HomeMy WebLinkAboutTHRESHOLD INSPECTION REPORT— - I N M L Engineering I..,. Consulting Engineers Threshold Inspector 2030 37" Avenue Vero Beach, Florida 32960 Phone: (772) 569-1257 Fax: (772) 569-4041 www.mlengineeringinc.corn PROJECT NAME: CLIENT: CONTRACTOR: Project No. 18-230 Building Official: Project Manager: Contractor: File Report No. 2 Mr. Andrew Manero — SLC Bldg. Dept. Mr. Gene Ross — Elliott Merrill Mr. Bob Stark — Structure -Con Mr. Khris McConnell — Structure -Con THRESHOLD INSPECTION REPORT OCEAN HARBOR NORTH CONDOS — BUILDING E 5167 NORTH HWY. A IA — UNITS 708 & 808 SLCBUILDING PERMIT NUMBER: 1812-0435 Ocean Harbor N. Condos — Bldg E DATE: February 21, 2019 Elliott Merrill Community Mgmt. LOCATION: Ft. Pierce, Florida Structure -Con PROJECT MGR: Mr. Khris McConnell INSPECTED BY: Mike Lue WEATHER: Sunny WORK INSPECTED: Final Inspection at Units 708 & 808 SCANNED BY St. Lucie County OBSERVATIONS The repaired areas of the concrete slabs were waterproofed with Sikaflex cementitious waterproofing and ready for tile. The tile is to be completed by the Owner All structural repairs are completed as indicated in the permitted plans. Ir -�157P %*0- W re - -1 A PL 0' Page I of 2 M L Engineering I Consulting Engineers Threshold Inspector 2030 3711 Avenue Vero Beach, Florida 32960 Phone: (772) 569-1257 Fax: (772) 569-4041 www.mlengineeringine.com Project No. 18-230 Building Official: Project Manager: Contractor: File Pic I Unit 808 Slab edge Report No. 2 Mr. Andrew Manero — SLC Bldg. Dept. Mr. Gene Ross — Elliott Merrill Mr. Bob Stark — Structure -Con Mr. Khris McConnell — Structure -Con Ends of new PT cables that have were stressed, cut and encapsulated with greased end caps Pic 2 Unit 808 floor slab Repaired slab edge, tile and shutter track to be reinstalled by Owner Pic 3 Unit 708 Repaired concrete slab where PT cables were locked off and spliced Page 2 of 2 M L Engineering Inc. Consulting Engineers Threshold Inspector 2030 37t' Avenue Vero Beach, Florida 32960 Phone: (772) 569-1257 Fax: (772) 569-4041 www.mlenginceringinc.com Project No. 18-230 Building Official: Project Manager: Contractor: File Report No. 1 Mr. Andrew Manero — SLC Bldg. Dept. Mr. Gene Ross — Elliott Merrill Mr. Bob Stark — Structure -Con Mr. Khris McConnell — Structure -Con THRESHOLD INSPECTION REPORT OCEAN HARBOR NORTH CONDOS — BUILDING E 5167 NORTH HWY. AIA — UNITS 708 & 808 SLC BUILDING PERMIT NUMBER: 1812-0435 PROJECTNAME: Ocean Harbor N. Condos —Bldg E DATE: February 11, 2019 CLIENT: Elliott Merrill Community Mgmt. LOCATION: Ft. Pierce, Florida CONTRACTOR: Structure -Con PROJECT MGR: Mr. Khris McConnell INSPECTED BY: Mike Lue WEATHER: Sunny WORK INSPECTED: Balcony repairs in progress. OBSERVATIONS: • The existing tile was carefully removed and the deteriorated concrete was excavated. • There are (2) affected post tension cables which have been located, locked off, and spliced away from the slab edge as indicated in the permit document. • There were existing galvanized electrical conduits within the slab which were in contact with the reinforcing steel and found to be corroded due to electrolysis which have been replaced. New reinforcing has been added, placed and coated with corrosion inhibitor. RECOMMENDATIONS: • Adjust all reinforcing to maintain the required clearances from the aluminum posts, galvanized conduits and proper concrete coverages. • Repour the concrete around the post tension anchors. • Stress the cables after the concrete has attained a minimum of 4,000 psi. • The post tension specialist General Building Services will submit the calibration certification for the hydraulic ram used to tension the cables. ��Holv PLO Page 1 of 2 M L Engineering Inc. Project No. 18-230 Report No. I Consulting Engineers Building Offlcial: Mr. Andrew Manero — SLC Bldg. Dept. 'Ibreshold Inspector Project Manager: Mr. Gene Ross — Elliott Merrill 2030 371h Avenue Contractor: Mr. Bob Stark — Structure -Con Vero Beach, Florida 32960 Mr. Khris McConnell — Structure -Con Phone: (772) 569-1257 File Fax: (772) 569-4041 www.miengineerin,ginc.com Pic I Unit 808 balcony edge. Two new PT cables. 'M Replaced section electrical conduit taped to prevent contact with reinforcing steel. Page 2 of 2 M L Engineering Inc. Consulting Engineers Threshold Inspector 2030 3711 Avenue Vero Beach, Florida 32960 Phone: (772) 569-1257 Fax: (772) 569-4041 www.mlengineeringinc.com Project No. 18-230 Building Official: Project Manager: Contractor: File Report No. 2 Mr. Andrew Mancro — SLC Bldg. Dept. Mr. Gene Ross —Elliott Merrill Mr. Bob Stark — Structure -Con Mr. Khris McConnell — Structure -Con THRESHOLD INSPECTION REPORT OCEAN HARBOR NORTH CONDOS — BUILDING E 5 167 NORTH HWY. A IA — UNITS 708 & 808 SLC BUILDING PERMIT NUMBER: 1812-0435 PROJECTNAME: Ocean Harbor N. Condos —Bldg E DATE: February 21, 2019 CLIENT: Elliott Merrill Community Mgmt. LOCATION: Ft. Pierce, Florida CONTRACTOR: Structure -Con PROJECT MGR: Mr. Khris McConnell INSPECTED BY: Mike Lue WEATHER: Sunny WORK INSPECTED: Final Inspection at Units 708 & 808 OBSERVATIONS The repaired areas of the concrete slabs were waterproofed with Sikaflex cementitious waterproofing and ready for tile. The tile is to be completed by the Owner All structural repairs are completed as indicated in the permitted plans. ... MS G 15113 : , VNI! , go Page 1 of 2 M L Engineering Inc. Pr Consulting Engineers Buil Threshold Inspector Proj 2030 371h Avenue Con Vero Beach, Florida 32960 Phone: (772) 569-1257 File Fax: (772) 569-4041 www.mlen2inceringinc.com oject No. 18-230 ding Official: ect Manager: tractor: Pic I Unit 808 Slab edge Report No. 2 Mr. Andrew Manero — SLC Bldg. Dept. Mr. Gene Ross — Elliott Merrill Mr. Bob Stark — Structure -Con Mr. Khris McConnell — Structure -Con Ends of new PT cables that have were stressed, cut and encapsulated with greased end caps Pic 2 Unit 808 floor slab Repaired slab edge, tile and shutter track to be reinstalled by Owner Pic 3 Unit 708 Repaired concrete slab where PT cables were locked off and spliced Page 2 of 2 M L Engineering Inc. Consulting Engineers Threshold Inspector 2030 3711 Avenue Vero Beach, Florida 32960 Phone: (772) 569-1257 Fax: (772) 569-4041 w%w.mlengineeringinc.com PROJECT NAME: CLIENT: CONTRACTOR: Project No. 18-230 Building Official: Project Manager: Contractor: File Report No. I Mr. Andrew Manero — SLC Bldg. Dept. Mr. Gene Ross — Elliott Merrill Mr. Bob Stark — Structure -Con Mr. Khris McConnell — Structure -Con THRESHOLD INSPECTION REPORT OCEAN HARBOR NORTH CONDOS —BUILDING E 5167 NORTH HWY. AIA — UNITS 708 & 808 SLC BUILDING PERMIT NUMBER: 1812-0435 Ocean Harbor N. Condos — Bldg E Elliott Merrill Community Mgmt. Structure -Con DATE: February 11, 2019 LOCATION: Ft. Pierce, Florida PROJECT MGR: Mr. Khris McConnell INSPECTED BY: Mike Luc WEATHER: Sunny WORK INSPECTED: Balcony repairs in progress. OBSERVATIONS: • The existing tile was carefully removed and the deteriorated concrete was excavated. • There are (2) affected post tension cables which have been located, locked off, and spliced away from the slab edge as indicated in the permit document. • There were existing galvanized electrical conduits within the slab which were in contact with the reinforcing steel and found to be corroded due to electrolysis which have been replaced. • New reinforcing has been added, placed and coated with corrosion inhibitor. RECOMMENDATIONS: • Adjust all reinforcing to maintain the required clearances from the aluminum posts, galvanized conduits and proper concrete coverages. • Repour the concrete around the post tension anchors. • Stress the cables after the concrete has attained a minimum of 4,000 psi. • The post tension specialist General Building Services will submit the calibration certification for the hydraulic ram used to tension the cables. Page 1 of 2 V M L Engineering Inc. Consulting Engineers 11reshold Inspector 2030 37� Avenue Vero Beach, Florida 32960 Phone: (772) 569-1257 Fax: (772) 569-4041 wwv�.mlengineeringincxorn Project No. 18-230 Building Official: Project Manager: Contractor., File Report No. I Mr. Andrew Mancro — SLC Bldg. Dept. Mr. Gene Ross — Elliott Merrill Mr. Bob Stark — Structure -Con Mr. Khris McConnell — Structure -Con Page 2 of 2 M L Engineering Inc. Project No. 18-230 Consulting Engineers Building Official: Mr. Andrew Maner0T_=qSENB1drW=p . Threshold Inspector Project Manager: Mr. Gene Ross — Elliott,Meffill 2030 37� Avenue Contractor: Mr. Bob Stark — Strutitum-Con Vero Beach, Florida 32960 Mr. Khris McConnell — Stnucture�.Con Phone: (772) 569-1257 File Fax: (772) 569-4041 ww�v.mlen�incerin2incxom THRESHOLD INSPECTION REPORT OCEAN HARBOR NORTH CONDOS — BUILDING E 5167 NORTH HWY. Al A — UNITS 708 & 808 SLC BUILDING PERMIT NUMBER: 1812-0435 PROJECTNAME: Ocean Harbor N. Condos —Bldg E DATE: mmlizanpin (17111 CLIENT: Elliott Merrill Community Mgmt. LOCATION: Ft. Pierce, Florida CONTRACTOR: Structure -Con PROJECT MGR: Mr. Khris McConnell INSPECTED BY: Mike Luc WEATHER: Sunny WORK INSPECTED: Balcony repairs in progress. OBSERVATIONS: • The existing tile was careftilly removed and the deteriorated concrete was excavated. • There are (2) affectea post tension cables which have been located, locked off, and spliced away from the slab edge as indicated in the permit document. • There were existing galvanized electrical conduits within the slab which were in contact with the reinforcing steel and found to be corroded due to electrolysis which have been replaced. • New reinforcing has been added, placed and coated with corrosion inhibitor. RECOMMENDATIONS: • Adjust all reinforcing to maintain the required clearances from the aluminum posts, galvanized conduits and proper concrete coverages. • Reg6ur the concrete around the post tension anchors. • Stress the cables after the concrete has attained a minimum of 4,000 psi. • The post tension specialist General Building Services will submit the calibration certification for the hydraulic ram used toension,.tbe cables. Page I of 2 M L Engineering Inc. Consulting Engineers Threshold Inspector 2030 37t� Avenue Vero Beach, Florida 32960 Phone: (772) 569-1257 Fax: (772) 569-4041 �v.mlcnginccrin%dnc.com Project No. 18-230 Building Official: Project Manager: Contractor: File Report No. I Mr. Andrew Manero — SLC Bldg. Dept. Mr. Gene Ross — Elliott Merrill Mr. Bob Stark — Structure -Con Mr. Khris McConnell — Structure -Con Page 2 of 2 I M L Engineering Inc. Consulting Engineers Threshold Inspector 2030 37� Avenue Vero Beach, Florida 32960 Phone: (772) 569-1257 Fax: (772) 569-4041 www.mletu�ineeringinc.com PROJECT NAME: CLIENT: CONTRACTOR: Project No. 18-230 Building Official: Project Manager: Contractor. File Report No. 1 Mr. Andrew Manero — SLC Bldg. Dept. Mr. Gene Ross — Elliott Merrill Mr. Bob Stark — Structure -Con Mr. Khris McConnell — Structure -Con THRESHOLD INSPECTION REPORT OCEAN HARBOR NORTH CONDOS — BUILDING E 5167 NORTH HWY. AIA — UNITS 708 & 808 SLC BUILDING PERMIT NUMBER: 1812-0435 Ocean Harbor N. Condos — Bldg E Elliott Merrill Community Mgmt. Structure -Con DATE: February 11, 2019 LOCATION: Ft. Pierce, Florida PROJECT MGR: Mr. Khris McConnell INSPECTED BY: Mike Lue WEATHER: Sunny I WORK INSPECTED: Balcony repairs in progress. OBSERVATIONS: • The existing tile was carefully removed and the deteriorated concrete was excavated. • There are (2) affected post tension cables which have been located, locked off, and spliced away from the slab edge as indicated in the permit document. • There were existing galvanized electrical conduits within the slab which were in contact with the reinforcing steel and found to be corroded due to electrolysis which have been replaced. • New reinforcing has been added, placed and coated with corrosion inhibitor. RECOMMENDATIONS: • Adjust all reinforcing to maintain die required clearances from the aluminum posts, galvanized conduits and proper concrete coverages. • Repour the concrete around the post tension anchors. • Stress the cables after the concrete has attained a minimum of 4,000 psi. • The post tension specialist General Building Services will submit the calibration certification for the hydraulic ram used to tension the cables. st, I I I I I Is# 8144, PLO all Page 1 of 2 k- M L Engineering Inc. Consulting Engineers Threshold Inspector 2030 37� Avenue Vem Beach, Florida 32960 Phone: (772) 569-1257 Fax: (772) 5694041 Nvww.ralenginceringinc.com Project No. 18-230 Report No. 1 Building Official: Mr. Andrew Manero — SLC Bldg. Dept. Project Manager: Mr. Gene Ross — Elliott Merrill Contractor. Mr. Bob Stark — Structuc-Con Mr. Khris McComell — Structu�Con File Pic I Unit 808 balcony edge. Two new -PT cables. Replaced section electrical conduit taped to prevent contact with reinforcing steel. Page 2 of 2 M L Engineering Inc. Consulting Engineers Threshold Inspector 2030 3711 Avenue Vem Beach, Florida 32960 Phone: (772) 569-1257 Fax: (772) 569-4041 www. ralenginecringinc.corn Project No. 18-230 Building Official: Project Manager: Contractor. File Report No. 2 Mr. Andrew Manero — SLC Bldg. Dept. Mr. Gene Ross — Elliott Merrill Mr. Bob Stark — Structure -Con Mr. Khris McConnell — Structuse-Con THRESHOLD INSPECTION REPORT OCEAN HARBOR NORTH CONDOS — BUILDING E 5167 NORTH HWY. A IA — UNITS 708 & 808 SLC BUILDING PERMIT NUMBER: 1812-0435 PROJECT NAME: Ocean Harbor N. Condos —Bldg F, DATE: February 21, 2019 CLIENT: Elliott Merrill Community Mgmt. LOCATION: Ft. Pierce, Florida CONTRACTOR: Structure -Con PROJECT MGR: Mr. Khris McConnell INSPECTED BY: Mike Lue WEATHER: Sunny WORK INSPECTED: Final Inspection at Units 708 & 808 OBSERVATIONS The repaired areas of the concrete slabs were waterproofed with Sikaflex cementitious waterproofing and ready for tile. The tile is to be completed by the Owner All structural repairs are completed as indicated in the permitted plans. -.0 �c 4% PL 0 % Page I of 2 M L Engineering Inc. Project No. 18-230 Consulting Engineers Building Official: Threshold Inspector Project Manager: 2030 3" Avenue Contractor: Vero Beach, Florida 32960 Phone: (772) 569-1257 File Fax: (772) 569-4041 Nv%�.rnlengiaccringincxom Unit 808 Slab edge Report No. 2 Mr. Andrew Manerc, — SLC Bldg. Dept. Mr. Gene Ross — Elliott Merrill Mr. Bob Stark — Structure -Con Mr. Khris McConnell — Structu�Con Ends of new PT cables that have were stressed, cut and encapsulated with greased end caps Pic 2 Unit 808 floor slab Repaired slab edge, tile and shutter track to be reinstalled by Owner Unit 708 Repaired concrete slab where PT cables were locked off and spliced Page 2 of 2