) or 10-tile stack 7:12 Lugged 6-tile stack (4 over 2) 7:12 Lugged 10-tile stack '6:12 Polystick TUP Flat 6-tile stack (4 over 2) 6:12 Lugged 6-tile stack (4 over 2) 4:12 Polystick TU Plus Flat or Lugged 6-tile stack (4 over 2) 7:12 Flat or Lugged SO -tile stack 6:12 Polyflex G or G FR Flat or Lugged 6-tile stack (4 over 2) 4:12 Polyflex SA P or SA P FR Flat or Lugged 6-tile stack (4 over 2) 4:12 NEMO ETC, U.C. Evaluation Report P12060.02.09-R24 Cernj![ute QfAuthoraa an 032455 67xEDITION 12027) FBC NON•HVHZ EVAWATION FL5259-R2a Polyglass Roof Underlaymerts; (954)233-1230 Revision 24:01/24/2018 Page 11 of 14 NNEMO I etc. 6. INSTALLATION: 6.1 Polyglass Roof Underlayments shall be installed in accordance with Polyglass published installation requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application, and prime the substrate (if applicable). 6.3.1 Non -Tile Applications: Shall be installed In compliance with the codified requirements for ASTM D226, Type II underlayment in FBC Table 1507.1.1 forthe type of prepared roof covering to be installed. Elastobase, Elastobase P or Mule -Hide Nail Base may be covered with a layer of Polystick, Polyflex SAP, Polyflex SA P FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR), self -adhered, Elastaflex G TU, Elastoflex S6 G or Elastoflex S6 G FR In hot asphalt or PoWlex G or Polyflex G FR, torch applied. Roof cover limitations are those are those associated with the top -layer underlayment, as set forth in Table 1. 6.3.2 Tile Applications: Elastobase, Elastobase P or Mule -Hide Nail Base are limited to use as a mechanically attached base sheet in the" Two Ply System" from FRSA/TRI April 2012 (04-12). Reference is made to Table 1 and Section 5.6.4 herein, coupled with FRSA/TRI April2012 (04-12) Installation Manual. 6.4.2 Shall be installed In compliance with the codified requirements for ASTM D1970(except Polystick TU In FBC Table 2507.2.1 for the type of prepared roof covering to be installed. Direct -to -Deck with Mechanically Fastened Roof Covers: All self -adhering materials, with the exception. of Polystick TU Plus, Poly lex SAP or SAP FR and Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) should be back -nailed in selvage edge seam in accordance with Polyglass / Mule - Hide back nailing guidelines. Nails shall be corrosion resistant, 11 gauge ring -shank type with a minimum 1-inch diameter metal disk or Simplex -type metal cap nail, at a minimum rate of 12" o.c. Polystick TU Plus should be back - nailed using the above noted fasteners and spacing, in area marked "nail area, area pare clever" on the face of membrane. The head lap membrane is tocover the area being back -nailed. All seal -lap seams (selvage laps) must be - firmly rolled with a minimum 28 lb. hand roller to ensure full contact and adhesion. For Dual Pro and Tile Pro, align the edge of the top sheet to the end of the.. glue pattern (the sheet will overlap the fabric). view of owlap Seem of Dual Pro and Tile Pro All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PG500 Modified Cement applied In between the application of the lap. Polystick TLI Plus, Dual Pro and Tile Pro may not be used in any exposed application such as crickets, exposed valleys, or exposed roof to wall details NEMO ETC LLC. Evaluation Report P12060.02.09-R24 Certyimte"fAuthurtmtIm d32455 67" EDITION(2017) FBC NON-HVHZ EVALUATION FL5299•R7a Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 12 of 14 NNEMOjetc. Repair of Polystick membranes is to be accomplished by applying Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PG500 Modified Cement to the area in need of repair, followed by a minimum 6 x 6 Inch patch of the Polystick material of like kind, set and hand rolled in place over the repair area. Patch laps, if needed, shall be Installed in a water shedding manner. All Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a minimum of 40-lb weighted -roller or, on steep slopes, use of a stiff broom with approximately 40-lbs of load applied for the field membrane. Hand rollers are acceptable for rolling of patches, laps (min. 28lb roller) or small areas of the roof that are not accessible to a large roller or broom. 6.4.3 Tile ADoilcations (not allowed forPahwickDual Pro, IRXeorPQh0FckMU-X): Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions noted above as aguideline. For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base Sheet fastening shall be not less than FRSA/TRI April 2012 (04-12), Table 1. For adhesive -set tile applications, referto Section 5.6.4 herein. 6.4.4 Two (2) Ply Underlayment Systems: Polystick MTS or MTS PLUS followed by Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Tile Pro, MU-X or Polyflex SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with the tap -layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired. Polystick MTS or MTS PLUS followed by Polystick TU P, TU Plus, TU Max, Tile Pro or Polyflex SAP is allowable for use under foam -on tile systems. Limits of use are those associated with the top -layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired. 6.5.1 Elastaflex G TU, Elastaflex S6 G or Elastaflex S6 G FR shall be installed in compliance with current Polyglass published Installation requirements. For use in tile applications: ✓ Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D5380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastaflex S6 G is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2022 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered file roof systems. ✓ Elastoflex S6 G FR Is for use as an alternate to "Mineral Surface Roll Roofing" (AST M D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System' from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. 6.5.2 For hot -asphalt -applications, Elastoflex G TU, Elastaflex S6 G or Elastaflex S6 G FR shall be fully asphalt -applied to the substrates noted in Section 5.5. Side laps shall be minimum 3-inch and end -laps minimum 6-Inch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully adhered In a complete mapping of hot asphalt with asphalt extending approximately 3/84nch beyond the lap edge. ......... . 6.6.1 Polyflex G or Polyflex G FR shall be installed in compliance with current Polyglass published installation requirements. For use in tile applications: ✓ Polyflex G is for use as an alternate to the Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems (Base Sheet Limited per 5.6.3). ✓ Poiyfiex G FR is for use as an alternate to the Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems (Base Sheet Limited per 5.6.3). NEMO ETC, Ur_ Evaluation Report P12060.02.09-R24 ceNf7 WgfAutharkoWn N32455 67 EDITION (2017) FBC NON-HVNZ EVALUATION FL5259-R78 Polyglass Roof UndertaMems, (934) 233-1230 Revision 24: 01/24/2028 Page 13 of 14 ONEMOletc. 6.6.2 Polyflex 6 or Polyflex G FR shall be fully torch -applied to the substrates noted in Section 5.6. Side laps shall be minimum 3-inch and end -laps minimum 6-Inch wide, offset minimum 3 feet from course to course. Side and end laps shall be fully heat -welded and inspected to ensure minimum 3/8-inch flow of modified compound beyond the lap edge. 6.7 Tile Staling: 6.7.1 Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the underlayment Refer to Table 2 herein, and Polyglass published requirements for tile staging. 6.7.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TRI April 2012 (04-12) must be used on all roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of battens or sail- boards, to prevent tile sliding and/or damage to the underlayment during the loading process. 6.7.3 Polyglass specifies the minimum cure time after installation of self -adhering membranes and before loading of roofing tiles Is forty-eight (48) hours. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. B. MANUFACTURING PLANTS: Contact the noted CIA agency for information on product locations covered for FA.C. 61G20-3 CIA requirements. The following plants have qualified products under their respective physical properties specifications. u s w511r t - r r!.4_bSdeed`ica"t1on�„��..ram-„",>:„,�,'�s��'a;�Puts, Fernley, NV, Hazleton, PA & Winter Haven, FL ASTMD1970Polystick MU-X Hazleton, PA M-D 13-DOD4 Eiastoll" G TU Hazleton, PA & Winter Haven, FL ASTM D1970 Polystick IR-Xe ASTM D1970 & FRSA/TRI April 2012 Polystick TU Plus ASTM D1970 & FRSA/TRI April 2012 PolysUck TU Max Tuscaloosa, AL ASTM D4601, Type 11 Polyglass 62 Base ' Winter Haven, FL ASTM D226 (physicals) Elastobase, Elastobase P ASTM D6509 Polyglass APP Base FRSA/TRI April 2012 Polystick MTS, Polystick MTS PLUS FRSA/TRI April 2012 Polystick TUP FRSA/TRI April 2012 Polyflex SAP, Pal ex SA P FR ASTM D1970 Polystick Dual Pro ASTM D1970 & FRSA/TRI April 2012 Polystick Tile Pro ASTM 06164 Elastallm S6, Elastaflex S6 G FR ASTM D6222 Polyflex G, Polyflex G FR 9. QUALITY ASSURANCE ENTRY: UL, LLC—QUA9625; (314) 578-3406; k.chancellor@us.ul.com -END OF EVALUATION REPORT - NEMO ETC, LLC. Evaluatlon Report P12060.02.09-R24 Cenflm afAOhoH lon 432455 dm EDITION (2a17)F13C NON-HVH2 EVALUATION Ft5259-R28 Polyglass Root Underlaymenu; (954) 233-3230 Revision 24: 01/24/2018 Page 14 of 14