HVAC Load Calculations
for
MCCOY REMODEUENCLOSURE
12348 HARBOUR RIDGE BLVD 3-2
PALM CITY, FLORIDA 34990
$C
Sr`. �Uc�e co FO
Uhfl,
SHGC WARNING:
The window performance values consist of the u-factor for the frame,
and Sofar Heat Gain Coefficient (SHGC) for the glass. These values have
a huge impact on the building thermal envelop and may have a significant
impact on the following:
• the size of the HVAC syslem(s), $$$
• the duct work layout and design, $$
• delays with permitting, $$$$
• inspector comments or failed Inspections $$
It is Important to us that your project stay on schedule and if there are
any changes to the design base it may impact any of the bullet points
above. KO Enemy Design must be contacted Immediately at
infoRkoenergydeslan.com or (5611327-7272 to help support any
changes to your project information.
Prepared By:
Karen Oliver
KO Energy Design
1470 N Congress Ave, Ste 106A
West Palm Beach, FL
561-327-7272
Wednesday, July 3, 2019
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
Rhvac : Residen}ial.8. Clght Commercial :Loads __ _ _ Ehte Software,Development,.lnc,'
'KO EnerpjDesign LLC _W � �' m ��-- MCCOY REMODEUENCLOSURE
DEL/ENC'LOSURE
WestPalm 'Beach FL 33411 .Paae.2-
Pro'ect Report
Glen, eralr0io•e Into rrh6 ion z :M
Project Title: MCCOY REMODEUENCLOSURE
Designed By: Karen Oliver
Project Date: Wednesday, July 3, 2019
Client Name: MCCOY REMODEUENCLOSURE
Client Address: 12348 HARBOUR RIDGE BLVD 3-2
Client City: PALM CITY, FLORIDA 34990
Company Name: KO Energy Design
Company Representative: Karen Oliver
Company Address: 1470 N Congress Ave, Ste 106A
Company City: West Palm Beach, FL
Company Phone: 561-327-7272
Company E-Mail Address: info@koenergydesign.com
Company Website: www.koenergydesign.com
Desig n.Data
Reference City: Fort Pierce, Florida
Building Orientation: Front door faces South
Daily Temperature Range: Medium
Latitude: 27 Degrees
Elevation: 25 ft.
Altitude Factor: 0.999
Outdoor Outdoor Outdoor Indoor Indoor Grains
I ry Rnlb Wet Bulh $eLHum RRI-H rn j cy Bulb rlifferenre
Winter: 42 39.4 n/a n/a 70 n/a
Summer: 90 78 59% 50% 75 61
=CheckFi'•ures7%"iOr.'ki,��
Total Building Supply CFM: 1,248 CFM Per Square ft.: 0.641
Square ft. of Room Area: 1,946 Square ft. Per Ton: 711
Volume (ft'): 15,687
Buildir5 %&gdsz
Total Heating Required Including Ventilation Air: 31,516 Btuh 31.516 MBH
Total Sensible Gain: 27,423 Btuh 84 %
Total Latent Gain: 5,409 Btuh 16 %
Total Cooling Required Including Ventilation Air: 32,832 Btuh 2.74 Tons (Based On Sensible + Latent)
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
CA ...\12348 Harbour Ridge Blvd-MJ.rh9 Wednesday, July 3, 2019, 1:56 PM
Rhvac Residential &;Light Com_ martial .Loads _ - _ .._ _ __Elite Software.Aevelopment,
_..,___._.._._-. _.._._._ _ _......_.
�KO -
Energy Des__ign LLC.
MdCOY REMODEL/ENCLOSURE.
Wegil Palm Beach, FL.33411 - -
- --
P
Miscellaneous Report
System 1 System #1 Outdoor
Outdoor Outdoor Indoor Indoor
Grains
In ut Dat _ Dry Bulb-
Wet Bulb_-.: R l.Hum Rel.Hum D Bulb 'Difference
Winter: 42
39.4 80% n/a 70
n/a
Summer: 90
78 59% 50% 75
61.09
Duct Sizing Inputs -'..
Main Trunk
Calculate: No
Runouts
No
Use Schedule: Yes
Yes
Roughness Factor: 0.00300
0.00300
Pressure Drop: 0.1200 in.wg.1100 ft.
0.1000 in.wg./100 ft.
Minimum Velocity: 0 ft./min
0 ft./min
Maximum Velocity: 0 ft./min
0 ft./min
Minimum Height: 0 in.
0 in.
Maximum Height: 0 in.
0 in.
Outside Air Data _
-
Winter
surrimpr
Infiltration Specified: 0.590 AC/hr
0.310 AC/hr
154 CFM
81 CFM
Infiltration Actual: 0.590 AC/hr
0.310 AC/hr
Above Grade Volume: X 15.687 Cu.ft.
X 15.687 Cu.ft.
9,255 Cu.ft./hr
X 0.0167
4,863 Cu.ft./hr
X 0_0167
Total Building Infiltration: 154 CFM
81 CFM
Total Building Ventilation: 0 CFM
0 CFM
--System 1--
Infiltration & Ventilation Sensible Gain Multiplier: 16.49
= (1.10 X 0.999 X 15.00 Summer Temp. Difference)
Infiltration & Ventilation Latent Gain Multiplier: 41.50
= (0.68 X 0.999 X 61.09 Grains Difference)
Infiltration & Ventilation Sensible Loss Multiplier: 30.77
= (1.10 X 0.999 X 28.00 Winter Temp. Difference)
Winter Infiltration Specified: 0.590 AC/hr (154 CFM), Construction: Semi -Loose
Summer Infiltration Specified: 0.310 AC/hr (81 CFM), Construction: Semi -Loose
[Duct Load Factor Scenarios fior.S stem.,�14131 ;i... '•
�tyF tAtt
f,uct%lation
Frome
No. T e" : Descri lion ` =Location C Ihn Lea a =nsu%Are
MDD
1 Supply Main Attic 16B
0.12 6 525
No
1 Return Main Cond. Space -
0.24 6 97
No
CA ... \12348 Harbour Ridge Blvd-MJ.rh9 Wednesday, July 3, 2019, 1:56 PM
.Rhvac-Residential&,LighfCommercia 'Loads ___ _ �Elile,Sottware.Development,lnc.
HO Energy Design LLC � � MCCOY REMODEL/ENCLOSURE
West Palm Beach FL 33411 PageA
Building Pie Chart
Roof 9%
Wall 15%
Glass 34%
,
Glass 36%
Roof 8%
Infiltration 15%
Ductwork 26%
Door 1 %
Infiltration 14%
Ductwork 20%
mquipment 99/6
Peogle 4%
Door 1 /o
CA ...\12348 Harbour Ridge Blvd-MJ.rh9
Wednesday, July 3, 2019, 1:56 PM
Rhvac _Residential 8 Light Commercial 'Loads - y
_ _ _
_
_Elite Software Development, lno.
KO Energy Deslgn LLC
-
MCCOY REMOD'EUENCLOSURE.
Wei Palm Beach FL 33411
-
.Page 5
System 1 System #1 Summary Loads
bescn fiord. __ ,�':'. -�r__+Qu n. .��.:..bLoss�_-.,
*•--Gaih�
w*Gam
Galn_
1A-hw-o: Glazingangle pane, operable window, heat- 164.9
4,155
0 5,595
5,595
absorbing, wood frame, U-value 0.9, SHGC 0.48
wgsgd: Glazing-wgsgd, U-value 1,05, SHGC 0.42 127.3
3,744
0 3,132
3,132
sgd7701e: Glazing-SGD Low-E, U-value 1.02, SHGC 0.27 102
2,913
0 3,174
3,174
11 D: Door -Wood - Solid Core, U-value 0.39 20
219
0 203
203
13A-3ocs: Wall -Block, board Insulation only, R3 board 966.1
4,517
0 2,468
2,468
insulation, open core, siding finish, U-value 0.167
12B-Osw: Wall -Frame, R-11 insulation in 2 x 4 stud 87.3
237
0 204
204
cavity, no board insulation, siding finish, wood studs,
U-value 0.097
16E-19: Roof/Ceiling-Under Attic with Insulation on Attic 1804.9
2,476
0 2,211
2,211
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Light Tile,
Slate or Concrete, R-19 insulation, U-value 0.049
1613-19: Roof/Ceiling-Under Attic with Insulation on Attic 194.1
266
0 476
476
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark
Asphalt Shingles or Dark Metal, Tar and Gravel or
Membrane R-19 insulation U-value 0.049
Subtotals for structure:
18,527
0 17,463
17,463
People: 3
600 690
1,290
Equipment:
0 2,873
2,873
Lighting: 0
0
0
Ductwork:
8,242
1,446 5,061
6,507
Infiltration: Winter CFM: 154, Summer CFM: 81
4,747
3,363 1,336
4,699
Venfilation• Winter CFM: 0. Summer CFM: 0
0
0 0
0
System 1 System #1 Load Totals:
31,516
5,409 27,423
32,832
fCtieck.Fi 'dress..n.. . , ' ''f� `_:
m
Supply CFM: 1,248 CFM Per Square ft.:
0.641
Square ft. of Room Area: 1,946 Square ft. Per Ton:
711
Volume (ft3): 15,687
S stem oad-
Total Heating Required Including Ventilation Air: 31,516 Btuh
31.516 MBH
Total Sensible Gain: 27,423 Btuh
84 %
Total Latent Gain: 5,409 Btuh
16 %
Total Cooling Required Including Ventilation Air: 32,832 Btuh
2.74 Tons (Based On Sensible + Latent)
ENotes
"
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and
ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according
to the manufacturer's performance data at
your design conditions.
C:\ ...\12346 Harbour Ridge Blvd-MJ.rh9 Wednesday, July 3, 2019, 1:56 PM
Project Information
Designed by:
Project date:
Client name:
Client address:
Client city:
Company name:
Company phone:
Field Verification Requirement
Karen Oliver
Wednesday, July 3, 2019
MCCOY REMODEUENCLOSURE
12348 HARBOUR RIDGE BLVD 3-2
PALM CITY, FLORIDA 34990
KO Energy Design
561-327-7272
KO Energy Design
561 327-7272
Field Verification Requirement
All inputs/defaults/building characteristics used for the ACCA Manual J Version 8
calculations must be verified by the Homeowner and/or must be verified by the builder/owner/contractor verifying that what
is built is consistent with the builderslowners project components used in this report. All data used for Manual J sizing
report is based on RFI received via customer.. K.O. Energy Design must be notified in writing of any said changes to RFI.
Equipment Selection
The equipment sizing below was carefully performed to meet or exceed the FL Mechanical Code. Alternate equivalent
equipment selection shall also meet the attached Requirements. Any change in SEER or size of equipment will require close
review and possible revision to this load calculation. K.O. Energy Design must be notified in writing of any said changes and
cannot take responsibility for any deviations from the recommendations below.
Equipment selected should be within the following parameters:
Net Gain 32,832 BTUH per Manual J. (This is the minimum amount of cooling necessary )
Max BTU 37,757 ( Max 15% increase per FBC mandatory requirements)
Recommended tonnage 3 ton.
We always recommend that a Duct leakage test and/or Blower door infiltration test be performed. This is especially
important on older homes that have not been upgraded since 2007. These tests will identify where excess leakage, from
ducts or unexpected infiltration may be entering the home. These are the primary causes for discomfort due to high humidity,
high electric bills, toxic air, and odors in your home.
Duct leakage test will indicate Air Duct Problems and insufficient seals:
A= Leaky connections; B= Leaky return; C= Furniture blocking registers; D= Leaks at air handler and air -filter slot and duct
tape failures; E=Fallen duct insulation; F=Leaky supply ducts; G= Kinks restricting airflow.
r-�
MCCOY REMODEL/ENCLOSURE
HVAC Load Calculations
for
MCCOY REMODEUENCLOSURE
12348 HARBOUR RIDGE BLVD 3-2
RFCFnF� PALM CITY, FLORIDA 34990
JUl I 0 1D79
Perm jttin
Sf; zt /e Co,,, , ent
SHGC WARNYNG:
The window performance values consist of the u-factor for the frame,
and Solar Heat Gain Coefficient (SHGC) for the glass. These values have
a huge impact on the building thermal envelop and may have a significant
impact on the following:
• the size of the HVAC system(s), $$$
• the ductwork layout and design, $$
• delays with permitting, $$$$
• inspector comments or failed Inspections $$
It is Important to us that your project stay on schedule and if there are
any changes to the design base it may impact any of the bullet points
above. KO Enemy Desim must be contacted Immediately at
Info(a.koenamvdesicn.com or (5611327-7272 to help support any
changes to your project information.
Prepared By:
Karen Oliver
KO Energy Design
REVIEWED FOR
1470 N Congress Ave, Ste 106A
Wes6,almBeach,FL
CODE COMPLIANCE
-327272
Wednesday, July3,2019
S To LUCIE COUNTY
EOCC
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual DGMa t,
Rhvac - Residential,& Light Commercial HVAC Loads - - - - Elite SoftwareDevelopment, Inc.
KO Energv-Design L_LC 'MCCOY REMODEUENCLOSURE
West m Beach, FL 33411 _ _ Page 2
Pro'ect Report
General Project Information
Project Title: MCCOY REMODEL/ENCLOSURE
Designed By: Karen Oliver
Project Date: Wednesday, July 3, 2019
Client Name: MCCOY REMODEL/ENCLOSURE
Client Address: 12348 HARBOUR RIDGE BLVD 3-2
Client City: PALM CITY, FLORIDA 34990
Company Name: KO Energy Design
Company Representative: Karen Oliver
Company Address: 1470 N Congress Ave, Ste 106A
Company City: West Palm Beach, FL
Company Phone: 561-327-7272
Company E-Mail Address: info@koenergydesign.com
Company Website: www.koenergydesign.com
Desi n Data
Reference City: Fort Pierce, Florida
Building Orientation: Front door faces South
Daily Temperature Range: Medium
Latitude: 27 Degrees
Elevation: 25 ft.
Altitude Factor: 0.999
Outdoor Outdoor Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hurn 1y Bulb Difference
Winter. 42 39.4 n/a n/a 70 n/a
Summer: 90 78 59% 50% 75 61
Check Fi ures
Total Building Supply CFM: 1,248 CFM Per Square ft.: 0.641
Square ft. of Room Area: 1,946 Square ft. Per Ton: 711
Volume (ft3): 15,687
Building Loads
Total Heating Required Including Ventilation Air: 31,516 Btuh 31.516 MBH
Total Sensible Gain: 27,423 Btuh 84 %
Total Latent Gain: 5,409 Btuh 16 %
Total Cooling Required Including Ventilation Air. 32,832 Btuh 2.74 Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\...\12348 Harbour Ridge Blvd-MJ.rh9 Wednesday, July 3, 2019, 1:56 PM
Rhvac - Residential :B.Light Commercial HVAC Loads - - - Elite software Development, Inc..
KO Ener. y'.Design LLC - MCCOY REMODEL/ENCLOSURE
West Palm Beach, FL 33411
Peas 3
Miscellaneous Report
System 1 System #1 Outdoor
Outdoor Outdoor Indoor Indoor
Grains
In ut Data D Bulb
WetBulb Rel.Hum Rel.Hum Dry Bulb Difference
Winter: 42
39.4 80% n/a 70
n/a
Summer: 90
78 59% 50% 75
61.09
Duct Sizinn Innuts
Main Trunk
Calculate: No
RUnnuts
No
Use Schedule: Yes
Yes
Roughness Factor: 0.00300
0.00300
Pressure Drop: 0.1200 in.wg./100 ft.
0.1000 in.wg./100 ft.
Minimum Velocity: 0 ft./min
0 ft./min
Maximum Velocity: 0 ft./min
0 ft./min
Minimum Height: 0 in.
0 in.
Maximum Height: 0 in.
0 in.
utsAir Data
Winter
Summet
Infiltration Specified: 0.590 AC/hr
0.310 AC/hr
154 CFM
81 CFM
Infiltration Actual: 0.590 AC/hr
0.310 AC/hr
Above Grade Volume: X 15 687 Cu.ft.
X 15,887 CU.ft.
9,255 Cu.ft./hr
X 0.0167
4,863 Cu.ft./hr
X 0-0167
Total Building Infiltration: 154 CFM
81 CFM
Total Building Ventilation: 0 CFM
0 CFM
—System 1—
Infiltration & Ventilation Sensible Gain Multiplier: 16.49
= (1.10 X 0.999 X 15.00 Summer Temp. Difference)
Infiltration & Ventilation Latent Gain Multiplier. 41.50
= (0.68 X 0.999 X 61.09 Grains Difference)
-Infiltration & Ventilation Sensible Loss Multiplier: 30.77
= (1.10 X 0.999 X 28.00 Winter Temp. Difference)
Winter Infiltration Specified: 0.590 AC/hr (154 CFM), Construction: Semi -Loose
Summer Infiltration Specified: 0.310 AC/hr (81 CFM), Construction: Semi -Loose
Fbuct d Factor Scenarios for System 1
Attic
Duct Duct .- Surface
From
No. Type Description Location Ceiling
Leakage nsul tin Areg-
M D
1 Supply Main Attic 16B
0.12 6 525
No
1 Return Main Cond. Space -
0.24 6 97
No
C:\ ...\12348 Harbour Ridge Blvd-MJ.rh9 Wednesday, July 3, 2019, 1:56 PM
Roof 9%
Wall 15%
Glass 34%
Roof 8%
Wall 8%
Glass 36%
Infiltration 15%
Ductwork 26%
Door 1 %
Infiltration 14%
Ductwork 20%
"quipment no/
People 4%
Door 1 A
CA ...\12348 Harbour Ridge Blvd-MJ.rh9 Wednesday, July 3, 2019, 1:56 PM
-Rhvac-Residential .BLight Commercial Loads
KO EnergV Design LLC
Elite Software Development; Inc.
MCCOY REMODEUENCLOSURE
e Paim Beach.1.1
Page 5
System 1 System #1 Summary Loads
Component
Area
San
Lat
Sen
Total
Description
Quan
Loss
Gain
Gain
Gain
IA-hw-o: Glazing -Single pane, operable window, heat-
164.9
4,155
0
5,595
5,595
absorbing, wood frame, U-value 0.9, SHGC 0.48
wgsgd: Glazing-wgsgd, U-value 1.05, SHGC 0.42
127.3
3,744
0
3,132
3,132
sgd7701e: GlazingSGD Low-E, U-value 1.02, SHGC 0.27
102
2,913
0
3,174
3,174
11 D: Door -Wood - Solid Core, U-value 0.39
20
219
0
203
203
13A-3ocs: Wall -Block, board insulation only, R-3 board
966.1
4,517
0
2,468
2,468
insulation, open core, siding finish, U-value 0.167
12B-0sw: Wall -Frame, R-11 insulation in 2 x 4 stud
87.3
237
0
204
204
cavity, no board insulation, siding finish, wood studs,
U-value 0.097
16E-19: Roof/Ceiling-Under Attic with Insulation on Attic
1804.9
2,476
0
2,211
2,211
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Light Tile,
Slate or Concrete, R-19 insulation, U-value 0.049
16B-19: Roof/Ceiling-Under Attic with Insulation on Attic
194.1
266
0
476
476
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark
Asphalt Shingles or Dark Metal, Tar and Gravel or
Membrane. R-19 insulation, U-value 0.049
Subtotals for structure:
18,527
0
17,463
17,463
People:
3
600
690
1,290
Equipment:
0
2,873
2,873
Lighting:
0
0
0
Ductwork:
8,242
1,446
5,061
6,507
Infiltration: Winter CFM: 154, Summer CFM: 81
4,747
3,363
1,336
4,699
Ventilation: Winter CFM: 0. Summer CFM• 0
0
0
0
0
System 1 System #1 Load Totals:
31,516
5,409
27,423
32,832
Check Figures
Supply CFM: 1,248
CFM Per Square ft.:
0.641
Square ft. of Room Area: 1,946
Square ft.
Per Ton:
711
Volume (ft'): 15,687
5 stem Loads
Total Heating Required Including Ventilation Air:
31,516 Btuh
31,516
MBH
Total Sensible Gain:
27,423 Btuh
84
%
Total Latent Gain:
5,409 Btuh
16
%
Total Cooling Required Including Ventilation Air:
32,832 Btuh
2.74
Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent
loads according to the manufacturer's performance data at
your design conditions.
CA ... 112348 Harbour Ridge Blvd-MJ.rh9 Wednesday, July 3, 2019, 1:56 PM
KO Energy Design
561 327-7272
Field Verification Requirement
Project Information
Designed by:
Karen Oliver
Project date:
Wednesday, July 3, 2019
Client name:
MCCOY REMODEL/ENCLOSURE
Client address:
12348 HARBOUR RIDGE BLVD 3-2
Client city:
PALM CITY, FLORIDA 34990
Company name:
KO Energy Design
Company phone:
561-327-7272
Field Verification Requirement
All inputs/defaults/building characteristics used for the ACCA Manual J Version 8
calculations must be verged by the Homeowner and/or must be verified by the builder/owner/contractor verifying that what
is built is consistent with the builder's/owners project components used in this report. All data used for Manual J sizing
report is based on RFI received via customer.. K.O. Energy Design must be notified in writing of any said changes to RFI.
Equipment Selection
The equipment sizing below was carefully performed to meet or exceed the FL Mechanical Code. Alternate equivalent
equipment selection shall also meet the attached Requirements. Any change in SEER or size of equipment will require close
review and possible revision to this load calculation. K.O. Energy Design must be notified in writing of any said changes and
cannot take responsibility for any deviations from the recommendations below.
Equipment selected should be within the following parameters:
Net Gain 32,832 BTUH per Manual J. (This is the minimum amount of cooling necessary )
Max BTU 37,757 ( Max 15% increase per FBC mandatory requirements)
Recommended tonnage 3 ton.
We always recommend that a Duct leakage test and/or Blower door infiltration test be performed. This is especially
important on older homes that have not been upgraded since 2007. These tests will identify where excess leakage, from
ducts or unexpected infiltration may be entering the home. These are the primary causes for discomfort due to high humidity,
high electric bills, toxic air, and odors in your home.
Duct leakage test will indicate Air Duct Problems and insufficient seals:
A= Leaky connections; B= Leaky return; C= Furniture blocking registers; D= Leaks at air handler and air -filter slot and duct
tape failures; E=Fallen duct insulation; F=Leaky supply ducts; G= Kinks restricting airflow.