Out office has calculated the required design pressures in accordance with ASCE 7-10
and Florida Building Code 2017 for the installation of accordion shutters at the above
referenced address.
Wind speed: V„ I,: 165 mph, Vaw: 128 mph
Exposure: D S'CQ
Enclosure Type: Enclosed
Shutter Size: 96" Maximum Height Sf`4C/eC NCO
Shutter Location: Covered Porch (See Attached Sketch) 0%
Required Design Pressure: +51.3 / -68.7 PSF
Shutters to be installed shall be equal to, or exceed the required design pressures as listed
above "Required Design Pressure".
Accordion Shutters shall be installed in accordance with the shutter manufacturer's
installation instructions and Florida Product Approval and Florida Building Code 2017.
- Accordion Shutters shallbe FL# 389.1. IW7 -oy15
ST. LUCIE COON
Thank you for your attention to this matter. BUILDING Divlsl
CONCFALO FASTENERS OR ATTACHMENTS REViE D
Submitted by: FOR � �
ARETHERESPONSIBUNOFTHE DAB �`-
PAUL WELCH INC. DATE I
CONTRACTOR OF RECORD PLA S o P RMIT
MUST BE KEPT JOL4. OR
No INSPECTION Vl� LL BE ;,L.^ n.
THES[ PLANS A,`•JD ALL PP,OP ,r
ARE SUBJECT TO OSED 4N Oj
Paul Welch, P.E. c"QU'RED BY FIELD INSPECTORS ITt
y T
Reg. No 29945 CONTRACTOR CORD` MAY BE 1dECESSAt;Y IN OROEg TO
CCif ALY 6�IITH ALL APPLICABLE CODE,^,
ti,
�qba -oq--i5
PAUL WELCH INC.
Mechanical * Electrical * Civil Engineering
1984 S.W. Biltmore St. Suite#114
Port Saint Lucie, FL 34984
Phone (772) 785 - 9888
Email pwelchinc@aol.com
February 19, 2019
Re: DiDomenico Shutter Installation
9550 S. Ocean Dr. (#1207) SCANNED
Jensen Beach, FL 34957 BY
To Whom It May Concern: St. Lucie County
R�c1wFO
FF� 2
PeN 10,8
tti
St. Cye pe a ent
Our office has calculated the required design pressures in accordance with ASCE 7-10
and Florida Building Code 2017 for the installation of accordion shutters at the above
referenced address.
Wind speed: Vdt: 165 mph, Vim: 128 mph
Exposure: D
Enclosure Type: Enclosed
Shutter Size: 96" Maximum Height
Shutter Location: Covered Porch (See Attached Sketch)
Required Design. Pressure: +51.3 / -68.7 PSF
Shutters to be installed shall be equal to, or exceed the required design pressures as listed
above "Required Design Pressure".
Accordion Shutters shall be installed in accordance with the shutter manufacturer's
installation instructions and Florida Product Approval and Florida Building Code 2017.
Accordion Shutters shall be FL# 389.1.
Thank you for your attention to this matter.
Submitted by:
PAUL LCH INC.
Paul W ch, P.E.
Reg. No 29945
CONCEALED FASTENERS OR ATTACHMENTS
ARE THE RESPONSIBILrrY OF THE
CONTRACTOR OF RECORD
lcfaz -af
ST. LUCiE
BUILDING I
t: m
MUST BE KEPT 4 J013 OR
No INMPECTIOP; :t'! . ME MASH
THESE PLANS AND ALL PROPOSCO VdORIf
ARE SUBJECT TO ANY CORRECiICN3
R=OUIRED EY FIELD INSPECTORS MAT
MAY BE NECESSARY IN ORDER TO
CO&FI Y WITFI ALL APPLICABLE CODES.