HomeMy WebLinkAboutMASTER PLANGENERAL NOTES 1. DESIGN CRITERIA: ALUMINUM SPECIFICATIONS: APPLICABLE CODES, REGULATIONS & STANDARDS: 1. THE 2017 FLORIDA BUILDING CODE, 6TH EDITION SPECIFICALLY CHAPTER 16 STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM & CHAPTER 23 WOOD. 2. ASIDE 7-10. & SE17 3. NDS NATIONAL DESIGN SPECIFICATION FOR WOOD. 4. ACI318 CONCRETE REFRENCE MANUAL. 5. PC] PRECAST & PRESTRESSED CONCRETE. 6. AA ASM 35 & AA ADM 1 WIND LOADS: 1. BUILDING OCCUPANCY CATEGORY, PARAGRAPH 1604.5 & TABLE 1604.5: RISK CATEGORY 2. 2. BASIC WIND SPEED, TABLE 1609C, STATE OF FLORIDA DEBRIS REGION & BASIC WIND SPEED, PARAGRAPH 1609.3.1 & TABLE 1609.3.1 EQUIVALENT BASIC WIND SPEED: 160 MPH EXPOSURE CATEGORY, PARAGRAPH 1609.4.3: D 3. SCREENED ROOF ENCLOSURE FBC 2017 CH. 20 TABLE 2002.4 CONCRETE & FOUNDATION DESIGN: 1. WHERE CONCRETE SPECIFICATIONS ARE REQUIRED, WHETHER IN THE SCREEN ENCLOSURE SCOPE OF NOT, BY ONE OR MORE REGULATORY AGENCY, THE FOLLOWING SPECIFICATIONS ARE APPLICABLE: A. CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING COMPONENTS: I. PORTLAND CEMENT TYPE 1 -ASTM C 150 II. AGGREGATES - LARGE AGGREGATE 3/4" MAX. - ASTM C 33 III. AIR ENTRAINING +/- 1 % - ASTM C 260 IV. WATER REDUCING AGENT-ASTM C 494 V. CLEAN POTABLE WATER VI. OTHER ADMIXTURES NOT PERMITTED B. METAL ACCESSORIES SHALL CONFORM TO: I. REINFORCING BARS - ASTM A615, GRADE 60 II. WELDED WIRE FABRIC -ASTM A185 C. CONCRETE SLUMP AT DISCHARGE CHUTE NOT LESS THAN 3" OR MORE THAN 5". WATER ADDED AFTER BATCHING IS NOT PERMITTED. D. PREPARE & PLACE CONCRETE PER AMERICAN CONCRETE INSTITUTE MANUAL OF STANDARD PRACTICE, PART 1, 2, & 3 INCLUDING HOT WHEATHER RECOMMENDATIONS. E. MOIST CURE OR POLYETHYLENE CURING PERMITTED. F. PRIOR TO PLACING CONCRETE, TREAT THE ENTIRE SUBSURFACE ARE FOR TERMITES IN COMPLIANCE WITH THE FBC. (CATEGORY 2 ROOMS ONLY) G. CONCRETE SHALL BE PLACED OVER A POLYETHYLENE VAPOR BARRIER. (CATEGORY 2 ROOMS ONLY) 2. FOOTING SIZE: EXISTING CONCRETE SLAB. NO ADDITIONAL FOOTING OR FOUNDATION SYSTEM IS REQUIRED BY THE PROPOSED CONSTRUCTION IF A MINIMUM 4" CONCRETE SLAB (3000 PSI) IS PROVIDED IN SOUND CONDITION, FREE FROM STRUCTURAL CRACKING, SPALLING & OTHER DETERIORATION. EXISTING FOUNDATION/FOOTING UNDER CONCRETE SLAB MINIMUM 8"x8" W/ (1) #5 BAR TO BE VERIFIED BY CONTRACTOR. SEE TYPICAL FOOTING DETAILS FOR NEW FOOTING DESIGN MINIMUM REQUIREMENTS. 3. WHEN APPLICABLE FOR ATTACHING NEW FOOTER TO EXISTING, DRILL & EPDXY NEW STEEL INTO EX. FOUNDATION WITH 1" MIN. HOLE, EMBED 4" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE (OR EQUAL) TYP. ALL LOCATIONS. 4. WHEN INSTALLING 4" CONCRETE SLAB -ADD ADJACENT TO EXISTING-DOWELL INTO EXISTING CONCRETE 48" O/C W/8" #5 REBARS- DRILL 3/4" HOLE 4" EMBEDMENT- EPDXY W/ NON -SHRINKING "SIMPSON EPDXY TIE" (OR EQUAL). 5. MINIMUM CONCRETE STRENGTH 3000 PSI UNLESS OTHER WISE NOTED. 1. ALUMINUM EXTRUSIONS SHALL BE 6005 T5 ALLOY UNLESS OTHERWISE SPECIFIED. 2. ALL SELF MATING BEAM SECTIONS ARE TO BE STITCHED WITH #12 SCREWS 6" FROM ENDS & 24" CENTER TO CENTER. 3. ROOF BRACING SHALL BE A MINIMUM 2"X2"X.050". 4. THE MINIMUM NORMAL THICKNESS OF PROTECTOR PANELS (KICKPLATES) SHALL BE AN INDUSTRY STANDARD OF 0.024 INCHES. 5. VINYL AND ACRYLIC PANELS SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH PER FBC. 6. SCREEN MATERIAL SHALL BE 18/14 SCREEN UNLESS APPROVED BY FLORIDA ENGINEERING LLC. FASTNER SPECIFICATIONS: 1. FASTNERS ARE REQUIRED TO BE SAE GRADE 2 OR BETTER ZINC PLATED. (CONCRETE ANCHORS ARE TO BE TAPCONS OR BETTER, INSTALLED TO MFG.) 2. IT IS THE OWNERS RESPONSIBILITY TO MAINTAIN THE SCREENS, AND FASTENERS TO MANUFACTURING SPECIFICATIONS. 3. WHERE WOOD DECK IS PRESENT USE 1/4"X3-1/2" GALV. LAG SCREWS IN LIEU OF MASONRY ANCHORS. UNLESS OTHERWISE SPECIFIED. 4. 1"X2" NON STRUCTURAL MEMBERS ATTACHED TO HOST A. FOR MASONRY/CONCRETE APPLICATION USE GALVANIZED 1/4"X2-3/4" TAPCONS OR EQUAL AT 24" O.C. AND 6" FROM ENDS B. FOR WOOD APPLICATION USE #14X2-3/4" WOOD SCREW AT 24" O.C. AND 6" FROM ENDS. C. FOR ALUMINUM APPLICATION USE #10X1-1/2" SMS OR TEK SCREW AT 24" O.C. AND 6" FROM ENDS D. WHERE VX2" INSTALLED THROUGHOUT AN "OPEN VIEW" SPACING SHALL BE REDUCED TO 18" O.C. AND 6" FROM ENDS MASONRY SPECIFICATIONS: 1. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED ON TYPE M OR S MORTAR. 2. ALL MORTAR SHALL BE TYPE M OR S. 3. ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE MAXIMUM COARSE AGGREGATE SIZE OF 3/8". 4. PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR'EXCEEDS 5'-0" IN HEIGHT. MISCELLANEOUS: LLl N 00 C)OI=Z;W, O �'o�� (D i= B _ m 00 Z �: CO c FILE. Ply,. P W 2. FOR FASTENERS WHICH ARE NOT VISIBLE AFTER INSTALLATION, THE CONTRACTOR SHALL VERIFY AND INSURE INSTALLATION HAS BEEN ACCOMPLISHED IN ACCORDANCE WITH . MANUFACTURERS SPECIFICATIONS AND IN ACCORDANCE WITH THE ATTACHED DETAILS. 3. FOR "PICTURE WINDOW" MODIFICATION TO EXISTING SCREEN ENCLOSURES, ALL OTHER "EXISTING SCREEN ENCLOSURE" FEATURES ARE TO MEET THE TYPICAL DETAILS AS PROVIDED IN THESE DETAILS. CONTRACTOR IS TO VERIFY & ASSURE EXISTING SCREEN ENCLOSURE IS STRUCTUALLY SOUND. 1. SCREENED ENCLOSURES CONTAINING SWIMMING POOLS SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF FBC R4101.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS. 2. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPERATE 4TH WALL SUPPORT SYSTEM IS SO TO BE ENGINEERED SO THAT NO ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. 3. DOOR LOCATION MAY BE RELOCATED BY CONTRACTOR IN THE FIELD. 4. WHERE PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR SHALL EPDXY TO DECK OR GROUT TO DECK w/3000 PSI GROUT WITH BONDING AGENT. 5. INTEGRITY OF EXISTING/ HOST STRUCTURE SHALL NOT BE COMPROMISED WITH THE ATTACHMENT OF THE PROPOSED STRUCTURE. 6. ALL 2X4 & GREATER ARE TO BE SMB UNLESS OTHERWISE INDICATED. RESPONSIBILITIES: 1. ALL SITE WORK SHALL BE PERFORMED BY A LISCENED CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDANANCES, AND THE ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES. LEGEND: (ALL MAY NOT APPLY) RECEIVED SCR = SCREEN KP = KICK PLATE MAY 0 2 2019 PW = PICTURE WINDOW X = HORIZ. SLIDING WINDOW ST. Lucie County, Permitting 0 = HORIZ. STATIONARY WINDOW DH = DOUBLE HUNG WINDOW SH= SINGLE HUNG WINDOW SIP = SOLID INSULATED PANEL CT = CABLE TIE SG = SUPER GUTTER CS = CLEAR SPAN KB = KNEE BRACE ALUMINUM MEMBERS DIMENSIONS HOLLOW SECTIONS 2 x 2: 2"x2"x0.044" p 2 x 3: 2"x3"x0.044" LU 2 x 4: 2"x4"x0.044" U > 2 x 5: 2"x5"x0.050" U m. OPEN BACK SECTIONS l/) -� 1 x 2: 1 "x2"4.044" 1 x 3: 1 "x3"x0.044" SNAP SECTIONS 2 x 2 SNAP: 2"x2"x0.050" 2 x 3 SNAP: 2"x3"x0.050" 2 x 4 SNAP: 2"x4"0.045" SELF MATING (SMB) 2 x 4 SMB: 2"x4"x0.044"x0.100" 2 x 5 SMB: 2"x5"x0.050"x0.100" 2 x 6 SMB: 2"4"4.050"0.120" 2 x 7 SMB: 2"x7"x0.057x0.120" 2 x 8 SMB: 2"x8"x0.072"x0.124" 2 x 9 SMB: 2"x9"x0.082"x0.124" 2 x 10 SMB: 2"x10"x0.092"4.398" NOTE: AS INDICATED ABOVE ALL MEMBER PROFILES ARE INDICATED IN INCHES. U� J � J m CD z W -� W z ly- - F- w Q Q OLo J "T LL '[I' C) DO M M co p U O0 LE LoLd L N F- ai c 0 '• 2 U F- IL m IT IT C) 00 O Z F- U W O 0.. W J O w Z U O_ I- W 7 > w U) J aLL Z J W O F� w w w w u1 O _ � °¢ Z ) Z(0of C)Y00 W 0)CO LL DESIGN DATE: 02/1612018 REVISION I: 02/23/2018 PAGE: REVISION 2: 0212812018 SCALE: NTS 1 6" 9'-0" 8'-0" 1X3 I 1X3 or1 r X X 'c'j 1X3`Xo'XN N X� CO BUILDINGS 1-3-5-7 BUILDINGS 6-8-10-12 #1-3206 SOUTH LAKEVIEW CIRCLE #3-3210 #5-3216 #6-3207 #7-3218 #8-3209 #10-3212 #12-3215 0 F- HOST 24" O/H -------------------------------- 3" x .024"x1LB INSULATED ROOF 3105-H14%"-1' SLOPE (MIN.) T- o ---------- ---------------------------- 0 cy r 3" x .024"x1 LB INSULATED ROOF _ 3105-1-114 %"-1' SLOPE tMIN.Z i� 1 -2 O/H 1 17'-8" CONCRETE LANDING 52" FROM STRUCTURE 3X3X.093 'm" O N coM 3/4" PICKETS 2X3 TYP. X 2X3 TYP. SEE PAGE 4 FOR DETAILS cD & SPECS. ih 093 co m N O X X M co 2X3 TYP. M 1X3 TYP. 16"X .024 KP 4" CONCRETE SLAB GROUND LEVEL —T-10" 16'-0" see-.:: •• . .. Q : 4/ N w A =;co CD z =g:Z o w O:J Q_ z o J m 0000 J UI co m Z Z ¢p E Cc) p U W J 0Do WQLLUUr1.E Z LLI c- N rn co ZOO-c� Q< < 5 Q _ = U O Lo o E-1 � LL Q M Nr IT O 00 0 Z H U w 0 a L J U z U 0 U w_ w � Y � J w Z 0 W F0 w Z)w W U0a IL 0 7 a Z w �MLL Y0 w DESIGN DATE: 02116/2018 REVISION 1: 02/23/2018 PAGE: REVISION 2: 02/28/2018 SCALE: NTS PRIGF T .024 FLASHING SEALED TO ECONDARY ANGLE MIN ALL (TYP.) //REDUIRED .125' THICK (NOT (4) #12x3/4" SMS FOR 2x3FASTENING SECONDARY EMBER) ANGLE TO COLUMN (TYP EACH SIDE) (B) 3/8- 0 CONCRETE SCREW -� ANCHOR INTO SECONDARY ANGLE (TYP EACH SIDE) (SEE TABLE) ANCHOR SPA (MIN) (iYP) (SEE TABLE) COLUMN SIZE 3/8" 0 CONCRETE SCREW ANCHOR B MIN SPA 2X3 0 0 2X4 1 3 2X5 1 3 2X6 1 4 2X7 1 1 5 2%8 2 3 2X9 2 4 2XIO 1 2 4.5 1c0.125"ANGLE 2) #10x3/4" SMS FASTENING COLUMN TO PRIMARY ANGLE O (TYP EACH SIDE) O O "x2" BASE MEMBER (TYP EACH SIDE) - -(I) 1W 0 CONCRETE SCREW ANCHOR INTO PRIMARY ANGLE AND @ IW 0 CONCRETE 3"MIN. SCREWANCHOR@ 24' O.C. BETWEEN COLUMNS NOTES: (TYP EACH SIDE) 1. NUMBER OF ANCHORS "B' IS EACH SIDE INTO THE SECONDARY ANGLE AND DOES NOT INCLUDE THE ANCHOR INTO THE IX2. 2. MINIMUM EMBEDMENT OF ANCHORS INTO CONCRETE FOOTING SHALL BE 2 3/4' AT ALL UPRIGHT LOCATIONS. ALL SCREW LENGTH AT UPRIGHT CONNECTIONS SHALL BE OF SUFFICIENT LENGTH FOR REQUIRED EMBEDMENT INTO CONCRETE FOOTING WHEN A PAVER DECK IS PRESENT. 3. CONCRETE SCREW ANCHOR DESIGNS ARE BASED ON THOSE LISTED ON S-1, D. FASTENERS, OTHER BRAND & TYPE SHALL BE APPROVED BY ENGINEER. 4.2X3 W/ 1X2 CORNER POST SHALL REQUIRE SAME BASE CONNECTIONS AS 2X4 SHOWN IN TABLE. 5.IF FOR AN IN -FILL, TOP OF COLUMN CONNECTIONS SIMILAR IF CONCRETE LINTEL IF WOOD LINTEL SUBSTITUTE 114" OXT LAG SCREW FOR 3/8" 0 LOT FOR BOTH PRIMARY & SECONDARY ANGLES. 6.2X2X.045 DOOR JAMB MEMBER SHALL CONNECT SIMILAR TO 2X3 MEMBER. 2"X3" OR LARGER UPRIGHT TO CONCRETE W1W0 PAVER DETAILS SCALE:NTS IN x CONCRETE OR FILLED MASONRY #1213/4- SMS @ 12' O.C. TOP & BOTTOM EXISTING RAFTER ORTRUSSER RECEIVING CHANNEL 2°NOMINAL FASCIAMIN. ROOF PANEL ATTACHMENT -MASONRY SCALE:NTS FOR ALUMINUM PANS OR GALVALUME STEEL PANS USE 912 X 911 6"W/ 5/8" NEO-WASHER (3) PER PAN FOR COMPOSITE PANELS #14 X 1" I.G. THAN PANEL THICKNESS SMS W/ 1-12" NEO-WASHER @ 12- O/C IS PER PANEL) HOST *PLAN N ALTERNATES FOR COL. TO 2"X2'AT HEADER:RIER BEAM 1- DETAIL'C' SHT 3 2- HEAVYANGLE W/IS ROOF TO CARRIER (3) #14 TEK EA SIDEBE CONNECTION THIS rCOLINING BEARING WALL FASTEN 1 X Y FASTEN TO ADD ADJOINING WALLLL ADJOININGWALL W/#12 W/18- D.C.1-12° SMS SMS @ 18' O.C. AND 6' FROM ENDS WHERE KICK PLATE IS INDICATED FASTEN W/910 X 9/16" SMS 8' O/C AT PERIMETER EXISTING CONCRETE TYPICALSIDEWALL lWTAPCON COLUMN 1-1, SCREEN ROOM END WALL SCALE: NTS JSED FOR PER PAGE) ED HEAD MFG. OR EQUAL) 6' FROM ENDS 24" O.C. PENETRATION INTO UNDERLYING FOOTING L6� O -,C #12x3/4'SMS @12"O.C. TOP I HKUUUH ne tivmU FOR ALUMINUM PANS: CHANNEL@12'O.C. #12X2"SMS THROUGH WALL "BOXED END": INTO WD FASCIA ALTERNATELY: (3) PER PAN (1) 1/4"x3" LAG BOLT THROUGH RECEIVING CHANNEL @ 12- O.C. ROOF PANEL ATTACHMENT- WOOD FRAME SCALE:NTS FOR ALUMINUM PANS OR GALVALUME STEEL PANS USE #12 X 9/16" W/ 5/8' NEO-WASHER (3) PER PAN FOR COMPOSITE PANELS #14 X 1"LG. THAN PANEL THICKNESS SMS W/ 1-12- NEO-WASHER @ 12" O/C (5 PER PANEL) r#12 X 314@12"O.0 TOP & BOTTOM W/ (3) #14 TEK EA SIDE 'p FPERPIAN PER PLAN .050 BEAM INTO BEAM ROOF TO CARRIER BEAM CONNECTION SCALE: NTS (2) 3l8" DUl EXPANSION BOLTS 2' FROM EDGE ® 2" FROM EDGE OF SLAB' L____I OF SLAB' -ALTERNATELY USE: (5)914 TEK SCREWS EA SIDE TOP VIEW IN UEU OF 114" DIA MACHINE BOLT (114"DDIA MACHINE % LTS WASHERS °°° 3S0' POST PER PLAN (1) 31W DIA EXPANSION 3SLt'x0.125 ANGLE BOLTS EA SIDE Ili 11 FRONT VIEW 3"x3" POST CONNECTION DETAIL SCALE: NTS i OC71tin 111111;;// ............ Q . (( N W = ' : q O O _ :Z W _ CD LO {X Q i O z P PURLIN °Sb III t MEMBER UPRIGHT, BEAN7-SNAP, SELF MATING, OR HOLLOW DETAIL "C" - GIRT OR PURLIN TO BEAM OR POST DETAIL SCALE:NTS (4) 318-W TAPCON THRU BOTTOM LEG OF ANGLE INTO CONO 1" 2" 33/4' FROM EDGE 1, OF SLAB TOP VIEW (3) 1/4" DIA MACHINE /COLUMN PER PLAN BOLTS W WASHERS _ /� CONC. FOOTING BELOW - FRONT VIEW ALT. COLUMN BASE ATTACHMEN DETAIL SCALE:NTS J m CC) J rn UI L M Z Z p 0 W J 0 a0 J 0.)Z LL Lo I Lu � M C Z 0 c WQ�CIDa) v U 0 `o o LL ;I- CL rnLU I-- U � A CM It '14- O T O Z U lLl 0 rL W J U of Z U 0 > 1-- w Y U ILL. O x0 U Of y Z) w w (non Z)w << zIDof YOU �cNOO w DESIGN DATE: 02/16/2018 REVISION I: 02/23/2018 pgGE: REVISION 2: 02/28/2018 SCALE: NTS wo ow z= 3a a Wa aW JW o % 1" X 1" X .044 PICKETT SPACED SO MW A 4" SPHERE SHALL NOT PASS TF nw \ u —a in 42" CHAIR RAIL PER PLAN VARIES-96"MAX PERIMETER (TOP) INSTALLATION NOTES: 1-FASTEN PERIMETER TO ALUM EAVE RAIL W#12 X 1-1/2" SMS 24" O/C AND WITHIN 6" OF INTERSECTING MEMBERS AND JOINTS. 2-FASTEN PERIMETER TO MASONRY W1/4" X 2-1/4" QUICKSET 24" O/C AND WITHIN 6" OF INTERSECTING MEMBERS AND JOINTS. ASSEMBLY NOTES: 1-FASTEN CHAIR RAIL (INTERNAL)TO PERIMETER W/(4) #10X1-1/2" SMS INTO SCREW BOSS OF CHAIR RAIL. 2-FASTEN PERIMETER MEMBERS AT CORNERS(INTERNAL) W (2) #10 X 1-1/2"SMS INTO SCREW BOSSES. 3-FASTEN PICKETT T/B W/(2) #10X1-1/2" SMS THROUGH INTERSECTING MEMBER INTO PICKETTS SEE FIG 1 a GENERAL NOTES AND SPECIFICATIONS: z 1-THE STRUCTURES INDICATED HERIN ARE DESIGNED TO BE INSTALLED o WITHIN MASONRY OR WOOD FRAME HOST STRUCTURES OF ADEQUTE a STRUCTURAL CAPACITY. THE CONTRACTOR SHALL VERIFY THAT THE HOST STRUCTURE IS IN GOOD CONDITION AND OF SUFFICIENT STRENGTH TO SUPPORT THE PROPOSED ADDITION. 2-ALUMINUM EXTRUSIONS SHALL MEET THE STRENGTH REQUIREMENTS OF ASTM B221 AFTER POWDER COATING. 3-ALL ALUMINUM EXTRUSIONS ARE TO BE A MINIMUM 6063 T6 DESIGN STATEMENT: THE INDICATED SCREEN/GAURD RAILING SYSTEMS USE LOADS FROM SECT 1607.7 OF THE FLORIDA BUILDING CODE 2014-5TH EDITION APPLICABLE CODES, REGULATIONS & STANDARDS: ASSEMBLY NOTES: APPLICABLE CODES, REGULATIONS & STANDARDS: 1-FASTEN CHAIR RAIL (INTERNAL) TO SMB 1.THE 2017 FLORIDA BUILDING CODE, 6TH EDITION SPECIFICALLY CHAPTER 16 CAGE COL W/ (4) #10X1-1/2" STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM & CHAPTER 23, WOOD AND SMS INTO SCREW BOSS OF CHAIR RAIL. AA ASM 35 and AA ADM 1 2-FASTEN PICKETT T/B W/(2) #10X1-1/2" 2. ASCE 7-10. SMS THROUGH INTERSECTING MEMBER INTO PICKETTS LIVE LOADS PER TABLE R301.5 GUARDRAILS AND HANDRAILS - 200 PSF, A SINGLE CONCENTRATED LOAD APPLIED IN ANY DIRECTION AT ANY POINT ALONG THE TOP GUARDRAIL IN -FILL COMPONENTS - 50 PSF \�rO Q L ..aJ '4[/ N co o LL O 0 Q ' o ,y •.� Z ai ?�� ............... //nnlnilk", J J Z LLB Lu Z uj O J LL 0 CO rn M Z Q E 0 cc) p U J O� LL Ln .E- LLI m N 1--M C 0 m a= � U L0 Irf may- O ,IT d M v v CD 00 O z F- U w I O ua J ------------ CHAIR RAIL z U O SEE SCREEN ENCLOSURE v w DETAILS FOR COL ANCHORAGE > w w J T_ w .__PICKETTz O Fw Dw SEE SCREEN ENCLOSURE W w a DETAILS FOR COL ANCHORAGE o _D < o m Z W o r o O Y W Co PERIMETER (BASE) z o U a DESIGN DATE: 02/16/2018 REVISION I: 02/23/2018 PAGE: FIG 1 REVISION 2: 02/28/2018 NTS 4 SCALE: NTS RECEIVED MAY 0 2 2019 ST. Lucie county, Permitting T HOST 24" O/H ;s. 3" x .024"x1 LB INSULA �i 3105-H14'/a"-1' SLOT of ----------- 1'---- ;.:I11 3" x .024"x1 LB INSULA' 3105-H141/4"-1' SLOF 1 7 2X3 TYP. BUILDING',_ •3206 SOUTH LAKEVIEW CIRCLE 1QS }- �S. CD fLL ro ` O O:, a 00 Cf z = N r �r ----- 71- sCANNED St. CU�SCounty 8'-0" -I I IOF o X X CO N N 1X3 CONCRETE LANDING 57' FROM STRUCTURE 3/,4" PICKETS SEE PAGE 4 FOR DETAILS & SPECS. `- 3X3X.093 3X3X?093 -. _ 0) - •.4df S Cq , x ........... OX X ce) YK _ co F 2X3 TYP. 1X3 TYP. 16"X .024• KP„, - COPV T-10" ,T-10" • Y FC1. 1 - FILE COPINT/ - 9'-0" 1X3 7 CO CO X X o V N ` ' Y 1 �, Z 4" CONCRETE SLAB GROUND LEVEL • I'J.'1 VuJ "annnllpnta�` O- U v m J �' • opo S J m '0) -. co, Z. •� rQ U U _ LLI .. U_ U?,.- � Z i— ,�yy L1. � of coO-d O J-:• a- .• � LL " O z t- U omw O. - u.i J U Z, O. U I= w w � z g �w W :D w w s U O n. w ¢ � z�b� YOU w U)�LL a DESIGN DATE: 0211612018 REVISION 1: 02/2312018 PAGE REVISION 2: OV2812018 SCALE: NTS (4) #12x3W' SMS FASTENING SECONDARY ANGLE TO COLUMN (TYP EACH SIDE) (B) 3/8" 0 CONCRETE SCREW ANCHOR INTO SECONDARY ANGLE (TYP EACH SIDE) (SEE TABLE) ANCHOR SPA (MIN) (TYP) (SEE TABLE) COLUMN 3/8" 0 CONCRETE SCREW ANCHOR MIN SPA 0 3 3 rO2 a15 NOTES: SECONDARY ANGLE MIN 0.125" THICK (NOT REQUIRED FOR 2x3 MEMBER) WRIMARY 2"x2" �3MIN. 0.125" ANGLE ) #10x3/4" SMS FASTENING OLUMN TO PRIMARY ANGLE TYP EACH SIDE) x2"BASEMEMBER TYP EACH SIDE) ) 1W 0 CONCRETE SCREW NCHOR INTO PRIMARY NGLE AND @ 1/4" 0 CONCRETE CREWANCHOR@ 4"O.C. BETWEEN COLUMNS (TYP EACH SIDE) 1. NUMBER OF ANCHORS "B" IS EACH SIDE INTO THE SECONDARY ANGLE AND DOES NOT INCLUDE THE ANCHOR INTO THE IX2. 2. MINIMUM EMBEDMENT OF ANCHORS INTO CONCRETE FOOTING SHALL BE 2 3/4" AT ALL UPRIGHT LOCATIONS. ALL SCREW LENGTH AT UPRIGHT CONNECTIONS SHALL BE OF SUFFICIENT' LENGTH FOR REQUIRED EMBEDMENT INTO CONCRETE FOOTING WHEN A PAVER DECK IS PRESENT. 3. CONCRETE SCREW ANCHOR DESIGNS ARE BASED ON THOSE LISTED ON S-1, D. FASTENERS, OTHER BRAND & TYPE SHALL BE APPROVED BY ENGINEER. 4.2X3 W/ IX2 CORNER POST SHALL REQUIRE SAME BASE CONNECTIONS AS 2X4 SHOWN IN TABLE. 5. IF FOR AN IN -FILL, TOP OF COLUMN CONNECTIONS SIMILAR IF CONCRETE LINTEL IF WOOD LINTEL SUBSTITUTE 1/4" OX3" LAG SCREW FOR 3/8" 0 LDT FOR BOTH PRIMARY & SECONDARY ANGLES. 6. 2X2X.045 DOOR JAMB MEMBER SHALL CONNECT SIMILAR TO 2X3 MEMBER. 2"x3" OR LARGER UPRIGHT TO CONCRETE WIWO PAVER DETAILS SCALE:NTS SEALED TO O " O`#124/4" SMS @ 12" O.C. TOP �- & BOTTOM RECEIVING CHANNEL CONCRETE OR FILLED FASTEN TO MASONRY WALL MASONRY W/ 114" X 3" TAPCONS 18" O/C (INTERNAL) ROOF PANEL ATTACHMENT -MASONRY SCALE:NTS SCANNED SY St. Lucie (-r,, FOR ALUMINUM PANS OR GALVALUME STEEL PANS USE #12 X 9116" W/ 5/8" NEO-WASHER (3) PER PAN 1/I W/ (3) FOR COMPOSITE PANELS #14 X 1" LG, THAN PANEL THICKNESS SMS W/ 1-10 NEO-WASHER @ 12" O/C (5 PER PANEL) HOST *ROOFN ALTERNATES FOR COL.TO 2"X2"AT HEADER:RIER BEAM 1- DETAIL "C" SHT 32- HEAVY ANGLE W/E ROOF TO CARRIER (3) #14 TEK EA SIDEAM CONNECTION THIS PAGE) INING BEARING WALL M EXISTING RAFTER ORTRUSSER O - ( #12X3/4" SMS @ 12" O.C. TOP & BOTTOM .040 X 3" OHEADER 2" NOMINAL STRUCTURAL \-FOR COMPOSITE PANELS: FASCIA MIN. (2)#12X2"SMS THROUGH RECEIVING FOR ALUMINUM PANS: CHANNEL @12"O.C. #12X2"SMS THROUGH ALTERNATELY: "BOXED END": INTO WD FASCIA (1) 1/4-.13" LAG BOLT (3) PER PAN THROUGH RECEIVING CHANNEL @ 12" O.C. ROOF PANEL ATTACHMENT - WOOD FRAME SCALE:NTS FOR ALUMINUM PANS OR GALVALUME STEEL PANS USE #12 X 9/16" W/ 5/8" NEO-WASHER (3) PER PAN FOR COMPOSITE PANELS #14 X 1"LG. THAN PANEL THICKNESS SMS W/ 1-1/2" NEO-WASHER @ 12" O/C (5 PER PANEL) #12 X 3/4@12"O.0 TOP & BOTTOM ROOFPERPLAN EXTRUDED.050 U HEADER a " NOTCH C CIEVE BEAM � BEM (5)#14x2TEKTHRUCOLINTTO X 2" ANGLE =K EA SIDE _--COLUMN PER PLAN ROOF TO CARRIER BEAM CONNECTION SCALE: NTS 1"X2" FASTEN TO/ ADJOINING WALL W#/12 X 1-1/2' 1"X 2" FASTEN TO ADJOINING WALL "ALTERNATELY USE: W/IF12 X 1-1/2"SMS (4) 914 TIES SCREWS EA. SIDE @ 18" O.C. CHAIR RAIL PER PLAN SMS @ 18" O.C. IN LIEU OF 4" DIA. MACHINE BOLT 1/4"X2-3/4" TAPCONS -OR EQUAL AT 24" 114"DIA MACHINE BOLTSw/WASHERS AND 6"FROM EN SC WHERE KICK PLATE IS INDICATED FASTEN W/ #10 X 9116" SMS WHERE SMB USED FOR (1) 3/8" DIA EXPANSION COL. ATTACH PER 8" O/C AT PERIMETER BOLTS EA SIDE D/ETAIL"B" l CONC. FOOTING - EXISTING CONCRETE TYPICAL SIDE WALL 1/4•TAPCON(RED HEAD MFG. OR EQUAL) 6"FROM ENDS 24"O.C. SCREEN ROOM END WALL SCALE: NTS ALUMINUM INTERNAL OR EXTERNAL RECEIVING CHANNEL W/(4) #10X75" INTO GIRT OR PURLIN & (2) #14x75" INTO BEAM OR UPRIGHT 0.062 ANGLE CLIPS MAYBE USED PURLIN \\\\1111111,11I /// d�.. •lL "4 NFL =Z:Co O Z Q- O O: — o 49 w O v• C� •. ••........... C R \ JUN 14 ')n, ST, Lucie Co nEY/ Pe%fffl/1Q II 1 MEMBER '"SMS INTO BOSSES UPRIGHT, BEAMSNAP, SELF MATING, OR HOLLOW DETAIL"C" - GIRT OR PURLIN TO BEAM OR POST DETAIL SCALE:NTS `(2) 3/8" DIA EXPANSION BOLTS / 3/8"x4"TOFATHRU BOTTOM LEGGOF ANGLE ---_I O INTO CONC. 1" ® FROM EDGE ,,.J(.. L____I OF SLAB' � 2" 33/4"FROM EDGE OF SLAB TOP VIEW TOP VIEW FRONT VIEW 3"x3" POST CONNECTION DETAIL SCALE:NTS PER PLAN OF ANGLE INTO CONC. FOOTING BELOW - FRONT VIEW ALT. COLUMN BASE ATTACHMEN DETAIL SCALE:NTS 00 UI M Z z p O WJ000 W Q LL Lo •I-- Z� ~_ LL, r w UI M C Z C 0� c W Q 0 Q U If OLo J d 1 I..L (M O O 0 Z 0 W 0 W J U Z U 0 F- W_ W U) 1'LL Z W O � U H 2 LU w Z) W s (n U O : a Z�0' O Y0 U AM UU LL DESIGN DATE: 02/16/2018 REVISION 1: 0212312018 1 PAGE: REVISION 2: 02/28/2018 3 REVISION 3: 06/06/2019