Subject: Wind Load Design Pressure Calculations (Components &
Site Information
Building Classification:
enclosed
Wind Speed (V It):
170 mph
Exposure Category:
d
Roof Type:
monoslope
Roof Slope (0):
1.2 deg
Mean Roof Height (h):
88.0 ft
Min. Building Dimension (L):
101.0 ft
Parapet >: 3 feet?
No
APR 3 0 2019
General Calculation
Directionality Factor (Kd):
0.85
Gust -Effect Factor (G):
0.85
Internal Pressure
Coefficient (GCp;):
± 0.18
Topographical Factor (K,t):
1.0
Velocity Pressure Exposure
Coefficient ( nK):
1.40
Velocity Pressure (qh):
88.13 psf
End Zone (a):
10.1 ft
ASD Method:
P = 0.6w
'
NOTES: Design is in accordance with ASCE 7-10 (ASD method) and the Florida Building Code Sixth Edition (2017j. Results
are not valid for use unless approved via original signature and raised engineer seal of a PE from Engineering F-xprg;s;
Valid gltly With
aised gine�
Results are based on contractor -supplied data and shall be field verified by others prior to use. Selection & installatioriof
W _—
products shall be approved using these dimensions and pressures as verified by others. '••
STP 1E OP
1'2019
Note: For openings to be properly rated in Zone 4, no part of the opening shall be within 10.1 feet of any building c&ger
'' 1'
T.ht
�� I
`.
T[j5t0, P.E.
This engineer has not field visited this location and if this cannot be clearly identified by others, the opening shall be rd7y
evaluated prior to installation of any fenestration. All other information provided above including mean roof height,
I I I I I
building minimum dimensions, opening sizes, & other supporting data was provided by others. For definitions of the
PE
328
above terms, visit EngineeringExpress.com/Wiki "
#9885
160 SW 12TH AVENUE, SUITE 106, DEERFIELD BEACH, FLORIDA 33442
50328 (043573-5434259259) PHONE: (954) 354-0660 — FAX: (954) 354-0443
AutoPrint ENGINEERING EXPRESS.COM PAGE 1 OF 1