HomeMy WebLinkAboutHVAC LOAD ANALYSISRECEIVED
MAR 12 2019
ST, 4.klCi@County, Permitting
Liberty Tire
HVAC Load Analysis
for
Liberty Tire
9675 Range Line Road
Port St. Lucie, Florida
SCq
St "Cie CoUC
my
60992
� Al OFOR 0
'q/o
a
Eric J. Svoboda, PE
Fort Pierce Engineering, Inc.
315 South 7th Street
Fort Pierce, FL 34950
Aft) aw Friday,
36
11, 2019
Chvac - Full Commercial HVAC Loads Calculation Program
,, -j�
•
-
-- -
Elite Software, Development,. Inc.
'Fort Pierce Engineering
_
Liberty ?ire
[Fo Pierce, FL 34450
Pa'e2
Building Summmy Loads
Building peaks in August at 1pm.
Bldg Load Area
Sen.
%Tot
Lat
San
Net
%Nett
Descriptions Quan
Loss
Loss '
Gain
Gain
Gain
Gain
Roof 2,617
4,318
9.24
0
5,144
5,144
3.92
Wall 1,926
4,322
9.25
0
2,431
2,431
1.85
Glass 98
2,684
5.74
0
4,234
4,234
3.23
Floor Slab 253
5,176
11.08
0
0
0
0.00
Skin Loads
16,501
35.30
0
11,809
11,809
9.01
Lighting 8,508
0
0.00
0
29,031
29,031
22.15
Equipment 4,254
0
0.00
0
14,515
14,515
11.08
Pool Latent 0
0
0.00
0
0
0
0.00
People 65
0
0.00
10,750
16,015
26,765
20.42
Partition 2,136
1,752
3.75
0
1,752
1,752
1.34
Cool. Pret. 0
0
0.00
0
0
0
0.00
Heat. Pret. 0
0
0.00
0
0
0
0.00
Cool. Vent. 800
0
0.00
34,994
11,430
46,424
35.42
Heat. Vent. 800
28,486
60.95
0
0
0
0.00
Cool.lnfil. 0
0
0.00
0
0
0
0.00
Heat.lnfil. 0
0
0.00
0
0
0
0.00
Draw-Thru Fan 0
0
0.00
0
766
766
0.58
Blow-Thru Fan 0
0
0.00
0
0
0
0.00
Reserve Cap. 0
0
0.00
0
0
0
0.00
Reheat Cap. 0
0
0.00
0
0
0
0.00
Supply Duct 0
0
0.00
0
0
0
0.00
Return Duct 0
0
0.00
0
0
0
0.00
Misc. Supply 0
0
0.00
0
0
0
0.00
Misc. Return 0
0
0.00
0
0
0
0.00
Building Totals
46,738
100.00
45,744
85,317
131,061
100.00
BuildingH-`> " Sen
[Summary
%Tot-
,
-,
Lat-
-
San
Net '.`
b/oNet
Loss,
Loss
Gain ..
- Gain
- Gain-
Gain,
Ventilation 28,486
60.95
34,994
11,430
46,424
35.42
r u, . r 0
Infiltration •,a•' ,
0.00
0
0
0
0.00
.• r
Pretreated Air! -. '+ 0
0.00
0
0
0
0.00
Room Loads ; _ •" •; -, -: :, 18,252
39.05
10,750
73,121
83,871
63.99
Plenum Loads 0
0.00
0
0
0
0.00
Fari/Duct/Misc Loads- 0
0.00
0
766
766
0.58
Building Totals ` : , 46,738
100.00
45,744
85,317
131,061
100.00
Check Figures
Total Building'Supply Air'(tiased on a 21 °
TD):
3,202
CFM
Total Building Vent: Air(24.98% of Supply):
800
CFM
Total Conditioned Air Space:
4,254
Sq.ft
Supply Air Per Unit Area:
0.7528
CFM/Sq.ft
Area Per Cooling Capacity:
389.5
Sq.ftfTon
Cooling Capacity Per Area:
0.0026
Tons/Sq.ft
Heating Capacity Per Area:
10.99
Btuh/Sq.ft
Total Heating Required With Outside Air:
46,738
Btuh
Total Cooling Required With Outside Air:
10.92
Tons
ZAR Pierce Engineering\18 Projects\18001-27 Liberty Tire\Calculations\HVAC\Liberty Tire Heat Load.CH8 Friday, January 11, 2019, 09:21 AM
1 Office
530
4,383
13,128
1,200
Direct
Direct
9am August
6
203
572
0
85
85
4,240
0.38
1.08
0
94
91
2 Women
42
39
719
200
Direct
Direct
10pm August
1
2
31
0
7
7
336
0.04
0.75
0
1
5
3 Mech
48
230
599
0
Direct
Direct
4pm August
0
11
26
0
8
8
384
0.22
0.54
0
5
4
Room Peak Totals:
620
4,653
14,446
1,400
Total Rooms: 3
7
216
629
0
100
100
Unique Rooms: 3
4,960
0.35
1.02
0
100
100
Z:\Ft Pierce Engineering\18 Projects\18001-27 Liberty Tire\Calculations\HVAC\Liberty Tire Heat Load.CHS Friday, January 11, 2019. 09:21 AM
Chvac - Full Commercial HVAC Loads Calculation Program
-
-
Elite Software Development, Inc.'
Fort Pierce', Engineering . • ... I
-
Liberty Tire
Eort PierceFL 34950--
-
Page 4'
Air Handler #1- AHU 1 - Total Load Summaly
Air Handler Description: AHU 1 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of
0.06 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.91
--- This system occurs 1 time(s) in the building. --
Air System Peak Time: 9am in August.
Outdoor Conditions: Clg: 790 IDS, 760 WB, 127.93 grains, Htg:
420 DB
Indoor Conditions: Clg: 750 DB, 50% RH, Htg: 750 DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Room Space sensible loss: 4,653 Btuh
Infiltration sensible loss: 0 Btuh
0
CFM
Outside Air sensible loss: 3,561 Btuh
100
CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
8,214 Btuh
Heating Supply Air: 4,653 / (.999 X 1.08 X 20) =
216
CFM
Winter Vent Outside Air (46.4% of supply) =
100
CFM
Room space sensible gain: 14,378 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 151 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
14,528 Btuh
Cooling Supply Air: 14,528 / (.999 X 1.1 X 21) =
629
CFM
Summer Vent Outside Air (15.9% of supply) =
100
CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 440 Btuh
100
CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
440 Stull
Total sensible gain on air handling system:
14,968 Btuh
Room space latent gain: 1,400 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 4,505 Btuh
Total latent gain on air handling system:
5,905 Btuh
Total system sensible and latent gain:
20,873 Btuh
Check Fi ures'-.-
Total Air Handler Supply Air (based on a 21 ° TD):
629
CFM
Total Air Handler Vent. Air (15.89% of Supply):
100
CFM
Total Conditioned Air Space:
620
Sq.ft
Supply Air Per Unit Area:
1.0153
CFM/Sq.ft
Area Per Cooling Capacity:
356.4
Sq.ft/Ton
Cooling Capacity Per Area:
0.0028
Tons/Sq.ft
Heating Capacity Per Area:
13.25
Btuh/Sq.ft
Total Heating Required With Outside Air:
8,214
Btuh
Total Cooling Required With Outside Air:
1.74
Tons
Z:1Ft Pierce Engineering118 Projects\18001-27 Liberty Tire\Calculations\HVACILiberty Tire Heat Load.CHS Friday, January 11, 2019, 09:21 AM
Chvac -Full Commercial HVAC'Loads
Calculation Program
-
--
Elite Software.. Development, Inc.
Fort Pierce Engineerinq
�tllr�dTlr�Ih1,
_
Liberty Tire
Fort Pie FL 4 _ ..
. , - ..
. �`,.+
. .....,�
. _,.
_ . _ _ � .
Page
Air Handler #2 - AHU 5 - Summmy
Loads
Rm Description
Area
Htg;Loss
Sen.Gain
Lat.Gain
Htg.O.A.
Clg.O A.
No Room Peak Time
People' ..
Htg.CFM
Clg.CFM
S.Exh
Req.CFM
Req.CFM
Volume
CFM/S ft
CFM/$ ft
WExh
ACt.CFM
Act.CFM
4 Locker Room
480
1,439
10,596
3,100
Direct
Direct
4pm August
20
209
405
0
209
209
3,840
0.43
0.84
0
209
234
5 Men
210
630
2,992
400
Direct
Direct
4pm August
2
91
114
0
91
91
1,680
0.43
0.55
0
91
66
Room Peak Totals:
690
2,069
13,588
3,500
Total Rooms: 2
22
300
520
0
300
300
Unique Rooms: 2
5,520
0.43
0.75
0
300
300
Z:\Ft Pierce Engineering\18 Projects\18001-27 Liberty Tire\Calculations\HVAC\Liberty Tire Heat Load.CH8 Friday, January 11, 2019, 09:21 AM
Chvac - Full Commercial HVAC Loads .Calculatiom Program j
,Elite: Software Development, Inc.
Fort Pierce Enpinearing JI°IJI
III
Liberty Tire.
F .Pierce, FL 34660 ---
-
a e.6'
Air Handler #2 - AHU 5 - Total Load Summa
Air Handler Description: AHU 5 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of
0.05 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.80
-- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in August.
Outdoor Conditions: Clg: 900 DB, 780 WB, 126.54 grains, Htg:
420 DB
Indoor Conditions: Cig: 750 DB, 50% RH, Htg: 750 DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Room Space sensible loss: 2,069 Btuh
Infiltration sensible loss: 0 Btuh
0
CFM
Outside Air sensible loss: 10,682 Btuh
300
CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
12,751 Btuh
Heating Supply Air: 2,069/(.999 X 1.08 X 6) =
300
CFM
Winter Vent Outside Air (100.0% of supply) =
300
CFM
Room space sensible gain: 13,588 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 124 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
13,712 Btuh
Cooling Supply Air: 13,712 / (.999 X 1.1 X 24) =
520
CFM
Summer Vent Outside Air (57.7% of supply) =
300
CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 4,946 Btuh
300
CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
4,946 Btuh
Total sensible gain on air handling system:
18,658 Btuh
Room space latent gain: 3,500 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 12,453 Btuh
Total latent gain on air handling system:
15,953 Btuh
Total system sensible and latent gain:
34,611 Btuh
Check Figures .
Total Air Handler Supply Air (based on a 240 TD):
520
CFM
Total Air Handler Vent. Air (57.71 % of Supply):
300
CFM
Total Conditioned Air Space:
690
Sq.ft
Supply Air Per Unit Area:
0.7534
CFM/Sq.ft
Area Per Cooling Capacity:
239.2
Sq.ftlron
Cooling Capacity Per Area:
0.0042
Tons/Sq.ft
Heating Capacity Per Area:
18.48
Btuh/Sq.ft
Total Heating Required With Outside Air:
12,751
Btuh
Total Cooling Required With Outside Air:
2.88
Tons
Z:\Ft Pierce Engineering\18 Projects\18001-27 Liberty Tire\Calculations\HVAC\Liberty Tire Heat Load.CH8 Friday, January 11, 2019, 09:21 AM
No Room Peak Time
6 Closet
4pm August
7 Human Resources
4pm August
8 Transportation
2pm August
9 Elec. Storage
3pm August
Room Peak Totals:
Total Rooms: 4
Unique Rooms: 4
Htg.CFM
CFM/Soft
75
225
890
0
Direct
Direct
0
10
39
0
10
10
600
0.14
0.52
0
7
8
252
643
3,685
600
Direct
Direct
3
30
161
0
33
33
2,016
0.12
0.64
0
19
33
288
1,195
4,654
600
Direct
Direct
3
55
204
0
38
38
2,304
0.19
0.71
0
36
41
144
1,289
2,052
0
Direct
Direct
0
60
90
0
19
19
1,152
0.41
0.62
0
38
18
759
3,351
11,281
1,200
6
155
494
0
100
100
6,072
0.20
0.65
0
100
100
ZAR Pierce Engineering\18 Projects\18001-27 Liberty TirelCalculationslHVAMI-iberty Tire Heat Load.CH8 Friday, January 11, 2019, 09:21 AM
Chvac - Fulf Commercial HVAC+Loads Calculation Program -
"'
"`
Elite. Software Development, Inc.'
Fort Pierce Enclineenrip I
Libertv'Tire
Forti F 5 ..
_ _..'- — pa
Air Handler #3 - AHU 6 - Total Load Summa
Air Handler Description: AHU 6 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of
0.05 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.90
--- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 3pm in August.
Outdoor Conditions: Clg: 90° DB, 78' WB, 125.80 grains, Htg:
420 DB
Indoor Conditions: Clg: 75° DB, 50% RH, Htg: 75' DB
Summer: Ventilation controls outside air, ---- Winter: Ventilation controls outside air.
Room Space sensible loss: 3,351 Btuh
Infiltration sensible loss: 0 Btuh
0
CFM
Outside Air sensible loss: 3,561 Btuh
100
CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
6,912 Btuh
Heating Supply Air: 3,351 / (.999 X 1.08 X 20) =
155
CFM
Winter Vent Outside Air (64.4% of supply) =
100
CFM
Room space sensible gain: 11,275 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 118 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
11,393 Btuh
Cooling Supply Air: 11,393 / (.999 X 1.1 X 21) =
494
CFM
Summer Vent Outside Air (20.3% of supply) =
100
CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 1,649 Btuh
100
CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
1,649 Btuh
Total sensible gain on air handling system:
13,041 Btuh
Room space latent gain: 1,200 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 4,151 Btuh
Total latent gain on air handling system:
5,351 Btuh
Total system sensible and latent gain:
18,393 Btuh
"Check Eiciures
Total Air Handler Supply Air (based on a 21 ° TD):
494
CFM
Total Air Handler Vent. Air (20.26% of Supply):
100
CFM
Total Conditioned Air Space:
759
Sq.ft
Supply Air Per Unit Area:
0.6504
CFM/Sq.ft
Area Per Cooling Capacity:
495.2
Sq.ftrron
Cooling Capacity Per Area:
0.0020
Tons/Sq.ft
Heating Capacity Per Area:
9.11
Btuh/Sq.ft
Total Heating Required With Outside Air:
6,912
Btuh
Total Cooling Required With Outside Air:
1.53
Tons
Z:1Ft Pierce Engineering\18 Projects\18001-27 Liberty Tire\CalculationsWAMLiberty Tire Heat Load.CH8 Friday, January 11, 2019, 09:21 AM
- Description Area
Htg.Loss Sen.Gain
- -Lat.Gain
Htg.O:A.
Clg.O.A.Room
LR_m-
Peak Time People
Htg.CFM Clg.CFM
S.Exh `.
Req.CFM
Req.CFM
Volume
CFM/Soft CFM/Saft
_W.Exh
Act.CFM
Act.CFM
10 Operations
1,035
3,882
3pm August
12
180
8,280
0.17
11 Quality Control
230
829
3pm August
3
38
1,840
0.17
12 Break Room
920
3,468
3pm August
15
161
7,360
0.17
Room Peak Totals:
2,185
8,179
Total Rooms: 3
30
379
Unique Rooms: 3
17,480
0.17
16,329
1,860
715
0
0.69
0
3,692
465
162
0
0.70
0
15,593
2,325
683
0
0.74
0
35,614
4,650
1,559
0
0.71
0
Direct
Direct
142
142
142
138
Direct
Direct
32
32
30
31
Direct
Direct
126
126
127
131
300
300
300
300
Z:\Ft Pierce Engineering\18 Projects\18001-27 Liberty Tire\Calculations\HVAC\Liberty Tire Heat Load.CH8 Friday, January 11, 2019, 09:21 AM
Chvac - Full Commercial HVAC Loads Calculation Program
Fort Pierce Engineering Ji{Iil
Elite SoftwareDeveiopment,lnc.
Liberty Tire
Fort Ei r FL 34950
--.
_.
-_ _ a e 10
Air Handler #4 - AHU 7 - Total Load Summaty
Air Handler Description: AHU 7 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.15 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.88
--- This
system occurs 1 time(s) in the building. ---
Air System Peak Time: 3pm in August.
Outdoor Conditions: Clg: 90° DB, 78' WB, 125.80 grains, Htg:
42° DB
Indoor Conditions: Clg: 750 DB, 50% RH, Htg: 75° DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Room Space sensible loss: 8,179 Btuh
Infiltration sensible loss: 0 Btuh
0
CFM
Outside Air sensible loss: 10,682 Btuh
300
CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
18,862 Btuh
Heating Supply Air: 8,179 / (.999 X 1.08 X 20) =
379
CFM
Winter Vent Outside Air (79.2% of supply) =
300
CFM
Room space sensible gain: 35,614 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 373 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
35,987 Btuh
Cooling Supply Air: 35,987 / (.999 X 1.1 X 21) =
1,559
CFM
Summer Vent Outside Air (19.2% of supply) =
300
CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 4,946 Btuh
300
CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
4,946 Btuh
Total sensible gain on air handling system:
40,933 Btuh
Room space latent gain: 4,650 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 12,453 Btuh
Total latent gain on air handling system:
17,103 Btuh
Total system sensible and latent gain:
58,036 Btuh
Check F ures;
. . L
Total Air Handler Supply Air (based on a 21° TD):
1,559
CFM
Total Air Handler Vent. Air (19.24% of Supply):
300
CFM
Total Conditioned Air Space:
2,185
Sq.ft
Supply Air Per Unit Area:
0.7136
CFM/Sq.ft
Area Per Cooling Capacity:
451.8
Sq.ft/Ton
Cooling Capacity Per Area:
0.0022
Tons/Sq.ft
Heating Capacity Per Area:
8.63
Btuh/Sq.ft
Total Heating Required With Outside Air:
18,862
Btuh
Total Cooling Required With Outside Air:
4.84
Tons
ZAFt Pierce Engineering\18 Projects118001-27 Liberty Tire\Calculations\HVACILiberty Tire Heat Load.CH8 Friday, January 11, 2019, 09:21 AM