HomeMy WebLinkAboutEVALUATION REPORTSCANNED NEMO I etc. BY Cert oute of Autharirntion#32455 �t. Lucie County 353 Christian Street, Unit #13 Oxford, Cr 06478 (203)262-9245 ENGINEER EVALUATE TEST CONSULT CERTIFY EVALUATION REPORT Polyglass USA, Inc. Evaluation Report P12060.02.09-R24 1111 West Newport Center Drive FL5259-R28 Deerfield Beach, FL 33442 Date of Issuance:02/24/2009 (954)233-1230 Revision 24:01/24/2018 SCOPE: This Evaluation Report is issued under Rule 61620-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the 6tb Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: Polyglass Roof Underlayments LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the product(s), the Quality Assurance or the production facility location(s). NEM01 etc. requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMO]etc. Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the jab site at the request of the Building Official. This Evaluation Report consists of pages 1 through 14. Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59166, Florida DCA ANE1983 The facsimile seal appearing was authorized by Robert Nieminen, P.E. on 01/24/201B. This does not serve as an electronically signed document. CERTIFICATION OF INDEPENDENCE: 1. NEMO [etc. does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. NEMO I etc. is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. S. This is a building code evaluation. Neither NEMO I etc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. ONEMOletc. ROOFING COMPONENT EVALUATION: 1. SCOPE: Product Category: Roofing Sub -Category: Underlayment Compliance Statement: ROOF Underlayments, as produced by PDlyglass USA, Inc., have demonstrated compliance with the following sections of the 6th Edition (2017) Florida Building Code through testing in accordance With the following Standards. Compliance is subject to the installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Prove Standard Year 1504.3.1 WindUpliftFM 4474 2011 1594.3.1 Wind Uplift UL 1897 2012 1507.2.3/ 1507.1.1 Physical Properties ASTM D226 2009 1507.2.4/1507.1.1,1507.2.9.2 Physical Properties ASTM D1970 2015 1507.3.3 Physical Properties FRSA/TRI April 2012 2012 1507.11.2 Physical Properties ASTM D6164 2011 1507.11.2 Physical Properties ASTM D6222 2012 TAS 110 Accelerated Weathering ASTM D4798 2011 3. REFERENCES: ` KROW Examination Reference Date FM Approvals (TST 1867) Wind Uplift 3004091 01/12/2000 PRI (W 5878) Physical Properties PRIO1111 04/08/2002 PRI (TST 5878) Physical Properties PUSA-005-02-01 01/31/2002 PRI (TST 5878) Physical Properties PUSA-013-02-01 12/23/2002 PRI (TST 5878) Physical Properties PUSA-013-02-02 12/23/2002 PRI (TST 5878) Physical Properties PUSA-013-02-03 12/23/2002 PRI (TST 5878) Physical Properties PUSA-018-02-01 07/14/2003 PRI (TST 5878) Physical Properties PUSA-028412-03 07/13/2005 PRI (TST 5878) Physical Properties PUSA-033-02-01 01/12/2006 PRI (TST 5878) Physical Properties PUSA-035-02-01 09/29/2005 PRI (TST 5878) Physical Properties PUSA-055-02-02 12/20/2007 PRI (TST 58781 Physical Properties PUSA,061-02-02 01/28/2008 PRI (TST 5878) Physical Properties PUSA-076-02-01 02/22/2008 PRI (TSr 5878) Physical Properties PUSA-083-02-01 04/14/2008 PRI (TST5878) Physical Properties PUSA-098-02-01 07/29/2009 MT1(TST 2508) Physical Properties JX2OH7A 04/01/2008 MTI (TST 2508) Physical Properties RX14EBA 01/29/2009 ERD (TST 6049) Physical Properties 11752.09.99-1 02/08/2000 ERD (TST 6049) Wind Uplift 11757.08.01-1 08/13/2001 ERD (TST 6049) Wind Uplift 11776.06.02 01/16/2003 ERD (TST 6049) Physical Properties 02200.07.03 07/14/2003 ERD (TST 6049) Wind Uplift P3740.01.07 02/04/2007 ERD (TST 6049) Physical Properties P5130.04.07-1 04/11/2007 ERD 0ST 6049) Wind Uplift P9260.03.08 03/21/2008 ERD (m 6049) Physical Properties P13450.08.09 08/23/2009 ERD (TST 6049) Wind Uplift P30540.11.09-R1 11/30/2009 ERD (TST 6049) Physical Properties P11030.11.09-1 11/30/2009 ERD (TST 6049) Wind Uplift P11030.11.09-2 11/30/2009 ERD (TST 6049) Physical Properties P31030.11.09-3 11/30/2009 ERD (TST 6049) Physical Properties P33360.06.10 D6/25/2010 ERD (TST 6049) Physical Properties P33370.03.11 03/02/2011 ERD (TST 6049) Physical Properties P33370.04.11 04/26/2011 ERD (TST 6049) Physical Properties P37300.10.11 10/19/2011 NEMO ETC, LLC. Evaluation Report P32060.02.09-R24 ce,tfimte 4fAuthmlzaWn N32455 6TM EDITION (2017) FHC NON-HVH2 EVALUATION FL5259-R28 Polyglass Roof Underlayments; (9541233-1230 Revision 24:0112412018 Page 2 of 14 ONEMOjetc. iDtlpf Examination Reference Date ERD (TST 6049) Physical Properties P40390.08.12-1 08/06/2012 ERD (TST 6049) Physical Properties P40390.08.12-2 08/07/2012 ERD (TST 6049) Physical Properties C41420.09.12-3 09/11/2012 ERD (TST 6049) Wind Uplift P39580.03.13 03/04/2013 ERD (TST 6049) Physical Properties P45370.04.13 04/26/2013 ERD (TST6049) Wind Uplift P1738.02.07-R2 04/29/2013 ERD (TST6049) Wind Uplift 11757.04.01-1-R1 04/30/2013 ERD (TST 6049) Wind Uplift P41630.08.13 08/06/2013 ERD (TST 6049) Wind Uplift 1311751.05.03-113 12/26/2013 ERD (TST 6049) Wind Uplift P11781.11.03-R1 11/26/2013 ERD (T57 6049) Physical Properties P45270.05.14 05/12/2014 ERD (TST 6049) Physical Properties 6020.07.14-1 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-2 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-3 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-4 09/08/2014 ERD (TST 6D49) Physical Properties 6020.09.14-5 09/08/2014 ERD (TST6049) Physical Properties 6920.09.146 09/08/2014 ERD (TST 6049) Physical Properties P46520.10.14 10/03/2014 ERD (576049) Physical Properties P43290.10.14 10/17/2014 ERD 0ST 6049) Physical Properties PLYG-SC7550.03.15 03/24/2015 ERD (TST 6049) Physical Properties P40390.04.15 04/03/2015 ERD (TST 6049) Physical Properties P44360.10.14R1 05/18/2015 ERD 0ST 6049) Physical Properties PLYG-SC8080.05.15-1 05/20/2015 ERD (TST 6049) Wind Uplift PLYG-SC8905.05.16-1 05/17/2016 ERD (TST 6049) Physical Properties PLYG-SC8080.07.16 07/15/2016 ERD (TST 6049) Wind Uplift PLYG-SC12025.10.16 20/12/2016 ERD (TST 6049) Physical Properties PLYG-SC13040.12.16 12/27/2016 ERD (TST 6049) Physical Properties PLYG-SC33900.03.17 03/10/2017 ERD OST 6049) Physical Properties PLYG-SC12115.08.17 08/08/2017 ICC-ES(EVL 23951 IBCCompliance ESR-1697 11/02/2014 Miami -Dade (CER 1592) HVHZ Compliance NUA 14-0717.08 01/22/2015 Polyglass USA Manufacturing Affidavit Products Current 02/18/2009 Polyglass USA P/LAffidavit Mule -Hide Cross Ltg 03/01/2008 Polyglass USA Materials Affidavit Polystick SA Compound 08/18/2011 UL, U.C. (QUA9625) Quality Control Service Confirmation Exp. 10/05/2018 4. PRODUCT DESCRIPTION: 4.1.1 Elastobase is a fiberglass reinforced, SBS modified bitumen base sheet. 4.1.2 Elastobase P is a polyester -reinforced, SBS modified bitumen base sheet. 4.1.3 Polyglass G2 Base is a fiberglass -reinforced, asphaltic base sheet. 4.1.4 Polyglass APP Base is a fiberglass -reinforced, APP modified bitumen base sheet. 4.2.1 PoIWIc:k MTS or Polystick IM PLUS is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, surfaced with polyolefinic film surface; meets FRSAfMI April 2012. 4.2.2 Polystick IR-Xe is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with an aggregate surface; meets ASTM D1970. 4.2.3 Polystick TU Plus is a nominal 80-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a polyester fabric surface; meets ASTM D1970 and FRS"I April 2012. NEMO ETC, LLG Evaluation Report P12060.02.09-R24 &rditmte ofauthoraatbn M32433 (P EDITION (2017)FBC NON-HVHZ EVALUATION F1.9259-11128 Polyglass Roof Underlaymentsl (934) 233-2230 Revision 24: D1/24/2018 Page 3 of 24 ONEMOletc. 4.2.4 Polystick TU P Is a nominal 130-mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester reinforced, with a granular surface; meets FRSA/TRI April 2012. 4.2.5 Polystick TU Max is a nominal 60-mil thick rubberized asphalt waterproofing membrane with a 190 g/m2 polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. 4.2.6 Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR) are polyester reinforced, APP modified bitumen cap sheets; meet FRSA/TRI April 2012. 4.2.7 Polystick Dual Prom is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyester fabric surface, meets ASTM D1970. 4.2.8 Polystick Tile Pro" is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. 4.2.9 Polystick MU-X is a nominal 54-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polypropylene film surface; meets AC188 and physical requirements of ASTM D1970 (See Section 5.8). 4.3.2 Elastoflex G TU is a polyester reinforced, modified bitumen tile underlayment composed of a sand -surfaced SBS modified bitumen back -side and granule -surfaced APP modified bitumen top -side. Elastoflex G TU Is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or Hot Asphalt applied "Cap Sheet' in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. 4.3.2 Elastoflex S6 G and Elastoflex S6 G FR are polyester reinforced, SBS modified bitumen cap sheets, meet ASTM D6164. Elastoflex S6 G and Elastoflex SB G FR are for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-22) beneath mechanically fastened tile roof systems. Elastoflex S6 G is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Elastoflex S6 G FR is for use as an alternate to Hot Asphalt applied "Cap Sheet' in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. 4.3.3 Polyflex G and Polyflex G FR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222. Polyflex G is for use as an alternate to Heat Applied "Cap Sheet' in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered the roof systems. Polyflex G FR Is for use as an alternate to Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. S. LIMITATIONS' 5.1 This is a building code evaluation. Neither NEMCG(etc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in the HVHZ. 5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire ratings of this product. 5.4 Polyglass Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering. NEMO ETC, LLC. Evaluation Report P12060.02.09-R24 Certif¢ote ofAuthor/zotion 432455 67 EI)MON(2017) FBC NON-HVHZ EVALUATION FL5259•RZB Polygiass Roof Undedayments; (954) 233.1230 Revision 24: 01/24/2018 Page 4 of 14 ONEM10jetc. 5.5 Allowable Roof Covers: ,..;s.-.. Underlayment Asphalt5hingles Nail -On The Foam -On The Metal wood Shakes Slate &shingles Elastabase Yes Yes Yes Yes Yes (BmeSheetInzplywoem) Jean Sheetne2 -pN am ym) ElastobaseP Yes Yes Yes yes yes Yes (Base Shea In 2-ply symm) (Base Sheet in 2-ply system) Polyglass G2 Base No Yes Yes No No No (Raze Sheetin2-ply,ax.) (Base Sheetin2-pry symm) Polyglass APP Base No Yes Yes No No No (Base Sheetin2-ply WAan) (Base Sheet In bply symm) Polystick NITS or NITS PLUS Yes Yes No Yes Yes Yes Polystick lR-Xe Yes No No No Yes Yes Palystick TUP _ No Yes Yes (See 5.5.1) No No No Polystick TU Plus Yes Yes Yes (See5.5.1) Yes Yes Yes Polystick TU Max No Yes Yes(See5.5.1) Yes No No Polystick Dual Pro Yes No No Yes Yes Yes Polystick Tile Pro Yes Yes Yes (See 5.5.1) Yes Yes Yes Polystick MU-X Yes No No yes Yes yes Elastoflex S6G Yes Yes Yes (See5.5.1) No Yes Yes Elastoflex S6 G PR Yes Yes No No Yes Yes Elastoflex GTU Yes Yes Yes (See 55.1) No Yes Yes PolyflexG Yes Yes Yes (See55.1) No Yes Yes PolyflexG FR Yes Yes No No Yes Yes Polyflex SAP or SAP FR Yes Yes Yes (See 55.1) No Yes Yes Mule -Hide SA-APP Cap Sheet Yes Yes Yes (See 55.1) No Yes Yes or SA-APP Cap Sheet (FR) 5.5.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / underlayment combinations. -7ABLE lA ALI[IWABLESiIi`�NESIVE�;UNPERLAYMENTCOMBINA±IONSt s `: Adhesive Florida Product Underlayments Approval DAP Foam Touch'n Seal StormBond Roof FL14506 Polystick TU Plus, Polystick TU Max Tile Adhesive Dow TileBond" FL22525 Polystick TU P, Polystick TU Plus, Polyflex SAP or Tile Pro Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro, ICP Adhesives Polysete AH-160 FL6332 Elastoflex G TU, Elastoflex 56 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR, Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro, ICP Adhesives Polyset® RTA-1 FL6276 Elastoflex G TU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR, Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) 1 Refer to Tile Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance. NEMO ETC, U.C. Evaluation Report P32060.02.09-R24 Certi/iruteefAutAnmptfpnp32455 Sn' EDITION (2017) Pat NON-HVHZ EVALUATION FL5259-RZB Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2028 Page 5 of 14 ONEMOletc. 5.6 Allowable Substrates; 5.6.1 Direct -Bond to Deck: Palystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: ➢ New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing plywood; New or existing, unprlmed .OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed Southern Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods "ZIP System" Panels (designed and installed to meet wind loads for project). Note: Polyglass does not require priming of new or existing plywood or OSB sheathing. New or existing plywood or OSB sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ ASTM D41 primed structural concrete. Polyflex G or Polyflex G FR torch -applied to: ➢ ASTM D41 primed structural concrete. 5.6.2 Bond -to -Insulation: Palystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: ➢ ASTM C1289, Type II, Class 1 polyisocyanurate or Type V polyisocyanurate-composite Insulation; Dens Deck DuraGuard; Dens Deck Prime; or SECUROCK Gypsum -Fiber Roof Board. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. Polyflex G or Polyflex G FR torch -applied to: ➢ ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum requirements of the prepared roof covering manufacturers Product Approval. For installations under foam -on tile systems, Insulation attachment shall he designed by a qualified design professional and installed based on testing of the insulation/underlayment system in accordance with FBC Section 1504.3.2. 5.6.3 Bond to Mechanically Attached Base Laver: Palystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or Tile Pro self -adhered to: ➢ ASTM D226, Type I or 11 felt; Elastobase; Elastobase P or Mule -Hide Nail Base. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ ASTM D226, Type I or II felt; Elastobase; Elastobase P, Mule -Hide Nail Base or Polyglass G2 Base. Polyflex G or Polyflex G FR torch -applied to: ➢ Elastobase; Elastobase P, Mule -Hide Nail Base, Polyglass G2 Base or Polyglass APP Base. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For installations under foam -on tile systems, base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein, or as tested in accordance with FBC Section 1504.3.1. NEMO ETC, U.C. Evaluation Report P32060.02.09-R24 certilZm ofAvthnriiation#32455 eEDmON(2017)FBC NON-HVH2 EVALUATION FL5259-R26 Polyglass Roof Underlayments; (954) 233-1230 RevlSlon 24: 01/24/2018 pages of 14 _, ONEMOletc. 5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12) does not address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not addressed in FRSA/TRI April 2012 (04-12) and are used in foam -on tile applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04- 12), Appendix A, Table 1A or FBC 2609 for determination of design wind loads. #1 Maximum Design Pressure=-90 psf: Deck: Min.15/32-inch plywood to meet project requirementsto satisfaction of Authority Having Jurisdiction. Primer: None Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment- Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #2 Maximum Design Pressure = -97.5 DO.. Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Poo" SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x IA" ring shank nails through 32 ga.,1-5/8" diametertin caps spaced 12-inch o.c. #3 Maximum Design Pressure = -205 psf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: WB-3000 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x W ring shank nails through 32 ga.,1-5/8" diameter tin caps spaced 12-inch o.c. #4 Maximum Design Pressure=-235 psf: Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: (Optional) PG100 or ASTM D41 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Joints: Min. flinch wide strips of Elastoflex SA-V over all plywood joints Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Poo" Polynex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #5 Maximum Design Pressure = -315 osf: Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Tile Pro, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. ' #6 Maximum Design Pressure=-622.5psf: Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #7 Maximum Design Pressure=-30.0psf•: Deck: Min.15/32-inch OSB to meet project requirements to satisfaction of Authority Having lurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 1.254nch longx 1-inch head diameter round metal cap nails Spacing: 64nch o.c. at the 34nch wide side laps and 64nch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP Fit, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. NEMO ETC, U.C. Evaluation Report P12060.02.09-R24 cerL57our cfAuthor Van 032455 6'"EDITION (2017)FSC NON-HVHZ EVALUATION FLS2594128 Polyglass Roof Underlayments7 (954) 233-1230 Revision 24: 01/24/2018 Page 7 of 14 ONEMOletc. #8 Maximum Design Pressure=-37.5 psf': Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga, x 1.25-inch long x 1-inch head diameter round metal cap nails Spacing: 6-inch o.c at the 3-inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #9 Maximum Design Pressure =-37.5 psf*: Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: One (1) or two (2) layers ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-inch longx 1-inch head diameter round metal cap nails Spacing: 6-inch o.c. at the 3-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt #10 Maximum Design Pressure=-45 psf*: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: One (1) layer ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-4nch x 3/8-Inch head diameter annular ring shank roofing nails at 1-5/8-inch diametertin caps Spacing: flinch o.c. at the 2-Inch wide side laps and flinch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional; for use with self -adhering underlayment only) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA -APT Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU, applied in full mopping of hot asphalt. #11 Maximum Design Pressure =-45 psf*: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Two (2) layers ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-inch long 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 9-inch o.c. at the 2-inch wide side laps and 9-inch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional; for use with self -adhering underlayment only) Palystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, PolystickTU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU or Elastoflex S5 G, applied in full mopping of hot asphalt #12 Maximum Design Pressure=-45_Did: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied rap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 9-inch o.c. at the 2-Inch wide side laps and 18-Inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #13 Maximum Design Pressure=-52.5 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 9-Inch o.c. at the 2-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #14 Maximum Design Pressure =-52.5 psf: Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: Simplex Original Cap Nails Spacing: 64nch o.c. at the 3-inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows. Base Ply: (Optional) Polystick NITS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, PolystickTU Plus, Polystick TU Max, Polyflex SAP, Polynex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule-HideSA-APP Cap Sheet (FR), self -adhered. NEMO ETC, LLC. Evaluation Report P32060.02.09-R24 GertiftmWGfAUfhai*vaon C32455 6'a EDITION (Z017)FBC NON-HVHZEVALUATION FL5259-RZB Polyglass Roof Underlayments; (954) 233-1Z30 Revision 24: 01/24/2018 Page 8 of 14 r� _t ONEMOletc. #15 Maximum Design Pressure = -52.5 psf: Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex Original Cap Nails Spacing: 6-inch me at the 3-inch wide side laps and &-inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #16 Maximum Design Pressure =-60 osf: Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hotasphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: 11 ga, x 1.25-inch long 3/8-inch head diameter annular ring shank roofing nails at 1-5/84rich diameter tin caps Spacing: 8-inch o.c. at the flinch wide side laps and B-inch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex GTU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G. torch -applied. #17 Maximum Design Pressure = -60 0 Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied up) Fasteners: OMG #12 Standard Roofgrip with OMG Flat Bottom Metal Plates Spacing: 12-inch a.c. at the flinch wide side laps and 12-inch O.C. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastaflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #18 Maximum Design Pressure =-67.5Osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having.lurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underloyment) Fasteners: 12 ga. x L25-inch long 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Sparing: 8-inch o.c. at the 4-inch wide side laps and 8-Inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastaflex S6 G, applied In full mapping of hot asphalt or torch -applied or Polyflex G, torch - applied. #19 Maximum Design Pressure=-75 psf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority HavingJurisdictlon. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment) Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG 3" Galvalume Steel Plates, OMG Roofgrip #14 with OMG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-inch insulation Plates or Simplex MAXX Cap Fasteners Spacing: 16inch o.c. at the 4-Inch wide side laps and 10-inch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #20 Maximum Design Pressure=-90 psh Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-inch o.c at the 2-inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #21 Maximum Design Pressure =-90psf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal Plates Spacing: 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or POlyfex G. torch -applied. #22 Maximum Design Pressure = -90 0 Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface) Fasteners: Tmfast #12 DP or Trufast #14 HD with Trufast 3" Metal Insulation Plates Spacing: 6-inch o.c at the 4-Inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt NEMO ETC, LLG Evaluation Report P32060.02.09-R24 ceafimte qFAuthorafion n324ss 0EDMON(20171 FBC NON-HVHZEVALUATION 'FL5259-RZB Polyglass Roof Underlayments; (954) 233-1230 Revision 24:02/2412018 Page 9 of 14 ONEMOletc. #23 Maximum Design Pressure = -90 osf: Deck: Min. 15/32-inch plywood to meet project requirementsto satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass 62 Base or Polyglass APP Base (requires use of torch -applied underlayment) Fasteners: Dekfast #14 with Dekfast Hex plates, CMG #14 HD with OMG 3" Galvalume Steel Plates, OMG Roofgrip #14 with CMG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-inch Insulation Plates or Simplex MAXX Cap Fasteners Spacing: 9-inch o.c. at the 4-inch wide side laps and 9-inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex SG G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #24 Maximum Design Pressure=-97.Sosf: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: it ga. x 1.25-inch x 3/8-Inch head diameter annular ring shank rooting nails at 1-5/8-inch diametertin caps Spacing: IlAnch o.c. at the 4-inch wide side laps and 4-inch o.c, at four (4) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #25 Maximum Design Pressure=-105 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-inch o.c. at the 24nch wide side laps and 6-inch o.c, at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #26 Maximum Design Pressure=-112.5 psf. Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 1.25-inch x 3/8-inch head diameter annular ring shank roafing nails at 1-5/8-inch diameter tin caps Spacing: 6-inch o.c at the 4-Inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows. Primer: PG300 or ASTM. D41 primer at all tin -caps Base Ply: Polystick MTS or Polystick MTS PLUS, self -adhered Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, PolyflexSAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #27 Maximum Design Pressure=-220 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torchapplied cap or poly -film surface for torch -applied cap) Fasteners: CMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3" Round Meal Plates or OMG Flat Bottom Metal Plates Spacing: 6-inch o.c. at the flinch wide side laps and 6-inch o.c. at five (5) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #28 Maximum Design Pressure=-120 Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface) Fasteners: Trufast #12 DP or Trufast #14 HD with Trufast 3" Metal Insulation Plates Spacing: 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at five (5) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt. 5.6.4.1 All other direct -deck, adhered Polyglass underlayment systems beneath foam -on tile systems carry a Maximum Design Pressure of -LS psf. NEMO ETC, LLc Ewluation Report P32060.02.09-1124 Cernficore ofAunmrhmnon 932455 6EDITION(2017) FBC NON-HVHZ EVALUATION FL5259-RZB Polyglass Roof Underlayments; (954) 233-2230 Revision 24: 01/24/2029 Page 10 of 14 ONEN10jetc. 5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A. Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WDl, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. 5.7 Exposure Limitations: Elastobase, Elastobase P, Polyglass G2 Base or Polyglass APP Base shall not be left exposed for longer than 30-days after installation. Polystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 90-days after installation. Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Dual Pro, Tile Pro or Elastoflex G TU shall not be leftexposed for longer than 180-days after installation. Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure limitation, unless the prepared roof covering is to be adhesive -set tile, in which case the maximum exposure is 30 days. Elastoflex S6 G or Elastoflex S6 G FR or Polyflex G or Polyflex G FR does not have an exposure limitation, unless the prepared roof covering is to be adhesive -set the (Elastoflex 56 G or Polyflex G only), in which case the maximum exposure is 180 days. 5.8 Polystick MU-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226 roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as set forth in Section 4.3, Note 1 of ASTM D1970-15, should be established as to slip resistance. 5.9 Tile Slippage Limitations (FRSA/TRI April 2012 (04-121): When loading roof tiles on the underlayment In direct -deck tile assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. LtT)tE'SUGEf,IYlIT1,TIOCVAWR4DI�IFiCFDC#.T1isfiNSfAYN,` underlayment Tile Profile Staging Method Maximum Slope Elastoflex G TU Flat lbtile stack 7:12 Lugged 8-tile stack (6 over 2) 6:12 Elastoflex S6 G or S6 G FR Flat or Lugged 6-tile stack (4 over 2) 4:12 Polystick MTS or MTS PLUS Flat 6-tile stack (4 over 2) 5:22 Lugged 6-tile stack (4 over 2) 4:12 Polystick Tile Pro Flat or Lugged 6-tile stack (4 over 2) 7:12 Polystick TU Max Flat &tile stack (4 over 2) or SO -tile stack 7:12 Lugged 6-tile stack (4'over 2) 7:12 Lugged ID -tile stack 6:12 Polystick TU P Flat 6-tile stack (4 over 2) 6:12 Lugged &tile stack (4 over 2) 4:12 Polystick TU Plus Flat or Lugged 6-tile stack (4 over 2) 7:12 Flat or Lugged 10-tile stack 6:12 Polyflex G or G FR Flat or Lugged 6-tile stack (4 over 2) 4:12 Polyflex SA P or SA P FR Flat or Lugged 6-tile stack (4 over 2) 4:12 MEMO ETC, Luc. Evaluation Report P12060.02.09-R24 Cerilficcte afAuthar&anan 032455 6'"EDITION (2017)FBC NON-HVHZ EVALUATION Ft5259-RZB Polyglass Roof Underlayments; (954) 233-2230 Rmislon 24:01/24/2018 Page 11 of 14 ONEMOletc. 6. INSTALLATION: 6.1 Polyglass Roof Undedayments shall be installed in accordance with Polyglass published installation requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application, and prime the substrate (if applicable). 6.3.2 Non -Tile Applications: Shall be installed in compliance with the codifiedrequirements for ASTM D226, Type II underlayment in FBC Table 1507.1.1 for the type of prepared roof covering to be installed. Elastobase, Elastobase P or Mule -Hide Nail Base may be covered with a layer of Polystick, PolyHex SAP, Polyflex SA P FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR), self -adhered, Elastoflex G TU, Elastoflex 56 G or Elastoflex S6 G FR in hot asphalt or Polyfiex G or Polyfiex G FR, torch applied. Roof cover limitations are those are those associated with the top -layer underlayment, as set forth in Table 1. 6.3.2 Tile Applications: Elastobase, Elastobase Por Mule -Hide Nail Base are limited to use as a mechanically attached base sheet in the 'Two Ply System" from FRSA/TRI April 2022 (04-12). Reference is made to Table 1 and Section 5.6.4 herein, coupled with FRSA/TRI April 2012 (04-12) Installation Manual. �b'.4 �,°'��,.�Ro(yTsttN�Sg`'P4f75,'�IR�,Xe,,�TyFPt„T,�,-l-fus, T.U*AI�?x,�pal�Frod�'fl�(eFf!�q(oF7VlU X,otrpolyB'e�x�Pfiolyftex•SAP ER,s. ,,.�.'a)171uI,e;,tlfdR�APP{„CaP.sS(40,,,eT��[�lllbde-Wd-B7�SR-)►;Pi?�alY�ShleGt(f,�Tt�"t-.±�r.s--.��a�.r ,_�_.�T`i.��+`r�',..,. ".. 6A.1 w Shall be installed in comDliance with the codified requirements for ASTM D1970 (except Polystick TU P) underlayment 6.4.2 In FBC Table 1507.1.2 for the type of prepared roof covering to be installed. Direct -to -Deck with Mechanically Fastened Roof Covers: All self -adhering materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP FR and Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) should be back -nailed in selvage edge seam in accordance with Polyglass / Mule - Hide back nailing guidelines. Nails shall be corrosion resistant, it gauge ring -shank type with a minimum 1-inch diameter metal disk or Simplex -type metal cap nail, at a minimum rate of 12" o.c. Polystick TU Plus should be back - nailed using the above noted fasteners and spacing, in area marked "nail area, area pare clever" an the face of membrane. The head lap membrane is to cover the area being back -nailed. All seal -lap seams (selvage laps) must be firmly rolled with a minimum 28 lb. hand - roller to ensure full contact and adhesion. For Dual Pro and Tile Pro, align the edge of the top sheet to the end of the glue pattern (the sheet will overlap the fabric). wew of Ovelap Seam of peal Pro and Tile Pro All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PGS00 Modified Cement applied in between the application of the lap. Polystick TU Plus, Dual Pro and Tile Pro may not be used in any exposed application such as crickets, exposed valleys, or exposed roof to wall details NEMO ETC, U.C. Evaluation Report P32060.02.09-R24 G" lmke ofRuftrwtiw#M455 ISM EDITION 12017) FBC NON-HVHZ EVALUATION FL5259-R2a Polyglaw Roof Underlayments; 1954) Z33-1230 Revision 24: 01/24/2018 Page 12 of 14 ONEMICIlletc. Repair of Polystick membranes is to be accomplished by applying Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass P000 Modified Cement to the area in need of repair, followed by a minimum 6 x 6 inch patch of the Polystick material of like kind, set and hand rolled in place over the repair area. Patch laps, if needed, shall be installed in a water shedding manner. All Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a minimum of 40-lb weighted -roller or, on steep slopes, use of a stiff broom with approximately 40-lbs of load applied forthe field membrane. Hand rollers are acceptable for rolling of patches, laps (min. 28lb roller) or small areas of the roof that are not accessible to a large roller or broom. 6.4.3 TiileApplications (not allowed for Polystick Dual Pro, IR-XeorPolystickMU : Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions noted above as a guideline. For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base Sheet fastening shall be not less than FRSA/TRI April 2012 (04-12), Table 1. For adhesive -set tile applications, refer to Section 5.6.4 herein. 6.4.4 Two (2) Ply Underlavment Systems: Polystick MTS or MTS PLUS followed by Polystick NITS, MTS PLUS, TU P, TU Plus, TU Max, Tile Pro, MU-X or Polyflex SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with the top -layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired. Polystick MTS or MTS PLUS followed by Polystick TU P, TU Plus, TU Max, rile Pro or Polyflex SAP is allowable for use under foam -on tile systems. Limits of use are those associated with the top -layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired. 6.5.1 Elastoflex G TU, Elastaflex S6 G or Elastoflex S6 G FR shall be installed in compliance with current Polyglass published installation requirements. For use in tile applications: ✓ Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 G is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRi April 2022 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the `Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 G FR is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 201Z (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the `Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. 6.5.2 For hot -asphalt -applications, Elastoflex G TU, Elastoflex S6 G or Elastaflex S6 G FR shall be fully asphalt -applied to the substrates noted in Section 5.6. Side laps shall be minimum 34nch and end -laps minimum 6-inch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully adhered in a complete mopping of hot asphalt with asphalt extending approximately 3/8-Inch beyond the, lap edge. 6.6.1 Polyflex G or Polyflex G FR shall be installed in compliance with current Polyglass published installation requirements. For use in tile applications: ✓ Polyflex G is for use as an alternate to the Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered file roof systems (Base Sheet Limited per 5.6.3). ✓ Polyflex G FR is for use as an alternate to the Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2022 (04-12) beneath mechanically fastened tile roof systems (Base Sheet Limited per 5-6.3). NENIO ETC, LLC. Evaluation Report P12080.02.09-R24 &Arlo ofAuthnrhoU #32455 eED17ION(2017)FBC NON-HVH2 EVALUATION FL5259-R78 Polyglass Roof Undedayments; (954) 233-1230 Revision 24:01/24/2018 Page 23 of 14 ONEMOjetc. 6.6.2 Polyflex G or Polyflex G FR shall be fully torch -applied to the substrates noted in Section 5.6. Side laps shall be minimum 3-inch and end -laps minimum 6-inch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully heat -welded and inspected to ensure minimum 3/8-inch flow of modified compound beyond the lap edge. 6.7 Tile Sta¢ine: 6.7.1 Tile shall be loaded and staged in a manner that prevents the slippage and/or damage to the underlayment. Refer to Table 2 herein, and Polyglass published requirements for tile staging. 6.7.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TRI April 2012 (04-12) must be used on all roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of battens or sail- boards, to prevent tile sliding and/or damage to the underlayment during the loading process. 6.7.3 Polyglass specifies the minimum cure time after installation of self -adhering membranes and before loading of roofing tiles is forty-eight (48) hours. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. 8. MANUFACTURING PLANTS: Contact the noted CIA agency for information on product locations covered for F.A.C. 61G20-3 CIA requirements. The following plants have qualified products under their respective physical properties specifications. Fernley, NV, Hazleton, PA & Winter Haven, FL ASTM D1970 Polystick MU-X Hazleton, PA M-D 13-0004 Elastoflex G TU Hazleton, PA & Winter Haven, FL ASTM D1970 Polystick IR-Xe ASTM 01970 & FRSA/TRI April 2012 Polystick TU Plus ASTM D1970 & FRSA/TRI April 2012 Polystick TU Max Tuscaloosa, AL - ASTM D4601, Type II Polyglass 62 Base Winter Haven, FL ASTM D226 (physicals) Elastobase, Elastobase P ASTM D6509 Polyglass APP Base FRSA/TRI April 2012 Polystick MTS, Polystick MTS PLUS FRSA/TRI April 2012 Polystick TU P FRSA/TRI April 2012 Polyflex SAP, Polyflex SAP FR ASTM D1970 - Polystick Dual Pro ASTM D1970 & FRSA/TRI April 2012 Polystick Tile Pro ASTM D6164 Elastoflex S6, Elastoflex S6 G FR ASTM D6222 Polyflex G, Polyflex G FR 9. QUALIFY AssuRANcE ENTITY: UL, LLC—QUA9625; (314) 578-3406; k.chancellor@us.ul.com -END OF EVALUATION REPORT - NEMO ETC, U.C. Evaluation Report P12060.02.09-R24 certrfl' re ofAuthorlmtlon 932455 61e EDIRON f2017)FBC NON-HVHZ EVALUATION FL5259-R28 Polyglaw Roof Underlayments; (954) 233-1230 Revislon 24:01/2412018 Page 14 of 14