HomeMy WebLinkAboutMANUAL S COMPLIANCE REPORTManual S Compliance Report Job: Lot 28 Tarpon Flats Mod...
1- wrightsoW p p Date: 01.18.14
Entire House sy: - ER
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax 407-333.3853 Web: W AMDEL-AIR.COM
For: Phoenix Realty Homes Inc, Lot 28 Tarpon Flats Model A GRW
3922 Duneside Drive, Fort Pierce, FL
Cooling Equipment
Design Conditions
design DB:
90.5°F
Sensible gain:
34952
Btuh
Outdoor design WB:
77.7°F
Latent gain:
5346
Btuh
Indoor design DB:
75.0°F
Total gain:
40299
Btuh
Indoor RH:
50%
Estimated airflow:
1583
cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: SpIitASHP
Manufacturer:
Carrier
Model: 25HBC548A**30+FX4DN(B,F)049L
Actual airflow:
1583
cfm
Sensible capacity:
36705
Btuh
105% of load
Latent capacity:
9045
Btuh.
169% of load
Total capacity:
45750
Btuh
114% of load SHR: 80%
Heating Equipment
Design Conditions
Outdoor, design DB: 43.1OF Heat loss: 31193 Btuh
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: SpIitASHP
Manufacturer: Carrier
Model: 25HBC548A**30+FX4DN(B,F)049L
Actual airflow: 1583
cfm
Output capacity: 47500
Btuh
152% of load
Supplemental heat required:
0 Btuh
Backup equipment type:
Elec strip
Manufacturer:
Model:
Actual airflow: 1583
cfm
Output capacity: 0
kW
0% of load Temp. rise: 0 OF
The above equipment was selected in accordance with ACCA Manual S.
ti. +Wrlghts0ft Right-Suite®Univemal201515.0.1BRSU08057
ACC%...t28TarponFlatsAGRILot28TarponFlatsModeIAGRWmp Calc=MJ8 Housefaces: W
Entering coil DB: 75.2°F
Entering coil WB: 63.1°F
Entering coil DB: 69.8°F
Capacity balance: 34 OF
Economic balance: -99 OF
2WS-Dec-18 15:04:59
Page 1
Component Constructions Job: Lot 28 Tarpon Flats Mod
-f}�- ...
wrightsoft' p Date: 01.18.14
Entire House By: ER
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Farc 407-3333853 Web: W W W.DEL-AIR.COM
eLroject intormation
For: Phoenix Realty Homes Inc, Lot 28 Tarpon Flats Model A GRW
3922'Duneside Drive, Fort Pierce, FL
Location:
Vero Beach Municipal AP, FL, US
Elevation: 30 ft
Latitude: 28"N
Outdoor: Heating
Dry bulb ("F) 43
Daily range ('F)
Wet bulb (°F) -
Wind speed (mph) 15.0
Indoor temperature (°F)
Design TD ("F)
Relative humidity (%)
CoolingMoisture
difference (gr1lb)
91
Infiltration:
16 (L )
Method
78
Construction quality
7.5
Fireplaces
Heating Cooling
70
75
27
16 .
30
50
-0.2 -
58.7
Simplified
Semi -tight
0
Construction descriptions or Area u-value Insul R Htg HTM - Loss Cig HTM Gain
R BWhM'--T ff-'F0uh Buh4P Buh ftw BWb
Walls.
13A-2ocs: 13A-2ocs
13A-2ocs 2: 13A-2ocs 2
13A-2ocs 1: 13A-2ocs 1
13A-2ocs 3:13A-2ocs 3
c.
Partitions
12C-Osw: 12C-Osw
Windows
2A-2om: 2 glazing, clr low-e outr, air gas, m8 no brk 6m mat, clr innr,
1/4" gap, 1/8" lhk; NFRC rated (SHGC=0.32): foreground = new
concrete (0.32); 2 ft overhang (5 ft window ht, 0.38 ft sep.); 6.67 It head
ht
2A-2om: 2 glazing, clr low-e outr, air gas, mtl no brk frm mat, clr innr,
1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); foreground = new
concrete (0.32): 2 ft overhang (6.33 It window ht, 0.38 It sep.); 6.67 ft
head ht
2A-2omd: 2 glazing, clr ow-e outr, air gas, mtl no brk firm mat, clr innr,
1/4" gap, 1/8" Ink: NFRC rated (SHGC=0.32); foreground = new
concrete (0.32); 13 It overhang (8 ft window ht, 0.38 It sep.); 6,67 ft
head ht f
n 273
0.258
4.1
6.94
1892
5.19
1413
e 145
0.258
4.1
6.94
1003
5.19
750
s 232
0.258
4.1
6.94
1607
5.19
1201
w 133
0.258
4.1
6.94
925
5.19
691
all 782
0.258
4.1
6.94
5427
5.19
4055
n 145
0.268
4.1
6.94
1004
5.19
750
e 84
0.258
4.1
6.94
582
5.19
435
s 78
0.258
4.1
6.94
541
5.19
404
all 306
0.258
4.1
6.94
2127
5.19
1589
e 72
0.258
4.1
6.94
499
5.19 -
373
w 26
0.258
4.1
6.94
180
5.19
135
all 98
0.268
4.1
6.94
680
5.19
508
s 56
0.258
4.1
6.94
389
5.19
290
w 81
0.258
4.1
6.94
562
5.19
420
all 137
0.258
4.1
6.94
950
5.19
710
315
0.096
13.0
2.58
812
1.37
432
n 13
0.600
0
16.1
215
16.0
213
n 27
0.600
0
16.1
430
16.0
427
all 40
0.600
0
16.1
646
16.0
640
e 51
0.600
0
16.1
818
45.2
2290
e 38
0.600
0
16.1
613
45.2
1717
e 34
0.600
0
16.1
545
45.2
1526
e 32
0.600
0
16.1
511
45.2
1431
all 154
0.600
0
16.1
2487
45.2
6964
e 96
MOD
0
16.1
1549
26.0
2497
wrightsoft' Right -Suite® universal 201515.0.18 RSU08057
ACCIN... t28TarponFlatsAGR\Lot28TarponFlatsModelAGRWrup Calc='MJ8 House faces: W
'
2A-2om: 2 glazing, clr low-e outr, air gas, mil no brk frm mat, clr innr,
s 6 0.600 0
1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); foreground = new
concrete (0.32); 2 ft overhang (3.17 ft window ht, 0.38 It sep.); 6.67 It
head ht
IOC-m: 2 clr low-e outr, air m8 no brk frm mat, clr innr,
s 20 0.600 0
glazing, gas,
1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); foreground = new
concrete (0.32); 18.67 ft overhang (8 ft window ht, 0.47 It sep.); 6.67 It
head ht
2A-2om: 2 glazing, clr low-e outr, air gas, mll no brk firm mat, clr innr,
w 8 0.600 0
1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); foreground = new
concrete (0.32); 2 ft overhang (4.17 ft window ht, 0.38 ft sep.); 6.67 It
head ht
2A-2om: 2 glazing, clr low-e outr, air gas, mtl no brk frm mat, clr innr,
w 31 0.600 0
1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); foreground = new
concrete (0.32); 2 ft overhang (5.17 It window ht, 0.38 ft sep.); 6.67 ft
head ht
1OC-m: 2 glazing, clr low-e outr, air gas, frill no brk frm mat, clr innr,
w 24 0.600 0
1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); foreground = new
,
concrete (0.32); 9.17 ft overhang (8 ft window ht, 0.7 it sep.); 6.67 It
head ht
2B-2fm: 2 glazing, clr low-e outr, air gas, mtl no brk frm mat, clr innr,
w 11 0.600 0
1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); foreground = new
concrete (0.32); 9.17 ft overhang (8 ft window ht, 0.17 ft sep.); 6.67 It
head ht
2A-2om: 2 glazing, clr low-e outr, air gas, frill no brk frm mat, clr innr,
w 31 0.600 0
1/4" gap, 1/8" lhk; NFRC rated (SHGC=0.32); foreground = new
,
concrete (0.32); 3 It overhang (5.17 ft window ht, 0.17 ft sep.); 6.67 ft
head ht
Doors
11 D0: Door, wd sc type n 21 0.390 0
Ceilings
16X19-Omd: Attic ceiling, mil roof mat, r-20 roof! ns, 1/2" gypsum board 1976 0.408 19.0
int fnsh
f
Floors '
22A-tpl; Bg floor, light dry soil, on grade depth 187 , 0.989 0
F wrightsoft' Right-Suileg Universal 201516.0.18 RSU08057
ACCK... t28TarponFlatsAGR\Lot28TarponFlatsMcdelAGRWrup Cale -MJ8 House faces: W
16.1
102
26.0
165
16.1
323
21.2
424
16.1
135
42.7
356
16.1
500
44.1
1367
16.1
387
23.5
564
16.1
172
27.7
295
16.1
500
39.3
1217
10.5 224 11.4 243
1.52 3010 1.50 2964
26.6 4975 0 0
2
ec Prot Summary Job: Lot 28 Tarpon Flats Mod
ft...
Wrightso' ry Date: 01.18.14
Entire House By: ER
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY. SANFORD, FL 32771 Phone: 407-333-2665 Fax 407-333.3853 Web: WWW.DEL-AIR.COM
For: Phoenix Realty Homes Inc, Lot 28 Tarpon Flats Model A GRW
3922 Duneside Drive, Fort Pierce, FL
Notes: LS by CA on 11.03.2015,Rvsd 12.18.2015 RH
Weather: Vero Beach Municipal AP, FL, US
Winter Design Conditions
Summer Design Conditions
Outside db 43 OF
Outside db
91
OF
Inside db 70 OF
Inside db
75
OF
Design TD 27 OF
Design TD
16
OF
Daily range
L
Relative humidity
50
%
Moisture difference
59
gr/lb
Heating Summary
Sensible Cooling Equipment
Load Sizing
Structure 27368 Btuh
Structure
32303
Btuh
Ducts 3825 Btuh
Ducts
2649
Btuh
Central vent (0 cfm) 0 Btuh
Central vent (0 cfm)
0
Btuh
Humidification 0 Btuh
Blower
0
Btuh
Piping 0 Btuh
Equipment load 31193 Btuh
Use manufacturer's data
y
Rate/swing multiplier
1.00
Infiltration
Equipment sensible load
34952
Btuh
MethodSimplified
Latent Cooling Equipment
Load
Sizing
Construction quality Semi -tight •
Fireplaces 0
Structure
2715
Btuh
Ducts
2631
Btuh
Heatingg Coolingg
Central vent (0 cfm)
0
Btuh
Area (ft21976 1976
Equipment latent load
5346
Btuh
Volume (Its) 18436 18436
Air changes/hour 0.26 0.14
Equipment total load
40299
Btuh
Equiv. AVF (cfm) 80 43
Req. total capacity at 0.75 SHR
3.9
ton
Heating Equipment Summary
Cooling Equipment
Summary
Make Carrier
Make Carrier
Trade CARRIER AIR CONDITIONING
Trade CARRIER AIR CONDITIONING
Model 25HBC548A**30
Cond 25HBC548A**30
AHRI ref 6936854
Coil FX4DN(B,F)049L
AHRI ref 6936854
Efficiency 8.5 HSPF
Efficiency 12.5 EER,
15 SEER
Heating input
Sensible cooling
35625
Btuh
Heating output 45500 Btuh @ 47*F
Latent cooling
11875
Btuh
Temperature rise 26 OF
Total cooling
47500
Btuh
Actual air flow 1583 cfm
Actual air flow
1583
cfm
Air flow factor 0.051 cfm/Btuh
Air flow factor
0.045
cfm/Btuh
Static pressure 0.30 in H2O
Static pressure
0.30
in H2O
Space thermostat
Load sensible heat ratio
0.87
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed...
,; AR04
vvright50fV Right Universal 201515.0.18 RSUDS057
'6
7nt ^
-suite®
Page 1
8
/R..Cf.... t28TarponFlatsAGR\Lot28TarponFlaisModeIAGRW.rup Cale = MJS House (aces:
W 5
wrightsoft` Right-J® Worksheet
Entire House
DEL -AIR HEATING &AIR
CONDITIONING
531 CODISCO WAY, SANFORD. FL 32771 Phone: 407-333-2665 Fax 407-333-3853 Web: WWW.DEL-AIR.COM
Job: Lot 28 Tarpon Flats Model A...
Date: 01.18.14
By: ER
1
Room name
Entire House
Mstr BdOn
2
Exposed wall
187.0 ft
42.0 ft
3
Roam height
9.3 it
9.3 it heat/cool
4
Room dimensions
16.0 x 15.5 it
5
Room arm
1976.0 ft'
248.0 ft'
Ty
Construction
U-value
Or
HTM
Area (ftl
Load
Area (ft'
Load
number
(Btuh/ftMF)
(Btut✓ft0
cr perimeter (it)
(Btuh)
or perimeter (it)
(Btuh)
Heat
Coal
Gross
NIP/S
Heat
Cod
Gross
NIP/S
Heat
Cod
6
W
13A-25H - - -
2A.2om
- 0.258
0.600
n
n
6,94
16.14
5.19
- 16.01
313
13
273
0
1892'
215
- -1413
213
'- --0
0
- 0
0
--- ---'0
0
- - 0
0
2A 2cm
0.600
n
16.14
16.01
27
'0
430
427'
0
0
0
0
__ _-
2 --
0.258
Ti
--'6.94
5.19
_
145
145
_ _ _
- 750
_
w
145
__
1004
- 750
11
W
_13A-2ocs
13A 2acs
_ _
0.258
_
-6
_-_-_
6 94
_
5.19
- 233
'145'
_1004
1818
-` 2290
0
0
-- '-0
' ` - 0
IIW--,�,
2A2cm
0.600
a
45.19
45.19
51
38
10
8
613
1717.
1717
0
0
0
0
-0
0
'0
_
I�G
W ----
rC
,,.
I' -loos 1 - '
2A-2o17d
______
0.258
0,600
a
e
_1_6.14
6.94
1.6.14
_
5.19
26.01
168
96
__
72
96
_,613
499
1549
373
_
0
0
_0
0
0
0
0
0
0
W-
_
13A 2ocs 2 '-
_
10.258
6_
6.94
_5.19
- 149
_
84
_
582
_ _2497
' -435
149
84
582
--- -435
2om
D.600
a
16.14
45.19
34
7
545
1528
-34
7
545
1526
EaW2A
2A20m
0.600
e,_
1614
45.19
32
6_
1431
32'
6
511
14.31
W
_
13A-2ocs
0.258
s
_.
6.94
5.19
238
_.
232
-_.__:511
1607
1201
_
0
_
0
_
0
_
0
IF r
24-2om
0.600
s
16.14
26.01
6
6
102
0
0
0
0
W
13A-2bcs2'---
-7-0.258
's
694
`'5.19
-- '98'-
- 78
_ _
541
_ _165
404
-'98
_
78
_ _.
541
-404
L_-_G.
OCGm_ _ _
_.0.600
s
1814
_21.21
20
20,
323
20
20
W
13A-2acs 3
D2513
s
6.94
56
_
56
_
389
_424
290
-
� 0
0
_ _ _323
0
_.424
0
_
IWI -�
13A tads- -"'0.258-
w
6.94
_ _SAS
5.19
_
173
133
_
925
_
691
--0
- _-0
-0
--.,._0
2A-tom'
0.600
w
16.14
42.66
8
3
135
356
0
0
0
0
I--G
t-G
2A-tom,
0.600
44.09
31
8
500
'1367
,
0
0
- 0
0
W
13A-2ocs 1 ` -
_
0.258
_w
w
_16.14
6.94
_ 5.19
61
26
180
- -135
-- - 0
- 0
- - -0
'0
10C-m
0.600
w
16.14
23.50
24
- 21
387
554
0
0
0
0
2B-2fm
0.600
w
16.14
11
10
172
295
0
0
0
w --
--13A-2ocs 3� -
- '0.258
_
w
6.94
_27.70
5.19
112
81
562
- -420
_
0
_
0
0
_0
.0
2A-2om - -
- 0.600
w
16.14
39.25
�31
-_14
1217
0
0
0--
0
P
"
12C-Osw
0.096
-
2.58
- --1.37
336
315
__500
812
�_-432
- -0
0
0
_
0
1160
0.390
n
10.49
11.39
21
21
224,
243
0
0
0
0
F_ -�
16X19-0nid,
0.408
-
-'1 52
1.50
' 1976
1976
3010
`2964
-248
248
378
372
6
_
22A tpl - - - - -
_
. - 0.989
_ .
26.60
_ _ - 0,00
_ 197.6
_ _ 187
-
_ _ 4975
_ 0
248
_ _
42
_
_ 1117
0
-
6
c) AED excursion
0
-257
Envelope loss/gain
25007
24991
5001
5085
12
a) Infiltration
2361
733
530
165
b) Room ventilation 1
0
0
0
0
13
Internal gains: Occupants @ 230
5
1150
1
230
Applianceslother
we
1200
Subtotal (lines 6 to 13)
27368
32303
5531
6660
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
27360
32303
5531
6660
15
Duct loads
14%
B%
3825
2649
14%
8%
773
548
Total mom lead
31183
34952
63041
7227
Air required (cfm)
1583
1583
1
1
320
27
. M -F]+ wrightsoftl Right-Sulte® Universal 2015 15.0.18 RSU08057
...I28TarponFlatsAGR\Lol28TarponFlatsModeIAGRWmp Cale =MJ8 House faces: W
Page 1
wrightsoft° Right-JO Worksheet
Entire House
DEL -AIR HEATING &AIR
CONDITIONING
531 CODISCO'WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fa c 407-33MS53 Web: VWM.DEL-AIR.COM
Job: Lot 28 Tarpon Flats Model A...
Date: 01.18.14
By: ER
1
Room name
Mstr WC
Mstr WIC
2
Exposed wall
6.0 ft
0 ft
'3
Room height
9.3 ft heat/cool
9.3 it heat/cool
4
Room dimensions
4.0 x 6.0 it
6.0 x 11.5 ft
5
Room area
24.0 ft'
69.0 it,
Ty
Constmction
U-value
Or
HTM
Area (fl0
Load
Area (ft5
Load
number
(BtulJft? °F)
(Stuh/ft5
or perimeter (it)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cod
Gross
N/P/S
Heat
Cod
Gross
N/P/S
Heat
Cod
6
IWI- _---
13A-2663 -
2A-2om
_ _ - 0.256
0.600
n:
in
- 6.94
16.14
-5.19
16.01
56
13
__ 43
'0
7296
215
. -„_221
213
__ : _ -0
0
`.0
0
.. - _- 0
0
0
- 0
I--v
'
2A-2om
- 0.600
---0.258
in
16,14
16.01
0
a'
'0
0
0'_
0
- 0
� 0
W-
13A-20cs 2 - - -�-
n -
- _ -6.94
5.19
-0
-- 0
_
- - -0
-
- -- 0
_ - _
0
_
0
_
0
_
0
11
l{J -
'13A-2a6s -. -
-0.258
- -a--
6.94
: '-5.19
.. -0
- 0'-
'- - 0
- 0
- p
" - -0
- - 0
0
2A-2om
'0.600
a
16.14
45.19
.0
10
0
0
- 0
10
0
0
2A-2om
a
16.14
45.19
'0
0
0
10
- 0
0
0
_'
-" 0
. _
W
L_ C
,__- _
13A-2acs 1
2A-2omd
_ _.0.600
_ 0.258
0.600
a
6.94
1_6.14
5.19
_ _ . _0
0
y __
0
0
0
0
. . _ _ 0
0
- - _ 0
0
-_ _
_ --0
0
.. _ _ _0
0
_ - a
0
13A-2ocs 2.'-_,
_ _-_0.258
_e
a
6.94
_ _26.01
5.19
_. _0
_ -.._0
_ _ _-.0
_ _,_ _0
-. _ _. 0
_ _ _ _0
_ 0
___._ -0
IWI --.
2A-2om
'2A-20m
0.600
0.600
a
a
1614
1614
45.19
0
0
0
0
0
0
0
0
0
0
0
0
0
0
- 0
-{ 0
I�
I_G
W
13A-2ocs _ _ _-
_
_0.258
_._.
s
.. _
6.94
_ _45:19
5.19
- _ _. __0
_ . , .0
.. _ _ _0
- _0
.. 0
_ _ _0
_ _ 0
_ 0
r
2A-20m
0.600
s
16,14
26.01
0
0
0
0
0
0
0
0
W
LC.
13A-20cs 2'
10C-m
- .0.258
0.600
s-
:_a
__
6.84
16.14
.-. .. 5.19
21.21
_ -0
_0
;0
0
_ -0
_. 0
0
_` _ a
_.. __0,
0
...0
-0
0
W
_
13A-2acs 3
0.258
s
6,94
5.19
0
_ _
0
_ _0
0
-
0
_0
0
__-
0
__0
0
_
0
IWI .. _--
-13A-2ccs - `.
2A-2om
_ 0.256
a600
w
w
"6.94
16.14
,- _5.19
42.66
'" ' "0
0
. _ _ _ -0
0
_ 0
0
_ _ -0
0
_ ..0
0
_. .0
0
0
0
0
0
2A-2om
0.600
w
16.14
44.09,
0'_
0
�0
0
0
0
0
0
134-2ocs-1 -- - -
- 0.258
-w -
-�6.94
LL---5.19
- --0
0
_
-0
_
0
0-
0
0
_
0
1oGm
0.600
w
16.14
23.50
0
0
0
0
0
0
0
0
L�_GG
2B-2fm
0.600
w
16.14
27.70
0
0
0
0
0
0
0
0
W
13A-2ocs 3'-
0.258
w
----0.94
5.19
- 0
- 0
- -0
- 0
0
0
0
-- 0
LG
2A-2om
0.600
16:14
39.25
0
0
0
0
0
0
0
0
_
P
12C-0sw
_
0.096
_w
-
2.58
1.37
_
0
0
0
0
_
0
0
_
0
- 0
1-D
111150
0.390
n
10.49
11.39
0
0
0
0
0
0
0
0
C _(tf
F f
_
16X19-0md
,22A 1pl -
0.408
.0,989
-1 52
2660
1.50
0.00
_
24
. 24
24
6
„ _ 37
160
_ 36
_ _0
69
09
_69
a
_ 105
- - 0
_ --104
_ 0
6
c)AED excursion
-18
-4
Envelope loss/gain
707
452
105
100
12
a) Infillmtion
76
24
0
0
b) Raamventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
0
0
Appliances/other
0
0
Subtotal (lines 6 to 13)
783
476
105
100
Less external load
0
0
'
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
783
476
105
100
15
Duct loads
14%
8%
109
39
14%
8%
15
8
Total room load
893
515
120
Air required (cfm)
45
23
':
' F" wrGghtsoft Right -Suite® Universal 2015 15.0.18 RSU08057
... t28TarponFlatsAGRlLot28TarponFlatsMadelAGRWmp 'Calc=MJ8 House faces: W
off
15:04:59
Page 2
+{f wrightsoft' Right-JO Worksheet
Entire House
DEL -AIR HEATING &AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax 407-3333853 Web: WWW.DEL-AIR.COM
Job: Lot 28 Tarpon Flats Model A...
Data: 01.18.14
By: ER
1
Room name
Mslr Blhnn
Great
2
Exposed wall
12.5 ft
24.5 It
3
Room height
9.3 it heat/cool
9.3 ft hewcool
4
Room dimensions
1.0 x 157.5 it
1.0 x 503.5 ft
5
Room area
157.5 W
503.5 ft2
Ty
Construction
U-value
Or
HTM
Area (ftT
Load
Area (ft0
Load
number
(Btuh/ft? °F)
(BtuNft5
or pedmeler (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
NIP/S
Heat
Cool
Gross
NIP/S
Heat
Cool
6
IW -
y--t;
134-2ors_.- "
-'"'"0.258
n-
- -6194
'5.19
117
'90---
-624'
` 467
0
- 0
"' - -0
- 0
2A tom
0.600
n
16.14
16.01
0
0'
'0
0
0
0
0
0
I--G
2A-2om
_ 0.600
n
16.14
1.6.01
_. 27
0
430
427
0
0
0
0
11
W
WII
_
13A-2dcs'2 _�
13A 2ocs
2A tom . _.-
2A.2orn
__ 0.258
0.258
0.600
0.600
_
_n_
e
a
e'
_ 6.94
6 94
16.14
16.14
_
_ 5.19
5.19
45.19
'_ 45.19
`_.. _0
0
0
_.___0
0
-0
_-_ _0
,--._,0
0
0
_0
__ �_ ..0
0
0
_ 0
... 0
0'
0'
_ 0
_ _ 0
0
0
_ _ 0
..0
0
0
.__ __0
-._-- - 0
0
0
-.. 'G_-
r
W � �
r r
734-26cs 7 - - -
2A-2omd
- -0.258
0.600
a
a
6.94
16.14
5.19
2.6.01
- - 0
0
� � - � '0
0
-- � -- 0
0
_ � 0
0
- - -168
96
__
72
95
_
499
1549
373
2497
IW
_ ___._ _
134-gods 2
�� 0.258
_
e :
- -6.94
_
- 5.19
-_ _ _ ._0
_ __ _,.0
__ , .0
_ ._ ..0
-0
- 0
0
__ _._0
2A-2om ,.
0,600
6
- 1614
45.19,
0
'0
0
'o
0
0.
0
0
I--v
L-G
7A-2om
0.600
e
45.19
0
'0
0
0
0
0.
0
0
w .__.
-13A-2ocs ___. .._ _
-0.258
_
s
_16.14
_ 6.94
_. 5.19
-_ .0
- '0
_ _ 0
_. 0
. _ 0
_ _� 0
__ _- 0
__ 0
LG_
2A-tam
13A-2ocs2'__
0.600
___._0.258
s_
s
16.14
- 6.94
26.01
__..5.18'
0
.. - 0
0
_ 0.
0
0
0
� 0
0
_ _ -0_
0
_. _0.
0
.0
0
_ _ _ .0
W
L--G
iOCm-
,0.600
s-..._j6.14-
21.21
0
0
0
_0
'.. 0
W
'..
W'l ^
13A-2ocs 3 _.. _ _ _ _
2A-tom
0.258
�. __ _
--0.258
0.600
s
_ - .
w
w
6.94
�6.94
'16.14
5.19
_. 5-19
4266
_.-
0
-- p'
0
_ _0
0
- 'p
,a
-_ _.,0
0
'p
0
_ _0
_ 0
_ ---p
0
_. -
0
-----p-
0
_ _
0
-..0
0
0
..;.... 0�
0'
0
---p
0
Ij
�__
2A-2am
0.258
- w
16.14
44.09
0
0
0
0
0
0
0
W
13A720cs-1---- ---
10C-m
0.258
0.600
w
w
6.94
16.14
5.tg
23.50
� 0
0
- p
0
_ ..0
0
- _ 0
0
_ _61
24
- - - 26
6
21
_
160
387
- � 135
564
2B-2fm - - --
0.600
w
16.14
27.70
0
0
0
10
172
295
Y.. _ -
13A-2ocs 3
- 0.258
W -
6.94
5.19
- - 0
0
_ _0
0
_
0
_ ..11
0
_-
0
- `0
0
2A-2om-_ , _ _ __
-_. 0.600
w
16,14
39.25
0
0
0
0
0
0
0
-r
R
�_D
12C-0sw
0.096
- -
Z58
1.37
0
0
-
0
-_
0
_0
0
0
-
0
0
100 _
0.390
n
1049
11.39
0
0
0
0
0
0
0
0
C -, -.
_
16X19-onld _ _ - _ _
_ 0.408
-
-_
1:52
_
1.50
158
158
_
240
_
236
_
504
504
__
767
7$0
F -'_
22A tol _ -
0.989
-
- 28.60
a.co
158
13
333
_
_0
_ _
- 504
- 25
_ - ' 652
6
c) AED excursion
-44
-246
Envelope loss/gain
1627
1085
4207
4373
12
a) Infiltration
158
49
309
96
b) Room ventilation
0
0
0
0
13
1ntemal gains: Occupants @ 230
0
0
3
690
Appliances/other
0
1230
Subtotal (lines 6to 13)
1785
1135
4517
6389
Less external lead
0
0
0
0
Less transfer
0
0
0
0
Redistdtxdion
0
0
0
0
14
Subtotal
1785
1135
4517
6389
15
Duct loads
149/.
6%
249
93
14%
8%
631
5
Total room load
2034
1228
51,,
"�
Air required(cfm)
103
56
.
- 21
ACCA to meet all
' r wrightNoft` Right -Suite® Universal 2015 15.0.18 RSU08057
'^4�"... t28TarponFlatsAGRlLot28TarponFlatsModeIAGRWmp Cale =We House faces: W
M
15:04:59
Page 3
wrightsoft° Right-M Worksheet
Entire House
DEL -AIR HEATING &AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax 407-333-3853 Web: WWW.DEL-AIR.COM
Job: Lot 28 Tarpon Flats Model A...
Date: 01.18.14
By: ER
1
Room name
Neck
Bdnn 3
2
Exposed wall
18.5 It
26.0 ft
3
Room height
9.3 It heat/cool
9.3 ft heat/cool
4
Room dimensions
1.0 x 125.5 ft
1.0 x 1920 R
5
Room area
126.5 W
192.0 W
Ty
Construction
U-value
Or
HTM
Area (ft�
Load
Area (ftj
Load
number
(Btuh/ "F)
(Btuwft�
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cad
Gross
NIP/S
Heat
Cod
Gross
N/P/S
Heal
Cool
6
IW
13A-2dcs-- .
_ _.0.258
-"n
_ '6.94
5.19
- _ 0
. 0'
0
__ _ 0
_ _ - 0
- 0
0
0
-
I---t;
2A-2om
0.600
n
16.14
16.01
0
0
'.0
0
0
'0
0
0
L-C_
2A-2om _
n
16.14
_16.01
0
0_
0
,.
0
0
0
0
0
W
13A-2ccs 2
13A-2acs- -
_0.600
0.258
-0258
n
- a-6.94
_ _ 6.94
_
5.19
5.19
- 0
112
_ _
_ 0
61
_ - 0
425
0
318
0
121
_ _ 0
83
_ 0
578
0
432
2A-2om.
-_2A-2om
0600
0.600
• e
a
1614
-16.14
45.19
45.19
51
0
10
0-
'818
0
2290
0
'0
38
0
8
0
613
0
1717
_ _
W
13A-2acs 7 _ _____
- - __-0.258
a
." -6.94
5.19_
- ___0
_ _ .0
__ __0
- _ -. _0
_ .0
. _ < 0
_ _ 0
_
0
rr
2A-2omd
0.600
a
W14
26.01
0
0
0
0
0
0
0
0
IW-_..
13A-2acs 2.._ _
_
0.258
:e
694
"5.19.
.. __._0
__........0
a...
..a
.. __.0
..0
.0
_ 0
2A-2om
-0.600
a
16.14
•45.19
0
0
0
0
0
0
�0
0
I--v
I-_G
2A-2om
0.600
a
A_614
0
0
0
0
0
0
0
_ 0
Wu _
_
13A-2acs- - -
- 0.258
-s
6.94
__45.19
- 5.19
61
_ _
61
421
_
-314
121
_
" 121-
_
842
629
I�
2A-2om
13A-26cs 2 _ _ _ _
10C-m
0.600
_ -0.258
0.600
s
--a-
_s
16.14
-6.94
16.14
26.01
.. 5.19
0
_ - - 0
0
0
0'
_ 0
0
- - 0
0
0
_ '. 0
0
0
. 0
0
0
0
0
0
_ -_ " 0
0
0
. _ _ _0
W " ..
LG-
W
_ _.
13A-2ocs 3
_.
0.258
.
s
6.94
_21.21
5.19
0
-
0
0
_
0
0
_
0
_ _
0
_0
0
W' -
13A-2ocs.. _.
- .0.258
__
w
6.94
5.19
_
0
0
... 0
.... 0
". 0
. - b
- .. 0
0
�--G
2A-tan-
0.600
w
16.14
42.56
0
0
0
0.
0
0
0-
0
LG
0.600
w
16.14
0
0
0
0
0
0
0
W _
_2A-2om
13A-2ocs 1 - - -
-'0.258
w
_
6.94
_4.4.99
5A9
_o
0
0
'0
-- -0
0
- 0
- -- -0
-0
0.600
w
16.14
23.50
0
0
0
0
0
0
0
0
LS10C-m
28-2fm
0.600
w
27.70
0
0
0
0
0
0
0
0
Y--a
- _
13A-2ccs3
0.258
w
_ _16.14
6.94
5.19,
0.
- 0
- 0
0,.,_.0
0.
._ _0
_ 0
2A-tan
w;
_ 16.14
39.25
0
0-_
0
0
0
0
-_ 0
0
P
_ _'._
12C-0sw
_ ._0.600
0.096
-
2.58
1.37
_ _.
0
0
0
0
_
37
37
96
_
51
1-D
11DO
0.390
n
10.49
1.1.39
0
0
0
0
0
0
0
0
C
_
16X19-0md
' 0.408
-
1.52
1.50
127
1W
- - - 193
- -
192
_
192
288
F
22A-tpl - _ _
- 0.989
_ 26.60
O.00
_
127
_
19
492
_1190
_ 01
_
_ 192
_
26
_292
- 692
�_ 0
_
6
c) AED excursion
-127
-119
Envelope loss/gain
2349
2985
3114
2998
12
a) Infiltration
234
72
328
102
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
1
230
0
0
Appliances/other
0
0
Subtotal Qinas 6 to 13)
2583
3288
3442
3100
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
2583
3288
3442
3100
15
Duct loads
14%
B%
361
270
14%
8%
481
254
Total mom load
2943
3557
3923
Air required(cfm)
149
161
19
' 1' wrightsof ' Right -Suite® Universal 2015 16.0.18 RSU08057
'CCk ... t28TarponFlatsAGRlLot28TarponFlalsMcdelAGRW mp Cale = We House faces: W
15:04:59
Page 4
wrightsoft' Right-JO Worksheet
Entire House
DEL -AIR HEATING &AIR
CONDITIONING
531 COD SOO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fac 407-333-3853 Web: WWW.DEL-AIR.COM
Job: Lot 28 Tarpon Flats Model A...
Date: 01.18.14
By: ER
1
Room name
Bthnn 2
Kitchen
2
Exposed wall
6.0 ft
0 ft
3
Room height
9.3 ft heat/cool
9.3 ft heaVcool
4
Room dimensions
10.0 x 6.0 ft
11.0 x 14.5 ft
5
Room area
60.0 8'
159.5 ft.
Ty
Construction
U-value
Or
HTM
Area (fly
Load
Area (ftj
Load
number
(BtutVft-F)
(Btutdit�
or perimeter (ft)
(Btuh)
or perimeter (it)
(Bluh)
Heat
Cool
Gross
N/P/S
Heal
Cccl
Gross
NIP/S
Heat
Cool
'
6
IW
_0
.. _ _0
__ _.0
___ .0
.. ._;0
.._ 0
_ ___.0
.01
0_
0
0
0
0
0
0
0
H--ra
�Zom
0.258
nr
i1619'
-0
11
_-
W
W�`�
13A-266s2 -
13A-20cs .___._...._0.258
0.258
n
'..e.__6.94-__5.19-..
_1694_
6.94
5.19
-
._...'0__
- -0
Q__-
-
- - 0
:.a
_
- - 0
,.___0
0
_.__-0
0
__ _0.-
'0
-.0
-
0
_,... 0
}L-(Ci
2A-2om
0.600
' a
16.14
45.19
0
0
0
0
0
0
0
0
0.600
a
16.14
45.19
0
0
0
0
- 0
0
0
0
W.
r
_ZA-20M
13A-20cs 1_ _.---=0.258
2A-2cmd
0.600
a
e
6.94
16.14
_
5.19
26.01
_ _ _
0
0
0-
0
-0
0
_ _
0
0
0
0
0-
0
0-
0
0
0
iIW
__
13A-2acs2_
-0258
_ Ae
__
-694
-539
;_,_-0
.- _ 0_
__._0.-__.
_0
__._0
__0
-... __0_
0
I--v
2A2om
0.600-
a
1814
'45.19
0
0
0
0
':0
0
0
0
2A-2cm_
_0.600
e_
4519
'0
0
0
0
00
__.
W
_. ._._.,..
13A-2ocs
0.258
s
__1614
6.94
5.19
_
56
_ .0
50
_
345
._.__.
257
0
_0.
0
0
0
L-G
2A-2om
s
16.14
6
102
165
,_._
0
0
0
W
LG
_ _ _ _ _ -
13A-2ccs 2
10C-m___..
_ _0.600
--0 258
0.600
- -a
s
_ _
6.94
16.14__21:21
_,25.01
5.19
_6
'0
0
_ -
'0
_ 0
_ _
0
.0
_ _ -
0
--0_
_ -0
0
0
__ __
0
_ _ 0
_ _
0'-
0
_
0
-0
W.
13A-2ocs 3
0.258
s
6.94
0
0
0
_.
0
0
0
0
W._. ._
H2A-2cm
13A-2dcs" ., _
_ `0,258
0.600
w'
w
694
16.14
_ _5.19
519
4256
._. - -0
0
. ;0
0
._ 0
0
_.. _..0
0'
.., _0
0
_0
0,
0
._ '; 0''
0'
' _ 0
0
7A-2om
0.600
-_w
44.09
0
0
0
0
0
'0
0'
0
W
13A-2ac5_i__
_0.258
w
_1614
6.94
. _-5.19
.. ;_ __ 0
_ _ _0
0
_ 0
_ _ -0
_ 0
_ _ 0
__ . _- 0
10C-m
0.600
w
16.14
23.50
0
0
0
0
0
0
0
0
213-2fm
0.600
w
27.70
0
0
0
0
0
0
0
0
W
13A-2acs 3
_. 0.258
w
_16.14
6.94
5.19
- �0
. 0
.. 0
-�0
0.0
0
- _0
L-C
2A-tom
0.600
w
16.14
39.25
0
0
0
0
-0
0
0
0
R
t-D
C
12C-Osw -
11DO
16X19-Omd
- 0.096
0.390
-
n
2.58
10.49
1.52
-- 1.37
11.39
1.50
_ _
126
0
,60
126
0
60
_
325
0
91
173
0
90
107
0
160
_
107
0
160
277
0
243
147
0
239
_
F !
22A tpl. _
_0.408
_ 0 989-.
_ 26.60
OAO_
60
.6
_
-160
0
-160
0
_ - 0
0
6
c) AED excursion
-26
-89
Envelope loss/gain
1023
659
520
298
12
a) Infiltration
76
24
0
0
b) Room ventilation
0
0
0
0
13
Inlerral gains: Occupants @ 230
0
0
0
0
Appliances/other
0
2000
Subtotal (lines 6 to 13)
1099
682
520
2298
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
1099
682
520
2298
15
Duct loads
14%
8%
154
56
14%
8%
73
188
Total room load
1252
738
5903
(cfm)
64
33
30
AAirrequired
Wright5of-V Right -Suite® Universal 201515.0.18 RSU08057
'`'��`...128TarponFlatsAGR\Lot28TarponFlatsModelAGRW.mp Cale = MJ8 House faces: W
15:04:59
Page 5
wrightsoft' Right-M Worksheet
Entire House
DEL -AIR HEATING &AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phcne:407-333-2665 Fax 407-333-3853 Web: WWW.DEL-AIR.COM
Job: Lot 28 Tarpon Flats Model A...
Date: 01.18.14
By: ER
1
Room name
Utility
Bonn 2
2
Exposed wall
6.5 ft
27.0 ft
3
Room height
9.3 ft heat/cool
9.3 ft heat/cool
4
Room dimensions
1.0 x 52.5 It
1.0 x 178.5 ft
5
Room area
52.5 W
178.5 ft-
Ty
Construction
U-value
Or
HTM
Area (ft�
Load
Area
Load
number
(BtulVWF)
(BtutVft5
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cod
6
'
13A-2oos-. __-.__.
_.. D.258
n
'-6.94
'_--5:19
_ _ _0
_. 0�_
_ -a.
_. "0-'
-` -140
140
' '' 971.
_.- .._726
IW
2A-2cm
0.600
n
16.14
16.01
0
0
0
0
0
0
0
0
2A-2om
0.600
n
16.01
0
0
_0
,0_
_0
-._. .__0
__G
W
'W
11
_ . _, _:
13A-2ocs 2
13A-lobs- _ _ __
_
0.258
0.258
_
n
a
_16.14
_ 6.94
6.94
_5.19
SAS
_.._
0
"' _0
_0
0
, .. 0
_0
0
0
_ ...
0
-_ _0
0
_ -,.0
_
0
_ ..._0
__..._
0
_.-- 0
0
-._ __, 0
2A-2om
0.600
a
16.14
45.19
0
0
0
a
::a
a
0
0
'2A-2am
0.600
a
1614
45.19
0
0
0
0
0
0
0
'0
_
W '
'13A-2ocs 1 " - -
- 0.258
a
-6.94
_ _
5.19
0
_
0
0
- -0
- - 0
_ v. -'0
---J--0
_
0
r
2A-2cmd
0.600
a
16.14
26.01
0
0
0
0
0
0
0
a
13A-2ocs2 _'_ ._...
0.258
e-
----6.94
_
5.19
__ .__.0
.0
.a
_ _-.0
.... .._0
"'"' g
___ 0
_. �0
-
IW,^-
?A-tom
0.600
a
16.14
-. 45.19
0
.0
a
'0
0
0
0
0
L-G
2A-2om
0.600
45.19
0
0
0
0
0
0
0
0
w___
13A-2ocs
0.250
_e
s
__16.14
6.94---5.19
_ ____. .0
_ _.0
- 0
- 0
_ 0
- .0
-__ _0
._,_.. 0
_ _
_ _
_0.600
_
5..19
_ 0
D
a
o
0
a
_ 0
.•-0
0
0
_ _ - 0
0-
__ 0
0,.
0
.._. 0
W�--_C.
0Cm_2
o258
s_.
is14
_..
__-0-
a
0=
D
0
0_
o
-__ o
W __
W'-
_
-
13A-2ocs 3
13A-26cs--- --
2A-2om
0.258
'' - 0.258
0.600
s
'w-'6.94
w,
6.94
16A4
_ 5,19
5.19
42.66
0_
'' � 61
8
0
52
3
0
363
135
0
271
. 356
0
- 112.--
0
0
- -81
' 0
0
- _ 562'
' 0
0
420
0
G
E2A-2om
0.600
w
16.14
44.09
0
0
0
0
31
8
500
1367
_
W
13A-2ocs 1 _
.-0.258
_
w
.
6.94
__
-5.19
- 0
0
. 0
- _ .0
._ 0
_ �0
_ _. -0
- 0
171
IOC-m
0.600
w
16.14
23.50
0
0
0
0
0
0
0
0
28-2rm
0.600
w
16A4
D
0
0
0
' 0
0
0
0
�.
_ _ _ _
13A-2acs 3
'--
0.258
_
w
_
_ _27.70
_0
0
_ 0.
_0
_ 0
_ _ 0
0
_ 0
L_C_
2A-2om.. _.
w
.6.14
39.19
R
11D Osw
_0.600
0.396
-
2.5 8
1.39
65
- 44
114
60
0
0
0
0
I--D
11D0
0.390
n
11.49
11.50
21
21
280
243
0
0
0
_ 0
C_
_ _
16X19-0md
0.408
-
1.52
-�
1.50
_
53,
_ _
53
80
--79
_ 179
�. �� 179
� - - 272'
_
�_268
_
F
22A-tpl _ _
.. ._0989
-
_
.2860
0.00
_
53
7
_ _
173
0
179
_ 27
718
0
6
c) AED excursion
67
404
Envelope loss/gam
1088
1076
3024
3184
12
e) Infiltration
82
25
341
106
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
0
0
Appliances/other
1000
0
Subtotal (lines 6 to 13)
1170
2101
3355
3290
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
1170
2101
3365
3290
15
Duct loads
14%
8'/0
163
172
14%
8%
470
270
Total room load
1333
2273
3835
3560
Air requiretl (cfm)
68
103
195
161
-Fl" wrightsoftl Right-SalteO Universal 201515,0.18 RSU08057
... t2BTarponFlatsAGRlLot28TarponFlatsModelAGRWrup Calo=We House faces: W
15:04:59
Page 6
+wrightsoft° Right-M Worksheet
Entire House
DEL -AIR HEATING &AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax 407-333-3853 Web: WWW.DEL-AIR.COM
Job: Lot 28 Tarpon Flats Model A...
Date: 01.18.14
By: ER
1
Room name
Beim 4/Den
Bthm13
2
Exposed wall
18.0 ft
0 0
3
Room height
9.3 ft heat/cool
9.3 ft heat/cool
4
Room dimensions
12.0 x 12.5 ft
10.0 x 5.5 ft
5
Room area
150.0 ft.
55.0 ft'
Ty
Construction
U-value
Or
HTM
Area (ft)
Load
Area (ft�
Load
number
(BtutJft;'F)
(Btuh/ft�
a perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
W - __
13A-2as. -: ,
. __ 0.258
- n
6.99
5.19
-' _. 0
-0
- _.. _.0
.:..... _0
_ - 0
- _ _.. 0
. _0
, - 0
II--w
2A-2om
0.600
n
16.14
16.01
0
0
0
0
0
0
.0
0
1-G
2A-2om
0.600
n
16.14
16.01
0
0
0
0
0
0
0
0
W .._
.
13A-20cs 2 _ _. -
-. _ 0.258
- u
6.94
5.19
_ _ 0
__ _ _ _0
. _ 0
.. ___ _0
_ _ _ 0
_ _ _ _0
0
- ' 0
11
W __'
13A,2ocs_.___ _
_ __-0.258
_e
--- _ _.-694
- 5.19
--._ `,0
- _` 0._
- 0
'--0
_-_. _ __0..
.0
_ 0
._. 0
'
2A 2om.
'0.600
a
16.14
45.19
0
0
0
0
0
0
0
0
2A-2om .
0.600
a
16.14
'45.19
0
0-
0
.-
0
0
0
0
0
_
W
13A-2od51 ___ __<
- _> 0.258
_ e .
- _ 0.94
5.19
_ _ _0
-__0
<_ _ 3
-_,_.
0
... _ _0
__ _ _ _ 0
_ _ _ _ 0
-0
'�_ f
2A-2omd
0.600
a
16.14
26.01
0
0
0
0
0
0
0
0
_
IWIj
__
13A-2ocs2
_
0.258
e_
__ 6.94
5.19
- 0
-..0
- 0-_...
._ -0
...-- 0
.. _0.
-0
0
^-
2A-20m
_ 0.600
a
16.14
45.19
0
0
0
0
'0
0
0
0
L_G_
7A-2om
0.600
a
16 14
, 0
0
0
0
0
W
13A-2ocs - - -
- �0.258
-s
- 6.94
_45.19
- 5.19
- 0
- 0
_0
0
_ _ _- _0
0
_ _
0
_ _
0
_
0
-0
0
LCZ
2A-2om
Q600
s
16.14
26.01
0
0
0
0
0
0
0
0
W
13A-2ccs 2 _ ._
- - -0.258
s
6.94
- -5.19
._ __-0
0
_ -0
. 0
-0
0
- 0
0
LrG
tO(3m. _-_ -_ -
_ 0.600
s
16.14
21.21
0
0
0
_ 0
. 0
-0
0
0
W
-_ --
13A-2ocs 3
0,258
s
_
6.94
5.19
_
56
56
389
290
0
_0
0
_
0
_
13A-2ccs-
0.600
w
6.14
5.66
0
0
0
0
0,
0
0'
0
2A-2on
'0.600
w-
16.14'
44.09
0'
0
0
0
0
0
0°
0
13A226
0.600
w
16:14
0
0
0
0
0
0
0
_
W
13A-26cs 1 � - -
--0.258
- w -
- - 6.94
_ _45..19
5.19
- -- 0
- - 0
- � 0
_ _0
- 0
0
_
0
_
� 0
- 0
10C-m
0.600
w
16.14
23.50
0
0
0
0
0
0
0
0
213-2fm
0.600
w
1.6.14
27.70
0
0
0
0
0
0
0
0
_ _
W
13A-2ocs 3 - -
- 0,258
w
_
6.84
5.19
_
1 112
_ _
81
562
-420
-- -0
- 0
- - 0
_
0
L-C
2A-2om
0.600
w
1.6:14
3125
31
14
500
1217
"_ 0
0
0
0
P
_
12C-0sw
_
0.096
-
258
1.37
0
0
0
0
0
_
0
0
0
Ln
11DO
l6X19-0md
0.390
n
10.49
11.39
.50
0
- 150
0
- `150
0
228
0
�
'0
0
0
5
_ 0
_ 0
83
-C
F
_
22A-tpl _ -
_
_
_- 0.989
-
- 26.60
.0.00
- 150
,
_ 18
_ 479
_
_ _ _
- 5
- 5
0
_
- _, 0
0
61
c) AED excursion
1463
-3
Envelope loss/gain
2158
2615
84
79
12
a) Infiltration
227
71
0
0
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants Q 230
0
0
0
0
Appliances/other
0
0
Subtotal (lines 6 to 13)
2385
2685
84
79
Less external load
0
0
0
0
Less transfer
0
a
0
0
Redistribution
0
0
0
0
14
Subtotal
2385
2685
e4
79
15
Duct loads
14%
8%
333
220
14%
8%
12
7
Told room load
2719
2906
95
Air required (cfm)
138
11
f�GsGA � wrlghtsoft- Right -Suite® Universal 201515.0.16 RSUD8057 Ot'YOat 18 1 :04:59
9 7
... t28TarponFlalsAGR\Lot28TarponFlatsModelAGRWrup Calc=MJB House faces: W -
Duct System Summary Job: Lot 28Tarpon Flats Mod
...
wrlghtsoft° y ry Date: 01.18.14
Entire House By: ER
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fas 407-333-3853 Web: WWW.DEL-AIR.COM
Project Information
For: Phoenix Realty Homes Inc, Lot 28 Tarpon Flats Model A GRW
3922 Duneside Drive, Fort Pierce, FL
External static pressure
Pressurelosses
Available static pressure
Supply / return available pressure
Lowest friction rate
Actual airflow
Total effective length (TEL)
Heating
0.30
in H2O
0.06
in H2O
0.24
in H2O
0.120 / 0.120
in H2O
0.134
in/100ft
1583
cfm
Cooling
0.30
in H2O
0.06
in H2O
0.24
in H2O
0.120 / 0.120
in H2O
0.134
in/100ft
1583
cfm
179 ft
Supply Branch Detail Table
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FIR
Diam
(in)
H x W
(in)
Duct
Matl
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
Bd=2
h 3835
195
161
0.157
8.0
Ox0
VIFx
53.0
100.0
st2
13don3
In 3923
199
152
0.216
8.0
Ox0
VIFx
25.9
85.0
stl
Bdnn 4/Den
h 2719
138
132
0.166
7.0
OxO
VIFX
44.9
100.0
st2
Bthrm2
h 1252
64
33
0.213
5.0
OxO
VIFx
27.7
85.0,
stl
Bthrm3
h 95
5
4
0.172
4.0
OxO
VIFx
39.4
100.0
st2
Great
c 3457
131
157
0.183
7.0
OxO
VIFx
31.1
100.0
st2
Great -A
c 3457
131
157
0.176
8.0
OxO
VIFx
36.0
100.0
st2
Mahan
c 2486
30
113
0.232
6.0
OXO
VIFX
18.5
85.0
stl
Mstr Bdnn'
c 3614
160
164
0.135
8.0
OXO
VIFx
63.1
115.0
st3
Mstr Bdrm-A
c 3614
160
164
0.134
8.0
OXO
VIFX
63.7
115.0
st3
Mstr Bthnn
In 2034
103
56
0.142
6.0
Ox0
VIFX
53.5
115.0
st3
Mstr WC
h 893
45
23
0.138
4.0
Ox0
VIFX
58.5
115.0
st3
Maur WIC
h 120
6
5
0.142
4.0
OXO
VIFX
53.9
115.0
st3
Nook
c 3557
149
161
0.214
7.0
Ox0
VIFX
27.2
85.0
stl
Utility
c 2273
68
103
0.218
6.0
Ox0
VIFX
25.2
85.0
stl
Trunk
Htg
Clg
Design
Veloc
Diam
H x W
Duct
Name
Type
(cfm)
(cfm)
FIR
(fpm)
(in)
(in)
Material
Trunk
st3
Peak AVF
475
411
0.134
604
12.0
0 x 0
VinlFlx
st2
st2
Peak AVF
1073
1021
0.134
607
18.0
0 x 0
VinlFlx
stl
stl
Peak AVF
1583
1583
0.134
726
20.0
0 x 0
VinlFlx
WiKjht:SOfC Right -suite® Universal 201515.0.18 RSU08057
ACCA... t28TarponFlatsAGR\Lol28TarponFlatsModelAGRWmp Cafe =MJB House faces: W
Page 1
Name
Grill
Size (in)
Htg
(cfm)
Clg
(cfm)
TEL
(ft)
Design
FIR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Stud/Joist
Opening (in)
Duct
Matl
Trunk
rb1
Ox0
1583
1583
0
0
0
0
Ox 0
VIFx
+ wrightsoft• Right -Suite® Universal 201515.0.18 RSU08057
ACCA ... l28TarponFlalsAGR\Lot28TarponFlatsModeIAGRW.mp Calc=MJ8 House faces: W
Page 2
FORM R405-2014
Florida Department of Business and Professional Regulations
Residential Whole Building Performance and Prescriptive Methods
ADDRESS: 3922 Duneside Drive Permit Number: 1511-0125
Fort Pierce, FL ,
MANDATORY REQUIREMENTS see individual code sections for full details.
? 401.3 Energy Performance Level (EPL) display card (Mandatory). The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
[Section 553.9085, Florida Statues] requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate compliance for the building. A copy of the EPL display card can be found in Appendix C.
? R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.1 through R402.4.4.
7 R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The
sealing methods between dissimilar materials shall allow for differential expansion and contraction.
• R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in
accordance with the manufacturer's instructions and the criteria listed in Table 402.4.1.1, as applicable to the method of construction.
Where required by the code official, an approved third party shall inspect all components and verify compliance.
• R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air
changes per hour in Climate Zones 1 and 2, and 3 air changes per hour in Climate Zones 3 through 8. Testing shall be conducted with
a blower door at a pressure of 0.2 inches w.g. (50 Pascals). Where required by the code official, testing shall be conducted by an
approved third party. A written report of the results of the test shall be signed by the party conducting the lest and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures;
2. Dampers including exhaust, intake, makeup air, backdraff and Flue dampers shall be closed, but not sealed beyond intended
infiltration control measures;
3. Interior doors, if installed at the time of the test, shall be open;
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed;
5. Healing and cooling systems, if installed at the time of the test, shall be turned off; and
6. Supply and return registers, if installed at the time of the lest, shall be fully open.
R402.4.2 Fireplaces. New wood-buming fireplaces shall have tight -fitting flue dampers and outdoor combustion air.
? R402.4.3 Fenestration air IeakageWindows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm
per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or
AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
? R402.4.4 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage '-
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E 283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
? R403.1.1 Thermostat provision (Mandatory). Al least one thermostat shall be provided for each separate heating and cooling system.
? R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the healing load.
? R403.2.2 Sealing (Mandatory)NJl ducts, air handlers, and filter boxes and building cavities that form the primary air containment
passageways for air distribution systems shall be considered ducts and plenum chambers, shall be constructed and sealed in accordance
with Section C403.2.7.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria by post -construction
or rough -in testing below.
Duct tightness.shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section
553.99, Florida Statutes, or as authorized by Florida Statutes, to be "substantially leak free" by either of the following:
1. Post -construction lest: Total leakage shall be less than or equal to 4 cfm (113 Umin) per 100 square feel (9.29 m2) of conditioned floor area
when tested at a pressure differential of 0.1 inches w.g. (25 Pa) across the entire system, including the manufacturers air handler enclosure. All
register boots shall be taped or otherwise sealed during the test.
2. Rough -in test: Total leakage shall be less than or equal to 4 cfm (113 Umin) per 100 square feet (9.29 m2) of conditioned floor area when tested
at a pressure differential of 0.1 inches w.g. (25Pa) across the system, including the manufacturers air handler enclosure. All registers shall be
taped or otherwisesealed during the test. If the air handler is not installed at the time of the test, total leakage shall be less than or equal to 3 cfm
(85 Umin) per 100 square feet (9.29 m2) of conditioned floor area.
Exceptions: _ ++
1. The total leakage test is not required for ducts and air handlers located entirely within the building envelope.
2. Duct testing is not mandatory for buildings complying by Section R405 of this code.
12118/2015 3:04 PM EnergyGaugeO USA - FlaRes2014 - Section R405.4.1 Con age 1 of 3
FORM R405-2014
MANDATORY REQUIREMENTS - (Continued)
? R403.2.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the
design air flow rate when tested in accordance with ASHRAE 193.
? R403.2.3 Building Cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
? R403.3 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105'F (41°C)
or below 55•F (13°C) shall be insulated to a minimum of R-3.,
? R403.3.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused
by sunlight, moisture, equipment maintenance, and wind, and shall provide shielding from solar radiation that can cause degradation of the
material. Adhesive tape shall not be permitted.
R403.4.1 Circulating hot water systems (Mandatory). Circulating hot water systems shall be provided with an automatic or readily
accessible manual switch that can turn off the hot-water circulating pump when the system Is not in use.
R403.4.3 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heal traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3'/: Inches (89 mm) in the hot water distribution line and mid water line located as close as possible
to the storage tank.
R403.4.4 Water heater efficiencies (Mandatory). Water heater efficiencies
7 R403.4.4.1 Storage water heater temperature controls
• R403.4.4.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls
capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum
temperature setting range shall be from 100•F to 140•F (38'C to 60°C).
• R403.4.4.1.2 Shutdown. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied
to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s)
of combustion types of service water healing systems to be turned off.
7 R403.4.4.2 Water heating equipment. Water heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2. in Chapter 4 of the Florida Building'Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide healing functions as part of a combination system shall satisfy all stated requirements for the appropriate water
heating category. Solar water heaters shall met the criteria Section R403.4.4.2.1.
4 R403.4.4.2.1 Solar water heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol, Collectors in installed solar water
heating systems should meet the following criteria:
1. Be installed with a till angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
7 R403.5 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation.
Outdoor air intakes and exhausts shall have automatic or gravity, dampers that close when the ventilation system Is not operating.
? R403.5.1 Whole -house mechanical ventilation system fan efficacy. Mechanical ventilation system fans shall meet the
efficacy requirements of Table R403.5.1.
Exception: Where mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be powered by an
electronically commutated motor.
? R403.5.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical
ventilation shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62, Ventilation for Acceptable Indoor Air Quality,
shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioned system make air shall be provided to conditioned space from attics, crawlspaces, attached closed
garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed spaces(s), then the walls of the space(s) from which air is drawn shall be insulated to a
minimum of R-11 and the ceiling shall be insulated to a minimum or R-19, space permitting, or R-10 otherwise.
R403.6 Heating and cooling equipment (Mandatory). The following sections are mandatory for cooling and heating equipment.
R403.6.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with ACCA Manual J or other approved healing and cooling calculation methodologies,
` based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and
indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1. This code does not allow designer safety factors, provisions for future expansion or other factors.
which affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanicalg A?
such as standard kitchen and bathroom exhaust systems.
• R403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that
calculated total load, but not more than 1.15 times greater than the total load calculated accorc
Section 403.6, or the closest available size provided by the manufacturer's product lines. The r
equipment shall not be less than the calculated latent load.
1211812015 3:04 PM EnergyGauge® USA - FlaRes2014 - Section R405.4.1 Cam Page 2 of 3
FORM R405-2014
MANDATORY REQUIREMENTS - (Continued)
? - R403.6.1.1 Cooling equipment capacity. (continued) The published value for AHRI total capacity is a nominal, rating -test value and
shall not be used for equipment sizing. Manufacture's expanded performance data shall be used to select cooling -only equipment. This
selection shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry bulb temperature for the
load calculation (or entering water temperature for water -source equipment), the blower cfm provided by the expanded performance data,
the design value for entering wet bulb temperature and the design value for entering dry bulb temperature.
Design values for entering wet bulb and dry bulb temperature shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multi -family residential equipment sizing may be selected so that its cooling rapacity is less than the
calculated total sensible load but not less than 60 percent of that load.
2. When signed and sealed by a Florida -registered engineer, in attached single- and multi -family units, the rapacity of
equipment may be sized in accordance with good design practice.
? R403.6.1.2 Heating equipment capacity
R403.6.1.2.1 Heat pumps. Heat pumps sizing shall be based on the cooling requirements as calculated according to Section
R403.6.1.1 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load.
R403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.6.1.
R403.6.1.2.3 Fossil fuel heating equipment. The rapacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.6.1.
? R403.6.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipmentcapacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.7 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
C403 and C404 of the Commercial Provisions in lieu of Section R403.
'! R403.8 Snow melt system controls (Mandatory). Snow and ice -melting systems, supplied through energy service to the building, shall
include automatic controls capable of shutting off the system when the pavement temperature is above 55°F, and no precipitation is falling
and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40'F.
? R403.9 Swimming pools, Inground spas and portable spas (Mandatory). The energy requirements for residential pools and
inground spas shall be as specified in Sections R403.9.1 through R403.9.3 and in accordance with ANSI/APSP-15. The energy
requirements for portable spas shall be in accordance with ANSI/APSP-14.
? R403.9.1 Pool and spa heaters. All pool healers shall be equipped with a readily accessible on -off switch that is mounted
outside the healer to allow shutting off the heater without adjusting the thermostat. setting.
R403.9.1.1 Gas and oil -fired pool and spa heaters. All gas- and oil -fired pool and space healers shall have a minimum
thermal efficiency of 82 percent for heaters manufactured on or after April 16, 2013 when tested in accordance with ANSI Z 21.56.
Pool heaters fired by natural gas or LP gas shall not have continuously burning pilot lights.
R403.9.1.2 Heat pump pool heaters. Heat pump pool healers shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A lest report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heal pumps are not required to meet this standard.
? R403.9.2 Time switches. Time switches or other control method that can automatically turn off and an heaters and pumps according to a
preset schedule shall be installed on all heaters and pumps. Healers, pumps and motors that have built in timers shall be deemed in
compliance with this equipment.
Exceptions:
• 1 Where public health standards require 24-hour pump operations.
2. Where pumps are required to operate solar- and waste -heat -recovery pool healing systems.
3. Where pumps are powered exclusively from on -site renewable generation.
? R403.9.3 Covers. Heated swimming pools and inground permanently installed spas shall be equipped with a vapor -retardant cover on or
at the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Outdoor pools deriving over 70 percent of the energy for heating from site -recovered energy, such as a heat pump or
solar energy source computed over an operating season.
? RR404.1 Lighting equipment (Mandatory). A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be
high -efficacy lamps or a minimum of 75 percent of permanently installed lighting fixtures shall contain only high efficacy lamps.
Exception: Low -voltage lighting shall not be required to utilize high -efficacy lamps.
? R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuousX
i 1
? R405.2 Performance ONLY. All ducts not entirely inside the building thermal envelope shall be insulated o of 6.
? R405.2.1 Performance ONLY. Ceilings shall have minimum insulation of R-19. Where single ass +b o po d _: n beam type or
concrete deck roofs do not have sufficent space, R-10 is allowed,
12/18/2015 3:04 PM EnergyGauge® USA - FlaRes2014 - Section R405.4.1 Com 0 D `Page 3 of 3
FORM R405-2014
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Lot28TarponFlalsModelAGRW Builder Name: Phoenix Realty Homes Inc
Street: 3922 Duneside Drive Permit Office:
City, State, Zip: Fort Pierce , FL , Permit Number: 1511-0125
Owner: Jurisdiction:
Design Location: FL, Fort Pierce
COMPONENT
CRITERIA
CHECK
Air barrier and thermal barrier
A continuous air barrier shall be installed in the building envelope.
Exterior thermal envelope contains a continuous barrier.
Breaks or joints in the air barrier shall be sealed.
Air -permeable insulation shall not be used as a sealing material.
Ceiling/aftic
The air barrier in any dropped ceiling/soffit shall be aligned with the
insulation and any gaps in the air barrier shall be sealed.
Access openings, drop down stairs or knee wall doors to unconditioned
attic spaces shall be sealed.
-
Corners and headers shall be insulated and the junction of the foundation
Walls
and sill plate shall be sealed.
The junction of the top plate and the top or exterior walls shall be sealed.
Exterior thermal envelope insulation for framed walls shall be installed in
substantial contact and continuous alignment with the air barrier.
Knee walls shall be sealed.
Windows, skylights and doors
The space between window/doorjambs and framing and skylights and
framing shall be sealed.
Rim joists
Rim joists are insulated and include an air barrier.
Floorsf (including above -garage
Insulation shall be installed to maintain permanent contact with underside
and cantilevered floors)
of subfloor decking.
The air barrier shall be installed at any exposed edge of insulation.
Crawl space walls
Where provided in lieu of floor insulation, insulation shall be permanently
attached to the crawlspace walls.
Exposed earth in unvented crawl spaces shall be covered with a Class I
vapor retarder with overlapping joints taped.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shaft openings to exterior or
unconditioned space shall be sealed.
Narrow cavities
Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled
by insulation that on installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spaces.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope shall be
air tight, IC rated, and sealed to the drywall.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring and plumbing in
exterior walls, or insulation that on installation readily conforms to available
space shall extend behind piping and wiring.
Shower/tub on exterior wall
Exterior walls adjacent to showers and tubs shall be insulated and the air
barrier installed separating them from the showers and tubs.
Elect Iical/phone box on
The air barrier shall be installed behind electrical or communication boxes or
air sealed boxes shall be installed.
HVAC register boots
HVAC register boots that penetrate building thermal envelope shall be
sealed to the sub -Floor or drywall.
Fireplace
An air barrier shall be installed on fireplace walls. Fireplaces shall h ve
gasketed doors
12/18/2015 3:04 PM EnergyGauge® USA - FlaRes2014 Section R405.4.1 Compliant Software wg,
1 of 1
FORM R405-2014
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2014 Florida Building Code, Energy Conservation via the
residential Simulated Performance method shall include
❑ This checklist
❑ A Form R405 report that documents that the Proposed Design complies with Section
R405.3 of the Florida Energy Code. This form shall include a summary page
indicating home address, a -ratio and the pass or fail status along with summary
areas and types of components, whether the home was simulated as a worst -case
orientation, name and version of the compliance software tool, name of individual
completing the compliance report (f page) and an input summary checklist that can
be used for field verification (usually 4 pages/may be greater).
❑ Energy Performance Level (EPL) Display Card (one page)
i ❑ Mandatory Requirements(three pages)
Required prior to CO for the Performance Method.,
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 -
one page)
❑ 'A completed Envelope Leakage Test Report(usually one page)
❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed
Form R405 Duct Leakage Test Report (usually one page)
11/3/2015 5:47:05 PM EnergyGauge® - USRFSB v4.0
FORM R405-2014
FLORIDA ENERGY EFFICIENCY CODE
FOR BUILDING CONSTRUCTION
Form R405 Duct Leakage Test Report
Performance Method
Project Name:
Lot28TarponFlatsModelAGRW
Builder Name: Phoenix Realty Homes Inc
Street:
3922 Duneside Drive
Permit Office:
City, Stale, Zip:
Fort Pierce , FL ,
Permit Number: 1511-0125
Design Location:
FL, Fort Pierce
Jurisdiction:
Duct Test Time: Post Construction
Duct Leakage Test Results
CFM25 Duct Leakage Test Values
Line
System
Outside Duct Leakage
1
System 1
cfm25(Out)
2
System 2
cfm25(Out)
3
System 3
cfm25(Out)
4
System 4
cfm25(Out)
5
Total House
Sum lines 1-4
Duct System
Divide by
Leakage
(Total Conditioned Floor Area)
_ (Qn,Out)
I hereby certify that the above duct testing
performance results demonstrate compliance
with the Florida Energy Code requirements in
accordance with Section R403.2.2.
SIGNATURE:
PRINTED NAME:
DATE:
Duct tightness shall be verified by
testing to Section 803 of the RESNET
Standards by an energy rater certified in
accordance with Section 553.99,
Florida Statutes.
BUILDING OFFICIAL:
DATE:
12/18/2015 3:04 PM EnergyGauge® USA - FlaRes2014 - Section R405.4.1 Compliant S PEOP
FIB