HomeMy WebLinkAboutEVALUATION REPORTSCANNED MEMO I etc. BY Certificate ofAufhorrration 832455 St. LUCID county 353 Christian Street, unit #13 Oxford, CT 06478 (203)262-9245 ENGINEER EVALUATE TEST CONSULT CERTIFY EVALUATION REPORT Polyglass USA, Inc. Evaluation Report P12060.02.09-R24 1111 West Newport Center Drive FL5259-1128 Deerfield Beach, FL 33442 Date of Issuance: 02/24/2009 (954) 233-1230 Revision 24: 01/24/2018 SCOPE: This Evaluation Report is issued under Rule 61G203 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the & Edition (2017) Florida Building Code sections noted herein. DESCRIPnON: Polyglass Roof Underlayments LAeEuNG: labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nleminen, P.E. of any changes to the product(s), the Quality Assurance or the production facility lodation(s). NEMOIetc. requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADvEignsEMENr: The Evaluation Report number preceded by the words "NEMO)etc. Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then It shall be done In its entirety. ' INsPEatoN: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for Inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 14. Prepared by: Ay�,mqa,a gF°3 1..:rZory = Robert J.M.Nieminen,P.E ; .,°a': ;�'.T` The facsimile seal appearingwes authorized by Robert Nieminen, Florida Registration No. 59166, Florida DCA ANE190 ya °-A^'g�4ygs P.E. an 01124/201E. This does not serve as an electronically 5={b atis"e. signed dowmeft CERnnrATION OF INDEPENDENCE: 1. NEMDIetc. does not have, nor does it Intend to acquire or will it acquire, a financial interest In any company manufacturing or distributing products it evaluates. 2. NEMOIair— is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nleminen, P.E. does not have nor will acquire, a financial Interest in any company manufacturing or distributing products for which the evaluation reports are being Issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest In any other entity involved in the approval process of the product. S. This Is a building code evaluation. Neither NEMOI etc. nor Robert Nieminen, P.E. are, in anyway, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used fur permitting or design guidance unless retained specifically for that purpose ROOFING COMPONENT EVALUATmN,. 1. SCOPE: Product Category: Roofing Sub -Category: Undedayment Compliance Statement: Roof Underlayments, as produced by Polyglass USA, Inc., have demonstrated compliance with the following sections of the 6th Edition (2017) Florida Building Code through testing In accordance with the following Standards. Compliance Is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. SrANDAROS: Section Prop env Standard year 1504.3.1 Wind Uplift FM 4474 2011 1504.3.1 Wind Uplift U11897 2012 1507.2.3 / 1507.L7 Physical Properties ASTM D226 2009 1507.2.4 / 1507.L1, 1507.2.9.2 Physical Properties ASTM D1970 2015 1507.3.3 Physical Properties FRSAIM April 2012 2012 1507AL2 Physical Properties ASfM D6164 2011 1507.1L2 Physical Properties ASTM D6222 2011 TAS 110 Accelerated Weathering ASTM D4798 2021 3. REFERENCES: Entity Examination Reference Date FM Approvals (TST 1867) Wind Uplift 3004091 01/22/20DD PRI (TSr5978) Physical Properties PRI01111 04/08/20M PRI M75878) Physical Properties PUSA-005-02-01 02/31/2002 .PRI CM 5878) Physical Properties PUSH-013-02-01 12/23/2002 PRI (TSTSIDE) Physical Properties PUSA-013-02-02 12/23/2002 PRI CM 5878) Physical Properties PUSA-013-02-03 12/23/2002 PRI (TST587S) Physical Properties PUSA-018-02-01 07/14/2003 PRI (TST587S) Physical Properties PUSA-028-02-01 07/13/2005 PRI (TST5878) Physical Properties PUSA-033-02-01 01/12/2006 PRI(7ST5878) Physical Properties PUSA-035-02-01 09/29/2005 PRI MT 5878) Physical Properties PUSA-USS42-02 12/10/2007 PRI UST 5878) Physical Properties PUSM061-02-02 01/28/200H PRI (TST 5878) Physical Properties PUSA-076-02-01 02/22/2008 PRI MS878) Physical Properties PUSA-083-02-01 04/14/2008 " PRI(TST5878) Physical Properties PUSA1088-02-01 07/29/2009 MTI (TST 2508) Physical Properties 1X201-17A 04/01/2008 MTI (757 2508) Physical Properties RX14EBA 01/29/2009 ERB OW 6049) Physical Properties 11752.09.99-1 02/08/2000 ERB (TST 6049) Wind Uplift 11757.08.01-1 08/13/2001 ERB (TST 6049) Wind Uplift 22776.05.02 01/16/2003 ERB (T5j 6D49) Physical Properties 02200.07.03 07/14/2003 ERB (TST 6049) Wind Uplift P1740.0L07 01/04/2007 ERB (TST 6049) Physical Properties P5110.04.07-1 04/12/2007 ERB (TST 6049) Wind Uplift P9260.03.08 03/21/2008 ERD=6049) Physical Properties .P13450.08.09 08/13/2009 ERB MT 6049) Wind Uplift P30540.11.09-R1 11/30/2009 ERB M6049) Physical Properties P11030.11.09.1 11/30/2009 ERB(M 6049) Wind Uplift P71030.11.09-2 11/36/2009 ERB (TST6049) Physical Properties P11030.11.09-3 11/30/2009 ERB (TST 6049) Physical Properties P33360.06.10 06/25/2010 ERD(M76049) Physical Properties P33370.03.11 03/02/2021 ERB (TST 6049) Physical Properties P33370.04.11 04/26/2011 ERB UST 6049) Physical Properties P37300.10.31 10/19/2011 Evaluation Report P32060.02A9-1124 NEMO Err- LIL o,rWM QfAYM"affWnx32Q55. a-EMTION(2o17) FBC NO&HVHZEVALUATION FL5259M Revision 24:01/24/2018 Poiyglass Roof Underlayments: (954) 233-t230 Page 2 of 14 4. Entity ERD (TST 6D49) ERD (M 6049) ERD (TSr W49) ERD (TST 6049) ERD (TSr 6049) ERD (TST 6049) ERD (Wfi%9) ERD OW 6049) ERD (m6049) ERD (TST 6049) ERD (TST 6D49) ERD (TST 6049) ERD (W 6649) ERD (TST 6049) ERD (TST 6D49) ERD (M 6049) ERD (TST 5049) ERD (TST 6049) ERD OW 6049) ERD (TST GD49) ERD (TS76049) ERD (TST 6049) ERD MT 6049) ERD (TST6049) ERD (TSr6049) ERD (TST6049) ERD (TS76049) ERD tW 6049) ERD CYST 6049) ICC,ES (EVL 2396) Miami -Dade (CER 1592) Polyglass USA PolygMss USA Polyglass USA UL, LLC. (QUA9625) PRODUCT DESCRIPDON: Examination . Physical Properties Physical Properties Physical Properties Wind Uplift Physical Properties Wind Uplift Wind Uplift Wind Uplift Wind Uplift Wind Uplift Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties wind Uplift Physical Properties wind Uplift Physical Properties Physical Properties Physical Properties ISCCompliance HVHZ Compliance Manufacturing Affidavit PA Affidavit Materials Affidavit Quality Control Reference P40390.08.12-1 KIN190.08.12-2 C41420.09.12-3 P396=03.13 P45370.04.13 P1738.02.07-R2 11757.04.01-1-R3 P41630.08.13 P117SLOS.03-Ri P217SLIL03-RI P45270.0&3.4 6MO.07.14.1 6020.09.24-2 6020.09.14-3 6020.09.14-4 6020.0914-5 602D.09.14-6 P46520.10.24 P43290.10.14 PLYG-SC7550.03.15 P40390.04AS P44360.10.14-R1 PLYG-SC6080.05.15-1 PLYG-SC8905.0516-1 PLYG-SC808f1.07.16 PLYG-SC12025.10.16 PLYG.SG13040.12.16 PLYG-SM1900.03.17 PLYG-SC12115.08.17 ESR-1697 NOA 14-0717.08 Products Current Mule -Hide Cross L% P0lystic k SA Compound Service Confirmation 4.L1 Elastobase Is a fiberglass reinforced, 58S modified bitumen base sheet 4,L2 Elastobase Pisa polyester -reinforced, SB.S modified bitumen base sheet. 4.1.3 Polyglass G2 Base is a fiberglass -reinforced, asphaltic base sheet 4.L4 Polygbm APP Base is a fiberglass -reinforced, APP modified bitumen base sheet ONEMOletc. Date 08/06/2012 OBIU712032 09/11/2012 03/04/2013 04/26/2013 04/29/2013 04/30/2013 08/06/2013 11/26/2013 W26/2013 05/12/2014 C9/08/2014 09/OS/2024 09/08/2014 09/08/2024 09/08/2024 09/08/2014 10/03/2014 10/17/2014 03/24/2015 04/03/2015 OSA8/20ss 05/20/2015 05/17/2016 07/16/2015 10/12/2016 12/27/2016 03/20/2017 09/09/2017 11/02/2014 01/22/20Ls 02/18/2009 03/01/2008 08/18/2012 Exp.10/05/2018 4.2.1 Polystiek MTS or Polystlek MTS PLUS is a nominal 60-mll thick rubberized asphalt waterproohng memorane, glass fiber reinforced, surfaced with polyolefinie film surface; meets FRSA/TRI April 2022. 422 Polysdck IR Xe is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with an aggregate surface; meets ASTM D1970. 42.3 Polystick TU Pius Is a nominal 80•mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. NWO ETr.LLC. Evaluation Report P12060.02D9-1124 QUWx2WOAurlmrRokbnd324W 6'a EDMON(2017) FRC NON-UVRL EVAWATION FL5259-M Potygtass Roof UndedaymeMs; 19%] 233-1230 Revision 24: M/24/2018 Page 3 of 14 ONEMOJetc. 42.4 Polystick TU P Is a nominal 130-mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester reinforced, with a granular surface; meets FRSA/TRI April 2012. 4.2.S Polystkk TU Max Is a nominal 60-mil thick rubberized asphalt waterproofing membrane with a 190 g/m= polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. 4,2.6 Potyflex SAP,. Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR) are polyester. reinforced, APP modified bitumen cap sheets; meet FRSA/TRI April 2012. 4.23 Polystkk Dual Pro`• is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyesterfabricsurrace; meets ASTM D3970. 4.2.8 Polystick Tile ProM is a nominal 60-mill thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyesterfabricsurface; meets ASTM 01970 and FRSA/TRI April 2012. 4.2.9 Polystirh MU-X is a nominal 54-mil thick. dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polypropylene film surface; meets AC188 and physical requirements of ASTM D2970 (See Section 5.8). 4.3.1 Elanciflex 6 TU is a polyester -reinforced, modified bitumen the underlayment composed of a. sand -surfaced SBS modified bitumen back -side and granule -surfaced APP modified bitumen topside. Elastoflex 6 1 U is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the `Single Ply System" from FRSA/rRi April 2012 (04-12) beneath mechanically fastened tile roof systems or Hot Asphalt applied "Cap Sheer in the 'Two Ply System" from FRSA/iRl April 2012 (04-12) beneath mechanically fastened or adhered the roof systems. 4.32 Elastoflex S6 6 and Elastoffex 56 G FR are polyester reinforced, SBS modified bitumen cap sheets; meet ASTM D6164. Elastoflex S6 6 and Elastoflex S6 G FR are for use as an alternate to "Mineral SurfaceeRoll Roofing" (ASrM D6380, Gass M) in the "Single Ply System" from FRSA/Ml April 2012 (04-12) beneath mechanially.fastened tile roof systems. Elastoflex S6 G Is for use as an alternate to Hot Asphalt applied "Cap Sheer in the "Two Ply System" from FRSA/rRI April 2012 (04-12) beneath mechanically fastened or adhered file roof systems. Elastoflex S6 G FR is for use as an alternate to Hot Asphalt applied "Cap Sheet' in the 'Two Ply System" from FRSAITRLApril 2012 (04-12) beneath mechanically fastened tile roof systems. 4.3.3 Polyflex G and Polyflex G FR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM 06222. Polyflex G Is for use as an alternate to Heat Applied "Cap Sheer in the "Two Ply System" from FRSAfM April 2012 (0442) beneath mechanically fastened. or adhered tile roof systems. Polyflex G FR Is for use as an alternate to Heat Applied "Cap Sheer in the "Two Ply System' from FRSA/TRI April 2012 (04-12) beneath mechanically fastened the roof systems. S. LIMITATIONS: 5.1 This is a building code evaluation. Neither NEMOletc nor Robert Nleminen, P.E. are, In any way, the Designer of Record for any project on which.this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in the HVHZ 53 Fire Classification Is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire ratings of this product. 5.4 Polyglass Roof Undedayments may be used with any prepared roof cover where the product is specifically referenced within FBC approval documents. if not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering.. NEMo etr, u.C. Evaluation Report P32060.02A9-R24 cyWoteufAetaonrenenM455 eEDMON 12022) FHC NON•NVHZEVAWATION Revlsion?A: 01/24/2018 Polyglm Roof underieyments; (95e) 233.1210 Page 4 of 14 ONEMO etc. 5.5 Mlowible Roof Covers: �A Undedayment Asphalt Shingles Na"nIlle Foam -On Ylle metal woad Shakes & Shingles slate Elaslabase Yes Yes hasp She lnzplyspumj Yes (BnasheetIn2-olysV0,,m) Yes Yes Yes Elastobase p Yes Yes MmShmjn2-ptV+namj yes (avx5heerin2-plyws ) Yes Yes Yes Polyeass G2 Base No Yes (gam Slx:etln2-pNsysmm) Yes loam shretin2-pNrysmm) NO No No Falyglass AFF) Base No Yes Yes No No No Po[Wck NITS a MTS PWS Yes Yes No Yes Yes Yes PoWckIR-Xe Yes No NO No Yes Yes PolystidcTU P No Yes Yes (See 5.5-11 No No No PoWdcTUPlus Yes Yes Yes (sees-1.1) Yes yes Yes PolystickTUMax No — Yes Yes (See55.1) Yes No No PoIy0dcDualPro Yes No No Yes Yes Yes PoN5ti&THePro Yes Yes Yes (See 53.11 Yes Yes yes PdystickMU-X Yes No No Yes Yes Yes Elastoflex 56 G Y. Yes Yes (See 5.5.1) No Yes Yes _Yes klastallex S5 G FR Yes Yes No No iw-- ElastallEx GTU Yes Yes Yes (see 5.S_1) No Yes Yes PaWexG Yes Yes Yes (See 551) No Yes Yes Pow"GFR Yes Yes No No Yes Yes PcNfIexSAPorSAPFR Yes Yes Yes (See S.S. No —yes Yes Nlule­HIde SA-APP Cap Sheet orSa-APP cap Sheet IFR) Yes Yes Ym (Sea55.1) No Yes Yes S.&J "Foam -On TileP is limited to use of the following Approved tile adhesives / underlayment combinations. 7777��.. Ile PERIAYMENICIm qloiw� Florlda Product Underiallnuents Adhesive Approval DAP Foam Touch 'n Sea[ StannBond Roof FL14506 PolystickTU Plus, PoWckTU Max Tile Adhesive Dow'nlelilondn FL22525 Poiystick Tu P, PclystickTU Plus, Polyffex SAP or Tile Pro polystick TU p, polysfick TU Plus, Polystick TU Max, Polysticknia Pro, ICP Adhesives Polyseto AH-160 FL6332 ElasWflex G TU, Ejastofea S6 6, Polyflex G, Polyflex SAP, POW" SA Cap FR. L Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) Polystidc TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro, po ICP Adhesives Polyset" RTA-I 276 FL6276 Elestoflex G TU, Elastaflex 56 G, PoWm 6, Polyflex SAP, PDJYHEX SA Cap K 1!1 C MZI I=Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) Refer to We Manufacturer's or Adhesive Manufacturer's Florida Product Approval far Overturning Moment Resistance Performance NEMO ETC, LLC. Evaluation Report P12060.0209-R24 FL5259-P2B eEDMON(2G17)FBCNON4WHZEVAWATlON Revision 24:01/24/2018 PoWass Roof UndedayaneaW (954) 233-1230 Page 5 of 14 ONEMOletc. 5.6 Allowable Substrates: 5.6.1 Direct -Bond to Decic Polystick (all variations), Dual Pro, Tile P% Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: D New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing plywood; New or existing, unprlmed OSB; ASTM D41 primed OSB, Southern Yellow Pine; ASTM D42 primed Southern Yellow Pine, ASTM D41 primed structural concrete; Huber Engineered Woods '21P System Panels (designed and installed to meet wind loads for project). Note: Polyglass does not require priming of new or existing plywood or OSB sheathing. New or existing plywood or OSB sheathing should he cleaned of all dirt and dehrk prior to application of Polystick membranes. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: D ASTM D41 primed structural mnati . Polyflex G or Polyflex G FR torch -applied to: D ASTM D41 primed structural concrete. 5.6.2 Band-talnsulation: Polystick (all variations), Polyflex SAP or SAP Fit, Mule -Hide SA-APP tap Sheet or SA-APP Cap Sheet (FR) self -adhered to: D ASTM C12g6, Type 11, Gass 1 polyisccyanurate or Type V polyisocyanurate-composite insulation; Dens Deck DuraGuard; Dens Deck Prime, arSECUROCK Gypsum -Fiber Roof Board. Elastoflex GTU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ Dens Deck Prime or SECUROCK Gypsum -fiber Roof Board. Polyflex G or Polyflex G FR torch -applied to: D ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. For Installation under mechanically attached prepared roof coverings, Insulation shall be attached per minimum requirements of the prepared roof covering manufacturers Product Approval. For installations under foam -on tile systems, Insulation attachment shall be designed by a qualified design professional and Installed based on testing of the insulation/underlayment system in accordance with FBC Section 3.50431. 5.63 Bond to Mechanically Attached Base Laver. Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or Tile Pro self -adhered to: D ASTM D226, Type or II felt; Elastobase; Elastobase P or Mule -Hide Nail Base. Elastoflex G TU, Elastoflex S6 G or Elastoflex SG G FR in hot asphalt to: D ASTM D226, Type I or II felt; Elastabase; Elastobase P, Mule -Hide Nail Base or Polyglass G2 Base. Polyflex G or Polyflex GFR torch -applied to: D Elastobase; Elastobase P, Mule -Hide Nail Base, Polyglass G2 Base or Polyglass APP Base. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For installations under foam -an file systems, base layer shall be attached per minimum requirements ofFRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein, or as tested in accordance with FBC Section 15043.1. NEMO ETC, U.C. Evaluatlon Report P12060.02.04-R24 Certyi4 VfA.thwmtbeMOS a"EDMON(2017)FOCNONi1VRZEVAWAMON F `�-i2`'9'RZB pdvgt 59 Raof Umierlaymears; ism) 233-1230 Rev1s1m 24: W24/201a Page 6 cf 14 ONEMOletc. 5.6.4 Wind Resistance for Underlavment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12) does not address wind uplift resistance of all undedayment systems beneath foam -on tile systems, where the underlayment forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not addressed in FRSA/TRI April 2012 (04-12) and are used in foam -on tile applications. Maximum Design Pressure Is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 15049 has already been applied). Refer to FRSA/iRI April 2012 (04- 12), Appendix A, Table >A or FBC 1609 for determination of design wind loads. #1 Maximum Design Pressure =-90osF. Deck Min.35/324neh plywood to meet project requirements to satisfaction of Authority HavingJurisdicdon. Primer. None Use Ply: (Optional) Polystick MTS or Polystick MTS PLUS, seH-adhered. Underiayment: Polystick TU P, PalystickTU Plus, PolyAck TU Max, Polyflex SAP, Poyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self- adhered. #2 Maximum Design Pressure - -97.5 osf. Deck: MIn 25/324ndi plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Undedaymem: PoWck TU P,Polystick TU Plus, Polystle kTu Max, Polyilex SAP, Polyflex SAP FR, Mule -Hide SA•APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x 136'ring shank nails through 32 ga., 1-SW illametertin caps spaced 12-Inch o.c. #3 Maximum DEsum Pressure =-105 oaf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer WB-3000 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlaymem: Polystick TU P, PoWck TU Plus, Polystiek TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), selfadhered and back -nailed within the selvedge edge side laps using 12 ga. x 2W ring shank nails through 32 ga.,1-5/g' diameter tin caps spaced 12-inch o.c. #4 Maximum Design Pressure --135 Bsf: Deck: Min.15/324nch plywood to meet project requirements to satisfaction of Authority Havinglurisdiction. Primer. lOptlonal) PG100 orASrM D42 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, selfadhered. Joints: Min. 4-Inch wide strips of Elastoflex SA-V over all plywood joints Undedayment: Polystick TU'P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, PoWec.SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP. Cap Sheet (FR), selfadhered. #5 Maximum Design Pressure=-315 tisf•. 'Deck: - Structural concrete to meet pmject requirements to satisfaction of Authority Having Jurisdiction. Primer. PG300 or ASTM D41 Base Ply. (Optional) Polystidk MTS or PoWck MTS PLUS, self -adhered. Underiaymehth Polystick TU P, Polystick TU Plus, Polystick: TU Max, Tile Pro, Polyflex SAP, Polyflex SAP FR,, Mule -Hide SA-APP Cap Sheet and Mule-Hlde SA -ARP Cap Sheet (FR), selfadhered. #6 maxim uinDeslanPressure = -MS pAf: Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction.. Primer. PG100 or ASTM D41 UndedaymenC Elastoflex G TU orElastoflexS6 G, applied in full mapping of hot asphalt or Polyflex G, torch -applied. #7 Maximum Design Pressure =-30Attsf* Deck: Min 15/32-Inch OSB to meet project requirements to satisfaction of Authority Having lurisdiction. Base Sheet: Elastobase or Mule -Hide Nall Base (poly -film top surface) Fasteners: 1t ga. x 1:75-Inch bngx 3-inch head diameter round metal cap nails .Spacing: 64nch o.c at the 3-inch wide side laps and 64ndh o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional) Palyetidk MTS or Polystick MIS PLUS, self -adhered. Underiayment: Polystick TU P, PolysddkTU Plus, Polysttck TU Max, Polyflex SAP, Potyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP. Cap Sheet (FR), self -adhered. NEMO EIS U.C. Evaluation Report P32060.(Z094M @,affmh OfAuthoMatim 0=40 do ERMON (2017) F13C NON-HVHZ EVALUATION FL3299'11211 Porygla8 Roof underiaya mts: (964) Z33-lao Revision 24: M/Z4/Z019 Pagel of 14 ONEMOJetc. #8 Max)murnDesignPressure=-37Sosf': Dedr Min. 3S/324nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet Elastahase or Mule -Hide Nall Base (poly-fllm top surface) Fasteners: 31 Be. x 1.254mh longx ltinch head diameter round metal cap nails Spacing: 6-inch ac at the 3-inch wide side laps and 6-Inch o.c. at two (2) equally spaced staggered center rows Base Ply: (Optional) Potystick MTS or Polystick MTS PLUS, self -adhered. Underayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP rap Sheet and Mule -Hide SA-APP Cap Sheet (FR), selfadhered #9. Maximum Design Pressure = -37.5 W ' Deck: Min.19/324ndh plywood to meet project requirements to satisfaction of Authority HaNingJurisdidlon. Base Sheet: One (1) or Two (2) layers ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-inch long 1-inch head diameter round metal cap nails Spadng: 6-Inch mc. at the }inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows. Undedayment: Elastofiex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt #20 Maximum Design Pressure =-45 psP: Deck: Min.19/324nch plywood to meet project requirements to satisfaction of Authority Havirg.lurisdiction. Base Sheet. One (1) layerASIM D226, Type II felt Fasteners: 11 ge.x 125-Inchx3/8-Inch head diameter annular ring shank roofing nails at 2-5/8-Inch diametertincaps Spacing- 4-inch o.c atthe 2-Inch wide side laps and flinch o.c. at two (2) equally spaced staggered center rows Base Ply: (Optional; for use with self -adhering underlaymem only) Polystick MTS or Potystick MTS PLUS, selfadhered. Underiaymertt: Polysdck TU P, PatystickTU Plus, Polystick TU Max, Polyflex SAP, Potyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastofiex G TU, applied In full mapping of hot asphalt. #21 Maximum Design Pressure =-0S psP: Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.. Base Sheet: Two (2) layers ASiM. D226, Type II felt Fasteners: 11 ga. x 1.254mb long x 3/84nch head diameter annular ring shank roofing nails at 1-5/8-Inch diameter tin caps Spacing. 9-Inch o.c at the 24nch wide side laps and 94nch o.c. at two (2) equally spaced staggered center rows Base W. (Optional; for use with self -adhering underlayment only) Potystick MTS or Polystick MTS PLUS, self -adhered. Underayment: Polystick TU P, Polystick TU Plus, PolystickTU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SJ1-APP Cap Sheet (FR), self -adhered or Elastoflex G TU or Etasmflex 56 G, applied in full mapping of hot asphalt. #22 Maximum Design Pressure =AS psf: Deck: Min.25/32-Inch plywood to meet project requirements to satisfaction of Authority HavingJurisdiction. Base Sheet: Elastohase(sanded top sorfacefor hotasphaltor torch-applled cap or poly -film surface for torch -applied rap) Fasteners: Simplex MA)OC Cap Fasteners Spacing: 9-inch o.o at the 24nch wide side laps and 18-inch o.c. attum (2) equally spaced staggered center rows. Underayment Elastoflex G TU or Elasto8ex S6 G, applied In fullmopping of hot asphalt or Pclyflex G, torch-applled. #13 MaWinumDesign Pressure=-52.5psF. Deck Mim 15/324nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastohase(sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 9-Inchor at the 2-Inch wide side laps and 12-Inch o.e attwo (2) equally spaced staggered center rows. Undedayment• Eiastaflex G TU or Elastoflex 55 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #14 Maximum Design Pressure=-52Spsf: Deck Min.15/324nch plywood to meet project requirements to satisfaction of Authority, Having Jurisdiction. Base Sheet: Elastohase or Mule -Hide Nail Base (poly -film topsurface) Fasteners Simplex Original Cap Nails Spacing: &inchme. atthe 34nch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows Base Ply. (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlaymem: Polystick TU P, Polystick TU Plus,.PolysUdcTU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. , NDMO ETC, LLC. Evaluation Report P12060.02.09-1124 CvtWJW CfAUMonmt= 03245S IPEDITION (M17) FBC NOUt-NVI42EVALUATION FL5259-M Polyglass Roof Undedayments; (951) 233-WO Rmisian 24:01/24/2018 Page 8 of 24 ONEMOletc. #15 Maximum Design Pressure = -525 Dsf: Deck: Min. 115/32-inch plywood to meet project requirements to satisfaction of Authority Having.ludsdiction. Base Sheet: Elastobase lsanded top surface for hotasphalt or torch -applied cep or poly -film surface for torch -applied cap) Fasteners: Simplex CrlginalCap.Nails Spacing: 64neh o.c. at the 3-inch wide side laps and &Inch o c at four (4) equally spaced staggered center rows. Underlayment Elastofiex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #16 Maximum Design Pressure =-60 psi: Deck. Min. 19/32-Intl[ plywood to meet project requirements to sausfactlonofAuthority Havingludsdiction. Base Sheet: Elastolase(sanded top surface for hot -asphalt or torch -applied rap or poly -film surface fortorchapplled cap) Fasteners: 11 ga. x L25-inch long 3/84nch head diameter annular ring shank raoflng nails at 1-5/8-Inch diameter tin caps Spacing. 8-inch o.c at the flinch wide side laps and 8-Inch o.e at three (3) equally spaced staggered Center rows. Underlayment: Elastoflex G TU or Elaswflex 55 G, applied in full mopping of hot asphalt or Polyflex G, torch-applled. #17 Maximum Design Pressure=-60 Dsf: Deck Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet. Elanobase(sanded top surface for hot -asphalt or torch -applied cap or poly -film surface fortorchapplied sup) Fasteners: OMG#12 Standard Roefgdp with OMG Flat Bottom Metal Plates Spacing. 12-Inch a.e at the 4-Inch wide side laps and 12-inch o.c at two (2) equally spaced staggered terrier rows. Underlayment. Elastoflex GTU or Elastallm S6 G, applied in full mopping of hot asphalt or Polyflex 6, torch -applied. #18 Maximum Design Pressure=-67.5Dsf: Deck Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisiiction. Base Sheet: Polyglass G2 Base orPolyglas APP Base (requires use of torch-oppiled underfayment) Fasteners: 12 ga. x 1.2541nch fmgx 3/84nch head diameterannular ring shank roofing nails at 1-5/8-inch diametertin caps Spacing: 8-inch o.c at the flinch wide side laps and B-Inch o c at four (4) equallyspaced staggered center rows. Underiayment Elastofiex G TU or Elestofiex S6 G, applied in full mopping of hot asphalt. or torch -applied or Polyflex G, torch - applied. #19 Maximum Design Pressure =--75 psF. Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Havinglurlsiiction. Base Sheet: Polyglas G2 Base or Polyglass APP Base (requires use oftorcfropplied undarlayment) Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG 3' Galvalume Steel Plates, CMG Rootdp #14 with OMG Flat Bottom Plates (AccuTrec), Tmfast HD with Trufast 3-inch Insulation Plates or Simplex MAXX Cap Fasteners Spacing: ID -Inch e.e at the 4-inch wide side laps and 10-Inch o.c at three (3) equally spaced staggered center rows. Underlayment Elastoflex G TU or Dastoflex S6 G, applied in fug mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #20 MaximumOesienPrpmure=-901) Deck: Min 15/324nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet Elastobase(sanded top surface for hatasphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners Simplex MAi(x Cap Fasteners Spacing: 64nrh o.c at the 2-Inth wide side laps and 64nrh o.c. attwo (2) equally spaced staggered center rows. Underlayment: Elastaflex G TU ar Elastaflex Sfi G, applied in full mopping of hotasphalt or Poly6ex G, torchapplled. #21 Maximum Design Pressure --98 mf: Deck: Min. 35/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet Elastobase(sanded top surface for hotasphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3' Round Metal Plates or OMG Flat Bottom Metal Plates Spacing: 6-inch o.c atthe flinch wide side laps and 6-Inch o.c at three (3) equally spaced staggered center rows. Undedaymem: Elastofirx GTU or Elastaflex S6 G, applied in full mopping of hot asphalt or Powex G, torchapplIed. #22 Maximum Desfen Pressure=-90 Dsf: Deck. Min 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sandedtop surface) Fasteners: Trufast#12 DP orTrufast#14 HO with Truiest 31 Metal Insulation Plates Spacing: 6-Inch o.c at the 4-inch wide side laps and 6-Inch o.e at three (3) equally spaced staggered center rows. Underlayment Elas[ofiex G TU or ElastoRex S5 G, applied In full mopping of hot asphalt NEMO EM LLC Evaluation Report P32060.02.03R24 CEd&amolAWmdmxmrba24s5 6EDmON(21117)FBCNON4P)MEVALUAMON FLS259-R26 Polyglass Roof Underlayments, (954) 213-122o Revision 24:01/2412MB Page 9 of I4 ONEMOJetc. #23 Maximum Design -Pressure = -90 ttsF. Deck: Min. 25/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet Polyglass 62 Base or Polyglass APP Base (requires use ojtorch-applied undadayment) Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG 3' Galvalume Steel Plates, OMG Roofgrip #14 with OMG Flat Bottom Plates (AccuTrdc), Trufast HD with Trufast 34ndt Insulation Plates or Simplex MAXX Cap Fasteners Spacing: 9-Inch o.c. at the 4-inch wide side laps and 94nch ox atfaur (4) equally spaced staggered center rows. Undedayment: Elastoifex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or torch -applied or Polyfiex G, torch - applied. #24 Maximum Design Pressure =-97-5 Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Having.lurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 1.254nch x 3/9-Inch head diameter annular ringshank roofing nails at 1-5/8-Inch dlametertincaps Spacing: 4-Inch ma at the 4-Inch wide side laps and 4-inch o.c. atfour (4) equally spaced staggered center rows. Base Ply: (Optional) Polystick M7S or Polystick MTS PLUS, self -adhered. Undedaymem: PoWck TU P, Polystick TU Plus. Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #25 Maximum Design Pressure=-105 osf: Deck: Min.15/324nch plywood to meet project requirements to satisfaction of Authority Havinglurisdiction. Base Sheet: Elastobase (sanded top surface for hotasphalt or torch-appffed cap or poly -film surface fortordrappiled rap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-Inch c.c. at the 24nrh wide side laps and 6-Inch o.c. at three (3) equally spared staggered center. rows. Undedaymerm Elastoflex G TU or Elastoflex 56.G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #26 Maximum Design Pressure=-112.5osF. Deck: ` Min. 19/32-inch plywood to meet projectrequlrements to wUsfaction aFAtMorityHavinglurisdictfon. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 go.x 1.25-inchx3/8-inch head diameter annular ring shank roofing nails at l-5/84nch diameter tin caps Spacing: 6-Inch o.c. at the 4-inch wide side laps and 6-inch o.t at four (4) equally spaced staggered center rows. Primer. P6300 or ASTM D41 primer at all tin -caps Base Ply: Polystick MTS or PoWck MTS PLUS, setfadhered Underiayment PoWtIckTU P, PolysUck TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #27 Maximum Design Pressure a.120 osf: Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sanded top surface for hot -asphalt ortorchapplied cap or poly -film surface fortorrhapplled cap) Fasteners: OMG #12 Standard Rcofgrip or OMG #14 Heavy Duty with OMG 3' Round Metal Plates or OMG Flat Bottom Metal Plates Spacing: 6-Inch o.c at the 4-Inch wide side laps and 6-0nch o.e. at five (5) equally spared staggered carder rows. Undedaymenr Elastoflex G TU or Elastofiex SG G. applied in full mopping of hat asphalt or Polyflex G, torch -applied. #29 Maximum Design Pressure=-220osG Deck Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface) Fasteners: Trufast#12 DP orTrufast#14 HD with Trufast 3' Metal Insulation Plates Spacing 6-Inch o.c. atthe 44nch wide side laps and 64nch o.e at five (5) equally spaced staggered center rows. Undedayment: Elastoflex6 TU or Elastollex S6 G, applied in fug mopping of hot asphalt 5.6.4.1 All other direct -deck, adhered Polyglass, undedayment systems beneath foam -on tilesystems carry a Maximum Design Pressure of-45 psf.. NERACIMLLM Evaluation Report P12060.02.09-R24 rWjkate olAuroorha0m 9324155 6M EWr10N(2017) Per N014401HEEVAWA110N FU759420 Pafyg%w Roof Underlaymentsi (954) 233-IM Revision 24:01/24/2018 Page 10 of 14 ONEMOletc. 5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed that required under FRSAfTRI April 2022 (04-22), Appendix A, Table SA. Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD3, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 217. Assemblies marked with an asterisk' carry the limitations set forth in Section.2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2015) for Zone 2/3 enhancements. 5.7 Exposure Umitations: Elastobase, Elastobase P, Polyglass G2 Base or Polygiass APP Base shall not be left exposed for longer than 30-days after installation. Polystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 90•days after Installation.. Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Dual Pro, Tile Pro or Elastoflex G TU shall not be left exposed for Ipngerthan 180-days after installation. Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure limitation, unless the prepared roof covering Is to be adhesive -set tile, in which case the maximum exposure is 30 days. Elastoflex: S6 G or Elastoflex S6 G FR or Polyflex G or Polyflex-G FR does not have an, exposure limitation, unless the prepared roof covering Is to be adhesive -set tile (Elastoflex S6 G or Polyflex G only), in which case the maximum exposure is 180 days. 5.8 Polystick MU-X has been found through comparative testing to have a lesser coeffident of friction than ASiM D226 roofing -felt in dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as set forth in Section 4.3,.Note 1 of ASTM D1970-15, should be established as to slip resistance. 5.9 Tile Sliopakre Limitations (FRSAM April 2012 (04-121)- When loading roof tiles on the underlayment In direct -deck tile assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. ' :;;:�2-: TiisiE*,t.':ilreSpvPiw`ieYiMiTATtvuswiGoi�e�i-4kWr.Tii�lN,si,�hnan;.: - - Underlayment Tide Profile Staging Method Maximum Slope tlastaflex,G TU Fiat 10-tile stack Lugged 9-tile stack (6 over 2) &12 EiastoflexS6 G or S6 G FR - Flat or Lugged &tile stack (4 over 2) 4:12 PotystickNlTSorPATSPLUS Flat 6-tllestack(4over2) 5:12 Lugged 6-tile stack (4 over.21 -stack 4:12 PoNstickTile Pro Flat or Lugged btile(4 over 2)' - 7:12 PoWckTU Max Flat 6-tile stack (4 over 2) or ID-tlle stack 7:12 Lugged &tile stack (4 ever 2) 7:22 Lugged 36tiTe stack 6:12. PolyskirkTUP Flat 6-tile stack (4 over 2) 6:12 Lugged 6-tile stack (4 over 2) - 4.12 PolystickTUPlus Flat"Lugged 6-tlle stack(4over2) 712 Rat or Lugged SU-tile stack 6:12 Pol9flex G or G FR - - - Flat of Lugged 6-tile stack (4 over 2) 4:12 - PoWex SAPorSAPFR Flat or Lugged 6-tile stack (4 over 2) 4:22 NEMOEMLLC. Evaluation Report P12060.02.09-R24 outr=w cfAuraor¢oaen E3240 6� EpmON(2017) FBC NONaMMEVALUATION FL5259-M Poly&. RaarUnderhyk00nts, (934) 233-MO Revision 24: 01/24/2028 Page 11 of 14 ONEMOjetc. 6. INSTALLATION: 6.1 Polyglass Roof Umlerlayments shall be installed in accordance with Polyglass published installation,requlrements subject to the Umitations set forth in Section 5 herein and the specifics; noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application, and prime the substrate (if applicable). •:'''.: iL ;lw: ear; :.r: •T. ?,: .,.. .. t'r9: tlastgbase;ElasfdbLet eP'lrMule-(1ideNaifHase'..-- Shall be installed in compliance with the codified requirements for ASTM D226, Type II underlayment in FBC Table 1507.11 for the type of prepared roof covering to be installed. tlastobas% tlastobase P or Mule -Hide Nag Base maybe covered with a layer of Polystick, Polyflex SAP, Polyflex SA P Fit, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR), self -adhered, Elastoflex G TU, Elastoflex S6 G or Elastoflex S5 G FR in hot asphalt or Polyflex G or Polyflax G FR, torch applied. Roof cover limitations are those are those assoclated with the top -layer underlayment, as set forth in Table 1, 6.3.2 Tile Applications: Elastobase, Elastobase P or Mule-i6de Nail Base are limited to use as a mechanically attached base sheet in the 'Two Ply system" from FRSA/TRI April 2022 (04-12). Reference Is made to Table 1 and Section 5.6.4 herein, coupled with FRSA/i'RI April 2012 (04-12) installation Manual. 6.4PolystictlNl#s.NMPits, M* i.3tl:P�TtJP.Ip,TUMaitiqu31 Y9rTtl�e odF,iNW1CorPolyflekSAp,PkCyfIPxSAPFRt` Mule Hides-7►pFiaJrS�ia aFlSiute ftoeSA94hpg1tSfP?et(FRYy 6.4.1 Shall be installed In compliance with the codified requirements for ASTM D1970 (except PolystickTU P) underlayment 6.4.2 In FBC Table 1507.L1 for the type of prepared roof covering to be installed. Direct -to -Deck with Mechanically Fastened Roof Covers: All setf-adhering materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP FR and Mule -Hide SA-APP Cap Sheet orSA-APP Cap Sheet (FR) should be back -nailed in selvage edge seam In accordance with Polyglass /.Mule - Hide back nailing guidelines. Nails shall be corrosion resistant, 11 gauge ring -shank type with a minimum 1-Inch diameter metal disk or Slmplex-type metal cap nail, at a minimum rate of 12' o.c. Polystick TU Pius should be back - nailed using the above noted fasteners and spacing, In area marked "nail area, area para clever" on the face of membrane. The head lap membrane is to cover the area being back -nailed. All seal -lap seams (selvage laps) must be firmly rolled with a minimum 28 lb. hand. roller to ensure full contact and adhesion. For Dual Pro and Tile Pro, align the edge of the top sheet to the end of the glue pattern (the sheet will overlap the fabric). in vrewaf O4elap Sam of Dual Pm and The Pro All over -fabric and over -granule end -laps shall have a 6-Inch wide, uniform layer of Polyplus So Premium Modified Wet/Dry Cement or Polyglass PGSOO Modified Cement applied In between the application of the lap. PolysUdk TU Plus, Dual Pro and Tile Pro may not be used in any exposed application such as wickets, exposed valleys, or exposed roof to wall details NENIO ETC, kLC. Ewluation Repart P32060.o209-R24 Wrtylm�ofAud+orbaaoa P3rlas 6w EDMON(=7) FBC NON4MUIEVALUATION FL5259-R28 Poh'6law Roof Underlayments: (954) 233-1230 Revislon 24: 01/24/2MB Page 12 of 14 ONEMOletc. Repair of Palystick membranes is to be accomplished by applying Palyplus 50 Premium Modified Wet/Dry Cement or Polyglass PGS00 Modified Cement to the area In need of repair, followed by a minimum 6 x 6 inch patch of the Polystick material of like kind, set and hand rolled in place over the repair area. Patch laps, if needed, shall be installed in a water shedding manner. All Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a minimum of 40-lb weighted -roller or, on steep slopes, use of a stiff broom with approximately 404bs of load applied for the field membrane. Hand rollers are acceptable for rolling of patches, laps (min.28lb roller) or small areas of the roof that are not accessible to a large roller or broom. 6.4.3 Tile Applications that allowed forPohatick Dual Pro IR-Xe orPolvstfck MULA Reference is made to FRSA%TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the Instructions noted above as a guideline. For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base Sheet fastening shall be not less than FRSA/TRI April 2012 (04-12), Table 1 For adhesive -set tile applications, refer to Section 5.6.4 herein. 6.4.4 Two (2) Ply Underlayment Systems: PolystIck MIS or MTS PLUS followed by Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Tile Pro, MU-X or Palyflax SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are these associated with the top4ayer material. This Is not a requirement, but is allowable if a 2-ply underiayment system Is desired. Polystick MIS or MTS PLUS followed by Polystick TU P, TU Plus, TU Max, Tile Pro or Polyflex SAP is allowable for use under foam -on tile systems. Limits of use are those associated with the top -layer material. This Is not a requirement, but is allowable If a 2-olv underiavment system is desired. 5.5.1 Elastoflex G TU, Elastoflex S6 G or Elastoflex SG G FR shall be installed In compliance with current Polyglass published installation requirements. For use In the applications: ✓ Elastoflex G Tina for use as an alternate to "Mineral Surface Roil Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRl April 2012 (04-12) beneath mechanically fastened the roof systems or the Hot Asphalt applied "Cap Sheet' in the" Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 G is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Gass M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened file roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered Tile roof systems. ✓ Elastoflex S6 G FR Is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet' in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened the roof systems. 6.5.2 For hot -asphalt -applications, Elastoflex G TU, Elastaflex S6 G or Elastoflex S6 G FR shall be fully asphalt -applied to the substrates noted in Section S.G. Side laps shall be minimum 3-inch and end -laps minimum 6-Inch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully adhered in complete mopping of hot asphalt with asphalt extending approximately 3/8-Inch beyond the lap edge. 6.6.1 Polyflex G or Polyflex G FR shall be installed in compliance with current Polyglass puousnea insteuavan regwremenu. For use in tile applications: ✓ Polyflex G Is for use as an alternate to the Heat Applied "Cap Sheep' In the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems (Base Sheet Limited per 5.6.3). ✓ Polyflex G FR is for use as an alternate to the Heat Applied 'Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-22) beneath mechanically fastened tile roof systems (Base Sheet Limited per 5.6.3). NEMO EFC, ILC EvaluaUon Report P12060.02M-R24 MaUlkraofAorlO&9bn/324W eEomoN 12a17) Fac NON4iVN2 Evammox Fsng-ma Poly&z Roof Underlsyments; (954) 233-1Z30 Revision 24: 01/24/2028 Page 13 of 14 ONEMojetc. 6.6.2 Polyflex G or Polyflex G FR shall be fully torch -applied to the substrates noted in Section 5.6. Side laps shall he minimum 3-inch and end -laps minimum 6-Inch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully heat -welded and inspected to ensure minimum 3/8-inch flow of modified compound beyond the lap edge. 9.1 Tile Staein¢; 6.7.1 Tile shall be loaded and staged Ina manner that prevents the slippage and/or damage to the underlayment Refer to Table 2 herein, and Polyglass published requirements for tile staging. 6.7.2 Battens and/or Counter-batbens, as required by the tile manufacturer and FRSA/TRI April 2012 (04-12) must be used on all roof slopes greater than 7;12. Precautions should be taken as needed, such as the use of battens or sail- boards, to prevent tile sliding and/or damage to the underlayment during the loading process. 6.73 Polyglass specifies the minimum cure time after Installation of self -adhering membranes and before loading of roofing tiles Is forty-eight (48) hours. 7. BUILDING PERMIT REQUIREMEIM'. As required by the Building Official or Authority Having Jurisdiction in orderto properly evaluate the installation of this product 8. .MANUFACTURING PLANTS: Contact the noted QA agency far Information an product locations covered for F.A.C. 61620-3 QA requirements. The following plants have qualified products under their respective physical properties specifications. .P rrt�.", ...:: -,: • . ; :.•..:, .. ...: . •Sler"fi[atioii�.�;�.;;�.t:r.:d _:�_�'i':� Pre u' s •, - - Fernley, NV, Hazleton, PA & winter Haven FL ASTM D3970 Pol ek MU-X Hazleton, PA M-D 13-0004. Elastoflex G TU Hazleton, PA & Winter Haven, FL ASTM D1970 Polystick IR-Xe ASrM D1970 & FRSA/rRI April 2012 Polystick TU Plus ASTM D1970 & FRSA/rRI April 2012 Polystick TU Max Tuscaloosa, AL ASTM D46M, Type II Polyglass G2 Base Winter Hawn, FL ASTM D226 (physicals) Elastobase, Elastobase P ASTM D6509 Polvalass APP Base FRSA/TRI April 2012 -PoI ek MTS, Polystick MTS PLUS FRSA/TRI April 2012 Poi sdckTUP F I April 2012 Polyflex SAP, Polyflex SA P FR ASrM D1970 Polystick Dual Pro ASTM D1970 & FRSA/TRI April 2022 Polystick Tile Pro ASTM D6164 Elastoflex S6, Elastoflex S6 G FR ASTM D6222 PoWex G, PolyflexG FR 9. QUALITY ASSURANCE ENTRY: UL, LLC—QUA9M; (314)578-3406;k.chancellar@us.ul.com - END OF EVALUATION REPORT - NEMO ETC, LLC. Evaluation Report P12060.02-09-R24 outfl[ufenJAudiw,baban 024S5 6ieEDMON(2017) FBC NON•N1INZEVAWATION n5759-R78 Pofy = Roof Undedayinatas; (954) 233-1230 Revision 24:02/2412018 Page 14 of 14