KELLER, SCHLEICHER & MacWILLIAM ENGINEERING AND TESTING, INC.
MARTIN (772) 337-7755 P.O. BOX 78-1377 SEBASTIAN FL 32978-1377 SEBASTIAN (772) 589-0712
PALM BEACH (561) 845-7445 www.ksmengineering.net MELBOURNE (321) 768-8488
FAX (561) 845-8876 E-Mail: KSMQKSMENGINEERING.NET ST. LUCIE (772) 229-9093
C.A.: 5693 FAX (772) 589-6469
February 7, 2019
Drew Dunlap
Dunlap Construction Group LLC SC,y
1708 Old Dixie Highway St ey/ ,
Vero Beach, Florida 32960 coo, y
Re: Ocean Resorts
5101 Highway A1A
Fort Pierce, Florida
Permit #: 1812-0035
KSM Project #: 190553-1 d
Dear Mr. Dunlap:
REcEww
FEB 12 7010
Permitting DePa ur ent
St. Lucie Co
Enclosed, please find the nuclear density test results performed on the footers at the
above refgtMfigd project.
n%W, 'Vestions, please feel free to contact us.
JEKft
E-mail to: drewdunlap@dunlap-construction.com; St. Lucie County Building Department
Ronald G. Keller, P.E.: 37293 / SI Lic. No.: 860 / Julie E. Keller, P.E.: 68366
w '
Tip C! ®lk
A% i ,L
KELLER, SCHLEICHER & MacWILLIAM ENGINEERING AND TESTING, INC.
MARTIN (772) 337-7755 P.O. BOX 78-1377, SEBASTIAN, FL 32978-1377 SEBASTIAN (772) 589-0712
PALM BEACH (561) 845-7445 www.ksmengineedng.net MELBOURNE (321) 768-8488
FAX (561) 845-8876 E-Mail: KSM@KSMENGINEERING.NET ST. LUCIE (772) 229-9093
C.A.: 5693 FAX (772) 589-6469
February 7, 2019
Drew Dunlap
Dunlap Construction Group LLC
1708 Old Dixie Highway
Vero Beach, Florida 32960
SC N ED
Re: Ocean Resorts
By
5101 Highway A1A
St. Lucie County
Fort Pierce, Florida
Permit #: 1812-0035
KSM Project#: 190553-1d
Dear Mr. Dunlap:
Enclosed, please find the nuclear density test results performed on the footers at the
please feel free to contact us.
JEK/jt
E-mail to: drewdunlap@dunlap-construction.com; St. Lucie County Building Department
Ronald G. Keller, P.E.: 37293 / SI Lic. No.: 860 / Julie E. Keller, P.E.: 68366
KELLER, SCHLEICHE
MARTIN (772) 337-7755 0.
PALM BEACH (561) 845-7445
FAX (561) 845-8876
C.A.: 5693
P.
April 5, 2019
R
& MacWILLIAM ENGINEERING AND TESTING, INC.
BOX 78-1377, SEBASTIAN, FL 32978-1377 SEBASTIAN (772) 589-0712
www.ksmengineering.net MELBOURNE (321) 768-8488
E-Mail: KSM@KSMENGINEERING.NET ST. LUCIE (772) 229-9093
FAX (772) 589-6469
Drew Dunlap
Dunlap Construction Group LLC
1708 Old Dixie Highway
Vero Beach, Florida 32960
Re: Ocean Resorts
5101 Highway A1A
Fort Pierce, Florida
Permit #: 1812-0036
KSM Project #: 190553-2d
Dear Mr. Dunlap:
SCANNED
By
St. Lucie County
Enclosed, please find the nuclear density test results performed on the footer pads for
the club house repair at the above referenced project.
lease feel free to contact us.
E-mail to:,drewdunlap@dunlap-construction.com
Fax and Mail to: St. Lucie County Building Department
Ronald G. Keller, P.E.: 37293 / SI Lic. No.: 860 / Julie E: Keller, P.E.: 68366 X
16 j2 -Coms
KELLER, SCHLEICHER & MaCWILLIAM ENGINEERING AND TESTING, INC.
MARTIN (772) 337-7755 P.O. BOX 78-1377, SEBASTIAN, FL 32978-1377 SEBASTIAN (772) 589-0712
PALM BEACH (561) 845-7445 www.ksmengineering.net MELBOURNE (321) 768-8488
FAX (561) 845-8876 E-Mail: KSM@KSMENGINEERING.NET ST. LUCIE (772) 229-9093
C.A.: 5693 FAX (772) 589-6469
February 7, 2019
Drew Dunlap 9"CErVED
Dunlap Construction Group LLC Ff9 0 ! 1
1708 Old Dixie Highway Pe nn019
Vero Beach, Florida 32960 st. cu De ent
a t
Re: Ocean Resorts — Retaining Wall Footer
5101 Highway A1A
Fort Pierce, Florida
KSM Project #: 190553-wc
Dear Mr. Dunlap:
As requested, KSM Engineering & Testing has performed a subsurface investigation for
the referenced project. The investigation was performed in accordance with generally
accepted soil and foundation engineering practices and Section 1800 of the latest
Florida Building Code. The purpose of this investigation was to evaluate the near
surface soils with respect to the proposed project and to estimate the allowable bearing
pressure of the soil.
The site investigation program consisted of performing one (1) dynamic cone
penetration test boring from existing grade to a depth of 7 feet. In addition, two (2)
hand auger borings were performed to inspect the consistency of the subsurface soils.
During the portable dynamic penetrometer test, a 35 lb. (16 kg) safety hammer is lifted
and allowed to fall 15 in. (38 centimeters). Hammer blows are counted by the operator
for each 10 centimeters of penetration with the counting facilitated by scribes spaced at
10 centimeters on each 1 meter long rod. Blows per 10 centimeter of penetration,
dynamic cone resistance and equivalent SPT 'N' values are measured and shown on
the attached logs. Please refer to the soil boring logs for specific information relative to
the soil description.
Based on the information obtained from this site investigation, we are pleased to offer
the following evaluation:
Dynamic Cone Penetrometer readings recorded during the investigation indicates that
the existing soil density is too loose to be considered satisfactory for the project. The
soils can support the proposed retaining wall so long as our 'site preparation
recommendations are followed.
Ronald G. Keller, P.E.: 37293 / SI Lic. No.: 860 / Julie E. Keller, P.E.: 68366
V1 Aff
NJ AA
KELLER, SCHLEICHER & MacWILLIAM ENGINEERING AND TESTING, INC.
MARTIN (772) 337-7755 P.O. BOX 78-1377, SEBASTIAN, FL 32978-1377 SEBASTIAN (772) 589-0712
PALM BEACH (561) 845-7445 www.ksmengineering.net MELBOURNE (321) 768-8488
FAX (561) 845-8876 E-Mail: KSM@KSMENGINEERING.NET ST. LUCIE (772) 229-9093
C.A.: 5693 FAX (772) 589-6469
5101 Highway A1A -2- February 7, 2019
Fort Pierce, Florida
Foundation:
Based on the existing soil conditions, it is our professional opinion, that the proposed
structure can be supported on conventional concrete, steel reinforced footings designed
for an allowable soil bearing pressure of 2,000 pounds per square foot, or less provided
that the site is properly prepared as recommended below.
Site Preparation:
In the footings, the disturbed footing subgrade should be recompacted to 95 percent
(minimum) of its modified dry Proctor value. This can be best achieved by using a
"jumping jack" compactor. This will tighten the top 3 feet of the very loose soils.
Closure:
This report has been prepared in accordance with generally accepted soil and
foundation engineering practices based on the results of the test borings and the
assumed loading conditions. No warranties, either expressed or implied, are intended
or made. This report does not reflect any variations which may occur between the
borings. If variations appear evident during the course of construction, it would be
necessary to re-evaluate the recommendations of this project.
Environmental conditions, wetland delineation, water quality, and municipal
requirements are not a part of this report.
We esr' ' ��of assistance to you on this phase of your project. When we may
be��def •, `�V._,S i��Ap you or should you have any questions, please feel free to
c@11t�•L�. C'•• 9 .
JEK:jt
E-mail to: drewdunlap@dunlap-construction.com
Ronald G. Keller, P.E.: 37293 / SI Lic. No.: 860 ! Julie E. Keller, P.E.: 68366
UP 2L 9
lJ♦ra
KELLER, SCHLEICHER & MacWILLIAM ENGINEERING AND TESTING, INC.
MARTIN (772) 337-7755 R O. BOX 78-1377, SEBASTIAN, FL 32978-1377 SEBASTIAN (772) 589-0712
PALM BEACH (561) 845-7445 www.ksmengineering.net MELBOURNE (321) 768-8488
FAX (561) 845-8876 E-Mail: KSM@KSMENGINEERING.NET ST. LUCIE (772) 229-9093
C.A.: 5693 FAX (772) 589-6469
February 7, 2019
Drew Dunlap
Dunlap Construction Group LLC
1708 Old Dixie Highway
Vero Beach, Florida 32960
Re: Ocean Resorts
5101 Highway A1A
Fort Pierce, Florida
Permit #: 1812-0035
KSM Project#: 190553-1d
Dear Mr. Dunlap:
SCANNED
BY
St. Lucie County
Enclosed, please find the nuclear density test results performed on the footers at the
lease feel free to contact us.
JEKlt
E-mail to: drewdunlap@dunlap-construction.com; St. Lucie County Building Department
Ronald G. Keller, P.E.: 37293 / SI Lie. No.: 860 / Julie E. Keller, P.E.: 68366
UP C 1 t
A%FJAVi
KELLER, SCHLEICHER & MacWILLIAM ENGINEERING AND TESTING, INC.
MARTIN (772) 337-7755 P.O. BOX 78-1377 SEBASTIAN FL 32978-1377 SEBASTIAN (772) 589-0712
PALM BEACH (561) 845-7445 www.ksmengineering.net � MELBOURNE (321) 768-8488
FAX (561) 845-8876 E-Mail: KSM@KSMENGINEERINCI T ST. LUCIE (772) 229-9093
C.A.: 5693 3 FAX (772) 589-6469
February 7, 2019 o a m
Drew Dunlap
Dunlap Construction Group LLC
1708 Old Dixie Highway
Vero Beach, Florida 32960
Re: Ocean Resorts — Retaining Wall Footer
5101 Highway A1A
Fort Pierce, Florida
KSM Project #: 190553-wc
Dear Mr. Dunlap:
As requested, KSM Engineering & Testing has performed a subsurface investigation for
the referenced 'project. The investigation, was performed,in accordance with generally
accepted soil and foundation engineering practices and Section 1800 of the latest
Florida Building Code. The purpose of this investigation was to evaluate the near
surface soils with respect to the proposed project and to estimate the allowable bearing
pressure of the soil.
The site investigation program consisted of performing one (1) dynamic cone
penetration test boring from existing grade to a depth of 7 feet. In addition, two (2)
hand auger borings were performed to inspect the consistency of the subsurface soils.
During the portable dynamic penetrometer test, a 35 lb. (16 kg) safety hammer is lifted
and allowed to fall 15 in. (38 centimeters). Hammer blows are counted by the operator
for each 10 centimeters of penetration with the counting facilitated by scribes spaced at
10 centimeters on each 1 meter long rod. Blows per 10 centimeter of penetration,
dynamic cone resistance and equivalent SPT 'N' values are measured and shown on
the attached logs. Please refer to the soil boring logs for specific information relative to
the soil description.
Based on the information obtained from this site investigation, we are pleased to offer
the following evaluation:
Dynamic Cone Penetrometer readings recorded during the investigation indicates that
the existing soil density is too loose to be°considered satisfactory for the project. The
soils can support the proposed retaining wall so long as our site preparation
recommendations are followed.
0
0
Ronald G. Keller, P.E.: 37293 / SI Lic. No.: 860 / Julie E. Keller, P.E.: 68366
Tip C 19
R1JAW
KELLER, SCHLEICHER & MacWILLIAM ENGINEERING AND TESTING, INC.
MARTIN (772) 337-7755 P.O. BOX 78-1377, SEBASTIAN, FL 32978-1377 SEBASTIAN (772) 589-0712
PALM BEACH (561) 845-7445 www.ksmenginearing.net MELBOURNE (321) 768-8488
FAX (561) 845-8876 E-Mail: KSM@KSMENGINEERING.NET ST. LUCIE (772) 229-9093
C.A.: 5693 FAX (772) 589-6469
5101 Highway A1A
Fort Pierce, Florida
Foundation:
-2-
SCANNED
BY
St. Lucie County
February 7, 2019
Based on the existing soil conditions, it is our professional opinion, that the proposed
structure can be supported on conventional concrete, steel reinforced footings designed
for an allowable soil bearing pressure of 2,000 pounds per square foot, or less provided
that the site is properly prepared as recommended below.
Site Preparation:
In the footings, the disturbed footing subgrade should be recompacted to 95 percent
(minimum) of its modified dry Proctor value. This can be best achieved by using a
'jumping jack' compactor. This will tighten the top 3 feet of the very loose soils.
Closure:
This report has been prepared in accordance with generally accepted soil and
foundation engineering practices based on the results of the test borings and the
assumed loading conditions. No warranties, either expressed or implied, are intended
or made. This report does not reflect any variations which may occur between the
borings. If variations appear evident during the course of construction, it would be
necessary to re-evaluate the recommendations of this project.
Environmental conditions, wetland delineation, water quality, and municipal
requirements are not a part of this report.
We
be.
OF
JEK:jt
of assistance to you on this phase of your project. When we may
Q9 you or should you have any questions, please feel free to
E-mail to: drewdunlap@dunlap-construction.com
Ronald G. Keller, P.E.: 37293 / SI Lic. No.: 860 / Julie E. Keller, P.E.: 68366