Loading...
HomeMy WebLinkAboutDESIGN CALCULATIONS_ asSeals .' easyseals.com SCANNED BY St. Lucie County DESIGN CALCULATIONS FOR NOONCI LETTERS ON RACEWAY 7582 S. Fed Hwy — Port St Lucie GENERAL NOTES: 1. Design is in accordance with the Florida Building Code 6th Edition (2017) for use within and outside the High Velocity Hurricane Zone (HVHZ). 2. Wind loads have been calculated per the requirements of ASCE 7-10 as shown herein. 3. These engineering calculations pertain only to the structural integrity of those systems, components, and/or other construction explicitly specified herein and/or in accompanying engineering drawings. The Index: existing host structure (if any) is assumed to be in good condition, Pg 1 Cover capable of supporting the loaded system, subject to building department Pg 2 Wind Loads approval. No warranty, either expressed or implied, is contained herein. Pg 3 Anchor Design 4. System components shall be as noted herein. All references to named components and installation shall conform to manufacturer's or industry specifications as summarized herein. S. Where site conditions deviate from those noted herein, revisions may E;g; be y�pn�g�""" �eef�t� �'�h4lseal valid required or a separate site -specific engineering evaluation performed. 6. Aluminum components in contact with steel or embedded in concrete Z`;' S F •�• t� (�. •..G shall be protected as prescribed in the 2015 Aluminum Design Manual, No. 6 382 Part 1. Steel components in contact with, but not encased in, concrete shall be coated, painted, or otherwise protected against corrosion. S ATED kr: 7. Engineer seal affixed hereto validates structural design as shown only. :�0o ec 2 Use of this specification by contractor, et. Al, indemnifies and saves rlSj a ��P,��# 67382 harmless this engineer for all costs &damages including legal fees & Ch�,,, apellate fees resulting from deviation from this design. Easy Se319.rr--t.re th # 31124 Federal Hwy, #200 Ean Seals.com Page 1 Bocaoca Raton, FL 33432 "1 fwsySealCALCULATIONS FOR WALL -MOUNTED SIGNS ry alis • l_ /SCE 7-10 Design Wind Loads WALL -MOUNTED SIGNS Building Specs V = 160 mph Basic wind speed Exposure C Calculations a=9.5 3-sec gust speed power law exponent zg = 900' Nominal ht. of otmos. boundary layer Gcpi = 0 Internal pressure coeff 160 mph - Exp "C" WALL -MOUNTED SIGNS ASD WIND PRESSURES SIGN CENTER CORNER HEIGHT (Zone 4) (Zone 5) 15 ft 31.2 psf 39.7 psf 20 ft 33.2 psf 42.2 psf 25 ft 34.8 psf 44.2 psf 30 ft 36.1 psf 46.0 psf 35 ft 37.3 psf 47.5 psf 40 ft 38.4 psf 48.8 psf 45 ft 39.3 psf 50.1 psf Soft 40.2 psf 51.2 psf 55 ft 41.0 psf 52.2 psf 60 ft 41.8 psf 53.2 psf 70 ft 35.3 psf 70.6 psf 80 ft 36.3 psf 72.6 psf 90 ft 37.2 psf 74.5 psf 100 ft 38.1 psf 76.1 psf 110 ft 38.8 psf 77.7 psf 120 ft 39.6 psf 79.1 psf 130 ft 40.2 psf '. 80.5 psf 140 ft 40.9 psf 81.7 psf 150 ft 41.5 psf 82.9 psf 175 ft 42.8 psf 85.7 psf 200 ft 44.1 psf 88.1 psf 250 ft 46.2 psf 92.3 psf ASD Load Combo Coeff: 0.6 Kd = 0.85 Directionality factor Kzt = 1.0 Topographic factor A = 10 sq ft Tributary area n Y Y q: a L a a U 0.85 47.3 -1.10 -1.40 0.90 50.2 -1.10 -1.40 0.95 52.7 -1.10 -1.40 0.98 54.7 -1.10 -1.40 1.01 56.5 -1.10 -1.40 1.04 58.1 -1.10 -1.40 1.07 59.6 -1.10 -1.40 1.09 60.9 -1.10 -1.40 1.12 62.2 -1.10 -1.40 1.14 63.3 -1.10 -1.40 1.17 65.4 -0.90 -1.80 1.21 67.3 -0.90 -1.80 1.24 69.0 -0.90 -1.80 1.27 70.5 -0.90 -1.80 1.29 71.9 -0.90 -1.80 1.32 73.3 -0.90 -1.80 1.34 74.5 -0.90 -1.80 1.36 75.7 -0.90 -1.80 1.38 76.8 -0.90 -1.80 1.42 79.3 -0.90 -1.80 1.46 81.6 -0.90 -1.80 1.53 85.5 -0.90 -1.80 Page 2 Q)Easyseais Wall Sign Anchor Design Structure Dimensions & Loading Design wind pressure: Sign type: Sign size: CALCULATIONS FOR WALL -MOUNTED SIGNS P = 46.0 psf Raceway h = 24.0 inches (height) Wall material: Masonry (ASTM C90, 1,500 psi min) Anchor type/size: 1/4" Tapcon Ref: ITW Tapcon, NOA 07-1126.10 Min Embedment: 1.25" Min edge dist: 2.5" Anchor tensile capacity: Tcap = 195.0 lb (per anchor) Check Anchors for Pullout Total Reaction: Anchor spacing req'd Rt= 92 Ib/ft s = 50.9 in O.C. ... = P*h (along raceway) ... _ (2*cap)/Rt Pairs of anchors at 51 inches on center (max) 4.3 feet on center OK, typical anchor option shown. Limit to pairs at 48" O.C. max. Ref anchor schedule for other anchor options. Page 3 ,z�• sF = seal easyseals.com DESIGN CALCULATIONS FOR NOONCI LETTERS ON RACEWAY 7582 S. Fed Hwy— Port St Lucie GENERAL NOTES: 1. Design is in accordance with the Florida Building Code 6th Edition (2017) for use within and outside the High Velocity Hurricane Zone (HVHZ). 2. Wind loads have been calculated per the requirements of ASCE 7-10 as shown herein. 3. These engineering calculations pertain only to the structural integrity of those systems, components, and/or other construction explicitly specified herein and/or in accompanying engineering drawings. The Index: existing host structure (if any) is assumed to be in good condition, Pg i Cover capable of supporting the loaded system, subject to building department Pg 2 Wind Loads approval. No warranty, either expressed or implied, is contained herein. Pg 3 Anchor Design 4. System components shall be as noted herein. All references to named components and installation shall conform to manufacturer's or industry specifications as summarized herein. 5. Where site conditions deviate from those noted herein, revisions may be y required or a separate site -specific engineering evaluation performed. •rrr� En N,Q.! it Qht��seal valid a 4 4 •� 6. Aluminum components in contact with steel or embedded in concrete ���•,� Z`;' `t . r�� shall be protected as prescribed in the 2015 Aluminum Design Manual, `' No. 67 8 Part 1. Steel components, in contact with, but not encased in, concrete shall be coated, painted, or otherwise protected against corrosion. 7. Engineer seal affixed hereto validates structural design as shown only. TATE O <4: Dec 2 Use of this specification by contractor, et. Al, indemnifies and saves Chrf ` 67382 x.,, harmless this engineer for all costs & damages including legal fees & ,Re# �`G.� apellate fees resulting from deviation from this design. Easy Se319toiniiflClt Auth # 31124 Federal Hwy, 11200 Easy Seals .corn Page 1 Bocaoca Raton, ton, FL 33432 1 EasySeaLs CALCULATIONS FOR WALL -MOUNTED SIGNS ASCE 7-10 Design Wind Loads WALL -MOUNTED SIGNS Building Specs V = 160 mph Basic wind speed Exposure C Calculations a = 9.5 3-sec gust speed power law exponent zg = 900' Nominal ht. of atmos. boundary layer Gcpi = 0 Internal pressure coeff 160 mph - Exp "C" WALL -MOUNTED SIGNS AID WIND PRESSURES SIGN CENTER CORNER HEIGHT (Zone 4) (Zone 5) 15 ft 31.2 psf 39.7 psf 20 ft 33.2 psf 42.2 psf 25 ft 34.8 psf 44.2 psf 30 ft 36.1 psf 46.0 psf 35 ft 37.3 psf 47.5 psf 40 ft 38.4 psf 48.8 psf 45 ft 39.3 psf 50.2 psf 50 ft 40.2 psf 51.2 psf 55 ft 42.0 psf 52.2 psf 60 ft 41.8 psf 53.2 psf 70 ft 35.3 psf 70.6 psf 80 ft 36.3 psf 72.6 psf 90 ft 37.2 psf 74.5 psf 100 ft 38.1 psf 76.1 psf 110 ft 38.8 psf 77.7 psf 120 ft 39.6 psf 79.1 psf 130 ft 40.2 psf 80.5 psf 140 ft 40.9 psf 81.7 psf 0 ft 41.5 psf 82.9 psf 5 ft 42.8 psf 85.7 psf 0 ft L25 44.1 psf 88.1 psf 0 ft 46.2 psf 92.3 psf AID Load Combo Coeff: 0.6 Kd= 0.85 Directionalityfactor Kzt= 1.0 Topographicfactor A = 30 sq ft Tributary area u Y Y qx a 0 a a 0.85 47.3 -1.10 -1.40 0.90 50.2 -1.10 -1.40 0.95 52.7 -1.10 -1.40 0.98 54.7 -1.10 -1.40 1.01 56.5 -1.10 -1.40 1.04 58.1 -1.10 -1.40 1.07 59.6 -1.10 -1.40 1.09 60.9 -1.10 -1.40 1.12 62.2 -1.10 -1.40 1.14 63.3 -1.10 -1.40 1.17 65.4 -0.90 -1.80 1.21 67.3 -0.90 -1.80 1.24 69.0 -0.90 -1.80 1.27 70.5 -0.90 -1.80 1.29 71.9 -0.90 -1.80 1.32 73.3 -0.90 -1.80 1.34 74.5 -0.90 -1.80 1.36 75.7 -0.90 -1.80 1.38 76.8 -0.90 -1.80 1.42 79.3 -0.90 -1.80 1.46 81.6 -0.90 -1.80 1.53 85.5 -0.90 -1.80 Page 2 Easyseats Wall Sign Anchor Design Structure Dimensions & Loading Design wind pressure: Sign type: Sign size: CALCULATIONS FOR WALL -MOUNTED SIGNS P = 46.0 psf Raceway h = 24.0 inches (height) Wall material: Masonry (ASfM C90, 1,500 psi min) Anchor type/size: 1/4" Tapcon Ref: ITW Tapcon, NOA 07-1126.10 Min Embedment: 1.25" Min edge dist: 2.5" Anchor tensile capacity: Tcap = 195.0 Ib (per anchor) Check Anchors for Pullout Total Reaction: Anchor spacing req'd Rt = 92 Ib/ft s = 50.9 in O.C. ... = P*h (along raceway) ... _ (2*cap)/Rt Pairs of anchors at 51 inches on center (max) 4.3 feet on center OK, typical anchor option shown. Limit to pairs at 48" O.C. max. Ref anchor schedule for other anchor options. Page 3