HomeMy WebLinkAboutEVALUATION REPORTSCANNED BY St. Lucie County NNEMOjetc. DECK APPLICATION TYPE DESCRIPTION PAGE TABLE IA Wood New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 5 1B Wood New or Reroof (Tear -Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 5-9 1C Wood New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 10-11 1D Wood New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 12 1E Wood New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 12-14 1F Wood New, Reroof (Tear -Off) or Recover D Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 15-17 1G Wood New or Reroof (Tear -Off) E Non -Insulated, Mech. Attached Base Sheet (nails), Bonded Roof Cover 18-21 111 Wood New, Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet (screws & plates), Bonded Roof Cover 21-25 11 Wood New or Reroof (Tear -Off) F Non -Insulated, Bonded Roof Cover 26 2A Steel or Structural concrete New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 27-29 2B Steel or Structural concrete New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 30-34 2C Steel or Structural concrete New, Reroof (Tear -Off) or Recover D Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 35-37 3A Structural concrete New or Reroof (Tear -Off) A-1 Bonded Insulation, Banded Roof Cover 38-46 3B Structural concrete New or Reroof (Tear -Off) F Non -Insulated, Bonded Roof Cover 46 4A Lightweight concrete New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 47-49 4B Lightweight concrete New or Reroof (Tear -Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover s0 4C Lightweight concrete New or Reroof (Tear -Off) E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 51-53 5A Cementitious wood fiber New or Reroof (Tear -Off) A-1 Bonded Insulation, Banded Roof Cover 54 SB Cementitious wood fiber New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 55 5C Cementitious wood fiber New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 56 SD Cementitious wood fiber New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 56 5E Cementitious wood fiber New, Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 56 6A Existing gypsum Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 57-59 6B Existing gypsum Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 59 6C Existing gypsum Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 60 6D Existing gypsum Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 60 7A Various Recover A-1 Bonded Insulation, Bonded Roof Cover 61-65 7B Various Recover F Non -Insulated, Bonded Base Sheet, Bonded Roof Cover 65 The following notes apply to the systems outlined herein: 1. The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. 2. Insulation / base sheet fasteners shall be of sufficient length for the following deck engagement: ➢Wood: Minimum 0.75-inch penetration. ➢ Steel: Minimum 0.75-inch penetration and engage the top flute of the steel deck. ➢ Structural concrete: Minimum 1-inch embedment into pilot hole in accordance with fastener manufacturer's published installation instructions. NEMO ETC, LLC Evaluation Report P9290.02.08-1121 for FL1654-1123 Certificate of Authorization H32455 0 EDITION (2017) FBC NON-HVH7 EVALUATION Revision 21: 10/08/2018 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 1 of 65 OONEMOJetc. 3. Unless otherwise noted, insulation maybe anyone layer or combination of polyisocyanurate,polystyrene, wood fiberboard, perlite,gypsum-based roof board or mineral -wool roof board that meets the CIA requirements of F.A.C. Rule 61G20-3 and is documented as meeting FBC 1505.1 and, for foam plastic, FBC Chapter 26, when installed with the roof cover. 4. Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type D (mechanically attached base sheet, bonded roof cover), whereby the base sheet fasteners are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck listings. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. S. Preliminary insulation attachment for System Type D: Unless otherwise noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (January 2016). 6. Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturers published instructions. ➢ Hot asphalt (HA): Full coverage at 25-30lbs/square. ➢ Dow INSTA STIK Quik Set Insulation Adhesive (D-15): Continuous 0.75 to 1-inch wide ribbons,12-inch o.c. D Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c. ➢ Millennium PG-1 Pump Grade Adhesive (M-PGI): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c. ➢ OMG OlyBond 500 (OB500): Continuous 0.75 to 1-inch wide ribbons,12-inch o.c. (PaceCart or SpotShot). Note: OlyBond Green maybe used where OlyBond 5OO is referenced. ➢ OlyBond Classic (OB Classic): Full coverage at 1 gal/square. ' ➢ ICP Adhesive & Sealants Polyset CR-20: Continuous 2.5-3.5-inch wide ribbons,12-inch o.c. ➢ Note: When multiple loyers(s) of insulation and/or coverboard are installed in ribbon -applied adhesive, boardjoints shall be staggered. ➢ Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing. 7. Unless otherwise noted, all insulations are flat -stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations maybe substituted with the following Maximum Design Pressure (MDP) limitations. In no case shall these values be used to 'increase' the MOP listings in the tables; rather if MDP listing below meets or exceeds that listed far a particular system in the tables, then the thinner board listed below may be used as a drop -in for the equivalent thicker material listed in the table: ➢ Millennium One Step Foamable Adhesive(M-OSFA): MDP -157.5 psf (Min. 0.5-inch thick) ➢ Millennium PG-1 Pump Grade Adhesive (M-PG3): MOP -157.5 psf (Min. 0.5-inch thick) ➢ OMG OlyBond 500 (OB500): MDP -45.0 psf (Min. 0.5-inch thick Multi -Max FA-3) ➢ OMG OlyBond 500 (OB500): MDP -187.5 psf (Min. 0.5-inch thick ISO 95+ GQ ➢ OMG OlyBond 500 (OB500): MDP -315.0 psf (Min. 0.5-inch thick ENRGY 3) ➢ OMG OlyBond 500 (OB500): MDP .487.5 psf (Min. 0.5-inch thick ACFoam II) ➢ ICP Adhesives & Sealants Polyset CR-20: MDP -117.5 psf (Min. 1.0-inch thick) 8. Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft. 9. For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WDl, FM Loss Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk" carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. 10. For fully bonded assemblies, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16, and no rational analysis is permitted. 11. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TA5105. 12. For existing substrates in a bonded recover or re -roof installation, the existing roof surface or existing roof deck shall be examined for compatibility and band performance with the selected adhesive, and the existing roof system (for recover) shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with AN51/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124. 13. For Recover Applications using System Type D, the insulation is optional; however, the existing roof system shall be suitable for a recover application. NEMO ETC, LLC Evaluation Report P9290.02.08-R21 for FL3654-1123 Certificate of Authorization #32455 6n' EDITION (2017) FBC NON-HVHZ EVALUATION Revision 21: 10/08/2018 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 2 of 65 MEMO I etc. 14. Lightweight Insulating Concrete (LWC) shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC is referenced, refer to current LWC Product Approval for specific deck construction and limitations. Unless otherwise noted, for systems where specific LWC is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top -coat thickness is 2-inches. For LWC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1. For "pre-existent' LWC references, listings were established through testing over lightweight concrete cast using only foaming agent (ASTM C896), water and Portland cement (ASTM C350), with no proprietary additives, in accordance with procedures adopted by Miami -Dade BCCO (FBC CER3592). Unless otherwise noted, use of these listings in new construction or re -roof (tear -off) applications is at the discretion of the Designer or Record and Authority Having Jurisdiction. 15. Unless otherwise noted, refer to the following references for bonded base, ply or cap sheet applications. REFERENCE LAYER MATERIAL APPLICATION BP -AA Base Ply One or more plies Polyglass G2 Base, FBC Approved ASTM D4601, Type II Ho[ Asphalt a[ 20-40 (Base and Ply sheets, Ply One or more plies Polyglass Ply IV, Polyglass Ply VI, FBC Approved ASTM D2178, Type IV or VI Ibs/square Asphalt -Applied) Note: Asphalt -applied sheets or insulation shall not be applied to poly -film surfaced membranes. Base Ply One ply Elastobase (sand/sand), Elastoflex V, Elastoflex S6, Elastoflex S6 Type II, Polyglass HT Base 650 PG350 at 1.5-2.0 SBS-CA1 Cap Ply Elastoflex VG, Elastoflex VG FR, Elastoflex 56, Elastoflex 56 Type II, Elastoflex S6 G, Elastoflex 56 G FR, Elastoshield TS-G, Elastoshield gal/square TS-G FR, Polyfresko G SBS (sand -backed), Polyfresko G SBS FR (sand -backed) Base Ply One ply Elastobase (sand/sand), Elastoflex V, Elastoflex S6, Elastoflex 56 Type II Polyplus 35 at 1.5-2.0 SBS-CA2 Cap Ply Elastoflex VG, Elastoflex VG FR, Elastoflex 56, Elastoflex S6 Type II, Elastoflex S6 G, Elastoflex S6 G FR, Elastoshield TS-G, Elastoshield gal/square TS-G FR, Polyfresko G SBS (sand -backed), Polyfresko G SBS FR (sand -backed) Base Ply or Ply One or more plies Elastobase (sand/sand or poly/sand), Elastobase P (sand/sand or poly/sand), Elastoflex V, Elastoflex 56, Elastoflex SBS-AA 56 Type II, Polyglass HT Base 650 Hot Asphalt at 20-40 (585, Asphalt -Applied) Cap Ply Elastoflex V, Elastoflex VG, Elastoflex VG FR, Elastoflex S6, Elastoflex 56 Type II, Elastoflex 56 G, Elastoflex 56 G FR, Elastoshield TS-G, Ibs/square Elastoshield TS-G FR, Polyfresko G 565 (sand -backed), Polyfresko G 5B5 FR (sand -backed) Nate: Asphalt -applied sheets or insulation shall not be applied to poly -film surfaced membranes. Base Ply or Ply or more plies Elastobase (sand/poly), Elastobase (poly/poly), Elastoflex V, Elastoflex 56, Elastoflex S6 Type II, Polyglass HT Base SBS-TA 6One 50 (SBS, Torch -Applied) Cap Ply Elastoflex V, Elastoflex VG, Elastoflex VG FR, Elastoflex S6, Elastoflex S6 Type II, Elastoflex 56 G, Elastoflex 56 G FR, Elastoshield TS- Torch -Applied G, Elastoshield TS-G FR, Polyfresko G SBS (poly-flm backed), Polyfresko G SBS FR (poly -film backed) Base Ply One or more plies Elastoflex SA V Base, Elastoflex SA V FR Base, Elastoflex SA V Plus, Elastoflex 5A V Plus FR SBS-SA Cap Ply Elastoflex SA P, Elastoflex SA P FR, Polyreflect (SBS, Self -Adhering) Note: Unless otherwise noted, permissible membrane substrates)or5B5-SA are limited to the5B5-5A Base Ply options herein, Self -Adhering Elastobase (poly/sand) or Elastobase (poly/poly). APP-CA1 Cap Ply Polyflex G FR PG350 at 1.5-2.0 gal/square APP-TA Base Ply or Ply One or more plies Polyglass APP Base, Polyflex, Polybond (APP, Torch -Applied) Cap Ply Polyflex, Polyflex G, Polyflex G FR, Polybond, Polybond G, Polyfresko G, Polyfresko G FR Torch -Applied Cap Ply Polyflex SA P, Polyflex SA P FR, Polyfresko G SA, Polykool APP SA (APP, Self -Adhering) Note: Unless otherwise noted, permissible membrane substratesforAPP-SA are limited tothe5B5-SA Base Ply options herein, Self -Adhering Elastobase (poly/sand) or Elastobase (poly/poly). NEMO ETC, LLC Evaluation Report P9290.02.08-1121 for FL1654-R23 Certificate of Authorization #32455 6'" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 21: 10/08/2018 Prepared by: Robert Niernmen, PE-59166 Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 3 of 65 16. Vapor barrier options for use over structural concrete deck followed by adhered insulation carry the following Maximum Design Pressure (MDP) limitations. applies: NNEMOjetc. The lesser of the MDP listings below vs. those in Table 3A OPTION # PRIMER VAPOR BARRIER INSULATION ADHESIVE MDP (PSF) TYPE ATTACH VB-1. PG100 Elastoflex SA V Plus Self -Adhering Inta-Stik or CR-20, 12-inch o.c. -60.0 VB-2. PG100 Polyglass APP Base Torch -applied Inta-Stik or CR-20, 12-inch o.c. -75.0 VB-3. PG100 Elastoflex SA P Self -Adhering Insta-Stik, 12-inch o.c. -75.0 VB-4. PG100 Elastoflex SAP Self -Adhering Millennium One Step Foamable Adhesive,12-inch o.c. -157.5 VB-5. PG300 Elastoflex SA P Self -Adhering I CR-20, 12-inch o.c. -270.0 VB-6. PG100 Elastoflex SA V Base, Elastoflex SA V FR Base, Elastoflex SA V Plus, Elastoflex SA V Plus FIR Self -Adhering Millennium One Step Foamable Adhesive, Millennium PG-1 Pump Grade I Adhesive, OlyBond 500 or CR-20, 12-inch o.c. -290.0 17. The following surfacing may be applied to the Cap Ply without adverse effect on the system wind load performance. Refer to current Florida Product Approval for approved Polyglass and KM Coatings roof coatings for application limitations and a Roofing Materials Directory for fire ratings associated with coating -usage. Option If Surfacing Florida. Product Approval SURF-1. PG300 Fibered Roof Coating FL10291 SURF-2. PG600 Non-Fibered Aluminum Roof Coating FL10291 SURF-3. PG65D Fibered Aluminum Roof Coating FL10291 SURF-4. PG700 High Quality Elastomeric Roof Coating FL10291 SURF-5. PG700QS (Quick Set) High Quality Elastomeric Roof Coating FL10291 SURF-6. PG800 Asphalt Emulsion Roof Coating FL10291 SURF-7. Polyplus 60 Premium Non-Fibered Aluminum Roof Coating FL10291 SURF-8. Polyplus 65 Premium Fibered Aluminum Roof Coating FL10291 SURF-9. Polybrite 70 Premium Grade Elastomeric Roof Coating FL10291 SURF-10. Polybrite 70QS(Quick Set) Premium Grade Elastomeric Roof Coating FL10291 SURF-11. Polybrite 71 HS FL10291 SURF-12. Polybrite 90 High Solids Silicone Roof Coating FL10291 SURF-13. Polybrite 95 Silicone Roof Coating FL10291 SURF-14. KM Acryl 15 FL27409 SURF-15. KM Acryl 15 QS FL27409 SURF-16. KM Acryl 25 FL27409 SURF-17. KM Acryl 25 QS FL27409 SURF-18. KM Acryl 40 HIS FL27409 SURF-19. KM Acryl 85 FL27409 SURF-20. KM PS#250 FL27409 SURF-21. KM PS#220 FL27409 18. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads. NEMO ETC, LLC Evaluation Report P9290.02.08-1121 for FL3654-1123 Certificate of Authorization #32455 6t" EDITION (2017) FBC NON-HVH2 EVALUATION Revision 21: 10/08/2018 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 4 of 65 *NEMO I etc. .os r 4 . .R •.a . . .:... •.. System Roof Cover (Note 15) Deck (Note 1) MDP (psf) Primer Joint Treatment 'Base Ply Ply Cap Ply Min. 15/32- (Optional)SBS-SA, SBS- SBS-SA, APP-SA, SBS- CNo W 170 Finch plywood None None SBS-SA TA, APP-TA TA, APP-TA -90.0 Min. 15/32- W-171 inch plywood (Optional) PG300 None Polyflex SA Base (Optional)APP-TA APP-TA -90.0 Min, 15/32- (Optional) SBS-SA, SBS- SBS-SA, APP-SA, SBS- W 172 inch plywood pG100 None SBS-SA TA, APP-TA TA, APP-TA Min. 15/32- Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled into Elastoflex SA V Base or (Optional) SBS-SA, SBS- SBS-SA, APP-SA, SBS- W-173 inch plywood (Optional) PG100 place to create continuous bond. Elastoflex SA V FR Base TA, APP-TA TA, APP-TA 97.5 Min. 15/32- SBS- SBS-SA, -$A, SBS- W 174 inch plywood POLYBRITE 745 None SBS-SA-105.0 TA, APP-TA5B5-SA, TA Min. 15/32- Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled into Elastoflex SA V Pius or (Optional) SBS-SA, SBS- SBS-SA, APP-SA, SBS- W-175 inch wood p y (Optional) PG100 place to create continuous hood. Elastoflex SA V Plus FR TA, APP-TA TA, APP-TA -135.0 Min. 15/32- Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled into W-176 inch plywood (Optional) PG100 place to create continuous bond. Polyflex SA Base (Optional)APP-TA APP-TA -135.0 NEMO ETC, LLC Evaluation Report P9290.02.08-R21 for FL1654-R23 Certificate of Authorization #32455 6'a EDITION (2017) FBC NON-HVHZ EVALUATION Revision 21: 10/08/2018 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 26 of 65