THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH CONDOS — BUILDING E
5167 NORTH HWY. A IA — UNITS 708 & 808
SLCBUILDING PERMIT NUMBER: 1812-0435
Ocean Harbor N. Condos — Bldg E DATE: February 21, 2019
Elliott Merrill Community Mgmt. LOCATION: Ft. Pierce, Florida
Structure -Con
PROJECT MGR: Mr. Khris McConnell
INSPECTED BY: Mike Lue WEATHER: Sunny
WORK INSPECTED:
Final Inspection at Units 708 & 808
SCANNED
BY
St. Lucie County
OBSERVATIONS
The repaired areas of the concrete slabs were waterproofed with Sikaflex cementitious waterproofing and ready for tile.
The tile is to be completed by the Owner
All structural repairs are completed as indicated in the permitted plans.
Ir
-�157P %*0-
W re
- -1 A
PL 0'
Page I of 2
M L Engineering I
Consulting Engineers
Threshold Inspector
2030 3711 Avenue
Vero Beach, Florida 32960
Phone: (772) 569-1257
Fax: (772) 569-4041
www.mlengineeringine.com
Project No. 18-230
Building Official:
Project Manager:
Contractor:
File
Pic I
Unit 808 Slab edge
Report No. 2
Mr. Andrew Manero — SLC Bldg. Dept.
Mr. Gene Ross — Elliott Merrill
Mr. Bob Stark — Structure -Con
Mr. Khris McConnell — Structure -Con
Ends of new PT cables that have were stressed, cut and
encapsulated with greased end caps
Pic 2
Unit 808 floor slab
Repaired slab edge, tile and shutter track to be
reinstalled by Owner
Pic 3
Unit 708
Repaired concrete slab where PT cables were locked
off and spliced
Page 2 of 2
M L Engineering Inc.
Consulting Engineers
Threshold Inspector
2030 37t' Avenue
Vero Beach, Florida 32960
Phone: (772) 569-1257
Fax: (772) 569-4041
www.mlenginceringinc.com
Project No. 18-230
Building Official:
Project Manager:
Contractor:
File
Report No. 1
Mr. Andrew Manero — SLC Bldg. Dept.
Mr. Gene Ross — Elliott Merrill
Mr. Bob Stark — Structure -Con
Mr. Khris McConnell — Structure -Con
THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH CONDOS — BUILDING E
5167 NORTH HWY. AIA — UNITS 708 & 808
SLC BUILDING PERMIT NUMBER: 1812-0435
PROJECTNAME:
Ocean Harbor N. Condos —Bldg E
DATE:
February 11, 2019
CLIENT:
Elliott Merrill Community Mgmt.
LOCATION:
Ft. Pierce, Florida
CONTRACTOR:
Structure -Con
PROJECT MGR:
Mr. Khris McConnell
INSPECTED BY: Mike Lue WEATHER: Sunny
WORK INSPECTED:
Balcony repairs in progress.
OBSERVATIONS:
• The existing tile was carefully removed and the deteriorated concrete was excavated.
• There are (2) affected post tension cables which have been located, locked off, and spliced away from the slab
edge as indicated in the permit document.
• There were existing galvanized electrical conduits within the slab which were in contact with the reinforcing
steel and found to be corroded due to electrolysis which have been replaced.
New reinforcing has been added, placed and coated with corrosion inhibitor.
RECOMMENDATIONS:
• Adjust all reinforcing to maintain the required clearances from the aluminum posts, galvanized conduits and
proper concrete coverages.
• Repour the concrete around the post tension anchors.
• Stress the cables after the concrete has attained a minimum of 4,000 psi.
• The post tension specialist General Building Services will submit the calibration certification for the hydraulic
ram used to tension the cables.
��Holv
PLO
Page 1 of 2
M L Engineering Inc. Project No. 18-230 Report No. I
Consulting Engineers Building Offlcial: Mr. Andrew Manero — SLC Bldg. Dept.
'Ibreshold Inspector Project Manager: Mr. Gene Ross — Elliott Merrill
2030 371h Avenue Contractor: Mr. Bob Stark — Structure -Con
Vero Beach, Florida 32960 Mr. Khris McConnell — Structure -Con
Phone: (772) 569-1257 File
Fax: (772) 569-4041
www.miengineerin,ginc.com
Pic I
Unit 808 balcony edge.
Two new PT cables.
'M
Replaced section electrical conduit taped to prevent
contact with reinforcing steel.
Page 2 of 2
M L Engineering Inc.
Consulting Engineers
Threshold Inspector
2030 3711 Avenue
Vero Beach, Florida 32960
Phone: (772) 569-1257
Fax: (772) 569-4041
www.mlengineeringinc.com
Project No. 18-230
Building Official:
Project Manager:
Contractor:
File
Report No. 2
Mr. Andrew Mancro — SLC Bldg. Dept.
Mr. Gene Ross —Elliott Merrill
Mr. Bob Stark — Structure -Con
Mr. Khris McConnell — Structure -Con
THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH CONDOS — BUILDING E
5 167 NORTH HWY. A IA — UNITS 708 & 808
SLC BUILDING PERMIT NUMBER: 1812-0435
PROJECTNAME:
Ocean Harbor N. Condos —Bldg E
DATE:
February 21, 2019
CLIENT:
Elliott Merrill Community Mgmt.
LOCATION:
Ft. Pierce, Florida
CONTRACTOR:
Structure -Con
PROJECT MGR:
Mr. Khris McConnell
INSPECTED BY:
Mike Lue
WEATHER:
Sunny
WORK INSPECTED:
Final Inspection at Units 708 & 808
OBSERVATIONS
The repaired areas of the concrete slabs were waterproofed with Sikaflex cementitious waterproofing and ready for tile.
The tile is to be completed by the Owner
All structural repairs are completed as indicated in the permitted plans.
... MS
G 15113
: , VNI! ,
go
Page 1 of 2
M L Engineering Inc.
Pr
Consulting Engineers
Buil
Threshold Inspector
Proj
2030 371h Avenue
Con
Vero Beach, Florida 32960
Phone: (772) 569-1257
File
Fax: (772) 569-4041
www.mlen2inceringinc.com
oject No. 18-230
ding Official:
ect Manager:
tractor:
Pic I
Unit 808 Slab edge
Report No. 2
Mr. Andrew Manero — SLC Bldg. Dept.
Mr. Gene Ross — Elliott Merrill
Mr. Bob Stark — Structure -Con
Mr. Khris McConnell — Structure -Con
Ends of new PT cables that have were stressed, cut and
encapsulated with greased end caps
Pic 2
Unit 808 floor slab
Repaired slab edge, tile and shutter track to be
reinstalled by Owner
Pic 3
Unit 708
Repaired concrete slab where PT cables were locked
off and spliced
Page 2 of 2
M L Engineering Inc.
Consulting Engineers
Threshold Inspector
2030 3711 Avenue
Vero Beach, Florida 32960
Phone: (772) 569-1257
Fax: (772) 569-4041
w%w.mlengineeringinc.com
PROJECT NAME:
CLIENT:
CONTRACTOR:
Project No. 18-230
Building Official:
Project Manager:
Contractor:
File
Report No. I
Mr. Andrew Manero — SLC Bldg. Dept.
Mr. Gene Ross — Elliott Merrill
Mr. Bob Stark — Structure -Con
Mr. Khris McConnell — Structure -Con
THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH CONDOS —BUILDING E
5167 NORTH HWY. AIA — UNITS 708 & 808
SLC BUILDING PERMIT NUMBER: 1812-0435
Ocean Harbor N. Condos — Bldg E
Elliott Merrill Community Mgmt.
Structure -Con
DATE:
February 11, 2019
LOCATION:
Ft. Pierce, Florida
PROJECT MGR:
Mr. Khris McConnell
INSPECTED BY: Mike Luc WEATHER: Sunny
WORK INSPECTED:
Balcony repairs in progress.
OBSERVATIONS:
• The existing tile was carefully removed and the deteriorated concrete was excavated.
• There are (2) affected post tension cables which have been located, locked off, and spliced away from the slab
edge as indicated in the permit document.
• There were existing galvanized electrical conduits within the slab which were in contact with the reinforcing
steel and found to be corroded due to electrolysis which have been replaced.
• New reinforcing has been added, placed and coated with corrosion inhibitor.
RECOMMENDATIONS:
• Adjust all reinforcing to maintain the required clearances from the aluminum posts, galvanized conduits and
proper concrete coverages.
• Repour the concrete around the post tension anchors.
• Stress the cables after the concrete has attained a minimum of 4,000 psi.
• The post tension specialist General Building Services will submit the calibration certification for the hydraulic
ram used to tension the cables.
Page 1 of 2
V
M L Engineering Inc.
Consulting Engineers
11reshold Inspector
2030 37� Avenue
Vero Beach, Florida 32960
Phone: (772) 569-1257
Fax: (772) 569-4041
wwv�.mlengineeringincxorn
Project No. 18-230
Building Official:
Project Manager:
Contractor.,
File
Report No. I
Mr. Andrew Mancro — SLC Bldg. Dept.
Mr. Gene Ross — Elliott Merrill
Mr. Bob Stark — Structure -Con
Mr. Khris McConnell — Structure -Con
Page 2 of 2
M L Engineering Inc. Project No. 18-230
Consulting Engineers
Building Official: Mr. Andrew Maner0T_=qSENB1drW=p .
Threshold Inspector
Project Manager: Mr. Gene Ross — Elliott,Meffill
2030 37� Avenue
Contractor: Mr. Bob Stark — Strutitum-Con
Vero Beach, Florida 32960 Mr. Khris McConnell — Stnucture�.Con
Phone: (772) 569-1257
File
Fax: (772) 569-4041
ww�v.mlen�incerin2incxom
THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH CONDOS — BUILDING E
5167 NORTH HWY. Al A — UNITS 708 & 808
SLC BUILDING PERMIT NUMBER: 1812-0435
PROJECTNAME:
Ocean Harbor N. Condos —Bldg E DATE: mmlizanpin (17111
CLIENT:
Elliott Merrill Community Mgmt. LOCATION: Ft. Pierce, Florida
CONTRACTOR:
Structure -Con PROJECT MGR: Mr. Khris McConnell
INSPECTED BY:
Mike Luc WEATHER: Sunny
WORK INSPECTED:
Balcony repairs in progress.
OBSERVATIONS:
• The existing tile was careftilly removed and the deteriorated concrete was excavated.
• There are (2) affectea post tension cables which have been located, locked off, and spliced away from the slab
edge as indicated in the permit document.
• There were existing galvanized electrical conduits within the slab which were in contact with the reinforcing
steel and found to be corroded due to electrolysis which have been replaced.
• New reinforcing has been added, placed and coated with corrosion inhibitor.
RECOMMENDATIONS:
• Adjust all reinforcing to maintain the required clearances from the aluminum posts, galvanized conduits and
proper concrete coverages.
• Reg6ur the concrete around the post tension anchors.
• Stress the cables after the concrete has attained a minimum of 4,000 psi.
• The post tension specialist General Building Services will submit the calibration certification for the hydraulic
ram used toension,.tbe cables.
Page I of 2
M L Engineering Inc.
Consulting Engineers
Threshold Inspector
2030 37t� Avenue
Vero Beach, Florida 32960
Phone: (772) 569-1257
Fax: (772) 569-4041
�v.mlcnginccrin%dnc.com
Project No. 18-230
Building Official:
Project Manager:
Contractor:
File
Report No. I
Mr. Andrew Manero — SLC Bldg. Dept.
Mr. Gene Ross — Elliott Merrill
Mr. Bob Stark — Structure -Con
Mr. Khris McConnell — Structure -Con
Page 2 of 2
I
M L Engineering Inc.
Consulting Engineers
Threshold Inspector
2030 37� Avenue
Vero Beach, Florida 32960
Phone: (772) 569-1257
Fax: (772) 569-4041
www.mletu�ineeringinc.com
PROJECT NAME:
CLIENT:
CONTRACTOR:
Project No. 18-230
Building Official:
Project Manager:
Contractor.
File
Report No. 1
Mr. Andrew Manero — SLC Bldg. Dept.
Mr. Gene Ross — Elliott Merrill
Mr. Bob Stark — Structure -Con
Mr. Khris McConnell — Structure -Con
THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH CONDOS — BUILDING E
5167 NORTH HWY. AIA — UNITS 708 & 808
SLC BUILDING PERMIT NUMBER: 1812-0435
Ocean Harbor N. Condos — Bldg E
Elliott Merrill Community Mgmt.
Structure -Con
DATE:
February 11, 2019
LOCATION:
Ft. Pierce, Florida
PROJECT MGR:
Mr. Khris McConnell
INSPECTED BY: Mike Lue WEATHER: Sunny I
WORK INSPECTED:
Balcony repairs in progress.
OBSERVATIONS:
• The existing tile was carefully removed and the deteriorated concrete was excavated.
• There are (2) affected post tension cables which have been located, locked off, and spliced away from the slab
edge as indicated in the permit document.
• There were existing galvanized electrical conduits within the slab which were in contact with the reinforcing
steel and found to be corroded due to electrolysis which have been replaced.
• New reinforcing has been added, placed and coated with corrosion inhibitor.
RECOMMENDATIONS:
• Adjust all reinforcing to maintain die required clearances from the aluminum posts, galvanized conduits and
proper concrete coverages.
• Repour the concrete around the post tension anchors.
• Stress the cables after the concrete has attained a minimum of 4,000 psi.
• The post tension specialist General Building Services will submit the calibration certification for the hydraulic
ram used to tension the cables.
st, I I I I I Is# 8144,
PLO
all
Page 1 of 2
k-
M L Engineering Inc.
Consulting Engineers
Threshold Inspector
2030 37� Avenue
Vem Beach, Florida 32960
Phone: (772) 569-1257
Fax: (772) 5694041
Nvww.ralenginceringinc.com
Project No. 18-230 Report No. 1
Building Official: Mr. Andrew Manero — SLC Bldg. Dept.
Project Manager: Mr. Gene Ross — Elliott Merrill
Contractor. Mr. Bob Stark — Structuc-Con
Mr. Khris McComell — Structu�Con
File
Pic I
Unit 808 balcony edge.
Two new -PT cables.
Replaced section electrical conduit taped to prevent
contact with reinforcing steel.
Page 2 of 2
M L Engineering Inc.
Consulting Engineers
Threshold Inspector
2030 3711 Avenue
Vem Beach, Florida 32960
Phone: (772) 569-1257
Fax: (772) 569-4041
www. ralenginecringinc.corn
Project No. 18-230
Building Official:
Project Manager:
Contractor.
File
Report No. 2
Mr. Andrew Manero — SLC Bldg. Dept.
Mr. Gene Ross — Elliott Merrill
Mr. Bob Stark — Structure -Con
Mr. Khris McConnell — Structuse-Con
THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH CONDOS — BUILDING E
5167 NORTH HWY. A IA — UNITS 708 & 808
SLC BUILDING PERMIT NUMBER: 1812-0435
PROJECT NAME: Ocean Harbor N. Condos —Bldg F, DATE: February 21, 2019
CLIENT: Elliott Merrill Community Mgmt. LOCATION: Ft. Pierce, Florida
CONTRACTOR: Structure -Con PROJECT MGR: Mr. Khris McConnell
INSPECTED BY: Mike Lue WEATHER: Sunny
WORK INSPECTED:
Final Inspection at Units 708 & 808
OBSERVATIONS
The repaired areas of the concrete slabs were waterproofed with Sikaflex cementitious waterproofing and ready for tile.
The tile is to be completed by the Owner
All structural repairs are completed as indicated in the permitted plans.
-.0
�c
4%
PL 0
%
Page I of 2
M L Engineering Inc.
Project No. 18-230
Consulting Engineers
Building Official:
Threshold Inspector
Project Manager:
2030 3" Avenue
Contractor:
Vero Beach, Florida 32960
Phone: (772) 569-1257
File
Fax: (772) 569-4041
Nv%�.rnlengiaccringincxom
Unit 808 Slab edge
Report No. 2
Mr. Andrew Manerc, — SLC Bldg. Dept.
Mr. Gene Ross — Elliott Merrill
Mr. Bob Stark — Structure -Con
Mr. Khris McConnell — Structu�Con
Ends of new PT cables that have were stressed, cut and
encapsulated with greased end caps
Pic 2
Unit 808 floor slab
Repaired slab edge, tile and shutter track to be
reinstalled by Owner
Unit 708
Repaired concrete slab where PT cables were locked
off and spliced
Page 2 of 2