EVALUATION REPORT
Polyglass USA, Inc. Evaluation Report P12060.02.09-R24
1111 West Newport Center Drive FLS2S9-R28
Deerfield Beach, FL 33442 Date of Issuance: 02/24/2009
(954) 233-1230 Revision 24: 01/24/2018
SCOPE:
This Evaluation Report is issued under Rule 61620-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E.
for use of the product under the Florida Building Cade and Florida Building Code, Residential Volume. The products
described herein have been evaluated for compliance with the & Edition (2017) Florida Building Code sections noted
herein.
DEscRnmON: Polyglass Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein.
coNmuED Compum E: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this
Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the
product(s), the Quality Assurance or the production facility lotation(s). NEMOIetc. requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
AovERTISEMENT; The Evaluation Report number preceded by the words "NEMOletc. Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. '
INsPEcnoN: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its
distributors and shall be available for Inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 14.
Prepared y.
�u,�rrg"w�a.r
Robert J.M. Nleminen, P.E.
Florida Registration No. 59166, Florida DUI ANE1983
�(tta.....a.a .
The fadm0e seal appearingwas authorized by Robert Nleminen,
P.E. on 0IA4/2018. This does not some as an alectrus Ically
signeddocument
CERtIRCATION OF INDEPENDENCE:
1. NEMOletc. does not have, nor does it Intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMOI etc. Is not owned, operated or controlled by any company manufacturing or distributing products It evaluates.
3. Robert Nleminen, P.E. does not have nor will acquire, a financial Interest in any company manufacturing or distributing products for
. which the evaluation reports are being Issued.
4. Robert Nleminen, P.E. does not have, nor will acquire, a financial interest in any other entity Involved in the approval process of the
product.
S. This Is a building code evaluation. Neither NEMOIetr- nor Robert Nleminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
M
d
W
�i
J
.d
N
Tl r�iry grvrv�ry NNlo ova^oo'oT o.8o� 6 o$0�o800`a
O
R .n.pp�qeq�C O�C O VG m 4pp,yy4{y.CCyy}}'�� tp'aateh 29 ROaui .rif 'l�0�CNo000
�g
.Q�igp9p.
jG�QQ V yy�- �I$O y� Ili v� fli V7N N vhl vl exxd any l� l��{ryry ER
E
�jLL=Q�LL��� � m6 M16666 a664�66 n� K'1titiO <.E6�6d66�
M
W 004 �aad3T ah alai Si "fah "� m "d m "� ma�wa""a
n n n n n n n a a n a a a n a n
m a a a a
p=35B36'�E��'�66L�3�'j6�6==6=6=6=C=33p 9pp 8,Qpp
OI m m m" m m m m m m m A OI m m
nan0pppnppp�nppp/^/m���m^n1a�o^p�pp^mnpc^^pola�olcc�op'�Q�p�a^ov��1(�l0000 �00000 099
2
Entity
ERD (TST 6049)
ERD (TST 6%9)
ERD (rSr 6049)
ERD M76049)
ERD M 6049)
ERD (TST 6049)
ERD (TSr6049)
ERD (TST 6049)
ERD (rSr 6049)
ERD (TST 6049)
ERD (rST 6049)
ERD(TSr 6049)
ERD (TST 6049)
ERD (TSr 6049)
ERD (TST 6049)
ERD tM 6049)
ERD (TST 6049)
ERD (TST 6049)
ERD (TST 6049)
ERD (TSr 6049)
ERD (TSr 6049)
ERD fFST6049)
ERD (W 6049)
ERD (TSr6049)
ERD (TST6049)
ERD (TSr 6049)
ERD (TST 6049)
ERD (TST 6049)
ERD (TST 6049)
ICC-ES (EVL 2396)
Miami -Dade (CER 2592)
PoWlass USA
Polyglass USA
Polyglass USA
UL, U.C. (QUA96M
Examination
Physical Propertles
Physical Properties
Physical Properties
Wind Uplift
Physical Properties
Wind Uplift
Wind Uplift
IMnd Uplift
Wind Uplift
Wind Uplift
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Wind Uplift
Physical Properties
Wind Uplift
Physical Properties
Physical Properties
Physical Properties
IBCCompliance
HVHZ Compliance
Manufacturing Affidavit
P/LAffidavlt
Materials Affidavit
Quality control
Reference
P40390.08.12-1
P40390.08.12-2
C41420.09.12-3
P396=03.13
P45370.04.13
P1738.02.07-112
11757.04.01-1-R1
P41630.08.13
P3175LO5.03-RI
PI178L11.03-RI
P45270.05.14
6020.07.24.2
6020.09.14-2
6020.09.14-3
6020.09.14-4
6020.09.24-5
602D.09.14-6
P46520.10.14
P4329).10.14
PLYG-SC7550.03.15
P40390.04.15
P44360.10.14-R1
PLYG-SCBM.OS15-1
PLYG-SC8905.05.16-1
PLYG-5C8080.07.16
PLYG-SC22025.10.16
PLYGSC33040.12.16
PLYG-SC11900.03.17
PLYG-SC12115.08.17
ESR-1697
NOA34-D717.08
Products Current
Mule -Hide Cross I%
Polystick SA Compound
Service Confirmation
4. PRoDUcr DERRIPnON:
41 - MectraiilrallyFas, ,'"e"drtJieleibymerits
4.2.1 Elastobase Is a fiberglass reinforced, SB5 modified bitumen base sheet.
4.1.2 Elastobase P is a polyester-relnforced, SOS modified bitumen base sheet.
4.1.3 Polyglass 62 Base is a fiberglass -reinforced, asphaltic base sheet
4.1.4 Polyglass APP Base is a fiberglass -reinforced, APP modified bitumen base sheet
®MEMO etc.
Date
08/06/2012
O8/07/2012
09/31/2012
03/04/2013
04/26/2013
04/29/2013
04/30/2013
08/06/2013
22/26/2013
11/26/2013
05/12/2014
09/DS/2014
09/08/2014
09/08/203A
09/09/2014
09/08/2024
09/08/2014
30/03/2014
10/17/2014
03/24/2015
04/03/2015
05/18/2015
05/20/2015
OS/17/2016
07/26/2016
10/12/2016
12/27/2016
03/20/2017
09/08/2017
11/01/2D14
01/22/2015
02/18/2009
03/01/2008
08/18/2011
Exp.10/05/2018
4.2.1 Polystick MrS or Polystick MTS PLUS is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass
fiber reinforced, surfaced with polyolefinle film surface; meets FRSA/YRI April 2012.
4.2.2 Polystick IR-%e Is a nominal 60-mll thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with an
aggregate surface; meets ASTM D1970.
4.23 Polystick TU Plus is a nominal 80-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a
polyester fabric surface; meets A5TM M70 and FRSAfM April 2012.
MEMO ETC, LLC Evaluation Report P12060.02.09-1124
rerty79ta ojnuNodartbn l32455 6poly�ass Roof U Perlaymams• (, 954) 233-1230 Revision 24. M 24/2018
Page 3 of 74
ONEMOJetc.
4.2.4 Polystick TU P is a nominal 130-mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester
reinforced, with a granular surface; meets FRSAfMI April 2022.
4.2.5 Polystick TU Max Is a nominal 60-mll thick rubberized asphalt waterproofing membrane with a 190 g/m2 polyester
fabric surface; meets ASTM D1970 and FRSA/TRI April 2012.
4.2.6 PoWex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR) are polyester.
reinforced, APP modified bitumen cap sheets, meet FRSA/TRI April 2012.
4.2.7 Polystick Dual Pro'" is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a polyester fabric surface; meets ASTM D1970.
4.2.8 Polystick Tile Pro'" is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012.
4.2.9 Polystick MU-X is a nominal 54-mil thick, dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a polypropylene film surface; meets AC188 and physical requirements of ASTM D2970 (See Section
5.8).
4.3.1 Elastoflex G TU is a polyester reinforced, modified bitumen tile underlayment composed of a sand -surfaced SBS
modified bitumen back -side and granule -surfaced APP modified bitumen top -side. Elastoflex G TU is for use as an
alternate to "Mineral Surface Roll Rooflng" (ASTM D6380, Gass M) in the Single Ply System" from FRSA/TRI April
2012 (04-12) beneath mechanically fastened tile roof systems or Hot Asphalt applied "Cap Sheet" in the "Two Ply
System" from FRSA/TRi April 2012 (04-12) beneath mechanically fastened or adhered the roof systems.
4.32 Elastoflex S6 G and Elastoflex S6 6 FR are polyester reinforced, SBS modified bitumen cap sheets; meet ASTM D6164.
Elastoflex S6 6 and Elastoflex S6 G FR are for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380,
Class M) In the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems.
Elastoflex S6 G Is for use as an alternate to Hot Asphalt applied "Cap Sheet•' in the "Two Ply Systare from FRSA/TRI
April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Elastoflex S6 G FR is for use as an
alternate to Hot Asphalt applied "Cap Sheet" In the 'Two Ply System' from FRSA/TRI April 2012 (04-12) beneath
mechanically fastened tile roof systems.
4.3.3 Polyflex G and Polyflex G FR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222.
Polyflex 6 is for use as an alternate to Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012
(04-12) beneath mechanically fastened or adhered tile roof systems. Polynex G FR Is for use as an alternate to Heat
Applied "Cap Sheet' in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile
roof systems.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither NEMOIetc. nor Robert Nieminen, P.E. are, in any way, the Designer of
Record for any project on which this Evaluation Report, or previous versions thereof, Is/was used for permitting or
design guidance unless retained spedficallyfor that purpose.
5.2 This Evaluation Report Is not for use in the HVHL
53 Fire Classification Is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire
ratings of this product
5.4 Polyglass Roof Undedayments may be used with any prepared roof cover where the product Is specifically referenced
within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for
approval based on this evaluation combined with supporting data forthe prepared roof covering.
NEMO ETS 1LC. Ewluatlon Report P12060.02.09-1124
a4lm rfA"th"dmtian M455 6m EDITION(2017) FBC NON-HVHZEVAWATION F1.5259-1128
PolygiaZ Raof Underlaymems; (954) 233-1230 Revision 24: 01/24/2018
Page 4 of 14
oNenno j etc.
5.5 Allowable Roof Covers:
Underlayment
Asphalt Shingles
Nalt-On Ilia
Foam -on Toe
metal
W-dShakes
Stshlreles
slate
Elastobase
Yes
Yes
1�5h�InZpfysVuor)
Yes
(B=Sh�ln2-plyv,�)
Yes
Yes
Yes
Etastobase P
Yes
Yes
Yes
Yes
Yes
yes
Polyglass G2 Base
No
Ieam Yes
Yes
No
No
No
Polygla5sAPP Base
No
Yes
Yes
No
No
No
Polystfick MTS or MTS PLUS
Yes
Yes
No
Yes
Yes
Yes
PolystickIR-)(e
Yes
No
NO
No
Yes
Yes —
PolpdckTU P
No
Yes
Yes (See S.5,1)
No
No
No
PoWck TU Plus
Yes
Yes
Yes (SeeS.SI)
Yes
Yes
Yes
PolyseckTU Max
No
Yes
Yes (SCeS5,I)
Yes
No
No
PGIVSUCkDUBIPM
Yes
No
No
Yes
Yes
Yes
PolystickThe Pro
Yes
Yes
Yes (See55.1)
Yes
Yes
Yes
POWI&MU-X
Yes
No
No —
Yes
Yes
yes
Elastoflex SSG
Yes
Yes
Yes (See 5.S.1)
No
yes
Yes
Elastoflex S6 G FR
—TC;—
Yes
No
No
Yes
Yes
EiastonexrTu
Yes
yes
Yes (SMS.S.1)
No
Yes
Yes—
PGWexG
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
PCIVf1exG FR
Yes
Yes
No
No
Yes
Yes
PoWexSAP urSAP Fit
Yes
Yes
(See55-1)
Na
Yes
Yes
Mule,HIde SA-APP rap Sheet
crSA-APP Cap Sheet (FR)
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
5.5.1 "Foam -On Tile" Is limited to use of the following Approved tile adhesives / underlayment combinations.
pus JLGA;,4i�lMl lyNpewwYdl
Florida Product Undedallments
AdhesiveApproval
CAP Foam Touch'n Seal Stormliond Roof
FL14505
poWckTU Plus, PolystickTU Max
Tile Adhesive
DowTllelhond"
FL22525
polysuckTu P, PaWckTU Plus, Polyflex SAP or Tile Pro
Polystick TU P, PolystickTU Plus, PC[Vsflck TU Max, Polystick Tile Pro,
JCP Adhesives Pclysetm AH-160
FL6332
Eiastaflex G TU, Ejastofiex S6 G, Polyflex G, Polyflex: SAP, PoWex SA Cap FR,
Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR)
Polystick TU P, PoWfick TU Plus, Polystick TU Max, Polystick Tile Pro,
ICP Adhesives PolysetO R`rA-1
FL6276
Elastoflex G TU, Elastoflex 55 G, PoWex G, Polyflex SAP, Polyflex SA Cap FR,
Mule -Hide SA-APP Cap Sheet or Mule -Hide SXAPP Cap Sheet (FRI
Refer to Tile Manufacturers or Adhesive manufacturer's Florida ProductApprovo)for Overturning Momert Resl5tOnw Perf0munce
NEMO ETC, LLQ Ewlu3UM RePort P12060.02.09-R24
CoWod. VfAdMr&otbn MARS BTM ODMON (20,7) Flic Nt)N4mz EuAwAnoN FL5259-R28
polygl= Roof Undedayments, (954) 233-1230 Rwislon 24:01/2412018
Page 3 of 14
ONEMOJetc.
5.6 Allowable Substrates:
5.6.1 Direct -Bond to Deck:
Polystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet
(FR) self -adhered to;
D New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing
plywood; New or existing, unprimed OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed
Southern Yellow Pine; ASTM D42 primed structural concrete; Huber Engineered Woods "ZIP System" Panels
(designed and installed to meetwind loads for project).
Note. Polyglass does not require priming of new or existing plywood or OSB sheathing. New or existing plywood or
OSS sheathing should be cleaned of all dirt and debris prior to application of Pawkk membranes.
Elastaflex G TU, Elastoflex S6 G or Elastoflex s6 G FR In hot asphalt to:
D ASTM D41 primed structural concrete.
Polyflex G or Polyflex G FR torchapplied to:
D ASTM D41 primed structural concrete.
5.6.2 Band -to -Insulation:
Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered
to:
D ASTM CIM, Type 11, Class 1 polyisocyanurate or Type V polyisocyanurate-composite insulation; Dens Deck
DuraGuard; Dens Deck Prime; or SECUROCKGypsum-Fiber Roof Board.
Elastoflex GTU, Elastoflex S6 G or Elastaflex 56 G FR In hot asphalt to:
D Dens Deck Prime or SECUROCK Gypsum-Flber Roof Board.
Polyflex G or Polyflex G FR torch -applied to:
D ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, Insulation shall be attached per minimum
requirements of the prepared roof covering manufacturer's Product Approval. For Installations under foam -on the
systems, Insulation attachment shall be designed by a qualified design professional and Installed based an testing of
the insulation/underlayment system in accordance with FBC Section 1504.3.1.
5.63 Bond to Mechanically Attached Base Laver.
Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or
Tile Pro self -adhered to:
D ASTM D226, Type I or It felt; Elastobase; Elastobase P or Mule -Hide Nall Base.
Elastoflex G TU, Elastaflex 56 G or Elastoflex S6 G FR In hot asphalt to:
D ASTM D226, Type I or II felt; Elastobase; Elastobase P, Mule -Hide Nall Base or Polyglass G2 Base.
Polyflex G or Polyflex G FR Larch -applied to:
D Elastobase; Elastobase P, Mule -Hide Nail Base, Polyglass G2 Base or Palyglass APP Base.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum
codified requirements. For Installations under foam -an the systems, base layer shall be attached per minimum
requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein, or as tested in
accordance with FBC Section 15043.1.
NEMOETC, LLC. Ewluaaoo Report P12060.02.09-R24
a9nJlrare ofANhorhaaantl324i5 6TM EUMON(2017) FBC NON4WHZEVALUATION Ft5259•R2B
Polygiess Roof Onderiaymcnb; (954) 233-1Z30 Revision 24: a1/W2036
Page 6 of 14
ONEMOJetc.
5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12) does not
address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment
forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not
addressed in FRSA/rRI April 2012 (04-22) and are used in foam -On the applications. Maximum Design Pressure Is the
result of testing for wind load resistance based On allowable wind loads, and reflects the ultimate passing pressure
divided by 2 (the 2 to 1 margin Of safety per FBC 15G4.9 has already been applied). Refer to FRSA/rRI April 2012 (04-
12), Appendix A, Table 1A or FBC 1609 for determination of design wind loads.
#1 Maximum Design Pressure =-90osh
Deck: MIn.15/324nch plywoodto meetpmject mquimmentstasaUsfactianufAuthority HavingJudsdiction.
Primer. None
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP F% Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
#2 Maximum Design Pressure --97.5pst
Deck: Min. 25/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: PG100 or ASTM D41
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Poyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x
3W ring shank nails through 32 ga., i-5/8' diameter tin caps spaced 12-inch a.c.
#3 Maximum Design Pressure =-105 0A
Deck: MIn.15/32-inch plywood to meet project requirements to satisfaction of Authority Having.lurlsdiction.
Primer. we-3000
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polysack TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x
135" ring shank nails through 32 ga., 1-5/8' diameter tin caps spaced 12-inch o.c.
44 Maximum Design Pressure =-135 psf:
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Havinglurisdiction.
Pdmer. (Optional) PG100 or ASTM D41
Base Ply: (Optional) Polysdck MTS or Polystick MTS PLUS, self -adhered.
Joints: MIn.4-Inch wide strips of Elastoflex SA-V over all plywood Joints
Underlayment Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule-Hkde SA-APP Cap Sheet (FR), self -adhered.
#5 Maximum Design Pressure --315osF.
Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: PG100 or ASTM D41
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Tile P% Polygex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap
Sheet and Mule -Hide SA-APP Cap Sheet (FR), seffadhered.
#6 Maximum Design Pressure=-6225
Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer. PG100 or ASrM D41
Underlayment- Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or Polyflex G, torchapplied.
#7 Maximum Design Pressure =-30.0 psP
Deck: Min.15/32-inch OSB to meet project requirements to satisfaction of Authority HavinglurisdlcLion.
Base Sheet: Elastobase or Mule -Hide Nail ease (poly -film top surface)
Fasteners: 11 ga. x 1.25-Inch long x 1-inch head diameter round metal cap nails
Spacing: 64nch o.c. at the }Inch wide side laps and 64nch o.c. at two (2) equally spaced staggered center rows.
Base Ply: (Optional) Polystick MTS or Polystick MIS PLUS, self -adhered.
Underlayment Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP F% Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
NEMO ETC, LLC, Evaluation Report P12060.02A9-R24
Gfdgk m ClAudMmi a u mC324ST IP ERMON 12017) FBC NON-HVHZ EVALUATION FL52s9-R28
PnlyDass Root Underlaymeats, ISM) 233-IMB Revision 24: 0S/24/2018
Page7 of M
ONEMOJetc.
#8 Maximum Design Pressure=-37.5 osf*:
Deck: Min.15/32inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet Elastobase or Mule -Hide Nail Base(poly-film top surface)
Fasteners: 11 ga. x 1.254nch longx finch head diameter round metal rap nails
Spacing: 6-Inch ac. at the }Inch wide side laps and 6-Inch o.c. at two (2) equally spaced staggered center rows
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlaymem: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflax SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
#9 Maximum Design Pressure =-37.5 psi
Deck: Min.19/32inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: One (1) or two (2) layers ASTM D226, Type ll felt
Fasteners: 11ga. x L25-inch long 1-inch head diameter round metal cap nails
Spacing: 6-Inch c.c. at the }Inch wide side laps and 12-Inch o.c. at two (2) equally spaced staggered center rows.
Undedayment: Elastotlex G TU or Elastaflex S6 G, applied in full mopping of hot asphalt
#10 Maximum Design Pressure --45 psf*;
Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority HavingJurisdiction.
Base Sheet: One (1) IayerASTM D226, Type II felt
Fasteners: 11 ge.x L25-Inchx3/8-inch head diameter annular ring shank roofing nails at 2-5/9-hrch diameter tin caps
Spacing: 4-Inch o.c. at the 2-inch wide side laps and 4-Inch o.c. at two (2) equally spaced staggered center rows.
Base Ply: (Optional; for use with self -adhering underiaymem only) Polystick MTS or Polystick MTS PLUS, selfadhered.
Underlaymem: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU, applied In full mopping of hot asphalt.
#11 Maximum Design Pressure =-45 psf°:
Deck: Min:L9/32-Inch plywood to meet project requirements to satisfaction of Authority Having Judsdiction..
Base Sheet: Two (2) layers ASTM D226, Type II felt
Fasteners: 11 ge.x 1.25-Inch long 3/84nch head diameter annular ring shank roofing nails at 2-5/8-Inch diameter tin caps
Spacing: 9-inch c.c. at the 24nch wide side laps and 94nch o.c at two (2) equally spaced staggered center rows.
Base Ply: (Optional; for use with self- adhering underlayment only) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underiaymem: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP Fit, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), selfadhered or Elastoflex G TU or Elastaflex S6 G, applied In full mopping of hot
asphalt
#12 Maximum Design Pressure =-45 psi:
Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority HavingJurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torchapplied cap or poly -film surface fortorch-applied cap)
Fasteners: Simplex MA70C Cap Fasteners
Spacing: 9-inch o.c. at the 24nch wide side laps and 1.8-Inch o.a at two (2) equally spaced staggered carrier rows.
Underlayment Elastaflex G TU or Elastaflex S6 G, applied In full mopping of hot asphalt or Pclyfiex G, torch -applied.
#13 Maximum Design Pressure=-52.5 psE
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority HavingJurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Smplat MAXX Cap Fasteners
Spacing: 9-inch or- at the 2-Inch wide side laps and 12-Inch O.C. at two (2) equally spaced staggered center rows.
Undedayment• Elastaflex G TU or Elastaflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#24 Maximum Design Pressure =-525 psi:
Deck Min.15%324nch plywood to meet project requirementsto satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase or Mule -Hide Nall Base(poly-film top surface)
Fasteners: Simplex Original Cap Nails
Spacing: 6-Inch o.c at the 34nch wide side laps and 6-inch ox at four(4) equally spaced staggered center rows
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlaymem: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP Fit, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
NEMO ETC, U.C. Evaluation Report P1206002.09-R24
Oe Wote ofAUftdWtion 032455 6TM EDITION (2017)FBC NON-HVN2 EVALUATION FL525.9-RZB
Polygki Roof Underlaymems; (9S4) 733.1230 RYisTan 24:0112412018
Page 8 of 14
00NEMICIletc.
#15 Maximum Design Pressure =-525 0511
Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority HavingJurisdiction.
Base Sheet: Elastobase(sanded top surface for hot -asphalt or tomhapplied cap or poly -film surface for tench -applied Cap)
Fasteners: Simplex Original Cap Nails
Spacing: 6-inch o.c at the 3-inch wide side laps and &inch o.c at four 14) equally spaced staggered center rows.
Underlayment Elastoflex G TU or Elastaflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#26 Maximum Design Pressure =-60 Dsf:
Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase(sanded top surface for hot -asphalt or torch -applied cap or poly -film surface fortorch-applied cap)
Fasteners 11 ga.x125-Inch longx 3/84nch head diameter annular ring shank roofing nails at 1-5/8-Inch diametertln caps
Spacing: 84nch o.c. at the 4-Inch wide side laps and 8-Inch o.c at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU a Elastoflex 56 G, appiled In full mopping of hat asphalt or Polyflex G, torch -applied.
#17 Maximum Design Pressure =-60 psf:
Deck Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having lurlst iction.
Base Sheet Elastobase(sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for tumliapplied cap)
Fasteners: OMG #12 Standard RoDfgdp with OMG Flat Bottom Metal Plates
Spacing. 12-inch a.c. atthe 4-Inch wide side laps and 124nch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastaflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#19 Maximum Design Pressure=-67.5 psf:
Deck Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet Polyglass 62 Base or Polyglass APP Base (requires use of torch -applied underayment)
Fasteners: 12 ga. x 1.25•inch long 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps
Spacing: 8-Inch me at the 4-Inch wide side laps and &Inch ac at four (4) equally spaced staggered center rows.
Underlayment: Elastotex G TU or Elastoflex 56 G, applied In full mopping of hot asphalt or torch -applied or Polyflex G, torch -
applied.
#19 Maximum Design Pressure=-75 psf.
Deck: Min.15/324nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of taro ipplled undMayment)
Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG 3" Galvalume Steel Plates, OMG Roofgrip #14 with
OMG Fiat Bottom Plates (AccuTrac). Trufast HD with Trufast 34ndh Insulation Plates or Simplex MAxX Cap
Fasteners
Spacing: 10dnch o.c. atthe 4-Inch wide side laps and 1G4nch ac at three (3) equally spaced staggered center rows.
Underlayment Elastoflex G TU or Mastofim 56 G, applied in fug mopping of hot asphalt or torch -applied or Polyflex G, torch -
applied.
#20 Maximum Design Pressure =-900sf:
Deck: Min. IS/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet Elastobase(sanded top surface for hot -asphalt or torch-appiled cap or poly -film surface for torch -applied cap)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 6-fnch o.c atthe 2-Inchwide side laps and &-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastaflex G TU or Elastoflex S6 G, applied in full mapping of hot asphalt or Polyflex G, torch -applied.
#21 Maximum Design Pressure =-90 osF.
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
BaseSheet: Elastobase(sanded top surface for hot -asphalt or torch -applied rap or potµfilm surface for torch -applied cap)
Fasteners: OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3' Round Metal Plates or CMG Flat Bottom Metal
Plates
Sparing: &-inch o.c at the 4-Inch wide side laps and &-Inch o.c at three (3) equally spaced staggered center rows.
Underlayment Elastoflex G TU or Elastaflex S6 G, applied In full mopping of hot asphalt or Patyflex G, torch -applied.
#22 Maximum Design Pressure =.90 osh
Deck Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase(sanded top surface)
Fasteners: Trufast #12 DP or Trrcast4114 HD with Trufast 3' Metal Insulation Plates
Spacing: 6-Inch o.c at the 44nch wide side laps and &•inch am at three (3) equally spaced staggered center rows.
Underlayment; Elastoflex G TU or Elastaflex S6 G, applied In full mopping of hot asphalt
NEMO ETC LLC Evaluation Report P32060.02.09-R24
rera5coftQFAutlndmtim 032455 eEDITION 12017) FBC NON4WKEVALUATION FL5259-1128
Polyglass Roof Underlayments, (954) 233,1230 Revldon 2,4:01/24/2018
Page 9 of 14
ONEMOletc.
#23 Maximum Design Pressure = -90 osi
Deck: Min. 25/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet. Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment)
Fasteners: Dekfast #14 with Dekfast Her plates, OMG #14 HD with OMG 3' Galvalume Steel Plates, CMG Roofgrip #14 with
OMG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-Inch Insulation Plates or Simplex MAXX Cap
Fasteners
Spacing: 94nch o.c. at the 4-Inch wide side laps and 9-Inch o.c. at four (4) equally spaced staggered center rows.
Undedaymem: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch- applied or Polyflex G, torch -
applied.
#24 Maximum Design Pressure = -97.S
Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners 11 ga.x L25-Inch x 3/8-Inch head diameter annular ring shank roafing nails at 1-5/8-Inch diameter tin caps
Spacing: 4-Inch o.c at the 4-Inch wide side laps and flinch o.c, at four (4) equally spaced staggered center rows.
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered
Undedayment: Polystick TU P, PolystickTU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
#25 Maximum Design Pressure =-105 A
Deck: Min.15/32Nnch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface fortorrh-applied cep)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 6-Inch o.c at the 24nch wide side laps and 6-inch mc. at three (3) equally spared staggered center rows.
Underayment: Elastoflex G TU or Elastoflex SS G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#26 Maximum Design Pressure --112.S P
Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: 11 ga-x 1.25-Inch x3194nch head diameter annular ring shank roofing nails at l-S/94nch diametertinraps
Spacing: 6-Inch o.c at the 4-inch wide side laps and 6-inth o.c at four (4) equally spaced staggered center rows.
Primer. PG1C0 or ASTM D41 primer at all tin -caps
Base Ply: Polyetick MTS or Polystick MTS PLUS, self -adhered
Underlayment. Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (Fit), self -adhered.
#27 Maximum Design Pressure=-120 osf:
Dacia Min.15/32-Inch plywood to meet project requirementsto satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surfacefor hot -asphalt or torch -applied cap or poly -film surface for torch-applled cap)
Fasteners: CMG #12 Standard Roofgdp or OMG #14 Heavy Duty with OMG 3' Round Metal Plates or OMG Flat Bottom Metal
Plates
Spacing. 6-Inch o.c. atthe 4-Inch wide side laps and 64nch o.c. atflve (5) equally spaced staggered center rows.
Underayment: Elastoflex G TU or Elastoflex 56 G, applied In full mopping of hot asphalt or Polyflex G, torch -applied.
#28 Maximum Design Pressure=-120ttsf:
Deck: Min.25/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface)
Fasteners: Trufast#12 OP orTrubst#14 HD with Trufast 3" Metal Insulation Plates
Spacing. 6-Inch o.c at the 4-Inch wide side laps and 6-inch o.c. at five (5) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt.
5.6.4.1 All other direct -deck, adhered Polyglass underlayment systems beneath foam -on file systems carry a Maximum
Design Pressure of -45 psf.
NEMO ETC, LLC. Evaluation Report P32060.02119424
feffl& eo/AuMadmnon 03240 eEDMON(2027) FBC NON-HVHZ EVALUATION FL5259-07a
Polyglass Roof Undarlayments; (954) 233-IZM Revision 24:01/24/2018
Page 10 of 14
r
ONEMOjetc.
5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed
that required under FRSA/TRI April 2012 (04-22), Appendix A, Table 1A.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design
pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density
designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are
ANSI/SPRI WD3, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RA5117. Assemblies marked
with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January
2016) for Zone 2/3 enhancements.
5.7 Exposure Limitations:
Elastabase, Elastobase P, Polyglass G2 Base or Polyglass APP Base shall not be left exposed for longer than 30-days
after Installation.
Polystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 90-days after Installation.
Polystick M1[5, MTS PLUS, TU P, TU Plus, TU Max, Dual Pro, Tile Pro or Elastoflex G TU shall not be left exposed for
longer than 180-days after Installation.
Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure
limitation, unless the prepared roof covering Is to be adhesive -set tile, in which case the maximum exposure Is 30
days.
Elastoflex S6 G or Elastoflex 56 G FR or Polyflex G or Polyflex G FR does not have an exposure limitation, unless the
prepared roof covering Is to be adhesive -set tile (Elastoflex S6 G or Polyflex G only), in which case the maximum
exposure Is 190 days.
5.8 Polystick MU-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226
roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as
set forth In Section 4.3, Note 1 of ASTM D1970-15, should be established as to slip resistance.
5.9 Tile Slippage Limitations (FRSA/TRI Avril 2022 (04-121),
When loading roof tiles on the underlayment In direct -deck tile assemblies, the maximum roof slope shall be as
follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles.
ibnsrnifDlfeFcoiix.X�irr'InsTA
g7roW- .`: •i', ,:�:; %-.
Underlayment
Tile Profile
Staging Method
Maximum Sloper
Elastoflex G TU
Rat
10-tile stark
7:12
Lugged
8-tile stack (6 over 2)
6:12
Elastoflex SSG or S6 G FR
Flator Lugged
6-tile stack (4 over 2)
4:12
Polystick MTS or MTS PLUS
Flat
6-tile stack (4 over 2)
5:12
Lugged
6-tile stack (4 over 2)
4:12
PolystickTilePm
Rat or Lugged
6-tile stack (4 over 2)
7:12
PolystickTU Max
Flat
6-tile stack (4 over 2) or 20-tile stark
7:12
Lugged
6-tilestack(4over2)
7:22
Lugged
10-tile stack
6:12
PolystTckTUP
Flat
6-tile stack (4 over 2)
6:22
Lugged
6-tile stack (4 over 2)
4:12
PolystickTU Plus
fl at or Lugged
5-tile stack (4 over 2)
7:12
Flator Lugged
10-tile stack
6:22
Polyflex G or G FR
Rat or Lugged
6-tile stack (4 over 2)
4:12
Polyflex SA P or SA P FR
Rat or Lugged
6-tile stack (4 war 2)
1 4:12
NEMO ETC, LLC. Evaluatlon Repoft P12060.02.09-R24
Qu*mle.fAuNa(e 40M455 dm EPMON(2017) FBC NON+NHZEVALUATION FL9299-R28
Poiyglass Roof Underlayments, (954) 233.12a0 Revlsion 24: OV2412MB
Page 11 of I4
ONEMOletc.
6. IrwAumn=:
6.1 Polyglass Roof Underlayments shall be installed in accordance with Polyglass published installation requirements
subject to the Umkatlons set forth in Section 5 herein and the specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove
any dust and debris prior to application, and prime the substrate (if applicable).
Shall be installed in compliance with the codified requirements for ASTM D226, Type II underiayment in FBC Table
1507.L3 for the type of prepared roof covering to be installed.
Elastobase, Elastobase P or Mule -Hide Nag Base may be covered with a layer of Poiystick, Polyflex SAP, Polyflex SA
P FR, Mule -Hide SAAPP Cap Sheet or SAAPP Cap Sheet (FR), self -adhered, Elastoflax G TU, Elastofiex S6 G or
Elastoflex S5 G FR in hot asphalt or Polyflex G or Polyflex G FR, torch applied. Roof cover limitations are those are
those associated with the top-layerunderlayment, as set forth in Table 1,
6.3.2 Tile Applications:
Elastobase, Elastobase P or Mule4gde Nall Base are limited to use as a mechanically attached base sheet in the `Two
Ply System" from FRSA/TRI April 2012 (04-12). Reference is made to Table 1 and Section 5.6.4 herein, coupled with
FRSA/TRI April 2012 (04-12) Installation Manual.
6.4i Po�stit:NEST_IVRSR[t1,511tt7(€3i1:PsTFJPI4¢r?UIVIdxi:P!S?►ATIELdrIviU>Cot.FOIYRek.SAp,PofyfleiC1CPFRt
Mule-Mde'SAcAp�!F.�p'Syfe�tor`Mute�UdeSglk P
6.4.1 Shall be Installed In compliance with the codified requirements for ASTM D1970 (except PolysdckTU P) underlayment
in FBC Table 1SO7.L1 for the type of prepared roof covering to be installed.
6.4.2 Direct -to -Deck with Mechanically Fastened Roof Covers:
All self -adhering materials, with the exceptlon of PolystIc k TU Plus, Palyflex SAP or SAP FR and Mule -Hide SA APP
Cap Sheet or SAAAPP Cap Sheet (FR) should be back -nailed in selvage edge seam In accordance with Polyglass / Mule -
Hide back nailing guidelines. Nails shall be corrosion resnstant, 11 gauge ring -shank type with a minimum 1-inch
diameter metal disk or Simplex -type metal cap nail, at a minimum rate of 12" o.c Polystick TU Plus should be back -
nailed using the above noted fasteners and spacing, in area marked "nail area, area pare clever" on the face of
membrane. The head lap membrane Is to cover the area being back -nailed.
All seal -lap seams (selvage laps) must be
firmly rolled with a minimum 28 lb. hand
rollerto ensure full contact and adhesion.
For Dual Pro and Tile Pro, align the edge of
the top sheet to the end of the glue pattern
(the sheet will overlap the fabric). LM
View of OwhpSeam of oral Pmaad nla Pro
All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyplus SO Premium Modified
Wet/Drytement or Polyglass PGSBO Modified Cement applied in between the application of the lap.
PolystickTU Pius, Dual Pro and Tile Pro may not be used in any exposed application such as crickets, exposed valleys,
or exposed roof to wall details
NEMO ETC, r Evaluation Repan PIM50.0209-I124
O°v pa VfAatha aamne'LCC 6w EDmON (20171 FOC 140144nuREVALUATION FL5759•R78
PoWW= Roof Underlayments, (9541233-IM Revision 24: "4/2M8
Page 12 of 14
ONEMOjetc.
Repair of Polystick membranes is to be accomplished by applying Polyplus 50 Premium Modified Wet/Dry Cement or
Polyglass P6500 Modified Cement to the area In need of repair, followed by a minimum 6 x 6 inch patch of the
Polystick material of like kind, set and hand rolled in place over the repair area. Patch laps, if needed, shall be
Installed In a water shedding manner.
All Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a
minimum of 404b weighted -roller or, on steep slopes, use of a stiff broom with approximately 40-lbs of load applied
for the field membrane. Hand rollers are acceptable for rolling of patches, laps (min.28111 roller) or small areas of the
roof that are not accessible to a large roller or broom.
6.4.3 Tile Applications (not allowed forPolvstick Dual P%IR-Xe or PalwUrk Mfl-X):
Reference Is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the Instructions
noted above as a guideline.
For mechanically fastened file roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base
Sheet fastening shall be not less than FRSA/TRI April 201Z (04-12). Table L
For adhesive -set tile applications, refer to Section 5.6A herein.
6.4.4 Two (2) Ply Underlayment Systems:
Polystick MTS or MTS PLUS followed by Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Tile Pro, MU-x or Polyflex
SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with
the top -layer material. This Is not a requirement, but is allowable if a 2-ply underlayment system Is desired.
Polystick NITS or MTS PLUS followed by Polystick TU P, TU Plus, TU Max, Tile Pro or Polyflex SAP is allowable for use
under foam -on tile systems. Limits of use are those associated with the top -layer material. This Is not a requirement,
but Is allowable if a 2-olv underlayment system Is desired.
6.5.1 lElastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR shall be installed In compliance with current Polyglass published
Installation requirements. For use In tile applications:
✓ Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing' (ASTM D5380, Class M) in the "Single
Ply System" from FRSA/TRJ April 2012 (04-22) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied 'Cap Sheet" in the `Two Ply System' from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or
adhered tile roof systems.
✓ Elastoflex S6 G is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply
System' from FRSA/TRI April 2022 (04-12) beneath mechanically fastened the roof systems or the Hot Asphalt
applied "Cap Sheet' In the'Two Ply System' from FR5A/TRI April 2012 (04-12) beneath mechanically fastened or
adhered the roof systems.
✓ Elastoflex S6 G FR is for use as an alternate to "Mineral Surface Roll Roofing' (ASTM D6380, Class M) in the "Single
Ply System' from FRSA/TRI April 2012 (04-22) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied 'Cap Sheet" in the'Two Ply System' from FRSA/TRI April 2012 (04-22) beneath mechanically fastened tile
roof systems.
6S.2 For hot -asphalt -applications, Elastoflex G TU, MastoftexS6 G or Elastotlex S6 G FR shall be fully asphalt -applied to the
substrates noted In Section 5.6. Side laps shall be minimum 3-inch and end -laps minimum 6-Inch wide, off -set
minimum 3 feet from course to course. Side and end laps shall be fully adhered In a complete mopping of hot asphalt
with asphalt extending approximately 3/8-Inch beyond the lap edge.
6.6.1 Polyflex G or Polyfiex G FR shall be installed In compliance with current Polyglass punllsne0 lnsrallauon regwremenrs.
For use in tile applications:
✓ Polyflex G Is for use as an alternate to the Heat Applied'Cap Sheet" In the 'Two Ply System" from FRSA/TRI April
2012 (04-12) beneath mechanically fastened or adhered the roof systems (Base Sheet Limited per5.63).
✓ Polyflex G FR is for use as an alternate to the Heat Applied 'Cap Sheet" In the 'Two Ply System' from FRSA/TRI
April 2012 (04-12) beneath mechanically fastened tile roof systems (Base Sheet Limited per 5.63).
NEMO ETC, ILG Ewluatlon Report P12060.02M-R24
¢RpC;ft,fAuMmlmtmn l3M4SS en'EDMON(Z017) FBC NON-HVH2 EVALUATION F`2594tza
Polyglom Roof Underlayruents, ism) 233-MO Rmldcn 24: 01/M12018
Page 23 of 14
ONEMO etc.
6.6.2 Polyflex 6 or Polyflex 6 FR shall be fully torch -applied to the substrates noted in Section 5.6. Side laps shall be
minimum 3-Inch and end -laps minimum 6-Inch wide, off -set minimum 3 feet from course to course. Side and end
laps shall be fully heat -welded and inspected to ensure minimum 3/8-inch flow of modified compound beyond the lap
edge.
6.7 Tile Stan:
6.7.1 Tile shall be loaded and staged In a manner that prevents tile slippage and/or damage to the underlayment. Refer to
Table 2 herein, and Polyglass published requirements for tile staging.
6.7.2 Battens and/or Counter -battens, as required by the file manufacturer and FRSA/TRI April 2D12 (04-12) must be used
on all roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of battens or sail-
boards, to prevent the sliding and/or damage to the undedayment during the loading process.
6.7.3 Polyglass specifies the minimum cure time after Installation of self -adhering membranes and before loading of
roofing tiles Is forty-eight (48) hours.
7. BUILDING PERMIT REQUIREMENTS'
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product
S. MANUFACTURING PLAN75:
Contact the noted QA agency for Information on product locations covered for F.A-C. 61620-3 QA requirements. The following
plants have qualified products under their respective physical properties specifications.
Femley, NV, Hazleton, PA & Winter Haven FL
ASTM D1970
PolysUck MU-X
Hazleton, PA
M-D 13-0004
Elastoflex G TU
Hazleton, PA & Winter Haven, FL
ASTM 01970
Polysdck IR-Xe .
ASTM D2970 & FRSA/fRl April 2012
PalVstick TU Plus
ASTM D1970 & FRSA MIApril 2012
Polystick TU Max
Tuscaloosa, AL
ASTM D46M, Type II
PolVgtaw G2 Base
Winter Haven, FL
ASTM D226 (p ical$)
Elastobase, Elastobase P
ASTM D6SC9
APP Base
FRSA/IRI April 2012
MTS, POlystick MTS PLUS -
FRSAj(RI April 2012
TU P
FRSArrlU ri12012
AP, Pol ex SA P FR
ASTM D1970
Dual Pro
AftlysUckTilePro
ASTM D3970 & FRSA/rRl April 201
Tile ProASTM
D6164
S6, Elastoflex S6 G FR
ASTM D6222
Po ex G FR
9. QUALITY ASSURANCE ENTITY.
Ut, LLC—QUA9625; (314) 578-3406; kchancellor@us.ul.com.
-END OF EVALUATION REPORT -