HomeMy WebLinkAboutFIELD AND LABORATORY REPORTUNIVERSAL
tuENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 329SS - P: 321.638.0808 - F: 321.638.0978
UES Project No.: 0310.1800244.0000
Date Typed: December 28, 2018
Construction Materials Testing Services ✓'
FIELD AND LABORATORY REPORT COVER PAGE s �4i� y9-P
Client: Vertical Construction Management cI,po a
1209 South White Chapel Boulevard Suite 180 °off Pit
Southlake, TX 76092
Project: Burger King #25281 Restauraunt
6598 South US Highway 1 (Rib Shack VP576) Kitterman,Port St. Lucie, St. Lucie County, FL
As requested, Universal Engineering Sciences, Inc. (UES) representative(s) performed construction materials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Work Order No.
Date
Type of Report
104527-1
12118/20181
Field Inspection Report
104528-1
1 12118/20181
Field Inspection Report
We hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the undersigned.
SCANNED
BY
St. Lucie County
ICC Email: cvaughn@verticalcm.com
Sincerely,
Universal
Certificate
J ' JZ
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
UNIVERSAL
NJENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmentat5ciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection &Plan Review
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
LIES Project No:
LIES DOCS No:
LIES Report No:
0310.1800244.0000
03-104528
On -Site Time (hrs): 1.25
Lab Time (hrs): 0.00
Travel Time (hrs): 1.00
Total Time (hrs): 2.25
Inspection Report
Client: Vertical Construction Management
1209 South White Chapel Boulevard Suite 180
Southlake, TX 76092
Project: Burger King #25281 Restauraunt
6598 South US Highway 1 (Rib Shack VP576) Kitterman,Port St. Lucie, St. Lucie
County, FL
Date of Activity: 12/18/2018
Technician: Cliff
As Requested, a Universal Engineering Sciences Technician was present at the above referenced location for the purpose
of Performed 3 DCPS tests to a depth of 3 feet on site wall footing. The test results show that the site wall footing bearing
soils can provide 3000 psf allowable bearing.
UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering 9 Environmental Sciences
Geophysical Services 9 Materials Testing 9 Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
LIES Project No: 0310.1800244.0000
LIES DOCS No:
LIES Report No: 03-104527
On -Site Time (hrs): 1.25
Lab Time (hrs): 0.00
Travel Time (hrs): 1.25
Total Time (hrs): 2.50
Inspection Report
Client: Vertical Construction Management
1209 South White Chapel Boulevard Suite 180
Southlake, TX 76092
Project: Burger King #25281 Restauraunt
6598 South US Highway 1 (Rib Shack V13576) Kitterman,Port St. Lucie, St. Lucie
County, FL
Date of Activity: 12118/2018
Technician: Ryan Richardson
As Requested, a Universal Engineering Sciences Technician was present at the above referenced location for the purpose
of assisting Cliff with dcps testing.
Universal Engineering Sciences
820 Brevard Avenue, Rockledge, FL 32955
Tested For. Project: _ BN C"-lCr�iy,.
Man rrienf ;�52 resIfa:-g
Date: 1 — Project No.: 09/01fg 00 2YLI'0000
Limited Field Exploration Report
with hand auger
UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
UES Project No.: 0310.1800244.0000
Date Typed: January 22, 2019
Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE
c
Client: Vertical Construction Management ✓4 ��Fa
1209 South White Chapel Boulevard Suite 180 r y2 �,
Southlake, TX 76092 st 4i� fir
!G"9pc'n O
Project: Burger King #25281 Restauraunt
6598 South US Highway 1 (Rib Shack VP576) Kitterman,Port St. Lucie, St. Lucie County, FL
As requested, Universal Engineering Sciences, Inc. (LIES) representative(s) performed construction materials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Work Order No.
Date
I Type of Report
105433-1
01/11/2019
4" x 8" Cylinder Test Specimens Report w/Activity Record
106003-1
1 01/16/2019
In -Place Density Test Report w/Activity Record
We hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the undersigned.
Attachments (2)
ICC Email: cvaughn@verticalcm.com
Sincerely,
Universal Engiriee
Certificate ofA.uthoi
L
ng Sciences, Inc.
Eation No: 00000549
C
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
This item has been electronically signed and sealed by
Richard E. Hoaglin, P.E. using a Digital Signature. Printed
copies of this document are not considered signed and
sealed and the signature must be veriffed on any electronic
copies.
'Revised May 2015
17 F?! I L C, .0 P `�
UES Project
UNIVERSAL ULIES DCS
ES Report Noo:' 105433 1 ARC 01110
019
ENGINEERING SCIENCES On -Site Time (hrs):2.50
Consultants In: Geotechnical Engineering a Environmental Sciences Lab Time (hrs): 0.00
Geophysical Services • Materials Testing , Threshold Inspection Travel Time (hrs): 1.00
Building Code Administration, Compliance Inspection & Plan Review Total Time (hrs): 3.50
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Vertical Construction Management
1209 South White Chapel Boulevard Suite 180
Southlake, TX 76092
Project: Burger King #25281 Restauraunt
6598 South US Highway 1 (Rib Shack VP576) Kitterman,Port St. Lucie, St. Lucie County, FL
Date of Activity: Friday, 11 January, 2019
Technician: Russell Brause
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
concrete testing for the Cross walk..
While on site, the technician observed the general condition of the areas to be tested and cast 1 set(s) of 4 - 4 x 8 specimen(s)
for compressive strength testing. The concrete tested on this day was found to be in accordance with the project plans and
specifications with regard to batch time, slump, and temperature.
As Requested, a Universal Engineering Sciences Technician was present at the above referenced location for the purpose of
concrete testing. Informed by contractor truck to be delayed 2 Hrs or longer dropped cylinders.
UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Compressive Strength of
4" x 8" Cylinder Test Specimens
(ASTM C-39)
Project No: 0310.1800244.0000
ReportNo.: 105433-1 CT 011119
WorkorderNo.: 105433
Lab No.:
Client Vertical Construction Management
1209 South White Chapel Boulevard
Suite 180, Southlake, TX 76092
Project Burger King #25281 Restauraunt
6598 South US Highway 1 (Rib Shack VP576) Kitterman,Port St. Lucie, St.
Lucie County, FL
Structural Element: Slab on Grade
Sample Location: Crosswalk.
Set# 1 of 1 1 Sample From: Concrete Truck
Sample By: Russell Brause On 01/11/2019 At Lab On or Before: 01/21/2019 i
General Information
Specified Strength / Sampling Times
Placement Information
General Contractor: -
Specified Strength: 3000 psi @ 28 days
Truck Load: 5.00 cu yds.
Subcontractor:
Mix Design Strength: 3000 psi @ 28 days
Cumulative Quantity: 5.00 cu yds.
Supplier: MASCHMEYER
Water Added at Site: NIA
Total Placement for the Day: 5.00 cu yds.
Truck No.: 437
Time Batched: 12:33 P.M.
Ticket No.: 2442235
Time Sampled: 1:27 P.M.
Mix Design: 30810000 Admixture:0
Weather Condition: Sunny
Field Test Results
Air Content: N/A Slump: 5.00 inches I Ambient Temp: 71 OF I Concrete Temp: 84 OF Unit Weight: NIA
Results of Laboratory Testing
Type
Actual
Actual
Avg.
Test
Max
Test
Test
Date
Age
Of
Dimen.1
Dimen.2
Dimen.
XSect.
Compressive
Compressive
Average
Results
Tested
Days
Fracture
(in)
(in)
(in)
Area (in')
Load (Ibs)
Strength(psi)
(psi)
1
01/21/2019
10
5
4.00
4.02
4:01
12.63
34,313 '
2,720
-
2
02/08/2019
28
-
-
-
-
-
-
-
-
3
02/08/2019
28
-
-
-
-
-
-
-
-
4
02/08/2019
28
-
-
-
-
-
-
-
-
Remarks
This form conforms with ASTM C39, Sampling and testing procedures were performed in general compliance with ASTM C31, C138,
C143, C172, C231, C511, C617, C1064, C1231, C42, C157, C192, C403 and/or C496 as applies. If an air test was not completed, that
deviates from C31 procedure. During initial field curing; some samples are kept at temperatures outside the allowable range, allowed to
dry, or are left in the field for longer than 24 hours. This is a deviation of ASTM C31 procedures. This report shall not be reproduced,
except in full, without the written approval of Universal Engineering Sciences.
1 of 1 Revised May 2018
LIES Project No: 310.1800244.00
00
UNIVERSAL LIES DCS
UES Report Noo: 106003 1 A C 01619
ENGINEERING SCIENCES On -Site Time (hrs): 1.00
Consultants In: Geotechnical Engineering @ Environmental Sciences Lab Time (hrs): 0.00
Geophysical Services 9 Materials Testing • Threshold Inspection Travel Time (hrs): 1.00
Building Code Administration, Compliance Inspection &Plan Review Total Time (hrs): 2.00
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Vertical Construction Management
1209 South White Chapel Boulevard Suite 180
Southlake, TX 76092
Project: Burger King #25281 Restauraunt
6598 South US Highway 1 (Rib Shack VP576) Kitterman,Port St. Lucie, St. Lucie County, FL
Date of Activity: Wednesday, 16 January, 2019
Technician: Russell Brause
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the Retaining Wall.
While on site, the technician observed the general condition of the areas to be tested and performed 3 density test(s) for
Retaining Wall.. All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to
meet the project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
As Requested, a Universal Engineering Sciences Technician was present at the above referenced location for the purpose of
picking up cylinder cast.
UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
UES Project No: 0310.1800244.0000
UES DOCS No:
UES Report No: 106003-1 DT 011619
In -Place Density Test Report
Client: Vertical Construction Management
1209 South White Chapel Boulevard Suite 180
Southlake, TX 76092
Project: Burger King #25281 Restauraunt
6598 South US Highway 1 (Rib Shack VP576) Kitterman,Port St. Lucie, St. Lucie
County, FL
Area Tested: Retaining Wall.
Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 01/16/2019
Lab: ASTM D1557 Modified Proctor
Technician: Russell Brause
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or sulflcial soil conditions
only and do not address the condition of the underlying soils below the tested depths.
Field Dry
Field
Test
Depth
Proctor
Density
Moisture
%
Comments
No.
Location of Test
Range
(inch)
(2)
(PCF)
%
Compaction
(3)
1.
E side ctr.
0 to -1 it
12.00
22405
112.7
9.4.
100
A
2
N side ctr.
0 to -1 ft
12.00
22405
113.0
7.4
100
A
3
S side ctr.
0 to -1 ft
12.00
22405
112.5
9.1
100
A
(1) Ref. Datum: 0 = Top of Footing
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
22405
113.0
10.5
This test was performed without deviation from ASTM procedures.
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
UNIVERSAL UES Project No: 0310.1800244.0000
UES DOCS No:
UES Report No: 106003-1 ARC 011619
ENGINEERING SCIENCES On -Site Time (hrs): 1.00
Consultants In: Geotechnical Engineering 9 Environmental Sciences Lab Time (hrs): 0.00
Geophysical Services • Materials Testing a Threshold Inspection Travel Time (hrs): 1.00
Building Code Administration, Compliance Inspection & Plan Review Total Time (hrs): 2.00
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Vertical Construction Management
1209 South White Chapel Boulevard Suite 180
Southlake, TX 76092
Project: Burger King #25281 Restauraunt
6598 South US Highway 1 (Rib Shack VP576) Kitterman,Port St. Lucie, St. Lucie County, FL
Date of Activity: Wednesday, 16 January, 2019
Technician: Russell Brause
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose
of earthwork testing for the Retaining Wall footing.
While on site, the technician observed the general condition of the areas to be tested and performed 3 density test(s) for
Retaining Wall.. All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to
meet the project compaction requirements of 95% of the maximum dry density per ASTM D-1557. .
As Requested, a Universal Engineering Sciences Technician was present at the above referenced location for the purpose of
picking up cylinder cast.
U N I V E R S A L LUES Project
IES DOCS Noo: 0310.1800244.0000
ENGINEERING SCIENCES UESReportNo: 106003-1 DT011619
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
In -Place Density Test Report
Client: Vertical Construction Management
1209 South White Chapel Boulevard Suite 180
Southlake, TX 76092
Project: Burger King #25281 Restauraunt
6598 South US Highway 1 (Rib Shack VP576) Kitterman,Port St. Lucie, St. Lucie
County, FL
Area Tested: Retaining W footing
Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 01/16/2019
Lab: ASTM D1557 Modified Proctor
Technician: Russell Brause
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the underlyinq soils below the tested depths.
Field Dry
Field
Test
Depth
Proctor
Density
Moisture
%
Comments
No.
Location of Test
Range
(inch)
(2)
(PCF)
%
Compaction
(3)
1
E side ctr.
0 to -1 ft
. 12.00
22405
112.7
9.4
100
A
2
N side ctr.
0 to -1 ft
12.00
22405
113.0
7.4
100
A
3
S side ctr.
0 to -1 ft
12.00
22405
112.5
9.1
100
A
(1) Ref. Datum: 0 = Bottom of Footing
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
22405
113.0
10.5
This test was performed without deviation from ASTM procedures.
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.