HomeMy WebLinkAboutMISCIN
PRO -DUCT
SERVICES
BLOWER DOOR&DUCT LEARAGETESTING
TESTING -ADJUSTING -BALANCING
-M9
RECEIVED
1A% %7 1010
Permitting p�u
St. LUCi¢
TESTING, ADJUSTING & BALANCING REPORT
for
STAN WEEKS & ASSOCIATES
EDWARDf LANDING
—BUILDING 10-
314Z 3144, 3146, 3148, 3150, 3152 Morning Dove Lane
Fort Pierce, FL 34982
SCANNED
BY
St. Lucie County
January 27, 2020
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES +++
Pro-Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJl@gmail.com
",eAjbW4lljk
PRO -DUCT
SERVICES
BLOWERDOOR& DUCT LEAKAOETESTINO
TESTING -ADJUSTING -BALANCING
TEST & BALANCE INSTRUMENTS
Evergreen Telemetry Capture Hood 151):
Range: 100-2500 CFM
Accuracy: +/- 3%
Calibration: May 17, 2019
Evergreen Telemetry Capture Hood 8D-14:
Range: 15-200 CFM
Accuracy: +/- 3%
Calibration: May 29, 2019
Evergreen Pressure/Velocity/Flow Sensing Module —Model S-PVF-1:
Range: 1-2, 14-32 inches HIS, 32' -158' F
Accuracy: +/- 3%
Calibration: June 5, 2019
Evergreen Wrist Reporter WR-401
Pro -Dud Services Technician: Michael Faurot
Certified NCI Contractor/Supervisor/Technician
NCI Commercial Certification ID: 19-229-03
— Equipment re -calibration is performed as required by testing guidelines. —
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJl@gmail.com
Ee d
Commercial aloe° Balancer
MICHAEL FAUROT
Has successfully completed the required training and passed
the written exam by the
Noting] iCo durl h1su e, I11c,
to perform HVAC commercial system balancing up to 20 tons
according to NO practical standards and procedures.
Certified Since
toa eL as administered and recognized by
CNnTtMilAbfcb�tt/ L»'
C-011]]0.1] IY /
ETra 553021
Ala at C=nwr mts 1;u Me Rob Falke, President
Pro -Duct Services, 1915 Rio Vista At Fort Pierce, FL 34949
772.528.2076 pro-ductservices/1@gmail.com
r'40,00 AW
PR0-DUCT
SERVICES
BLOWERDOOR& DUCTLEAKACETESTING
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 10
3142 Morning Dove Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
flue
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
41
38
Kitchen/Living Rm
2
CD
10 x 10
160
172
156
Bathroom
3
CD
8 x 4
15
33
26
Bedroom 1
4
CD
12 x 8
180
181
181
Bedroom 2 Vent 1
5
CD
10 x 10
125
109
109
Bedroom 2 Vent 2
.6
CD
10 x 10
125
114
114
TOTAL
635
624
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS I requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista Rit Fort Pierce, FL 34949
772.528.2076 pro-ductservicesfl@gmailcom
"'o-Ambliv4k
PRO-OUCT
SERVICES
BLOWERDOOR& DUCTLEAKAOETESTINO
i
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 10
3144 Morning Dove Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
size
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
31
31
Kitchen/Living Rm
2
CD
10 x 10
160
181
162
Bathroom
3
CD
8 x 4
15
37
30
Bedroom 1
4
CD
12 x 8
180
142
168
Bedroom 2 Vent 1
5
CD
10 x 10
125
101
108
Bedroom 2 Vent 2
6
CD
10 x 10
1 125
123
111
TOTAL
635
610
FAN DATA Panasonic Whispergreen Model FV-05-IIUSK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS requirements.
... ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJl@gmail.com
PRO -DUCT
SERVICES
BLOWERDOOR& DUCTLEAKABETESTINO
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 10
3146 Morning Dove Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
Size
Design
CPM
Pre Test
CPM
FINAL
CFM
Entrance
1
CD
8 x 4
30
31
31
Kitchen/Living Rm
2
CD
10 x 10
160
196
168
Bathroom
3
CD
8 x 4
15
37
29
Bedroom 1
4
CD
12 x 8
180
151
162
Bedroom 2 Vent 1
5
CD
10 x 10
125
91
108
Bedroom 2 Vent 2
6
CD
30 x 10
125
102
113
TOTAL
635
611
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
" Mechanical components working as designed and match plan
COMMENTS requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJl@gmail.com
PRO -DUCT
SERVICES
BLOWERDOOR& DUCTLEAKAGETESTING
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 10
3148 Morning Dove Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
Site
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
32
32
Kitchen/Living Rm
2
CD
10 x 10
160
151
151
Bathroom
3
CD
8 x 4
15
41
32
Bedroom 1
4
CD
12 x 8
180
163
165
Bedroom 2 Vent 1
5
CD
10 x 10
125
102
119
Bedroom 2 Vent 2
6
CD
10 x 10
125
98
107
TOTAL
635
606
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesfl@gmail.com
n
PRO -DUCT
SERVICES
BLOWERDOOR& DUCTLEAKAGETESTING
TESTING-ADJUSTING-BAIANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 10
3150 Morning Dove Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
Size
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
i
CD
8 x 4
30
27
29
Kitchen/Living Rm
2
CD
10 x 30
160
178
171
Bathroom
3
CD
8 x 4
1s
37
28
Bedroom 1
4
CD
12 x 8
180
162
168
Bedroom 2 Vent 1
5
CD
SO x 10
125
116
116
Bedroom 2 Vent 2
6
CD
30 x 10
125
112
112
TOTAL
635
624
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista At Fort Pierce, FL 34949
772.528.2076 pro-ductservicesj!@gmail.com
",OAnm�k
PRO -DUCT
SERVICES
BLOWERDOOR& DUCT LEAKAOETESTINO
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 10
3152 Morning Dove Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
site
Design
CFM
Pre West
CFM
FINAL
CFM
Entrance
i
CD
8 x 4
30
31
31
Kitchen/Living Rm
2
CD
10 x 10
160
153
153
Bathroom
3
CD
8 x 4
15
35
29
Bedroom 1
4
CD
12 x 8
180
166
166
Bedroom 2 Vent 1
5
CD
10 x 10
125
107
107
Bedroom 2 Vent 2
6
CD
10 x 10
125
99
105
TOTAL
635
591
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
i COMMENTS I requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NO STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista Ra Fort Pierce, FL 34949
772.528.2076 pro-ductservices,/l@,gmail.com
PRO-OUCT
SERVICES
BLOWERDOOR&DUCT LEAKAGETESTING
TESTING -ADJUSTING -BALANCING
TESTING, ADJUSTING, & BALANCING WARRANTY
for
ftan Weeks do Associates
Edwards Landing —BUILDING to
All Testing, Adjusting, & Balancing performed on this project by Pro -Duct Services is under
warranty for a period of One Year from the date of completion of the Test & Balance, unless
otherwise noted. Warranty will be considered null and void if another TAB company is
brought in to evaluate the project without notifying Pro -Duct Services to be present at the
time of the additional testing.
Date of TAB Testing: 01/24/2020 Warranty Expiration Date: 01/31/2021
Pro -Duct Services Authorized Signature:
Pro -Duct Services Technician:
Michael Faurot
Certified NCI Contractor/Supervisor/Technician
NCI Commercial Certification ID: 19-229-03
BPI Certification ID: SOS9122
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
`j Ccrtlfled�G
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJl@gmailcom
r
PRO -DUCT
SERVICES
BLOWERDOOR & DUCT LEAKAOE TESTINO
TESTING-ADJ U STI N G- BALAN C I N G
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJleagmail.com
Date: -11 to III
Project Address:
Planning & Development Si
Building & Code Regulation
2300'Virginia Ave
Fort Pieme, FL 34982
772-462-2165 fax 772-4
Request for 30-Day Temporary.Powet
Permit Number: 1812-0149
3142-3152 .Morning Dew Lane, Ft. Pierce, FL 34981
THE UNDERSIGNED HEREBY REQUEST RELEASE OF ELECTRICAL' POWER TO THE ABOVE DESCRIBED
PROPERTY, FORIA PERIOD NOT TO EXCEED THIRTY (30) DAYS, FOR THE PURPOSE] OF TESTING SYSTEMS
AND EQUIPMENT IN PREPARATION FOR A FINAL INSPECTION. IN CONSIDERATION' OF APPROVAL OF THE
REQUEST WE HEREBY ACKNOWLEDGE AND AGREE AS FOLLOWS:
1. This temporary power release is requested for the above stated', purpose only, and there will be no
occupanty of any type, other than that permitted by construction during this time period.
2. As witness by our signatures, we hereby agree to abide 'by all terms and' conditions of this agreement,
including Building Division Policy, which is incorporated herein by reference.
3. All conditions and requirements listed In the attached document entitled "Requlre ents for 30 Day
Powerifor Testing" have been fulfilled and the premise Is ready for compliance inspection:
4. All requests for extension -beyond 30 days must be made in writing to the Building Official stating
the reason for the request. Power may be removed from the site and/or a Stop Work Order issued if
the Final Inspection has not been approved within 30 days. A fee of $100.00 will be required to lift
the Stop Work Order.
WE HEREBY RELEASE AND AGREE TO HOLD HARMLESS, ST. LUCIE COUNTY, AND THEIR EMPLOYEES FROM
WlISECr
ES'AND CLAIMS OF ANY TYPE OF NATURE WHICH MAY -ARISE NOW OR IN THE FUTURE OUT
NSACTION, INCLUDING ANY DAMAGE WHICH MAYBE INCURRED DUE TO THE
ON OF ELECTRICAL POWER IN THE EVENT OF VIOLATION OF THIS AGREEMENT.
Ii
SCANNED
BY
St. Lucie County
Fort PJ-rce Utilities
206 S 1' Street
Fort Pierce, FL 34950
on Behalf of:
EDWARDS LANDING, LLC
2324 CONGRESS AVE STE 2E
WEST PALM BEACH FL 33406-7668
USA
Authority _O
Receipt Number: PYMT00005555603
Receipt Date: 10/18/2017
Customer ID: 250040
Location ID: 10007193
Re Service Address:
2503 EDWARDS RD PVT LIFT STA
FORT PIERCE FL 34981
USA
OCT 15 2019
Total Amount Received by Check 5,000.00
ST. Lucie County, permitting
SCANNED
BY
St, Lucie County
Fort P` -ce Utilities Authority
206 S ( _ Street
Fort Pierce, FL 34950
On Behalf of:
EDWARDS LANDING, LLC
2324 CONGRESS AVE STE 2E
WEST PALM BEACH FL 33406-7668
USA
Receipt Number:
Receipt Date:
Customer ID:
Location ID:
Re Service Address:
PYMT00005555602
10/18/2017
250040
10007193
2503 EDWARDS RD PVT LIFT STA
FORT PIERCE FL 34981
USA
Total Amount Received by Check $215,906.55