Order (Ref) #: 48958 (043516-3883912037) Project Details: LAGRAND CONDO DOOR REPLACEMENT
Contractor: 1&G CARPENTRY, INC. 5167 N. HIGHWAY AlA, UNIT 1104
7030 S.W. 16TH COURT PEMBROKE FORT PIERCE, ST. LUCIE COUNTY, FL
PINES, FL
Subject: Wind Load Design Pressure Calculations (Components & Cladding)
Site Information
Building Classification:
enclosed
Wind Speed (V It):
170 mph
Exposure Category:
d
Roof Type:
monoslope
Roof Slope (0):
1.2 deg
Mean Roof Height (h):
97.0 ft
Min. Building Dimension (L):
71.0 ft
Parapet >: 3 feet?
No
General Calculation
Directionality Factor (Kd):
0.85
Gust -Effect Factor (G):
0.85
Internal Pressure
Coefficient (GCp, . )•
± 0.18
Topographical Factor (Kt):
1.0
Velocity Pressure Exposure
Coefficient K
Coe ( n)�
1.43
Velocity Pressure (qh):
89.64 psf
End Zone (a):
7.1 ft
ASD Method:
P = 0.6w
0®
• ' �
r : r r
�m
r Ir
��
r • r
r • r
NOTES: Design is in accordance with ASCE 7-10 (Aso method( and the Florida Building Code Sixth Edition (2017). �WUTA
!!!!
are not valid for use unless approved via original signature and raised engineer seal of a PE from Engineering�Eg re�
Results based data be field by Selection %)idn
Val Sn1 ft h ised Engineer
T� Se
are on contractor -supplied and shall verified others prior to use. &iris Oft
EN •,
SF'./��
products shall be approved using these dimensions and pressures as verified by others.
No
Note: For openings to be properly rated in Zone 4, no part of the opening shall be within 7.1 feet of anZbfdirig corner.
O
E8232B
We Fe bru 20 2019
This engineer has not field visited this location and if this cannot be clearly identified by others, the op —min A ll be re-
*Gordon DI st0, P.E.
evaluated prior to installation of any fenestration. All other information provided above Including mean r height,
building minimum dimensions, opening sizes,& other supporting data was provided by others. For deli a of the ST
EOF PE 8
above terms, visi[EngineeringExpress.com/Vyiki" i ��'•, F�
••' 5
160 SW 12TH AVENUE, SUITE 106, DEERFIELD BEACH, FLORIDA 33442
48958 (043516-3883912037) PHONE: (954) 354-0660 - FAX: (954) 354-0443
AutoPrint ENGINEERINGEXPRESS.COM PAGE 1 OF 1