HomeMy WebLinkAboutFIELD WIRING CONDUIT LISTLiberty Tire Recycling, Port St. Lucie - M140ED
FIELD WIRING CONDUIT LIST
SCANNED
BY
St. Lucie County
LCH 5/1/19
ENCLOSURES, JUNCTION BOXES & REMOTE DEVICES
Control Panel #1
CP1
(mounted on 24" Floor Stand)
36"H x 30"W x 12"D
Motor Starter Panel #1
MSP1
(Mounted on 12" Floor Stand)
60"H x 36"W x 12"D
Motor Starter Panel #2
MSP2
(Mounted on 12" Floor Stand)
60"H x 36"W x 12"D
Line Control Panel
LCP
78"H x 32"W x 24"D
(factory-assebled with MSP2) m
Motor Starter Panel #3
MSP3
87"H x 86"W x 24"D
(factory -assembled with LCP,
JB1
Junction Box #1
8"H x 10"W x 6"D
Factory -mounted to Shredder Stand
Loading Control Stationl
LCS
8"H x 10"W x 6"D
Factory -mounted to Picking Conveyor
Shred Pile Junction Box
SPJB
8"H x 10"W x 6"D
Factory -mounted
Infeed Conveyor Junction Box
C4JB
8"H x 10"W x 6"D
Factory -mounted
C8JB
Returns Conveyor Junction Box
g"H x 10"W x 6"D
Factory -mounted
POWER FEEDS
MSPI
460VAC/3Ph/60Hz; 3 phases +ground / Dual Feed
2 x 350 amps
MSP2
460VAC/3Ph/60Hz; 3 phases + ground
150 amps
MSP3
460VAC/3Ph/60Hz; 3 phases -power In+ground
100 amps
REVIEWED FOR
CODE COMPLIANCE
ST. LUCIE COUNTY
SOCC
Page 1
Liberty Tire Recycling, Port St. Lucie - M140ED
FIELD WIRING CONDUIT LIST
LCH 5/1/19
POWER CONDUITS (field wired) (460VAC/3Ph/60Hz; 3 phases + ground)
From
To
For
MSP1
M1
Shredder Motor #1(symmetrical shielded cable)
250 HP
MSP2
M2
Shredder Motor #2(symmetrical shielded cable)
250 HP
MSP3
M3
Ground Loading Conveyor (Cl) Motor
2 HP
MSP3
M4
Loading #1 Conveyor (C2) Motor
5 HP
MSP3
M5
Loading #2 Conveyor (0) Motor
5 HP
MSP3
M6
Shredder Infeed Conveyor (CV1) Motor
3 HP
MSP3
M7
Discharge Conveyor (CS) Motor
2 HP
MSP3
M8
Disc Screen Feed Conveyor (C6) Motor
3 HP
MSP3
M9
BHS Disc Screen (C7) Motor
5 HP
MSP3
M10
Returns Conveyor (C8) Motor
3 HP
MSP3
Mll
Accepts #1 Conveyor (C9) Motor
2 HP
MSP3
M12
Accepts #2 Conveyor (C10) Motor
3 HP
MSP3
M13
Take Away Conveyor (Cll) Motor
2 HP
MSP3
M14
Walking Floor Feed Conveyor (C12) Motor
3 HP
REVIEWED FOR
CODE COMPLIANCE
ST. LUCIE COUN'
SOCC
CONTROL CONDUITS (field wired) (24VDC)
Page 2
Liberty Tire Recycling, Port St. Lucie - M140ED
FIELD WIRING CONDUIT LIST LCH 5/1/19
From
To
Conductors
22 14AWG Wires (including spares)
CP1
MSPI
1 Belden #8771 Cables
10 14AWG Wires (including spares)
CP1
MSP2
1 Belden #8771 Cables
Cust
3 14AWG Wires
CP1
OK to Run
(wire to Grizzly panel)
16 14AWG Wires (including spares)
CP1
JB1
2 Belden #8771 Cables
11 14AWG Wires (including spares)
CP1
LCP
1 Belden #8771 Cables
Discharge Conv.
LCP
4 14AWG Wires (including spares)
Motion Detector
LCP
BHS Disc Screen
12 14AWG Wires (including spares)
Infeed Conv. Pull
LCP
9 14AWG Wires (including spares)
Cabel a -stops
LCP
Returns Conv.
9 14AWG Wires (including spares)
Pull Cabe[ a -stops
LCP
remote e-stop #2
8 14AWG Wires (including spares)
LCP
remote e-stop #2
8 14AWG Wires (including spares)
LCP
SPJB
11 14AWG Wires (including spares)
LCP
I LCS
17 14AWG Wires (including spares)
NOTE: CATS to be strung to LCP if/when program trouble shooting is required
REVIEWED FOR
CODE COMPLIANCE
ST. LUCIE C®UNTy
EI®CC
Page 3