HomeMy WebLinkAboutMANUAL S COMPLIANCE REPORTManual S Compliance Report Job: Lot 28 Tarpon Flats Mod... 1- wrightsoW p p Date: 01.18.14 Entire House sy: - ER DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax 407-333.3853 Web: W AMDEL-AIR.COM For: Phoenix Realty Homes Inc, Lot 28 Tarpon Flats Model A GRW 3922 Duneside Drive, Fort Pierce, FL Cooling Equipment Design Conditions design DB: 90.5°F Sensible gain: 34952 Btuh Outdoor design WB: 77.7°F Latent gain: 5346 Btuh Indoor design DB: 75.0°F Total gain: 40299 Btuh Indoor RH: 50% Estimated airflow: 1583 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: SpIitASHP Manufacturer: Carrier Model: 25HBC548A**30+FX4DN(B,F)049L Actual airflow: 1583 cfm Sensible capacity: 36705 Btuh 105% of load Latent capacity: 9045 Btuh. 169% of load Total capacity: 45750 Btuh 114% of load SHR: 80% Heating Equipment Design Conditions Outdoor, design DB: 43.1OF Heat loss: 31193 Btuh Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: SpIitASHP Manufacturer: Carrier Model: 25HBC548A**30+FX4DN(B,F)049L Actual airflow: 1583 cfm Output capacity: 47500 Btuh 152% of load Supplemental heat required: 0 Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1583 cfm Output capacity: 0 kW 0% of load Temp. rise: 0 OF The above equipment was selected in accordance with ACCA Manual S. ti. +Wrlghts0ft Right-Suite®Univemal201515.0.1BRSU08057 ACC%...t28TarponFlatsAGRILot28TarponFlatsModeIAGRWmp Calc=MJ8 Housefaces: W Entering coil DB: 75.2°F Entering coil WB: 63.1°F Entering coil DB: 69.8°F Capacity balance: 34 OF Economic balance: -99 OF 2WS-Dec-18 15:04:59 Page 1 Component Constructions Job: Lot 28 Tarpon Flats Mod -f}�- ... wrightsoft' p Date: 01.18.14 Entire House By: ER DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Farc 407-3333853 Web: W W W.DEL-AIR.COM eLroject intormation For: Phoenix Realty Homes Inc, Lot 28 Tarpon Flats Model A GRW 3922'Duneside Drive, Fort Pierce, FL Location: Vero Beach Municipal AP, FL, US Elevation: 30 ft Latitude: 28"N Outdoor: Heating Dry bulb ("F) 43 Daily range ('F) Wet bulb (°F) - Wind speed (mph) 15.0 Indoor temperature (°F) Design TD ("F) Relative humidity (%) CoolingMoisture difference (gr1lb) 91 Infiltration: 16 (L ) Method 78 Construction quality 7.5 Fireplaces Heating Cooling 70 75 27 16 . 30 50 -0.2 - 58.7 Simplified Semi -tight 0 Construction descriptions or Area u-value Insul R Htg HTM - Loss Cig HTM Gain R BWhM'--T ff-'F0uh Buh4P Buh ftw BWb Walls. 13A-2ocs: 13A-2ocs 13A-2ocs 2: 13A-2ocs 2 13A-2ocs 1: 13A-2ocs 1 13A-2ocs 3:13A-2ocs 3 c. Partitions 12C-Osw: 12C-Osw Windows 2A-2om: 2 glazing, clr low-e outr, air gas, m8 no brk 6m mat, clr innr, 1/4" gap, 1/8" lhk; NFRC rated (SHGC=0.32): foreground = new concrete (0.32); 2 ft overhang (5 ft window ht, 0.38 ft sep.); 6.67 It head ht 2A-2om: 2 glazing, clr low-e outr, air gas, mtl no brk frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); foreground = new concrete (0.32): 2 ft overhang (6.33 It window ht, 0.38 It sep.); 6.67 ft head ht 2A-2omd: 2 glazing, clr ow-e outr, air gas, mtl no brk firm mat, clr innr, 1/4" gap, 1/8" Ink: NFRC rated (SHGC=0.32); foreground = new concrete (0.32); 13 It overhang (8 ft window ht, 0.38 It sep.); 6,67 ft head ht f n 273 0.258 4.1 6.94 1892 5.19 1413 e 145 0.258 4.1 6.94 1003 5.19 750 s 232 0.258 4.1 6.94 1607 5.19 1201 w 133 0.258 4.1 6.94 925 5.19 691 all 782 0.258 4.1 6.94 5427 5.19 4055 n 145 0.268 4.1 6.94 1004 5.19 750 e 84 0.258 4.1 6.94 582 5.19 435 s 78 0.258 4.1 6.94 541 5.19 404 all 306 0.258 4.1 6.94 2127 5.19 1589 e 72 0.258 4.1 6.94 499 5.19 - 373 w 26 0.258 4.1 6.94 180 5.19 135 all 98 0.268 4.1 6.94 680 5.19 508 s 56 0.258 4.1 6.94 389 5.19 290 w 81 0.258 4.1 6.94 562 5.19 420 all 137 0.258 4.1 6.94 950 5.19 710 315 0.096 13.0 2.58 812 1.37 432 n 13 0.600 0 16.1 215 16.0 213 n 27 0.600 0 16.1 430 16.0 427 all 40 0.600 0 16.1 646 16.0 640 e 51 0.600 0 16.1 818 45.2 2290 e 38 0.600 0 16.1 613 45.2 1717 e 34 0.600 0 16.1 545 45.2 1526 e 32 0.600 0 16.1 511 45.2 1431 all 154 0.600 0 16.1 2487 45.2 6964 e 96 MOD 0 16.1 1549 26.0 2497 wrightsoft' Right -Suite® universal 201515.0.18 RSU08057 ACCIN... t28TarponFlatsAGR\Lot28TarponFlatsModelAGRWrup Calc='MJ8 House faces: W ' 2A-2om: 2 glazing, clr low-e outr, air gas, mil no brk frm mat, clr innr, s 6 0.600 0 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); foreground = new concrete (0.32); 2 ft overhang (3.17 ft window ht, 0.38 It sep.); 6.67 It head ht IOC-m: 2 clr low-e outr, air m8 no brk frm mat, clr innr, s 20 0.600 0 glazing, gas, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); foreground = new concrete (0.32); 18.67 ft overhang (8 ft window ht, 0.47 It sep.); 6.67 It head ht 2A-2om: 2 glazing, clr low-e outr, air gas, mll no brk firm mat, clr innr, w 8 0.600 0 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); foreground = new concrete (0.32); 2 ft overhang (4.17 ft window ht, 0.38 ft sep.); 6.67 It head ht 2A-2om: 2 glazing, clr low-e outr, air gas, mtl no brk frm mat, clr innr, w 31 0.600 0 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); foreground = new concrete (0.32); 2 ft overhang (5.17 It window ht, 0.38 ft sep.); 6.67 ft head ht 1OC-m: 2 glazing, clr low-e outr, air gas, frill no brk frm mat, clr innr, w 24 0.600 0 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); foreground = new , concrete (0.32); 9.17 ft overhang (8 ft window ht, 0.7 it sep.); 6.67 It head ht 2B-2fm: 2 glazing, clr low-e outr, air gas, mtl no brk frm mat, clr innr, w 11 0.600 0 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32); foreground = new concrete (0.32); 9.17 ft overhang (8 ft window ht, 0.17 ft sep.); 6.67 It head ht 2A-2om: 2 glazing, clr low-e outr, air gas, frill no brk frm mat, clr innr, w 31 0.600 0 1/4" gap, 1/8" lhk; NFRC rated (SHGC=0.32); foreground = new , concrete (0.32); 3 It overhang (5.17 ft window ht, 0.17 ft sep.); 6.67 ft head ht Doors 11 D0: Door, wd sc type n 21 0.390 0 Ceilings 16X19-Omd: Attic ceiling, mil roof mat, r-20 roof! ns, 1/2" gypsum board 1976 0.408 19.0 int fnsh f Floors ' 22A-tpl; Bg floor, light dry soil, on grade depth 187 , 0.989 0 F wrightsoft' Right-Suileg Universal 201516.0.18 RSU08057 ACCK... t28TarponFlatsAGR\Lot28TarponFlatsMcdelAGRWrup Cale -MJ8 House faces: W 16.1 102 26.0 165 16.1 323 21.2 424 16.1 135 42.7 356 16.1 500 44.1 1367 16.1 387 23.5 564 16.1 172 27.7 295 16.1 500 39.3 1217 10.5 224 11.4 243 1.52 3010 1.50 2964 26.6 4975 0 0 2 ec Prot Summary Job: Lot 28 Tarpon Flats Mod ft... Wrightso' ry Date: 01.18.14 Entire House By: ER DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY. SANFORD, FL 32771 Phone: 407-333-2665 Fax 407-333.3853 Web: WWW.DEL-AIR.COM For: Phoenix Realty Homes Inc, Lot 28 Tarpon Flats Model A GRW 3922 Duneside Drive, Fort Pierce, FL Notes: LS by CA on 11.03.2015,Rvsd 12.18.2015 RH Weather: Vero Beach Municipal AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 43 OF Outside db 91 OF Inside db 70 OF Inside db 75 OF Design TD 27 OF Design TD 16 OF Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 27368 Btuh Structure 32303 Btuh Ducts 3825 Btuh Ducts 2649 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 31193 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Infiltration Equipment sensible load 34952 Btuh MethodSimplified Latent Cooling Equipment Load Sizing Construction quality Semi -tight • Fireplaces 0 Structure 2715 Btuh Ducts 2631 Btuh Heatingg Coolingg Central vent (0 cfm) 0 Btuh Area (ft21976 1976 Equipment latent load 5346 Btuh Volume (Its) 18436 18436 Air changes/hour 0.26 0.14 Equipment total load 40299 Btuh Equiv. AVF (cfm) 80 43 Req. total capacity at 0.75 SHR 3.9 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER AIR CONDITIONING Trade CARRIER AIR CONDITIONING Model 25HBC548A**30 Cond 25HBC548A**30 AHRI ref 6936854 Coil FX4DN(B,F)049L AHRI ref 6936854 Efficiency 8.5 HSPF Efficiency 12.5 EER, 15 SEER Heating input Sensible cooling 35625 Btuh Heating output 45500 Btuh @ 47*F Latent cooling 11875 Btuh Temperature rise 26 OF Total cooling 47500 Btuh Actual air flow 1583 cfm Actual air flow 1583 cfm Air flow factor 0.051 cfm/Btuh Air flow factor 0.045 cfm/Btuh Static pressure 0.30 in H2O Static pressure 0.30 in H2O Space thermostat Load sensible heat ratio 0.87 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed... ,; AR04 vvright50fV Right Universal 201515.0.18 RSUDS057 '6 7nt ^ -suite® Page 1 8 /R..Cf.... t28TarponFlatsAGR\Lot28TarponFlaisModeIAGRW.rup Cale = MJS House (aces: W 5 wrightsoft` Right-J® Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO WAY, SANFORD. FL 32771 Phone: 407-333-2665 Fax 407-333-3853 Web: WWW.DEL-AIR.COM Job: Lot 28 Tarpon Flats Model A... Date: 01.18.14 By: ER 1 Room name Entire House Mstr BdOn 2 Exposed wall 187.0 ft 42.0 ft 3 Roam height 9.3 it 9.3 it heat/cool 4 Room dimensions 16.0 x 15.5 it 5 Room arm 1976.0 ft' 248.0 ft' Ty Construction U-value Or HTM Area (ftl Load Area (ft' Load number (Btuh/ftMF) (Btut✓ft0 cr perimeter (it) (Btuh) or perimeter (it) (Btuh) Heat Coal Gross NIP/S Heat Cod Gross NIP/S Heat Cod 6 W 13A-25H - - - 2A.2om - 0.258 0.600 n n 6,94 16.14 5.19 - 16.01 313 13 273 0 1892' 215 - -1413 213 '- --0 0 - 0 0 --- ---'0 0 - - 0 0 2A 2cm 0.600 n 16.14 16.01 27 '0 430 427' 0 0 0 0 __ _- 2 -- 0.258 Ti --'6.94 5.19 _ 145 145 _ _ _ - 750 _ w 145 __ 1004 - 750 11 W _13A-2ocs 13A 2acs _ _ 0.258 _ -6 _-_-_ 6 94 _ 5.19 - 233 '145' _1004 1818 -` 2290 0 0 -- '-0 ' ` - 0 IIW--,�, 2A2cm 0.600 a 45.19 45.19 51 38 10 8 613 1717. 1717 0 0 0 0 -0 0 '0 _ I�G W ---- rC ,,. I' -loos 1 - ' 2A-2o17d ______ 0.258 0,600 a e _1_6.14 6.94 1.6.14 _ 5.19 26.01 168 96 __ 72 96 _,613 499 1549 373 _ 0 0 _0 0 0 0 0 0 0 W- _ 13A 2ocs 2 '- _ 10.258 6_ ­6.94 _5.19 - 149 _ 84 _ 582 _ _2497 ' -435 149 84 582 --- -435 2om D.600 a 16.14 45.19 34 7 545 1528 -34 7 545 1526 EaW2A 2A20m 0.600 e,_ 1614 45.19 32 6_ 1431 32' 6 511 14.31 W _ 13A-2ocs 0.258 s _. 6.94 5.19 238 _. 232 -_.__:511 1607 1201 _ 0 _ 0 _ 0 _ 0 IF r 24-2om 0.600 s 16.14 26.01 6 6 102 0 0 0 0 W 13A-2bcs2'--- -7-0.258 's 694 `'5.19 -- '98'- - 78 _ _ 541 _ _165 404 -'98 _ 78 _ _. 541 -404 L_-_G. OCGm_ _ _ _.0.600 s 1814 _21.21 20 20, 323 20 20 W 13A-2acs 3 D2513 s 6.94 56 _ 56 _ 389 _424 290 - � 0 0 _ _ _323 0 _.424 0 _ IWI -� 13A tads- -"'0.258- w 6.94 _ _SAS 5.19 _ 173 133 _ 925 _ 691 --0 - _-0 -0 --.,._0 2A-tom' 0.600 w 16.14 42.66 8 3 135 356 0 0 0 0 I--G t-G 2A-tom, 0.600 44.09 31 8 500 '1367 , 0 0 - 0 0 W 13A-2ocs 1 ` - _ 0.258 _w w _16.14 6.94 _ 5.19 61 26 180 - -135 -- - 0 - 0 - - -0 '0 10C-m 0.600 w 16.14 23.50 24 - 21 387 554 0 0 0 0 2B-2fm 0.600 w 16.14 11 10 172 295 0 0 0 w -- --13A-2ocs 3� - - '0.258 _ w 6.94 _27.70 5.19 112 81 562 - -420 _ 0 _ 0 0 _0 .0 2A-2om - - - 0.600 w 16.14 39.25 �31 -_14 1217 0 0 0-- 0 P " 12C-Osw 0.096 - 2.58 - --1.37 336 315 __500 812 �_-432 - -0 0 0 _ 0 1160 0.390 n 10.49 11.39 21 21 224, 243 0 0 0 0 F_ -� 16X19-0nid, 0.408 - -'1 52 1.50 ' 1976 1976 3010 `2964 -248 248 378 372 6 _ 22A tpl - - - - - _ . - 0.989 _ . 26.60 _ _ - 0,00 _ 197.6 _ _ 187 - _ _ 4975 _ 0 248 _ _ 42 _ _ 1117 0 - 6 c) AED excursion 0 -257 Envelope loss/gain 25007 24991 5001 5085 12 a) Infiltration 2361 733 530 165 b) Room ventilation 1 0 0 0 0 13 Internal gains: Occupants @ 230 5 1150 1 230 Applianceslother we 1200 Subtotal (lines 6 to 13) 27368 32303 5531 6660 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 27360 32303 5531 6660 15 Duct loads 14% B% 3825 2649 14% 8% 773 548 Total mom lead 31183 34952 63041 7227 Air required (cfm) 1583 1583 1 1 320 27 . M -F]+ wrightsoftl Right-Sulte® Universal 2015 15.0.18 RSU08057 ...I28TarponFlatsAGR\Lol28TarponFlatsModeIAGRWmp Cale =MJ8 House faces: W Page 1 wrightsoft° Right-JO Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO'WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fa c 407-33MS53 Web: VWM.DEL-AIR.COM Job: Lot 28 Tarpon Flats Model A... Date: 01.18.14 By: ER 1 Room name Mstr WC Mstr WIC 2 Exposed wall 6.0 ft 0 ft '3 Room height 9.3 ft heat/cool 9.3 it heat/cool 4 Room dimensions 4.0 x 6.0 it 6.0 x 11.5 ft 5 Room area 24.0 ft' 69.0 it, Ty Constmction U-value Or HTM Area (fl0 Load Area (ft5 Load number (BtulJft? °F) (Stuh/ft5 or perimeter (it) (Btuh) or perimeter (ft) (Btuh) Heat Cod Gross N/P/S Heat Cod Gross N/P/S Heat Cod 6 IWI- _--- 13A-2663 - 2A-2om _ _ - 0.256 0.600 n: in - 6.94 16.14 -5.19 16.01 56 13 __ 43 '0 7296 215 . -„_221 213 __ : _ -0 0 `.0 0 .. - _- 0 0 0 - 0 I--v ' 2A-2om - 0.600 ---0.258 in 16,14 16.01 0 a' '0 0 0'_ 0 - 0 � 0 W- 13A-20cs 2 - - -�- n - - _ -6.94 5.19 -0 -- 0 _ - - -0 - - -- 0 _ - _ 0 _ 0 _ 0 _ 0 11 l{J - '13A-2a6s -. - -0.258 - -a-- 6.94 : '-5.19 .. -0 - 0'- '- - 0 - 0 - p " - -0 - - 0 0 2A-2om '0.600 a 16.14 45.19 .0 10 0 0 - 0 10 0 0 2A-2om a 16.14 45.19 '0 0 0 10 - 0 0 0 _' -" 0 . _ W L_ C ,__- _ 13A-2acs 1 2A-2omd _ _.0.600 _ 0.258 0.600 a 6.94 1_6.14 5.19 _ _ . _0 0 y __ 0 0 0 0 . . _ _ 0 0 - - _ 0 0 -_ _ _ --0 0 .. _ _ _0 0 _ - a 0 13A-2ocs 2.'-_, _ _-_0.258 _e a 6.94 _ _26.01 5.19 _. _0 _ -.._0 _ _ _-.0 _ _,_ _0 -. _ _. 0 _ _ _ _0 _ 0 ___._ -0 IWI --. 2A-2om '2A-20m 0.600 0.600 a a 1614 1614 45.19 0 0 0 0 0 0 0 0 0 0 0 0 0 0 - 0 -{ 0 I� I_G W 13A-2ocs _ _ _- _ _0.258 _._. s .. _ 6.94 _ _45:19 5.19 - _ _. __0 _ . , .0 .. _ _ _0 - _0 .. 0 _ _ _0 _ _ 0 _ 0 r 2A-20m 0.600 s 16,14 26.01 0 0 0 0 0 0 0 0 W LC. 13A-20cs 2' 10C-m - .0.258 0.600 s- :_a __ 6.84 16.14 .-. .. 5.19 21.21 _ -0 _0 ;0 0 _ -0 _. 0 0 _` _ a _.. __0, 0 ...0 -0 0 W _ 13A-2acs 3 0.258 s 6,94 5.19 0 _ _ 0 _ _0 0 - 0 _0 0 __- 0 __0 0 _ 0 IWI .. _-- -13A-2ccs - `. 2A-2om _ 0.256 a600 w w "6.94 16.14 ,- _5.19 42.66 '" ' "0 0 . _ _ _ -0 0 _ 0 0 _ _ -0 0 _ ..0 0 _. .0 0 0 0 0 0 2A-2om 0.600 w 16.14 44.09, 0'_ 0 �0 0 0 0 0 0 134-2ocs-1 -- - - - 0.258 -w - -�6.94 LL---5.19 - --0 0 _ -0 _ 0 0- 0 0 _ 0 1oGm 0.600 w 16.14 23.50 0 0 0 0 0 0 0 0 L�_GG 2B-2fm 0.600 w 16.14 27.70 0 0 0 0 0 0 0 0 W 13A-2ocs 3'- 0.258 w ----0.94 5.19 - 0 - 0 - -0 - 0 0 0 0 -- 0 LG 2A-2om 0.600 16:14 39.25 0 0 0 0 0 0 0 0 _ P 12C-0sw _ 0.096 _w - 2.58 1.37 _ 0 0 0 0 _ 0 0 _ 0 - 0 1-D 111150 0.390 n 10.49 11.39 0 0 0 0 0 0 0 0 C _(tf F f _ 16X19-0md ,22A 1pl - 0.408 .0,989 -1 52 2660 1.50 0.00 _ 24 . 24 24 6 „ _ 37 160 _ 36 _ _0 69 09 _69 a _ 105 - - 0 _ --104 _ 0 6 c)AED excursion -18 -4 Envelope loss/gain 707 452 105 100 12 a) Infillmtion 76 24 0 0 b) Raamventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 783 476 105 100 Less external load 0 0 ' 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 783 476 105 100 15 Duct loads 14% 8% 109 39 14% 8% 15 8 Total room load 893 515 120 Air required (cfm) 45 23 ': ' F" wrGghtsoft Right -Suite® Universal 2015 15.0.18 RSU08057 ... t28TarponFlatsAGRlLot28TarponFlatsMadelAGRWmp 'Calc=MJ8 House faces: W off 15:04:59 Page 2 +{f wrightsoft' Right-JO Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax 407-3333853 Web: WWW.DEL-AIR.COM Job: Lot 28 Tarpon Flats Model A... Data: 01.18.14 By: ER 1 Room name Mslr Blhnn Great 2 Exposed wall 12.5 ft 24.5 It 3 Room height 9.3 it heat/cool 9.3 ft hewcool 4 Room dimensions 1.0 x 157.5 it 1.0 x 503.5 ft 5 Room area 157.5 W 503.5 ft2 Ty Construction U-value Or HTM Area (ftT Load Area (ft0 Load number (Btuh/ft? °F) (BtuNft5 or pedmeler (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross NIP/S Heat Cool Gross NIP/S Heat Cool 6 IW - y--t; 134-2ors_.- " -'"'"0.258 n- - -6194 '5.19 117 '90--- -624' ` 467 0 - 0 "' - -0 - 0 2A tom 0.600 n 16.14 16.01 0 0' '0 0 0 0 0 0 I--G 2A-2om _ 0.600 n 16.14 1.6.01 _. 27 0 430 427 0 0 0 0 11 W WII _ 13A-2dcs'2 _� 13A 2ocs 2A tom . _.- 2A.2orn __ 0.258 0.258 0.600 0.600 _ _n_ e a e' _ 6.94 6 94 16.14 16.14 _ _ 5.19 5.19 45.19 '_ 45.19 `_.. _0 0 0 _.___0 0 -0 _-_ _0 ,--._,0 0 0 _0 __ �_ ..0 0 0 _ 0 ... 0 0' 0' _ 0 _ _ 0 0 0 _ _ 0 ..0 0 0 .__ __0 -._-- - 0 0 0 -.. 'G_- r W � � r r 734-26cs 7 - - - 2A-2omd - -0.258 0.600 a a 6.94 16.14 5.19 2.6.01 - - 0 0 � � - � '0 0 -- � -- 0 0 _ � 0 0 - - -168 96 __ 72 95 _ 499 1549 373 2497 IW _ ___._ _ 134-gods 2 �� 0.258 _ e : - -6.94 _ - 5.19 -_ _ _ ._0 _ __ _,.0 __ , .0 _ ._ ..0 -0 - 0 0 __ _._0 2A-2om ,. 0,600 6 - 1614 45.19, 0 '0 0 'o 0 0. 0 0 I--v L-G 7A-2om 0.600 e 45.19 0 '0 0 0 0 0. 0 0 w .__. -13A-2ocs ___. .._ _ -0.258 _ s _16.14 _ 6.94 _. 5.19 -_ .0 - '0 _ _ 0 _. 0 . _ 0 _ _� 0 __ _- 0 __ 0 LG_ 2A-tam 13A-2ocs2'__ 0.600 ___._0.258 s_ s 16.14 - 6.94 26.01 __..5.18' 0 .. - 0 0 _ 0. 0 0 0 � 0 0 _ _ -0_ 0 _. _0. 0 .0 0 _ _ _ .0 W L--G iOCm- ,0.600 s-..._j6.14- 21.21 0 0 0 _0 '.. 0 W '.. W'l ^ 13A-2ocs 3 _.. _ _ _ _ 2A-tom 0.258 �. __ _ --0.258 0.600 s _ - . w w 6.94 �6.94 '16.14 5.19 _. 5-19 4266 _.- 0 -- p' 0 _ _0 0 - 'p ,a -_ _.,0 0 'p 0 _ _0 _ 0 _ ---p 0 _. - 0 -----p- 0 _ _ 0 -..0 0 0 ..;.... 0� 0' 0 ---p 0 Ij �__ 2A-2am 0.258 - w 16.14 44.09 0 0 0 0 0 0 0 W 13A720cs-1---- --- 10C-m 0.258 0.600 w w 6.94 16.14 5.tg 23.50 � 0 0 - p 0 _ ..0 0 - _ 0 0 _ _61 24 - - - 26 6 21 _ 160 387 - � 135 564 2B-2fm - - -- 0.600 w 16.14 27.70 0 0 0 10 172 295 Y.. _ - 13A-2ocs 3 - 0.258 W - 6.94 5.19 - - 0 0 _ _0 0 _ 0 _ ..11 0 _- 0 - `0 0 2A-2om-_ , _ _ __ -_. 0.600 w 16,14 39.25 0 0 0 0 0 0 0 -r R �_D 12C-0sw 0.096 - - Z58 1.37 0 0 - 0 -_ 0 _0 0 0 - 0 0 100 _ 0.390 n 1049 11.39 0 0 0 0 0 0 0 0 C -, -. _ 16X19-onld _ _ - _ _ _ 0.408 - -_ 1:52 _ 1.50 158 158 _ 240 _ 236 _ 504 504 __ 767 7$0 F -'_ 22A tol _ - 0.989 - - 28.60 a.co 158 13 333 _ _0 _ _ - 504 - 25 _ - ' 652 6 c) AED excursion -44 -246 Envelope loss/gain 1627 1085 4207 4373 12 a) Infiltration 158 49 309 96 b) Room ventilation 0 0 0 0 13 1ntemal gains: Occupants @ 230 0 0 3 690 Appliances/other 0 1230 Subtotal (lines 6to 13) 1785 1135 4517 6389 Less external lead 0 0 0 0 Less transfer 0 0 0 0 Redistdtxdion 0 0 0 0 14 Subtotal 1785 1135 4517 6389 15 Duct loads 149/. 6% 249 93 14% 8% 631 5 Total room load 2034 1228 51,, "� Air required(cfm) 103 56 . - 21 ACCA to meet all ' r wrightNoft` Right -Suite® Universal 2015 15.0.18 RSU08057 '^4�"... t28TarponFlatsAGRlLot28TarponFlatsModeIAGRWmp Cale =We House faces: W M 15:04:59 Page 3 wrightsoft° Right-M Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax 407-333-3853 Web: WWW.DEL-AIR.COM Job: Lot 28 Tarpon Flats Model A... Date: 01.18.14 By: ER 1 Room name Neck Bdnn 3 2 Exposed wall 18.5 It 26.0 ft 3 Room height 9.3 It heat/cool 9.3 ft heat/cool 4 Room dimensions 1.0 x 125.5 ft 1.0 x 1920 R 5 Room area 126.5 W 192.0 W Ty Construction U-value Or HTM Area (ft� Load Area (ftj Load number (Btuh/ "F) (Btuwft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cad Gross NIP/S Heat Cod Gross N/P/S Heal Cool 6 IW 13A-2dcs-- . _ _.0.258 -"n _ '6.94 5.19 - _ 0 . 0' 0 __ _ 0 _ _ - 0 - 0 0 0 - I---t; 2A-2om 0.600 n 16.14 16.01 0 0 '.0 0 0 '0 0 0 L-C_ 2A-2om _ n 16.14 _16.01 0 0_ 0 ,. 0 0 0 0 0 W 13A-2ccs 2 13A-2acs- - _0.600 0.258 -0258 n - a-6.94 _ _ 6.94 _ 5.19 5.19 - 0 112 _ _ _ 0 61 _ - 0 425 0 318 0 121 _ _ 0 83 _ 0 578 0 432 2A-2om. -_2A-2om 0600 0.600 • e a 1614 -16.14 45.19 45.19 51 0 10 0- '818 0 2290 0 '0 38 0 8 0 613 0 1717 _ _ W 13A-2acs 7 _ _____ - - __-0.258 a ." -6.94 5.19_ - ___0 _ _ .0 __ __0 - _ -. _0 _ .0 . _ < 0 _ _ 0 _ 0 rr 2A-2omd 0.600 a W14 26.01 0 0 0 0 0 0 0 0 IW-_.. 13A-2acs 2.._ _ _ 0.258 :e 694 "5.19. .. __._0 __........0 a... ..a .. __.0 ..0 .0 _ 0 2A-2om -0.600 a 16.14 •45.19 0 0 0 0 0 0 �0 0 I--v I-_G 2A-2om 0.600 a A_614 0 0 0 0 0 0 0 _ 0 Wu _ _ 13A-2acs- - - - 0.258 -s 6.94 __45.19 - 5.19 61 _ _ 61 421 _ -314 121 _ " 121- _ 842 629 I� 2A-2om 13A-26cs 2 _ _ _ _ 10C-m 0.600 _ -0.258 0.600 s --a- _s 16.14 -6.94 16.14 26.01 .. 5.19 0 _ - - 0 0 0 0' _ 0 0 - - 0 0 0 _ '. 0 0 0 . 0 0 0 0 0 0 _ -_ " 0 0 0 . _ _ _0 W " .. LG- W _ _. 13A-2ocs 3 _. 0.258 . s 6.94 _21.21 5.19 0 - 0 0 _ 0 0 _ 0 _ _ 0 _0 0 W' - 13A-2ocs.. _. - .0.258 __ w 6.94 5.19 _ 0 0 ... 0 .... 0 ". 0 . - b - .. 0 0 �--G 2A-tan- 0.600 w 16.14 42.56 0 0 0 0. 0 0 0- 0 LG 0.600 w 16.14 0 0 0 0 0 0 0 W _ _2A-2om 13A-2ocs 1 - - - -'0.258 w _ 6.94 _4.4.99 5A9 _o 0 0 '0 -- -0 0 - 0 - -- -0 -0 0.600 w 16.14 23.50 0 0 0 0 0 0 0 0 LS10C-m 28-2fm 0.600 w 27.70 0 0 0 0 0 0 0 0 Y--a - _ 13A-2ccs3 0.258 w _ _16.14 6.94 5.19, 0. - 0 - 0 0,.,_.0 0. ._ _0 _ 0 2A-tan w; _ 16.14 39.25 0 0-_ 0 0 0 0 -_ 0 0 P _ _'._ 12C-0sw _ ._0.600 0.096 - 2.58 1.37 _ _. 0 0 0 0 _ 37 37 96 _ 51 1-D 11DO 0.390 n 10.49 1.1.39 0 0 0 0 0 0 0 0 C _ 16X19-0md ' 0.408 - 1.52 1.50 127 1W - - - 193 - - 192 _ 192 288 F 22A-tpl - _ _ - 0.989 _ 26.60 O.00 _ 127 _ 19 492 _1190 _ 01 _ _ 192 _ 26 _292 - 692 �_ 0 _ 6 c) AED excursion -127 -119 Envelope loss/gain 2349 2985 3114 2998 12 a) Infiltration 234 72 328 102 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 1 230 0 0 Appliances/other 0 0 Subtotal Qinas 6 to 13) 2583 3288 3442 3100 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2583 3288 3442 3100 15 Duct loads 14% B% 361 270 14% 8% 481 254 Total mom load 2943 3557 3923 Air required(cfm) 149 161 19 ' 1' wrightsof ' Right -Suite® Universal 2015 16.0.18 RSU08057 'CCk ... t28TarponFlatsAGRlLot28TarponFlalsMcdelAGRW mp Cale = We House faces: W 15:04:59 Page 4 wrightsoft' Right-JO Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 COD SOO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fac 407-333-3853 Web: WWW.DEL-AIR.COM Job: Lot 28 Tarpon Flats Model A... Date: 01.18.14 By: ER 1 Room name Bthnn 2 Kitchen 2 Exposed wall 6.0 ft 0 ft 3 Room height 9.3 ft heat/cool 9.3 ft heaVcool 4 Room dimensions 10.0 x 6.0 ft 11.0 x 14.5 ft 5 Room area 60.0 8' 159.5 ft. Ty Construction U-value Or HTM Area (fly Load Area (ftj Load number (BtutVft-F) (Btutdit� or perimeter (ft) (Btuh) or perimeter (it) (Bluh) Heat Cool Gross N/P/S Heal Cccl Gross NIP/S Heat Cool ' 6 IW _0 .. _ _0 __ _.0 ___ .0 .. ._;0 .._ 0 _ ___.0 .01 0_ 0 0 0 0 0 0 0 H--ra �Zom 0.258 nr i1619' -0 11 _- W W�`� 13A-266s2 - 13A-20cs .___._...._0.258 0.258 n '..e.__6.94-__5.19-.. _1694_ 6.94 5.19 - ._...'0__ - -0 Q__- - - - 0 :.a _ - - 0 ,.___0 0 _.__-0 0 __ _0.- '0 -.0 - 0 _,... 0 }L-(Ci 2A-2om 0.600 ' a 16.14 45.19 0 0 0 0 0 0 0 0 0.600 a 16.14 45.19 0 0 0 0 - 0 0 0 0 W. r _ZA-20M 13A-20cs 1_ _.---=0.258 2A-2cmd 0.600 a e 6.94 16.14 _ 5.19 26.01 _ _ _ 0 0 0- 0 -0 0 _ _ 0 0 0 0 0- 0 0- 0 0 0 iIW __ 13A-2acs2_ -0258 _ Ae __ -694 -539 ;_,_-0 .- _ 0_ __._0.-__. _0 __._0 __0 -... __0_ 0 I--v 2A2om 0.600- a 1814 '45.19 0 0 0 0 ':0 0 0 0 2A-2cm_ _0.600 e_ 4519 '0 0 0 0 00 __. W _. ._._.,.. 13A-2ocs 0.258 s __1614 6.94 5.19 _ 56 _ .0 50 _ 345 ._.__. 257 0 _0. 0 0 0 L-G 2A-2om s 16.14 6 102 165 ,_._ 0 0 0 W LG _ _ _ _ _ - 13A-2ccs 2 10C-m___.. _ _0.600 --0 258 0.600 - -a s _ _ 6.94 16.14__21:21 _,25.01 5.19 _6 '0 0 _ - '0 _ 0 _ _ 0 .0 _ _ - 0 --0_ _ -0 0 0 __ __ 0 _ _ 0 _ _ 0'- 0 _ 0 -0 W. 13A-2ocs 3 0.258 s 6.94 0 0 0 _. 0 0 0 0 W._. ._ H2A-2cm 13A-2dcs" ., _ _ `0,258 0.600 w' w 694 16.14 _ _5.19 519 4256 ._. - -0 0 . ;0 0 ._ 0 0 _.. _..0 0' .., _0 0 _0 0, 0 ._ '; 0'' 0' ' _ 0 0 7A-2om 0.600 -_w 44.09 0 0 0 0 0 '0 0' 0 W 13A-2ac5_i__ _0.258 w _1614 6.94 . _-5.19 .. ;_ __ 0 _ _ _0 0 _ 0 _ _ -0 _ 0 _ _ 0 __ . _- 0 10C-m 0.600 w 16.14 23.50 0 0 0 0 0 0 0 0 213-2fm 0.600 w 27.70 0 0 0 0 0 0 0 0 W 13A-2acs 3 _. 0.258 w _16.14 6.94 5.19 - �0 . 0 .. 0 -�0 0.0 0 - _0 L-C 2A-tom 0.600 w 16.14 39.25 0 0 0 0 -0 0 0 0 R t-D C 12C-Osw - 11DO 16X19-Omd - 0.096 0.390 - n 2.58 10.49 1.52 -- 1.37 11.39 1.50 _ _ 126 0 ,60 126 0 60 _ 325 0 91 173 0 90 107 0 160 _ 107 0 160 277 0 243 147 0 239 _ F ! 22A tpl. _ _0.408 _ 0 989-. _ 26.60 OAO_ 60 .6 _ -160 0 -160 0 _ - 0 0 6 c) AED excursion -26 -89 Envelope loss/gain 1023 659 520 298 12 a) Infiltration 76 24 0 0 b) Room ventilation 0 0 0 0 13 Inlerral gains: Occupants @ 230 0 0 0 0 Appliances/other 0 2000 Subtotal (lines 6 to 13) 1099 682 520 2298 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1099 682 520 2298 15 Duct loads 14% 8% 154 56 14% 8% 73 188 Total room load 1252 738 5903 (cfm) 64 33 30 AAirrequired Wright5of-V Right -Suite® Universal 201515.0.18 RSU08057 '`'��`...128TarponFlatsAGR\Lot28TarponFlatsModelAGRW.mp Cale = MJ8 House faces: W 15:04:59 Page 5 wrightsoft' Right-M Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phcne:407-333-2665 Fax 407-333-3853 Web: WWW.DEL-AIR.COM Job: Lot 28 Tarpon Flats Model A... Date: 01.18.14 By: ER 1 Room name Utility Bonn 2 2 Exposed wall 6.5 ft 27.0 ft 3 Room height 9.3 ft heat/cool 9.3 ft heat/cool 4 Room dimensions 1.0 x 52.5 It 1.0 x 178.5 ft 5 Room area 52.5 W 178.5 ft- Ty Construction U-value Or HTM Area (ft� Load Area Load number (BtulVWF) (BtutVft5 or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cod 6 ' 13A-2oos-. __-.__. _.. D.258 n '-6.94 '_--5:19 _ _ _0 _. 0�_ _ -a. _. "0-' -` -140 140 ' '' 971. _.- .._726 IW 2A-2cm 0.600 n 16.14 16.01 0 0 0 0 0 0 0 0 2A-2om 0.600 n 16.01 0 0 _0 ,0_ _0 -._. .__0 __G W 'W 11 _ . _, _: 13A-2ocs 2 13A-lobs- _ _ __ _ 0.258 0.258 _ n a _16.14 _ 6.94 6.94 _5.19 SAS _.._ 0 "' _0 _0 0 , .. 0 _0 0 0 _ ... 0 -_ _0 0 _ -,.0 _ 0 _ ..._0 __..._ 0 _.-- 0 0 -._ __, 0 2A-2om 0.600 a 16.14 45.19 0 0 0 a ::a a 0 0 '2A-2am 0.600 a 1614 45.19 0 0 0 0 0 0 0 '0 _ W ' '13A-2ocs 1 " - - - 0.258 a -6.94 _ _ 5.19 0 _ 0 0 - -0 - - 0 _ v. -'0 ---J--0 _ 0 r 2A-2cmd 0.600 a 16.14 26.01 0 0 0 0 0 0 0 a 13A-2ocs2 _'_ ._... 0.258 e- ----6.94 _ 5.19 __ .__.0 .0 .a _ _-.0 .... .._0 "'"' g ___ 0 _. �0 - IW,^- ?A-tom 0.600 a 16.14 -. 45.19 0 .0 a '0 0 0 0 0 L-G 2A-2om 0.600 45.19 0 0 0 0 0 0 0 0 w___ 13A-2ocs 0.250 _e s __16.14 6.94---5.19 _ ____. .0 _ _.0 - 0 - 0 _ 0 - .0 -__ _0 ._,_.. 0 _ _ _ _ _0.600 _ 5..19 _ 0 D a o 0 a _ 0 .•-0 0 0 _ _ - 0 0- __ 0 0,. 0 .._. 0 W�--_C. 0Cm_2 o258 s_. is14 _.. __-0- a 0= D 0 0_ o -__ o W __ W'- _ - 13A-2ocs 3 13A-26cs--- -- 2A-2om 0.258 '' - 0.258 0.600 s 'w-'6.94 w, 6.94 16A4 _ 5,19 5.19 42.66 0_ '' � 61 8 0 52 3 0 363 135 0 271 . 356 0 - 112.-- 0 0 - -81 ' 0 0 - _ 562' ' 0 0 420 0 G E2A-2om 0.600 w 16.14 44.09 0 0 0 0 31 8 500 1367 _ W 13A-2ocs 1 _ .-0.258 _ w . 6.94 __ -5.19 - 0 0 . 0 - _ .0 ._ 0 _ �0 _ _. -0 - 0 171 IOC-m 0.600 w 16.14 23.50 0 0 0 0 0 0 0 0 28-2rm 0.600 w 16A4 D 0 0 0 ' 0 0 0 0 �. _ _ _ _ 13A-2acs 3 '-- 0.258 _ w _ _ _27.70 _0 0 _ 0. _0 _ 0 _ _ 0 0 _ 0 L_C_ 2A-2om.. _. w .6.14 39.19 R 11D Osw _0.600 0.396 - 2.5 8 1.39 65 - 44 114 60 0 0 0 0 I--D 11D0 0.390 n 11.49 11.50 21 21 280 243 0 0 0 _ 0 C_ _ _ 16X19-0md 0.408 - 1.52 -� 1.50 _ 53, _ _ 53 80 --79 _ 179 �. �� 179 � - - 272' _ �_268 _ F 22A-tpl _ _ .. ._0989 - _ .2860 0.00 _ 53 7 _ _ 173 0 179 _ 27 718 0 6 c) AED excursion 67 404 Envelope loss/gam 1088 1076 3024 3184 12 e) Infiltration 82 25 341 106 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 1000 0 Subtotal (lines 6 to 13) 1170 2101 3355 3290 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1170 2101 3365 3290 15 Duct loads 14% 8'/0 163 172 14% 8% 470 270 Total room load 1333 2273 3835 3560 Air requiretl (cfm) 68 103 195 161 -Fl" wrightsoftl Right-SalteO Universal 201515,0.18 RSU08057 ... t2BTarponFlatsAGRlLot28TarponFlatsModelAGRWrup Calo=We House faces: W 15:04:59 Page 6 +wrightsoft° Right-M Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax 407-333-3853 Web: WWW.DEL-AIR.COM Job: Lot 28 Tarpon Flats Model A... Date: 01.18.14 By: ER 1 Room name Beim 4/Den Bthm13 2 Exposed wall 18.0 ft 0 0 3 Room height 9.3 ft heat/cool 9.3 ft heat/cool 4 Room dimensions 12.0 x 12.5 ft 10.0 x 5.5 ft 5 Room area 150.0 ft. 55.0 ft' Ty Construction U-value Or HTM Area (ft) Load Area (ft� Load number (BtutJft;'F) (Btuh/ft� a perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W - __ 13A-2as. -: , . __ 0.258 - n 6.99 5.19 -' _. 0 -0 - _.. _.0 .:..... _0 _ - 0 - _ _.. 0 . _0 , - 0 II--w 2A-2om 0.600 n 16.14 16.01 0 0 0 0 0 0 .0 0 1-G 2A-2om 0.600 n 16.14 16.01 0 0 0 0 0 0 0 0 W .._ . 13A-20cs 2 _ _. - -. _ 0.258 - u 6.94 5.19 _ _ 0 __ _ _ _0 . _ 0 .. ___ _0 _ _ _ 0 _ _ _ _0 0 - ' 0 11 W __' 13A,2ocs_.___ _ _ __-0.258 _e --- _ _.-694 - 5.19 --._ `,0 - _` 0._ - 0 '--0 _-_. _ __0.. .0 _ 0 ._. 0 ' 2A 2om. '0.600 a 16.14 45.19 0 0 0 0 0 0 0 0 2A-2om . 0.600 a 16.14 '45.19 0 0- 0 .- 0 0 0 0 0 _ W 13A-2od51 ___ __< - _> 0.258 _ e . - _ 0.94 5.19 _ _ _0 -__0 <_ _ 3 -_,_. 0 ... _ _0 __ _ _ _ 0 _ _ _ _ 0 -0 '�_ f 2A-2omd 0.600 a 16.14 26.01 0 0 0 0 0 0 0 0 _ IWIj __ 13A-2ocs2 _ 0.258 e_ __ 6.94 5.19 - 0 -..0 - 0-_... ._ -0 ...-- 0 .. _0. -0 0 ^- 2A-20m _ 0.600 a 16.14 45.19 0 0 0 0 '0 0 0 0 L_G_ 7A-2om 0.600 a 16 14 , 0 0 0 0 0 W 13A-2ocs - - - - �0.258 -s - 6.94 _45.19 - 5.19 - 0 - 0 _0 0 _ _ _- _0 0 _ _ 0 _ _ 0 _ 0 -0 0 LCZ 2A-2om Q600 s 16.14 26.01 0 0 0 0 0 0 0 0 W 13A-2ccs 2 _ ._ - - -0.258 s 6.94 - -5.19 ._ __-0 0 _ -0 . 0 -0 0 - 0 0 LrG tO(3m. _-_ -_ - _ 0.600 s 16.14 21.21 0 0 0 _ 0 . 0 -0 0 0 W -_ -- 13A-2ocs 3 0,258 s _ 6.94 5.19 _ 56 56 389 290 0 _0 0 _ 0 _ 13A-2ccs- 0.600 w 6.14 5.66 0 0 0 0 0, 0 0' 0 2A-2on '0.600 w- 16.14' 44.09 0' 0 0 0 0 0 0° 0 13A226 0.600 w 16:14 0 0 0 0 0 0 0 _ W 13A-26cs 1 � - - --0.258 - w - - - 6.94 _ _45..19 5.19 - -- 0 - - 0 - � 0 _ _0 - 0 0 _ 0 _ � 0 - 0 10C-m 0.600 w 16.14 23.50 0 0 0 0 0 0 0 0 213-2fm 0.600 w 1.6.14 27.70 0 0 0 0 0 0 0 0 _ _ W 13A-2ocs 3 - - - 0,258 w _ 6.84 5.19 _ 1 112 _ _ 81 562 -420 -- -0 - 0 - - 0 _ 0 L-C 2A-2om 0.600 w 1.6:14 3125 31 14 500 1217 "_ 0 0 0 0 P _ 12C-0sw _ 0.096 - 258 1.37 0 0 0 0 0 _ 0 0 0 Ln 11DO l6X19-0md 0.390 n 10.49 11.39 .50 0 - 150 0 - `150 0 228 0 � '0 0 0 5 _ 0 _ 0 83 -C F _ 22A-tpl _ - _ _ _- 0.989 - - 26.60 .0.00 - 150 , _ 18 _ 479 _ _ _ _ - 5 - 5 0 _ - _, 0 0 61 c) AED excursion 1463 -3 Envelope loss/gain 2158 2615 84 79 12 a) Infiltration 227 71 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants Q 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 2385 2685 84 79 Less external load 0 0 0 0 Less transfer 0 a 0 0 Redistribution 0 0 0 0 14 Subtotal 2385 2685 e4 79 15 Duct loads 14% 8% 333 220 14% 8% 12 7 Told room load 2719 2906 95 Air required (cfm) 138 11 f�GsGA � wrlghtsoft- Right -Suite® Universal 201515.0.16 RSUD8057 Ot'YOat 18 1 :04:59 9 7 ... t28TarponFlalsAGR\Lot28TarponFlatsModelAGRWrup Calc=MJB House faces: W - Duct System Summary Job: Lot 28Tarpon Flats Mod ... wrlghtsoft° y ry Date: 01.18.14 Entire House By: ER DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fas 407-333-3853 Web: WWW.DEL-AIR.COM Project Information For: Phoenix Realty Homes Inc, Lot 28 Tarpon Flats Model A GRW 3922 Duneside Drive, Fort Pierce, FL External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.30 in H2O 0.06 in H2O 0.24 in H2O 0.120 / 0.120 in H2O 0.134 in/100ft 1583 cfm Cooling 0.30 in H2O 0.06 in H2O 0.24 in H2O 0.120 / 0.120 in H2O 0.134 in/100ft 1583 cfm 179 ft Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Bd=2 h 3835 195 161 0.157 8.0 Ox0 VIFx 53.0 100.0 st2 13don3 In 3923 199 152 0.216 8.0 Ox0 VIFx 25.9 85.0 stl Bdnn 4/Den h 2719 138 132 0.166 7.0 OxO VIFX 44.9 100.0 st2 Bthrm2 h 1252 64 33 0.213 5.0 OxO VIFx 27.7 85.0, stl Bthrm3 h 95 5 4 0.172 4.0 OxO VIFx 39.4 100.0 st2 Great c 3457 131 157 0.183 7.0 OxO VIFx 31.1 100.0 st2 Great -A c 3457 131 157 0.176 8.0 OxO VIFx 36.0 100.0 st2 Mahan c 2486 30 113 0.232 6.0 OXO VIFX 18.5 85.0 stl Mstr Bdnn' c 3614 160 164 0.135 8.0 OXO VIFx 63.1 115.0 st3 Mstr Bdrm-A c 3614 160 164 0.134 8.0 OXO VIFX 63.7 115.0 st3 Mstr Bthnn In 2034 103 56 0.142 6.0 Ox0 VIFX 53.5 115.0 st3 Mstr WC h 893 45 23 0.138 4.0 Ox0 VIFX 58.5 115.0 st3 Maur WIC h 120 6 5 0.142 4.0 OXO VIFX 53.9 115.0 st3 Nook c 3557 149 161 0.214 7.0 Ox0 VIFX 27.2 85.0 stl Utility c 2273 68 103 0.218 6.0 Ox0 VIFX 25.2 85.0 stl Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st3 Peak AVF 475 411 0.134 604 12.0 0 x 0 VinlFlx st2 st2 Peak AVF 1073 1021 0.134 607 18.0 0 x 0 VinlFlx stl stl Peak AVF 1583 1583 0.134 726 20.0 0 x 0 VinlFlx WiKjht:SOfC Right -suite® Universal 201515.0.18 RSU08057 ACCA... t28TarponFlatsAGR\Lol28TarponFlatsModelAGRWmp Cafe =MJB House faces: W Page 1 Name Grill Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox0 1583 1583 0 0 0 0 Ox 0 VIFx + wrightsoft• Right -Suite® Universal 201515.0.18 RSU08057 ACCA ... l28TarponFlalsAGR\Lot28TarponFlatsModeIAGRW.mp Calc=MJ8 House faces: W Page 2 FORM R405-2014 Florida Department of Business and Professional Regulations Residential Whole Building Performance and Prescriptive Methods ADDRESS: 3922 Duneside Drive Permit Number: 1511-0125 Fort Pierce, FL , MANDATORY REQUIREMENTS see individual code sections for full details. ? 401.3 Energy Performance Level (EPL) display card (Mandatory). The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law [Section 553.9085, Florida Statues] requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate compliance for the building. A copy of the EPL display card can be found in Appendix C. ? R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.1 through R402.4.4. 7 R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. • R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table 402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. • R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air changes per hour in Climate Zones 1 and 2, and 3 air changes per hour in Climate Zones 3 through 8. Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g. (50 Pascals). Where required by the code official, testing shall be conducted by an approved third party. A written report of the results of the test shall be signed by the party conducting the lest and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures; 2. Dampers including exhaust, intake, makeup air, backdraff and Flue dampers shall be closed, but not sealed beyond intended infiltration control measures; 3. Interior doors, if installed at the time of the test, shall be open; 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed; 5. Healing and cooling systems, if installed at the time of the test, shall be turned off; and 6. Supply and return registers, if installed at the time of the lest, shall be fully open. R402.4.2 Fireplaces. New wood-buming fireplaces shall have tight -fitting flue dampers and outdoor combustion air. ? R402.4.3 Fenestration air IeakageWindows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. ? R402.4.4 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage '- between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E 283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. ? R403.1.1 Thermostat provision (Mandatory). Al least one thermostat shall be provided for each separate heating and cooling system. ? R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the healing load. ? R403.2.2 Sealing (Mandatory)NJl ducts, air handlers, and filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts and plenum chambers, shall be constructed and sealed in accordance with Section C403.2.7.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria by post -construction or rough -in testing below. Duct tightness.shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section 553.99, Florida Statutes, or as authorized by Florida Statutes, to be "substantially leak free" by either of the following: 1. Post -construction lest: Total leakage shall be less than or equal to 4 cfm (113 Umin) per 100 square feel (9.29 m2) of conditioned floor area when tested at a pressure differential of 0.1 inches w.g. (25 Pa) across the entire system, including the manufacturers air handler enclosure. All register boots shall be taped or otherwise sealed during the test. 2. Rough -in test: Total leakage shall be less than or equal to 4 cfm (113 Umin) per 100 square feet (9.29 m2) of conditioned floor area when tested at a pressure differential of 0.1 inches w.g. (25Pa) across the system, including the manufacturers air handler enclosure. All registers shall be taped or otherwisesealed during the test. If the air handler is not installed at the time of the test, total leakage shall be less than or equal to 3 cfm (85 Umin) per 100 square feet (9.29 m2) of conditioned floor area. Exceptions: _ ++ 1. The total leakage test is not required for ducts and air handlers located entirely within the building envelope. 2. Duct testing is not mandatory for buildings complying by Section R405 of this code. 12118/2015 3:04 PM EnergyGaugeO USA - FlaRes2014 - Section R405.4.1 Con age 1 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) ? R403.2.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design air flow rate when tested in accordance with ASHRAE 193. ? R403.2.3 Building Cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. ? R403.3 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105'F (41°C) or below 55•F (13°C) shall be insulated to a minimum of R-3., ? R403.3.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance, and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.4.1 Circulating hot water systems (Mandatory). Circulating hot water systems shall be provided with an automatic or readily accessible manual switch that can turn off the hot-water circulating pump when the system Is not in use. R403.4.3 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heal traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'/: Inches (89 mm) in the hot water distribution line and mid water line located as close as possible to the storage tank. R403.4.4 Water heater efficiencies (Mandatory). Water heater efficiencies 7 R403.4.4.1 Storage water heater temperature controls • R403.4.4.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100•F to 140•F (38'C to 60°C). • R403.4.4.1.2 Shutdown. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water healing systems to be turned off. 7 R403.4.4.2 Water heating equipment. Water heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2. in Chapter 4 of the Florida Building'Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide healing functions as part of a combination system shall satisfy all stated requirements for the appropriate water heating category. Solar water heaters shall met the criteria Section R403.4.4.2.1. 4 R403.4.4.2.1 Solar water heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol, Collectors in installed solar water heating systems should meet the following criteria: 1. Be installed with a till angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. 7 R403.5 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation. Outdoor air intakes and exhausts shall have automatic or gravity, dampers that close when the ventilation system Is not operating. ? R403.5.1 Whole -house mechanical ventilation system fan efficacy. Mechanical ventilation system fans shall meet the efficacy requirements of Table R403.5.1. Exception: Where mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be powered by an electronically commutated motor. ? R403.5.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioned system make air shall be provided to conditioned space from attics, crawlspaces, attached closed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed spaces(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum or R-19, space permitting, or R-10 otherwise. R403.6 Heating and cooling equipment (Mandatory). The following sections are mandatory for cooling and heating equipment. R403.6.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved healing and cooling calculation methodologies, ` based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This code does not allow designer safety factors, provisions for future expansion or other factors. which affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanicalg A? such as standard kitchen and bathroom exhaust systems. • R403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that calculated total load, but not more than 1.15 times greater than the total load calculated accorc Section 403.6, or the closest available size provided by the manufacturer's product lines. The r equipment shall not be less than the calculated latent load. 1211812015 3:04 PM EnergyGauge® USA - FlaRes2014 - Section R405.4.1 Cam Page 2 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) ? - R403.6.1.1 Cooling equipment capacity. (continued) The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacture's expanded performance data shall be used to select cooling -only equipment. This selection shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower cfm provided by the expanded performance data, the design value for entering wet bulb temperature and the design value for entering dry bulb temperature. Design values for entering wet bulb and dry bulb temperature shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multi -family residential equipment sizing may be selected so that its cooling rapacity is less than the calculated total sensible load but not less than 60 percent of that load. 2. When signed and sealed by a Florida -registered engineer, in attached single- and multi -family units, the rapacity of equipment may be sized in accordance with good design practice. ? R403.6.1.2 Heating equipment capacity R403.6.1.2.1 Heat pumps. Heat pumps sizing shall be based on the cooling requirements as calculated according to Section R403.6.1.1 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load. R403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.6.1. R403.6.1.2.3 Fossil fuel heating equipment. The rapacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.6.1. ? R403.6.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipmentcapacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.7 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Commercial Provisions in lieu of Section R403. '! R403.8 Snow melt system controls (Mandatory). Snow and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 55°F, and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40'F. ? R403.9 Swimming pools, Inground spas and portable spas (Mandatory). The energy requirements for residential pools and inground spas shall be as specified in Sections R403.9.1 through R403.9.3 and in accordance with ANSI/APSP-15. The energy requirements for portable spas shall be in accordance with ANSI/APSP-14. ? R403.9.1 Pool and spa heaters. All pool healers shall be equipped with a readily accessible on -off switch that is mounted outside the healer to allow shutting off the heater without adjusting the thermostat. setting. R403.9.1.1 Gas and oil -fired pool and spa heaters. All gas- and oil -fired pool and space healers shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16, 2013 when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural gas or LP gas shall not have continuously burning pilot lights. R403.9.1.2 Heat pump pool heaters. Heat pump pool healers shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A lest report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heal pumps are not required to meet this standard. ? R403.9.2 Time switches. Time switches or other control method that can automatically turn off and an heaters and pumps according to a preset schedule shall be installed on all heaters and pumps. Healers, pumps and motors that have built in timers shall be deemed in compliance with this equipment. Exceptions: • 1 Where public health standards require 24-hour pump operations. 2. Where pumps are required to operate solar- and waste -heat -recovery pool healing systems. 3. Where pumps are powered exclusively from on -site renewable generation. ? R403.9.3 Covers. Heated swimming pools and inground permanently installed spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Outdoor pools deriving over 70 percent of the energy for heating from site -recovered energy, such as a heat pump or solar energy source computed over an operating season. ? RR404.1 Lighting equipment (Mandatory). A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be high -efficacy lamps or a minimum of 75 percent of permanently installed lighting fixtures shall contain only high efficacy lamps. Exception: Low -voltage lighting shall not be required to utilize high -efficacy lamps. ? R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuousX i 1 ? R405.2 Performance ONLY. All ducts not entirely inside the building thermal envelope shall be insulated o of 6. ? R405.2.1 Performance ONLY. Ceilings shall have minimum insulation of R-19. Where single ass +b o po d _: n beam type or concrete deck roofs do not have sufficent space, R-10 is allowed, 12/18/2015 3:04 PM EnergyGauge® USA - FlaRes2014 - Section R405.4.1 Com 0 D `Page 3 of 3 FORM R405-2014 TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot28TarponFlalsModelAGRW Builder Name: Phoenix Realty Homes Inc Street: 3922 Duneside Drive Permit Office: City, State, Zip: Fort Pierce , FL , Permit Number: 1511-0125 Owner: Jurisdiction: Design Location: FL, Fort Pierce COMPONENT CRITERIA CHECK Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope. Exterior thermal envelope contains a continuous barrier. Breaks or joints in the air barrier shall be sealed. Air -permeable insulation shall not be used as a sealing material. Ceiling/aftic The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. - Corners and headers shall be insulated and the junction of the foundation Walls and sill plate shall be sealed. The junction of the top plate and the top or exterior walls shall be sealed. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Knee walls shall be sealed. Windows, skylights and doors The space between window/doorjambs and framing and skylights and framing shall be sealed. Rim joists Rim joists are insulated and include an air barrier. Floorsf (including above -garage Insulation shall be installed to maintain permanent contact with underside and cantilevered floors) of subfloor decking. The air barrier shall be installed at any exposed edge of insulation. Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently attached to the crawlspace walls. Exposed earth in unvented crawl spaces shall be covered with a Class I vapor retarder with overlapping joints taped. Shafts, penetrations Duct shafts, utility penetrations, and flue shaft openings to exterior or unconditioned space shall be sealed. Narrow cavities Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be air tight, IC rated, and sealed to the drywall. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind piping and wiring. Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air barrier installed separating them from the showers and tubs. Elect Iical/phone box on The air barrier shall be installed behind electrical or communication boxes or air sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub -Floor or drywall. Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall h ve gasketed doors 12/18/2015 3:04 PM EnergyGauge® USA - FlaRes2014 Section R405.4.1 Compliant Software wg, 1 of 1 FORM R405-2014 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2014 Florida Building Code, Energy Conservation via the residential Simulated Performance method shall include ❑ This checklist ❑ A Form R405 report that documents that the Proposed Design complies with Section R405.3 of the Florida Energy Code. This form shall include a summary page indicating home address, a -ratio and the pass or fail status along with summary areas and types of components, whether the home was simulated as a worst -case orientation, name and version of the compliance software tool, name of individual completing the compliance report (f page) and an input summary checklist that can be used for field verification (usually 4 pages/may be greater). ❑ Energy Performance Level (EPL) Display Card (one page) i ❑ Mandatory Requirements(three pages) Required prior to CO for the Performance Method., ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ 'A completed Envelope Leakage Test Report(usually one page) ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed Form R405 Duct Leakage Test Report (usually one page) 11/3/2015 5:47:05 PM EnergyGauge® - USRFSB v4.0 FORM R405-2014 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Form R405 Duct Leakage Test Report Performance Method Project Name: Lot28TarponFlatsModelAGRW Builder Name: Phoenix Realty Homes Inc Street: 3922 Duneside Drive Permit Office: City, Stale, Zip: Fort Pierce , FL , Permit Number: 1511-0125 Design Location: FL, Fort Pierce Jurisdiction: Duct Test Time: Post Construction Duct Leakage Test Results CFM25 Duct Leakage Test Values Line System Outside Duct Leakage 1 System 1 cfm25(Out) 2 System 2 cfm25(Out) 3 System 3 cfm25(Out) 4 System 4 cfm25(Out) 5 Total House Sum lines 1-4 Duct System Divide by Leakage (Total Conditioned Floor Area) _ (Qn,Out) I hereby certify that the above duct testing performance results demonstrate compliance with the Florida Energy Code requirements in accordance with Section R403.2.2. SIGNATURE: PRINTED NAME: DATE: Duct tightness shall be verified by testing to Section 803 of the RESNET Standards by an energy rater certified in accordance with Section 553.99, Florida Statutes. BUILDING OFFICIAL: DATE: 12/18/2015 3:04 PM EnergyGauge® USA - FlaRes2014 - Section R405.4.1 Compliant S PEOP FIB