HomeMy WebLinkAboutPROJECT INFORMATIONSCANNED
BY
St. Lucie County
PRO -DUCT
SERVICES
BLOWERDOOR&DUCTLEAKAGETESTING
TESTING -ADJUSTING -BALANCING
RECEwzo
JAN 27 202U
Pent n9 Oe
s. i ucr4 rouunty
TESTING, ADJUSTING & BALANCING REPORT
for
STAN WEEKS & ASSOCIATES
EDWARM LAMING
BUILDING 9-
31M., 3130, 313Z MM,, 3136, 3138MorningDOW Lane
Fort Pierce, FL 34982
January 27, 2020
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES f i i
T ,cymroh. 1
'� I ��Certlfled�C
Pro -Duct Services, 1915 Rio Vista R64 Fort Pierce, FL 34949
772.528.2076 pro-ductservicesfl@gmail.com
PRO -DUCT
SERVICES
BLOWER DOOR& OUCTLEAKAOETESTINO
TESTING -ADJUSTING -BALANCING
TEST & BALANCE INSTRUMENTS
Evergreen Telemetry Capture Hood 1513:
Range: 100-2500 CFM
Accuracy: +/- 3%
Calibration: May 17, 2019
Evergreen Telemetry Capture Hood 8D-14:
Range: 15-200 CFM
Accuracy: +/- 3%
Calibration: May 29, 2019
Evergreen Pressure/Velocity/Flow Sensing Module —Model S-PVF-1:
Range: 1-2, 14-32 inches HG, 32° -158° F
Accuracy: +/- 3%
Calibration: June 5, 2019
Evergreen Wrist Reporter WR-401
Pro -Dud Services Technician: Michael Faurot
Certified NCI Contractor/Supervisor/Technician
NCI Commercial Certification ID: 19-229-03
— Equipment re -calibration is performed as required by testing guidelines. —
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJl@gmaii.com
certmed
tufnercial Air Balancer
MICHAEL FAUROT
Has successfully completed the required training and passed
the written exam by the
NatiDR61 iC0111101 hu, [tile, Jim
to perform HVAC commercial system balancing up to 20 tons
according to NO practical standards and procedures.
CertiFied Since
May 9, 2019
Cortifleas administered and recognized by
fanmerUY.Weatnm �.
140
r , no at cm ro e mstnute,nw Rob Falke, President
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesjl@gmail.com
",0AWb*4k
PRO -DUCT
SERVICES
BLOWERDOOR& DUCT LEAKAGETESTING
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 9
3128 Morning Dove Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
Size
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
27
27
Kitchen/Living Rm
2
CD
10 x 10
160
182
164
Bathroom
3
CD
8 x 4
i5
31
22
Bedroom 1
4
CD
12 x 8
180
160
167
Bedroom 2 Vent 1
5
CD
10 x 10
125
110
114
Bedroom 2 Vent 2
6
CD
10 x 10
125
107
109
TOTAL
635
603
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS I requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesfl@gmail.com
PRO-OUCT
SERVICES
BLOWERDOOR& DUCTLEAKAGE TESTING
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 9
3130 Morning Dove Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
size
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
41
30
Kitchen/Living Rm
2
CD
10 x 10
160
163
163
Bathroom
3
CD
8 x 4
15
29
27
Bedroom 1
4
CD
12 x 8
180
171
171
Bedroom 2 Vent 1
5
CD
10 x 10
125
91
109
Bedroom 2 Vent 2
6
CD
10 x 10
125
86
112
TOTAL
635
612
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS I requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES i i F
Pro -Duct Services, 1915 Rio Vista Ri4 Fort Pierce, FL 34949
772.528.2076 pro-ductservicesfl@gmail.com
PRO -DUCT
SERVICES
BLOWERDOOR& DUCTLEAKAGETESTING
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 9
3132 Morning Dove Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
Size
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
31
31
Kitchen/Living Rm
2
CD
10 x 10
160
160
160
Bathroom
3
CD
8 x 4
i5
32
26
Bedroom 1
4
CD
12 x 8
180
167
167
Bedroom 2 Vent 1
5
CD
10 x 10
125
109
109
Bedroom 2 Vent 2
6
CD
10 x 30
1 125
101
108
TOTAL
635
601
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesjl@gmaiLcom
I
PRO-OUCT
SERVICES
BLOWERDOOR& DUCTLEAKAGETESTING
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 9
3134 Morning Dove Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
Slice
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
i
CD
8 x 4
30
32
32
Kitchen/Living Rm
2
CD
10 x 10
160
158
is5
Bathroom
3
CD
8 x 4
15
24
24
Bedroom 1
4
CD
12 x 8
180
165
167
Bedroom 2 Vent 1
5
CD
10 x 30
125
108
109
Bedroom 2 Vent 2
6
CD
lox 10
125
109
112
TOTAL
635
599
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NO STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJl@gmaiLcom
I — 0- "Wt4 k
PRO -DUCT
SERVICES
BLOWERDOOR& DUCTLEAKAOETESTINO
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 9
3136 Morning Dove Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
size
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
9
32
Kitchen/Living Rm
2
CD
10 x 10
160
150
161
Bathroom
3
CD
8 x 4
15
38
29
Bedroom 1
4
CD
12 x 8
180
182
176
Bedroom 2 Vent 1
5
CD
10 x 30
125
113
113
Bedroom 2 Vent 2
6
CD
10 x 10
125
104
108
TOTAL
635
619
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS I requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista Rd Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJl@gmail.com
kk "�4_eiv4k
PRO -DUCT
SERVICES
BLOWERDOOR&DUCT LEAKAOETESTINO
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 9
3138 Morning Dove Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
Size
Design
CFM
pre'Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
28
28
Kitchen/Living Rm
2
CD
10 x 10
160
167
162
Bathroom
3
CD
8 x 4
15
35
25
Bedroom 1
4
CD
12 x 8
180
171
171
Bedroom 2 Vent 1
5
CD
10 x 10
125
107
111
Bedroom 2 Vent 2
6
CD
30 x 10
1 125
1 93
308
TOTAL
635
605
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS I requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista Rit Fort Pierce, FL 34949
772.528.2076 pro-ductservicesjl@gmaii.com
PRO -DUCT
SERVICES
BLOWER DOOR& DUCTLEAKAGETESTING
TESTING -ADJUSTING -BALANCING
TESTING, ADJUSTING, & BALANCING WARRANTY
for
Jtan Weeks AAssociates
Edwards Landing —BUILDING 9
All Testing, Adjusting, & Balancing performed on this project by Pro -Duct Services is under
warranty for a period of One Year from the date of completion of the Test & Balance, unless
otherwise noted. Warranty will be considered null and void if another TAB company is
brought in to evaluate the project without notifying Pro -Duct Services to be present at the
time of the additional testing.
Date of TAB Testing: 01/24/2020
Pro -Duct Services Authorized Signature:
Pro -Duct Services Technician:
Warranty Expiration Date: 01/31/2021
Michael Faurot
Certified NCI Contractor/Supervisor/Technician
NCI Commercial Certification ID: 19-229-03
BPI Certification ID: 5059122
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
avmro,:.�
,•,�'' pC rxrtlrledN
re.u+uw..r
BPI w,,.a,m
/cc
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservices,J1@gmail.com
PRO -DUCT
SERVICES
BLOWERDOOR& DUCT LEAKAGE TESTING
TESTING -ADJUSTING -BALANCING
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJl@gmaii.com
0 —0'
Planning & Development Services
Building &'Code Regulation Division
2300 Virginia Ave
Fort Pierce, FL 34982
772-462-2165 Fax 772-462-6443
Request for 30-Day Temporary Power
Date: 1) 1 )q) Ig Permit Number:
Project Address:
3128-3138 'Moming Dew
181
Ft. Pierce, FL 34981
THE UNDERSIGNED HEREBY REQUEST RELEASE OF ELECTRICAL POWER TO THE ABOVE DESCRIBED
PROPERTY, FOR A PERIOD NOT TO EXCEED THIRTY (30) DAYS, FOR THE PURPOSE OF TESTING SYSTEMS
AND EQUIPMENT, IN PREPARATION FOR A FINAL INSPECTION. IN CONSIDERATION OF APPROVAL OF THE
REQUEST WE HEREBY ACKNOWLEDGE AND AGREE AS FOLLOWS:
1. This temporary power release is requested for the above stated purpose only, and there will be no
occupancy of any .type, other than that permitted by construction during this time, period.
2. As witness by our signatures, we hereby agree to abide by all terms and conditions of this agreement,
including. Building Division Policy, which Is incorporated herein by reference.
3. All conkons and requirements fated in the attached document entitled ".Requirements for 30 Day
Power for Testing" have been fulfilled and the premise is ready for compliance inspection.
4. All requests for an extension beyond 30 days must bef made in writing to the Building Officlal stating
the reason for the request. Power may be removed from the site and/or a Stop Work Order issued if
the Final Inspection
as not been approved within 30 days. A fee of $100.00 wili�be required to rift
the Stop Work
WE HEREBY RELEASE -AND AGREE TO HOLD ,HARMLESS,.ST.'LUCIE COUNTY, AND THEIR EMPLOYEES FROM
ALL LIABI ES AND CLAIMS OF ANY TYPE OF NATURE WHICH MAY ARISE NOW ORdN THE FUTURE OUT
OF IS NSACTION, INCLUDING ANY DAMAGE WHICH MAY BE INCURRED DUE TO THE
D N E ON:OF ELECTRICAL POWER IN THE EVENT OF VIOLATION OF THIS AGREEMENT.
c) lq
DATE
SCANNED
BY
St. Lucie County
Fort Pie --a Utilities
206 S 61 Street
Fort Pierce, FL 34950
On Behalf of:
EDWARDS LANDING, LLC
2324 CONGRESS AVE STE 2E
WEST PALM BEACH FL 33406-7668
USA
Authority ',L�
Receipt Number: PYMT00005555603
Receipt Date: 10/18/2017
Customer ID: 250040
Location ID: 10007193
Re Service Address:
2503 EDWARDS RD PVT LIFT STA
FORT PIERCE FL 34981
USA
RECEIVED
OCT 1 5 2019
ST. Lucie County, Permitting
Total Amount Received by Check
SCANNED
BY
St. Lucie County
$5,000.00
Fort Pie.' 1a Utilities Authority
206 S Gt\__.'Street
Fort Pierce, FL 34950
On Behalf of:
EDWARDS LANDING, LLC
2324 CONGRESS AVE STE 2E
WEST PALM BEACH FL 33406-7668
USA
r�
Receipt Number:
Receipt Date:
Customer ID:
Location ID:
Re Service Address:
'PYMT00005555602
10/18/2017
250040
10007193
2503 EDWARDS RD PVT LIFT STA
FORT PIERCE FL 34981
USA
Total. Amount Received by Check $215,906.55