HomeMy WebLinkAboutWIND LOAD DESIGN PRESSURE CALCULATIONSF', c W o Z U Z 00 a� U � (n J co `4-W�� ENGINI'- `RING NZ.FE EXPRESS Order (Ref) #: 48958 (043516-3830208333) Contractor: J&G CARPENTRY, INC. Project Details: COLOHAN CONDO DOOR REPLACEMENT 7030 S.W. 16TH COURT PEMBROKE PINES, FL 5167 N. HIGHWAY AlA, UNIT 803 FORT PIERCE, ST. LUCIE COUNTY, FL Subject: Wind Load Design Pressure Calculations (Components & Cladding) Site Information Building Classification: enclosed Wind Speed (V It): 170 mph Exposure Category: d Roof Type: monoslope Roof Slope (0): 1.2 deg Mean Roof Height (h): 97.0 ft Min. Building Dimension (L): 71.0 ft Parapet >_ 3 feet? No General Calculation Directionality Factor (Kd): 0.85 Gust -Effect Factor (G): 0.85 Internal Pressure Coefficient(GCpi . )• ±0.18 Topographical Factor (Kt): 1.0 Velocity Pressure Exposure Coefficient ( nK): 1.43 Velocity Pressure (qh): 89.64 psf End Zone (a): 7.1 ft ASD Method: P = 0.6w "'r' Im - ©®� r: r r �m � r �� r• r r• r NOTES: Design is in accordance with ASCE 7-10 (ASD method) and the Florida Building Code Sixth Edition (2017). Results l'-1 are not valid for use unless approved via original signature and raised engineer seal of a PE from Engineering Express. t ��lib ��If W Raised Engineer Results are based on contractor -supplied data and shall be field verified by others prior to use. Selection & instal\�tidnp�f M • �/e $ �dV� �oducts shall be approved using these dimensions and pressures as verified by others. �.• LIOEN �f & Note: For openings to be properly rated in Zone 4, no part of the opening shall be within 7.1 feet of any building corner. OV0 r LT-. 2019 This engineer has not field visited this location and if this cannot be clearly identified by others, the opening3h*bg re- G frdon atti to- P.E. evaluated prior to installation of any fenestration. All other information provided above including mean roof hggltt, �T 7'r building minimum dimensions, opening sizes,& other supporting data was provided by others. For definitions�Bthe P 2?U above terms, visit EngineeringExpress.com/Wild TAT 9J38£v 160 SW 12TH AVENUE, SUITE 106, DEERFIELD BEACH, FLORIDA 33442 48958 (043516-3830208333) PHONE: (954) 354-0660 - FAX: (954) 354-0443 AutoPrint ENGINEERINGEXPRESS.COM PAGE 1 OF 1