HOILERSMITH LTD. Telephone0 (519)527-0500 166 MAIN ST. S., SEAFORTH, ONTARIO NOK 1 WO Far9 (M)52r-0150 COMBUSTION TESTFIRE REPORT Full Modulation Gas SCANNED BY DATE December19,2018 St. Lucie county ULTIMATE OWNER MacDonald Steel Ltd. r . Cambridge, ON BOILER MODEL NO CF3LS-70-G-15 BOILER SERIAL NO. 53004 BOILER H.P. 70 DESIGN PRESSURE 15 PSIG BURNER MODEL NO. C2-G-20BHTDC BURNER SERIAL NO. 101867296 BURNER MOTOR 1 HP ( 460 V/ 3 PH16OHz) AMPS 1.7 RUN 1.6 FLA FUEL -GAS TYPE: NATURAL INLET PRESSURE 10 PSIG (LOCKED UP) TUBE RETARDERS ALL-24' l0 TEST LOCATION BSM X JOB TUBETYPE STD DIELECTRIC TEST 19-Dec-18 (Criterion Model AVC-25V), (1200V AC, 60 Hz,1 Second) Calibration Date 4Jul-18 GAS LOW -FIRE MID -FIRE HIGH -FIRE Input 676 MBH 1800 MBH 2810 MBH 02 6.7 % 4.9 % 4.1 % CO 3 PPM 4 PPM 6 PPM CO2 8.1 % 9.1 % 9.5 % NOX 63 PPM 54 PPM 48 PPM Inlet Pressure (On) 9.75 PSIG 9.5 PSIG 9.5 PSIG Pilot Pressure (On) 6 "WC "WC "WC Manifold Pressure 0.3 "WC 1.8 "WC 4 "WC Gross Stack 224 OF 288 OF 338 OF Net Stack 152 OF 219 OF 269 of Combustion Efficiency 85.9 % 84.3 % $3.2 % Draft(OK1On)" 'WC "WC — 'WG — "WC — "WC — "WC . Furnace Presssure 0.02 " WC 0.2 " WC 0.6 " WC Pressure Corr. Factor 1.72 1.72 1.72 Steam Pressure 1 PSIG 2.5 PSIG 5 PSIG or Water Temperature — OF of — of Water Return/ Feedwaler Temperature — of — OF — OF Analyzer Used KANE ' SPECIFY NEGATIVE - OR POSITIVE + COMMENTS: : SW. REV 201914671 MFG. CODE 64662 dela asanualMoaftus9on repodslWn nloddallan gas