Loading...
HomeMy WebLinkAboutENGINEERING SUBMITTAL07/11/2019 THU 9:49 FAX 772 3367566 AC advantage, inc. 2013/016 +, Sle1 14'trrawnv .o..,,,p :.eti< Nutr�rny 'x.praro.r,r24 C AA`` a�_'ta�ge� Engineering Submittal Wind Load Certification July 2, 2019 Model/Tag: AC-1,2,3,4,6 Design Parameters: FBC 2017 & ASCE 7-10 Wind Speed: 165 Exposure: C Rlsk Category: 2 Job Name & Location: Rocky's Ace Hardware 7594 US Hwy 1 Port Saint Lucie, FL 34952 BUlrHMARK ENGINFZWNG Of THE TREASURE COAST LLC. 606 Delaware Ave. (772) 267-IBSS Fort Pierce, FL34946 benchmarkenglneeringtcQgmmil.com (�IwCETVED ,,JL 112119 ST. Lucie County, permitting SCANNED St. LucBy County Bowdoin G. Hutchinson P.E. FL 4 P.E. 70878 07/11/2019 THU 9:49 FAX 772 3367566 AC advantage, inc. U014/016 Model/Tag: AC-1,2,3,4,6 Design Parameters W 47 in (Min) WL 23.5 in Ws 23.5 in L 88 in (Max) HFru 41 In (Max) HC 0 in (Max) HFW 20.5 in WCM 928 Ib (Est) VwIND 165 mph Exp C Max Ht 60 ft Wind Loading Per ASCE 7-10: Wind Pressure QH=.O0256 (KZ)(KZr)(KD)(VWIND)A2 KZ 1.13 KZT 1.0 KD 0.9 VWIND 155 mph QH= 70.91b/ftA2 Lateral Farce FWL=QH (GCR) AF GCR 3.1 AF 25.1 ftA2 FWL= 5,505lb Uplift Fwu=QH (GCR) AF GCR 1.5 AF 28.7 ftA2 riNu= 3,054lb Sum Moments Mwr= 112,862 In lb Mwu= 71,764 in lb MWCM= -21,808 In lb M= 162,818 in lb W� Fasteners: F-. Required Fastener Resistance on Critical Side FR= 3,464 LB RTU to Eidsting Curb Fastener Selected Fastener Ex. 16 ga Straps w/ 1/2" Thru Bolts & Fender Washers Inner & Outer Curb Min. Plumber of Fasteners Over RTU: Notes: I. Submittal excludes existing curb 2. Roof structure by others Bowdoin G. Hu FL # P. E. 70878 JUL 1 1 2019 ST. Lucia County, Permitting 2185 lb per (rearThru) 3 each