HomeMy WebLinkAboutMISC LETTERApril 29, 2016
St. Lucie County Building Deparment
2300 Virginia Ave
Fort Pierce, FL 34982
Re: Tarpon Flats - Electric power is in the entire subdivision for all new homes.
Dear St. Lucie County Building Department:
Florida Power & Light Company
S
'
St.4Uc�&c" FO
Unty
Thank you for contacting FPL early in your planning process. At the present time FPL has sufficient capacity
to provide electric service to your property. We have facilities currently available at this location.
Please advise me early in the planning process once the final plans have been approved. This information will
help us to provide you with the best service in accordance with applicable rates, rules and regulations. You
may also respond to us through www.fpl:com. Please contact me if you have any questions.
Sincerely,
Melanie Wildrick
Associate Technical Specialist
A NEXTera ENERGY Company
DE,- -', BEACH NAPLES CAFE` 'BAN
RAND ,ALL STOFFT
I��bII6
disunctivc in,i itionW architecture
November 13, 2015 RECEIVED
To: St. Lucie County, Planning & Zoning DEC 17 2015
Re: 3922 Duneside Drive PER.101 rTING
Tarpon Flats, Lot 28, Model A St. Lucie County, FL
Fort Pierce, FL.
Permit Number: 1511-0125
Dear Plans Reviewer:
In reference to the Plan Review Comments by Planning & Zoning staff completed on 11.12.15, I am respectfully
submitting this letter addressing the comments as well as (2) Two Signed and Sealed, Revised copies of the affected
sheets as outlined below. All affected sheets have been clouded as Delta #1 in the Title Block of each sheet:
r
Zoning Review:
Comment # 1: Driveway width on the survey is not matching the driveway width on the site plan.
Response #1: Driveway width has been adjusted on the survey and the architectural site plan to match. Please see
revised survey and sheet 'SP.
Comment #2: Dimension of the garage on the survey are not matching with the foundation/ floor plan. The garage on
the survey is larger.
Response #2: Please see revised survey matching dimensions shown on the structural and architectural drawings.
Comment #3: The property exists of two flood zones. The survey indicates that the rear part is Flood Zone X and the
main part is Flood Zone AE. According to the FEMA maps, this is the opposite. Please check the surveyor and submit
corrected surveys.
Response #3: Please see revised survey matching the Flood Zone designations outlined in the FEAM maps.
This concludes our responses associated with Revision #1.
Please feel free to contact this office with any questions or concerns related to this submittal.
Since
sJ
Randall E. Stofft, AIA
President
RES. Donald W. Durante
42 N. SWINTON AVE, SUITE 1
DELRAY BEACH, FLORIDA 33444
561-243-0799 - PHONE
561-243-0299 - FAX
W W W.STOFFT.COM
AA0003379
DE;'-- BEACH NAPLES CAR,' ',AN
akhi, RRANDALL STOFFT
CTS
diainetivc inspkationnl .mNWe wm
November 13, 2015
To: St. Lucie County, Planning & Zoning RECEIVED
Re: 3922 Duneside Drive DEC 17 2015
Tarpon Flats, Lot 28, Model A
Fort Pierce, FL. PERMITTING
Permit Number: 1511-0125 St. Lucie County, FL
Dear Plans Reviewer:
In reference to the Plan Review Comments by Planning & Zoning staff completed on 11.12.15, I am respectfully
submitting this letter addressing the comments as well as (2) Two Signed and Sealed, Revised copies of the affected
sheets as outlined below. All affected sheets have been clouded as Delta #1 in the Title Block of each sheet. -
Zoning Review:
Comment #1: Driveway width on the survey is not matching the driveway width on the site plan.
Response #1: Driveway width has been adjusted on the survey and the architectural site plan to match. Please see
revised survey and sheet'SP'.
Comment #2: Dimension of the garage on the survey are not matching with the foundation/ floor plan. The garage on
the survey is larger.
Response #2: Please see revised survey matching dimensions shown on the structural and architectural drawings.
Comment #3: The property exists of two flood zones. The survey indicates that the rear part is Flood Zone X and the
main part is Flood Zone AE. According to the FEMA maps, this is the opposite. Please check the surveyor and submit
corrected surveys.
Response 43: Please see revised survey matching the Flood Zone designations outlined in the FEMA maps.
This concludes our responses associated with Revision #1.
Please feel free,to contact this office with any questions or concerns related to this submittal.
Randall E. Stofft, AIA
President
RES. Donald W. Durante
42 N. SWINTON AVE, SUITE I
DELRAY BEACH, FLORIDA 33444
561-243-0799-PHONE
561-243-0299 - FAX
WN'WsTOFFT.COPd
AA0003379
D1 'Y BEACH NAPLES CAE,^7ZAN
ldjblijl RANDAs L STOFFT
distinctive inspimtion:d =hitecwrc
December 17, 2015
To: St. Lucie County, Planning & Zoning
Re: 3922 Duneside Drive
Tarpon Flats, Lot 28, Model A
Fort Pierce, FL.
Permit Number: 1511-0125
Dear Plans Reviewer:
in reference to the Plan Review Comments by Planning & Zoning staff completed on 12.12.15, I am respectfully
submitting this letter addressing the comments as well as (2) Two Signed and Sealed, Revised copies of the affected
sheets as outlined below. All affected sheets have been clouded as Delta #2 in the Title Block of each sheet:
Plans Examiner Review:
Comment # 1: Energy cale's show a 3 and 4 inch separation distance, please clarify.
Response #1: GC to submit required documents.
Comment 92: Energy calcs call out R-0.1 insulation, sheet CS notes thermal protection call out R-19 blanket
insulation, A303 shows and calls out sucarseal spray foam insulation. Please correct and submit correct signed and
sealed documents in duplicate. Note: if sucraseal product is being used please submit product information to be
reviewed for astm standards and testing.
Response #2: Sucraseal spray foam is being used as noted on sheet A303. Sheet CS has been revised to reflect spray
foam insulation. Additionally, please see ICC Evaluation Report provided. GC to submit revised Energy Calcs as
needed.
Comment #3: Please show on plans door from garage to house meeting the requirements of R302.5 of the 2014
Residential Building Code. Door must be self -closing.
Response #3: Please see revised sheets A101 & A303 for revised & added notes.
Comment #4: Please submit the energy performance sheets or submit the NFRC Fenestration manufacturer
certificate for the u-factor & the shgc showing compliance with chapter 4, section 402.1.1 of the 2014 Energy Code,
5th Edition.
Response #4: GC to submit required documents.
Comment #5: Please see notes on plans, submit soil report.
Response #5: GC to submit required documents.
42 N. SWINTON AVE, SUITE 1
DELRAY BEACH, FLORIDA 33444
561-243-0799 - PHONE
561-243-0299 - FAX
wW WsTOFFT.COn
.AA0003379
A.
I���Illl RANDAS L STOFFT
dietlnchve inspirational architccwrc
Comment #6: Roof section of the energy talcs call out gable or shed roof system, plans call out a hip roof system,
please clarify.
Response #6: GC to submit required documents.
Comment#7: Please clarify the concrete unit masonry note T for special inspector.
Response #7: Please see revised sheet CSfor revised note eliminating the special inspector notes. A special
inspector is not required.
Zoning Review:
Comment #1: Driveway width on the survey is not matching the driveway on the site plan
11/17/15 received corrected survey. driveway width still different from site plan. The site plans shows
a 20.67' wide driveway. If this is incorrect, then please correct the site plan to match the survey.
Response #1: Please see revised sheet SP and revised survey showing the driveways at the same width.
This concludes our responses associated with Revision #2.
Please feel free to contact this office with any questions or concerns related to this submittal.
Sinter
est
Randall E. Stofft, AIA
President
RES. Donald W. Durante
42 N. SWINTON AVE, SUITE 1
DELRAY BEACH, FLORIDA 33444
561-243-0799 - PHONE
561-243-0299 - FAX
Www,STOFFT.COM
AA0003379
EA BEACH NAPLES CAP;.^"EAN
December 17, 2015
To: St. Lucie County, Planning & Zoning
Re: 3922 Duneside Drive
Tarpon Flats, Lot 28, Model A
Fort Pierce, FL.
Permit Number: 1511-0125
Dear Plans Reviewer:
,jEtIIII RANDALL STCIFFT
ARCdielinctive inspirutlomd urchiteL.
I
In reference to the Plan Review Comments by Planning & Zoning staff completed on 12-12.15, I am respectfully
submitting this letter addressing the comments as well as (2) Two Signed and Sealed, Revised copies of the affected
sheets as outlined below. All affected sheets have been clouded as Delta #2 in the Title Block of each sheet:
Plans Examiner Review:
Comment #1: Energy cale's show a 3 and 4 inch separation distance, please clarify.
Response #1: GC to submit required documents.
Comment #2: Energy calcs call out R-0.1 insulation, sheet CS notes thermal protection call out R-19 blanket
insulation, A303 shows and calls out sucarseal spray foam insulation. Please correct and submit correct signed and
sealed documents in duplicate. Note: if sucraseal product is being used please submit product information to be
reviewed for astm standards and testing.
Response #2: Sucraseal spray foam is being used as noted on sheet A303. Sheet CS has been revised to reflect spray
foam insulation. Additionally, please see ICC Evaluation Report provided. GC to submit revised Energy Cales as
needed.
Comment #3: Please show on plans door from garage to house meeting the requirements of R302.5 of the 2014
Residential Building Code. Door must be self -closing.
Response #3: Please see revised sheets A101 & A303 for revised & added notes.
Comment #4: Please submit the energy performance sheets or submit the NFRC Fenestration manufacturer
certificate for the u-factor & the shge showing compliance with chapter 4, section 402.1.1 of the 2014 Energy Code,
5th Edition.
Response 94: GC to submit required documents.
Comment #5: Please see notes on plans, submit soil report.
Response #5: GC to submit required documents.
42 N. SWINTON AVE, SUITE 1
DELRAY BEACH, FLORIDA 33444
561-243-0799 - PHONE
561-243-0299 — FAX
wWw,STOFFT.COM
AA0003379
I kipI RANDALL STOFFT
ARCCTS
dmflncWe inspirntlnnal ...h,We Wlc.
Comment #6: Roof section of the energy calcs call out gable or shed roof system, plans call out a hip roof system,
please clarify.
Response #6. GC to submit required documents.
Comment #7: Please clarify the concrete unit masonry note T for special inspector.
Response #7. Please see revised sheet CS for revised note eliminating the special inspector notes. A special
inspector is not required.
Zoning Review:
Comment # 1: Driveway width on the survey is not matching the driveway on the site plan
11/17/15 received corrected survey. driveway width still different from site plan. The site plans shows
a 20.67' wide driveway. If this is incorrect, then please correct the site plan to match the survey.
Response #1: Please see revised sheet SP and revised survey showing the driveways at the same width.
This concludes our responses associated with Revision #2.