HomeMy WebLinkAboutSUBMITTAL- Submittal #03 30 00-16.0
03 30 00 - Cast -in -Place
SCANNED Concrete
Ahrens Companies St. Lu LAYcie County Project: 18-000037- MRO Hangar - Treasure Coast Int. Airport
1461 Kinetic Road 3191 Jet Center Terrace
Lake Park, Florida 33403 Fort Pierce, Florida 34982
Phone: (561) 863-9004
Fax: (561) 863-9007
Structural Concrete Mixes
SPEC SECTION: 03 30 00 - Cast -in -Place Concrete SUBMITTAL MANAGER: LaMaya Jennings (AHRENS COMPANIES)
STATUS: Open DATE CREATED: 06112/2019
ISSUE DATE: // REVISION: 0
RESPONSIBLE RF CONCRETE CONSTRUCTION, INC. RECEIVED FROM: JEREMY FOULKS
CONTRACTOR:
RECEIVED DATE: 06/13/2019 SUBMIT BY: 06/13/2019
FINAL DUE DATE: 06/20/2019 LOCATION: Vero Beach
TYPE: Product Information COST CODE:
APPROVERS: Sean Day (Avcon Engineers & Planners), Sue Finney (Avcon Engineers & Planners), Ian Johnson (Avcon Engineers &
Planners), Robert Palm (Avcon Engineers & Planners)
BALL IN COURT:
Sean Day (Avcon Engineers & Planners), Sue Finney (Avcon Engineers & Planners), Ian Johnson (Avcon Engineers & Planners)
, Robert Palm (Avcon Engineers & Planners)
DISTRIBUTION:
JEREMY FOULKS (RF CONCRETE CONSTRUCTION, INC.) , NANCY CORCORAN (RF CONCRETE CONSTRUCTION, INC.)
DESCRIPTION:
This mix needs to go to the structural engineer, not the civil engineer. These are mixes for everything except the hanger slab.
ATTACHMENTS:
MRO Hangar Structutal Concrete 201906121215 odf
SUBMITTAL WORKFLOW
#
NAME
SUBMITTERI
APPROVER
SENT DATE
DUE DATE
RETURNED
DATE
RESPONSE
ATTACHMENTS
COMMENTS
1
Sean Day
Approver
6/20/2019
Pending
2
Sue Finney
Approver
6/20/2019
Pending
3
Ian Johnson
Approver
6/20/2019
Pending
4
Robert Palm
Approver
6/20/2019
Pending
FILE COPY
Ahrens Companies Page 1 of 2 Printed On: 06/13/2019 08 :26 AM
AHERNS COMPANIES
1461 KINETIC ROAD
LAKE PARK, FL 33403
Shop Drawing / Product Date Review
REVIED BY LaMaya Jennings DATE 6M 3/2019
REVIEWED FOR COMPLIANCE
APPROVED
APPROVED AS NOTED
REJECTED
Review is for conformance with design concept only and intent and
general compliance with contract documents/specifications. Subcontractor
shall be responsible for all quantities, dimensions, compliance with
documents and related codes, verification of work and trades and
fabrication or techniques of construction.
BY
Submittal #03 30 00-16.0
03 30 00 - Cast -in -Place
COPIES TO
Concrete
Ahrens Companies Page 2 of 2 Printed On: 06/13/2019 08 :26 AM
Tri-County ReadyMix D Fanem Ready Ma
O North/Central Ready Mix
❑ West Cuast Ready Mix
2500 S.W. 2nd Ave. 801 U.S. Highway One
3928 South Nova Road
515 Gene Green Rd.
115i�,��
Ft. Lauderdale, FL 33315 North Palm Beach. FL 33408
Port Orange, FL 32127
Nokomis, FL 34275
Phone: (954) 761-1944 Phone..(561)904-7007
Phone: (386) 163-5940
Phone:(941)412-1260
,,.�' CONCRETE
rax: (954)760-5925 Pax: (561)904-7024
Fax: (386)763-5969
Fax: (941)412-1609
Materials for Life'
Date Issued 5/7/2019
Submittal No. 25679
Contractor: RF Concrete Construction
PO Box 650789
Vero Beach -
Florida 32965
Project: Treasure Coast International Airport
Dear SirlMadam:
We are submitting the following concrete mix design(s) for approval of use for the above referenced project:
Mix Code Number Description Intended Use
SW6951130 SPEC WIC 0.50 #57
SW695R32 SPEC W/C 0.50 #57 HRWR
THE MIX CODE NUMBER MUST BE USED WHEN ORDERING CONCRETE.
The proposed mixes have been proportioned in accordance with the applicable sections of ACI 211, and the
concrete section of your specifications and/or your request.
The proposed mix design(s) will meet the stated strengths, when test specimens are made, cured and tested in
accordance with current ASTM standards, and evaluated per ACI recommended standards and practices.
It is TITAN Concrete's policy to statistically analyze strength tests as a measure of Quality Assurance. As
required per ASTM C 94-00: Sec. 4.6. please instruct the testing laboratory for this project to include TITAN
Concrete on their distribution list at testreports0titanamerica.com for all strength test reports for this project.
X NO EXCEPTION TAKEN _MAKE CORRECTIONS NOTED
_SUBMIT SPECIFIED ITEMS _REVISE & RESUBMIT
_REJECTED _UNREVIEWED. FOR RECORD PURPOSES ONLY
Checking is only for general conformance with the design concept of the
project and general compliance with the information given in the contract
documents. Any action shown is subject to the requirements of the plans
and specifications. Contractor is responsible for dimensions which shall
be confirmed and correlated at the job site; fabrication processes and
techniques of construction; coordination of his work and that of all other
trades and the satisfactory performance of his work.
AVCON, INC.
By: LDV Date: 6-13-19
t t
Danielle Rexroad
Concrete Quality Technical Support Representative
1992 - 2019 Quadrel, Inc. Pagel
Quadrat !Service SM
TITAN
CONCRIHIM
Mat:rials for Life
DTri-County Ready Mi::.
2500 S.w. Ind Are,
Ft Lauderdale, FL 33315
Phone: (954) 761-1944
Fax: (954)760-5925
DEastem Ready Mix
801 U.S. Ilighuray One
North Palm Beach, FL 33408
Phone: (561) 904-7007
Fax: (561)904-7024
Submittal No. 25679
Dale Issued: 5/7/2019
Customer: RF Concrete Construction
Project: Treasure Coast International Airport Usage
Qvouth/Cemral Ready Mix
3928 South Nor. Road
Port Orange, FL 32127
Phone: (386) 763-5940
Fax: (386)763-5969
�:�_st Coast Ready Mix
425 Commercial Q., Suite B3
Venice, FL 34292
Phone: (941) 486-2220
Fax: (941)486-2222
Mix Coder SW69SR30 Mix Code must be used when ordering concrete.
SPEC W/C 0.50 #57
Material ASTM Spec. Gravity Volume (oz/cy)
Weight (Iblcy)
Cement Type IL
C-595 3.15
600
#57
C-33 2.38
1,600
Manufactured Sand
C-33 2.55
1,246
Water
C-94 1.00
36.0 galley
300
Type A & D Water Reducer
C-494 1.00
30
Air Entrainer
C-260 1.00
2
.Specified Fc: 4000 psi @ 28 days
Specified Slump: 4.00 to 6.00 "
Specified Air. 1.50 To 4.50 %
Designed WIC + P Ratio: 0.50
Designed Volume: 27.00
Designed Unit Weight: 138.7
TOTAL
cuff.
lbs./cu.ft.
3,746
NOTES:
TITAN Concrete has no knowledge or authority regarding where this mix is to be placed; therefore, it is the responsibility of the
project architect, engineer, and/or contractor to ensure that the above designed mix parameters of compressive strength,
water -to -cement ratio, cement content, and air content are appropriate for the anticipated environmental conditions (i.e.
ACI-318, and local Building Codes); and that acceptance testing is conducted in accordance to all applicable ASTM test
procedures by a facility evaluated by and accredited by industry agencies for proper lab protocol and that test results are
evaluated by ACI standards.
Chemical admixtures are added in accordance with the manufacturer's recommendations. TITAN Concrete reserves the right
to adjust these dosages to meet the changes in jobsite, demands.
TITAN Concrete also reserves the right to adjust cementitious contents in accordance to ACI 318.
The minimum requirements for testing of ready mixed concreteat the project site are established in ACI 311.6 Specification for
Ready Mixed Concrete Testing Services when acceptance of concreteas delivered to the site is based on specific
field -measured properties and laboratory -measured compressive strength.
TITAN Concrete requests to be included on the distribution list for test data.
TITAN Concrete reserves the right to substitute material sources that meet the same specification requirements and exhibit
substantially equivalent performance.
Unless indicated otherwise, Titan may use either Type I/ll or Type IL cement in this mix.
X NO EXCEPTION TAKEN _MAKE CORRECTIONS NOTED
_SUBMIT SPECIFIED ITEMS _REVISE & RESUBMIT
REJECTED UNREVIEWED. FOR RECORD PURPOSES ONLY
COMMENTS;
Checking is only for general conformance with the design concept of the
project and general compliance with the information given in the contract
documents. Any action shown is subject to the requirements of the plans
and specifications. Contractor is responsible for dimensions which shall
be confirmed and correlated at the job site; fabrication processes and
techniques of construction; coordination of his work and that of all other
trades and the satisfactory performance of his work.
AVCON, INC.
By: LDV
Dale: 6-13-19
1992- 2019 Quadrel, Inc. Paget Quadrat lSBNlce BM
Date: 5p/2019
Mix Name: SW695R30
mmo
.I
noon
JVVV
8000
7000
6000
5000
4000
3000
onnn
TITAN
t4aleriais for Life'
Units: US
U
• 11
�-
IrW
IMME
mm
®
C 11
m-
r
11
�-I�7�
. ..
II II
In
II
I II
100 200 300 400 500 600 700 4500 5000 5500 6000 6500 7000 7500 8000 8500
Maturity Hours PSI
95%n of tests lie above cross -hatched area
STRENGTH SUMMARY, Compression Either 4" x 8" Or 6" x 12"
Strengths
No. Of Avg 28 Std
Tests Day Dev
---------------------
30 6520 560
DETAILED STRENGTH, Compression -Either 4" x 8" Or 6" x 12"
Batch
Test
Strengths
Number
Number
28 Day
----------------------------------
I60663380
1642115
5920
I60663415
1649115.
6000
I60663415
1649215
6180
I60663416
1649315
6370
I60663416
.1649415
6750
I60663417
1649515
6700
I60663417
1649615
6510
I60663418
1649715
7400
I60663919
1649815
7030
I60663420
1649915
6760
I60663439
1654715
7620
I60663440
1654815
7930
I60663440
PN21015
6380
16O6L3440
1654915
7030
I60663441
PN21115
6860
I60663442
1655115
6380
I60663441
1655015-01
6650
I62103998
D01016
5750
I62103998
D00816
5750
160116094
P000416
7110
I601.16094
P000316
7120
1992-2019Quadmi.Inc. Page3 Quadrel iService SM
DETAILED
STRENGTH, Compression Either 4"
Batch
Test
Strengths
_ Number
Number
28 Day
__________________________________
I62104148
D03716
5590
I62104147
D03616
5970
I60116355
PO01516
6630
I60116356
PO01616
6900
162106304
D09017
6000
160118437
PO065
5830
160227974
FL10218
5990
160227971
FL10118
5850
160228370
FL17218
6670
x 8" Or 6" x 12"
1992-2019 Qmdrel, Inc. Page4 QUadfel!Service SM
OTri-County Ready Mit
derd.ld FL
Ft l:auderdale, FL 33315
TITAN Ft.
+�% CQTIV>CQiE'6E Phone: (954) 761-1944
OFaaem Ready Mix
No U.S. Highway One
North Palm Beach, FL 33406
Phoan(561)904-7007
' Materials for Life` Fax: (954)760.5925
Fax: (561)904,7024
Submittal No. 25679
Date Issued: 517/2019
Customer: RF Concrete Construction
Project: Treasure Coast International Airport Usage
1111onh/Central Ready Mix
3928 Sowh Nova Road
Pot Orange, FL 32127
Phone: (386) 763-5940
Fax: (386)763-5969
„rst Coast Ready Mix
425 Cummetciat Ct., Suite B3
Venice, FL 34292
Phone: (941) 486-2220
Fax: (941)486-2222
Mix Code: SW69SR32 Mix Code must be used when ordering concrete.
SPEC W/C 0.50 #57 HRWR
Material ASTM Spec. Gravity Volume (oz/cy)
Weight (Ib/cy)
Cement Type IL
C-595 3.15
530
#,57
C-33 2.38
1.630
Manufactured Sand
G-33 2.55
1.291
Water
C-94 1.00
32.0 gal/cy
267
Type B Retarder
C-494 1.00
19
Type F High RangeWaterReducer
C-494 1-00
20
Air Entrainer
C-260 1.00
1
Specified Fc : 4000 psi @ 28 days
Specified Slump: 6.50 to 9.50 "
Specified Air: 1.50 To.4.50 %
Designed WIC + P Ratio: 0.50
Designed Volume: 27.00
Designed Unit Weight: 137.7
TOTAL
cuff.
lbs./cu.ft.
3,718
NOTES:
TITAN Concrete has no knowledge or authority regarding where this mix is to be placed; therefore, it is the responsibility of the
project architect, engineer, and/or contractor to ensure that the above designed mix parameters of compressive strength,
water -to -cement ratio, cement content, and air content are appropriate for the anticipated environmental conditions (i.e.
ACI-318, and local Building Codes); and that acceptance testing is conducted in accordance to all applicable ASTM test
procedures by a facility evaluated by and accredited by industry agencies for proper lab protocol and thattest results are
evaluated by ACI standards.
Chemical admixtures are added in accordance with the manufacturer's recommendations. TITAN Concrete reserves the right
to adjust these dosages to meet the changes in jobsite demands.
TITAN Concrete also reserves the right to adjust cementitious contents in accordance to ACI 318.
The minimum requirements for testing of ready mixed concrete at the project site are established in ACI 311.6 Specification. for
Ready Mixed Concrete Testing Services when acceptance of concrete as delivered to the site is based on specific
field -measured properties and laboratory -measured compressive strength.
TITAN Concrete requests tobeincluded on the distribution list for lest data.
TITAN Concrete reserves the right to substitute material sources that meet the same specification requirements and exhibit .
substantially equivalent performance.
Unless indicated otherwise, Titan may use either Type 1/II or Type IL cement in this mix.
X NO EXCEPTION TAKEN _MAKE CORRECTIONS NOTED
_SUBMIT SPECIFIED ITEMS _REVISE & RESUBMIT
REJECTED UNREVIEWED. FOR RECORD PURPOSES ONLY
COMMENTS: Checking is only for general conformance with the design concept of the
project and general compliance with the information given in the contract
documents. Any action shown is subject to the requirements of the plans
and specifications. Contractor is responsible for dimensions which shall
be confirmed and correlated at the job site; fabrication processes and
techniques of construction; coordination of his work and that of all other
trades and the satisfactory performance of his work.
AVCON, INC.
By: LDV Date: 6-13-19
tv9z-zol9QasarelInc. Pages ----- ----- sM
Date: 5/7/2019
Mix Name:
7000
6590 --
moo
5500
5000
4500 i
4000 j
3500
SW69SR32
.I
7000
6500
6000
5500
5000
4500
4000
3500
teTITAN
CON(CRETE
h1aterfals for Life'
units: US
iI
loom,
r r
moo
■o
�
a l i
■■■
! ■■
l l
/
®�
■ r ■■
L 1.
rr®�
1 � ■
■
t t
100 200 300 400 500 600 700 3000 3500 4000 4500 5000 5500 6000 6500 7000 7500 6000 VV
Maturity Hours PSI
95% of tests lie above cross -hatched area
STRENGTH SUMMARY, Compression Either 4" x 8" Or 6" x 12"
Strengths
No. Of Avg 28 Std
Tests Day Dev
----------------------------
19 5590 650
DETAILED
STRENGTH, Compression Either 4" x 8" Or 6" x 12"
Batch
Test
Strengths
Number
----------------------------------
Number-
28 Day
786527
EL-234
6510
786533
EL-235
6580
786538
EL-236
6620
786546
EL-237
6580
786550
EL-238
6590
786554
EL-239
6560
523397
E523397
4890
510093
E510093
5470
595713
E595713
5540
511055
E510055
5680
538803
E538803
5120
573308
E573308
5130
511883.
E511883
5720
560082
E560082
5540
590673
E590673
4620
590883
E590883
5460
I69090943
M81142A
4590
I69090943
M811#3
4550
I69090942
M811#1
4560
1992- 20L9. Quudre61nc. Page6 Quadrel iService. SM
TITAN'
y �MEIRLC/8
Tian Florida Cement and Aggregates
Quality Control Department
11000 NW 121s1 Way
Medley, FL 33178
+1 (305) 364-2200
vnnv.tiUnameriw.ccm
STANDARD(s):......... ........... ....�................ ASTM C595 / C595M - 10
MANUFACTURING FACILITY :....... ................ PENNSUCO(MEDLEY. FL -USA)
SILO(sl:......... _........... ................. _._... 8.10
Type ...... ................... IL (14)
Date ... _.................... March 11, 2019
Production Date ....... . 2101119 to 2128119
STANDARD REQUIREMENTS..
Item ASTM Units Limit 'Specification Results for
Period
Aircanlenlofmader,voWme C185 % max 12 8
Compressive strength
1 day Clo91C10gM psi 2356.
3 days C109IC109M psi min 1890 4142
7 days C1091C109M psi min 2900 5282
(')28 dads D100'C109M pal min 3620 6759
"Denslly C188 otCaa — _ 3.77
Time of sitting
near nisi mmures mmgB 108
Vicat. C191 hours - max 7
NOTES:
This product and the dnkerused In its production vrene manufactured in the United States of America.
The aneuntof nsoslone In the finish cement win not wry by more than H-2.5 rates Is of the Mished cement
017C2 testing vaaa pinioned by CTL Group, quanified vendor to part= Ws testing (AASHTO R18 accredited and IAS 17025 accrddited).
TWs product aim meets the requirements of ASTM C1t57 Type GU and Type MS.
"Valve reported for Compressive strength for 28days o vrespmids to the prevous monthly period.
"Test result represents Per averegeofthe previous 12 months.
Cynthia Jimenez
QC Manager
Form Rev.11 May2018
EmBASF
We create chemistry
Certificate of. Conformance
MasterAir® AE 90 Admixture (formerly MB-AE 90)
BASF Corporation Air -Entraining Admixture for Concrete
I, Richard Hubbard, Sr. Technical Marketing Specialist for BASF Corporation, Cleveland, Ohio,
certify:
That MasterAir AE 90 admixture is a BASF Corporation Air -Entraining Admixture for concrete;
and
That MasterAir AE 90 and MB AE 90 admixture are the same product having identical
composition, differing only in designation; and
That no calcium chloride or chloride based ingredient is used in the manufacture of MasterAir AE
90 admixture; and
That MasterAir AE 90 admixture, based on the chlorides originating from all the ingredients used
in its manufacture, contributes less than 0.000068 percent (0.68 ppm) chloride ions by weight of
the cement when used at the rate of 65 ml- per 100 kg (1 fluid ounce per 100 pounds) of cement;
and
That MasterAir AE 90 admixture meets the requirements of ASTM C260, the Standard
Specification for Air -Entraining Admixtures for Concrete, as well as the requirements for air -
entraining admixtures as specified in Corps of Engineers' CRD-C 13 and AASHTO M154.
6��OAJ j A64 -Ml
Richard Hubbard
Sr. Technical Marketing Specialist
BASF Corporation MASTER®
.Admixtures Systems
23700 hi Boulevard »BUILDERS
Cleveland, Ohio 44122
Telephone (216) 839-7500 SOLUTIONS
®®BASF
We create chemistry
Certificate of Conformance
MasterGlenium® 7920
BASF Corporation Admixture for Concrete
To Whom It May Concern:
I, Richard Hubbard, Sr. Technical Marketing Specialist for BASF Corporation, Cleveland, Ohio,
certify:
That MasterGlenium 7920 admixture is a high -range water -reducing admixture manufactured by
BASF Corporation; and
That no calcium chloride or chloride based ingredient is used in the manufacture of
MasterGlenium 7920 admixture; and
That MasterGlenium 7920 admixture, based on the chlorides originating from all the ingredients
used in its manufacture, contributes less than 0.00021 percent (2.1 ppm) chloride ions by weight
of the -cement when used at the rate of 65 mL per 100 kg (1 Fluid ounce per 100 pounds) of
cement; and
That MasterGlenium 7920 admixture meets the requirements for a Type A, Water -Reducing and
Type F, Water -Reducing, High Range Admixture specified in ASTM C494IC494M and AASHTO
M194, the Standard Specification for Chemical Admixtures for Concrete, as well as the
requirements for Type A and Type F admixtures as specified in. Corps of Engineers' CRD-C 87.
j -,,,.,gam
Richard Hubbard
Sr. Technical Marketing Specialist
BASF Corporation
Admixtures Systems MASTER °
23709 Chagrin 44122Boulevard >>BUILDERS
Cleveland, Ohio 44122
Telephone (216) 839.7500 SOLUTIONS
We create chemistry
Certificate of Conformance
MasterPozzolith® 700 Admixture (formerly Pozzolith 700N)
BASF Corporation Water -Reducing Admixture for Concrete
I, Richard Hubbard, Sr. Technical Marketing Specialist for BASF Corporation, Cleveland, Ohio,
certify:
That MasterPozzolith 700 admixture is a BASF Corporation Water -Reducing Admixture for
concrete; and
That MasterPozzolith 700 admixture and Pozzolith 700N admixture are the same product having
identical composition, differing only in designation; and
That no calcium chloride or chloride based ingredient is used in the manufacture of
MasterPozzolith 700 admixture; and
That MasterPozzolith 700 admixture, based on the chlorides originating from all the ingredients
used in its manufacture, contributes less than 0.00060 percent (6.0 ppm) chloride ions by weight
of the cement when used at the rate of 65 ml- per 100 kg (1 fluid ounce per 100 pounds) of
cement; and
That MasterPozzolith 700 admixture meets the requirements for a Type A, Water -Reducing,
Type B, Retarding, and Type D, Water -Reducing and Retarding Admixture specified in ASTM
C494/C494M and AASHTO M194, the Standard Specifications for Chemical Admixtures for
Concrete, as well as the requirements for Type A, Type B and Type D admixtures as specified in
Corps of Engineers' CRD-C 87.
kjb&4 mU
Richard Hubbard
Sr. Technical Marketing Specialist
BASF Corporatlon
Admixtures Systems MASTER'
23700 Chagrin Boulevard »BUILDERS
Cleveland, Oho 44122
Telephone P6) 839-7500 SOLUTIONS
We create chemistry
Certificate of Conformance
MasterSet® R 961 Admixture (formerly Pozzolith 961 R)
BASF Corporation Admixture for Concrete
I, Richard Hubbard, Sr. Technical Marketing Specialist for BASF Corporation, Cleveland, Ohio,
certify:
That MasterSet R 961 admixture is a BASF Corporation Set Retarding Admixture for concrete;
and
That MasterSet R 961 and Pozzolith 961 R admixture are the same product having identical
composition, differing only in designation; and
That no calcium chloride or chloride based ingredient is used in the manufacture of MasterSet R
061 admixture; and
That MasterSet R 961 admixture, based on the chlorides originating from all the ingredients
used in its manufacture, contributes less than 0.00013 percent (1.3 ppm) chloride ions by weight
of the cement when used at the rate of 65 ml- per 100 kg (1 fluid ounce per100 pounds) of
cement; and
That MasterSet R 961 admixture meets the requirements for a Type B, Retarding and Type D,
Water -Reducing and Retarding Admixture specified in ASTM C494/C494M and AASHTO M194,
the Standard Specification for Chemical Admixtures for Concrete, as well as the requirements
for Type B and Type D admixtures as specified in Corps of Engineers' CRD-C 87.
Richard Hubbard
Sr. Technical Marketing Specialist
BASF Corporation
Admixtures Systems MASTER®
23700 Chagrin Boulevard *BUILDERS
Cleveland, Ohio 44122
Telephone (216):839-7500 SOLUTIONS
We create chemistry
February 16, 2016
Project:
Project location: .
Certificate of Conformance
MasterSure® Z 60 Admixture (formerly RheoTEC Z-60)
BASF Corporation Admixture for Concrete
I, Richard Hubbard, Sr. Technical Marketing Specialist for BASF Corporation, Cleveland, Ohio,
certify:
That MasterSure Z 60 admixture is a Workability -Retaining Admixture manufactured by BASF
Corporation; and
That MasterSure Z 60 admixture and RheoTEC Z-60 admixture are the same product having
identical composition, differing only in designation; and
That no calcium chloride or chloride based ingredient is used in the manufacture of MasterSure
Z 60 admixture; and
That MasterSure Z 60 admixture, based on the chlorides originating from all the ingredients used
in its manufacture, contributes less than 0.00007 percent (0.7 ppm) chloride ions by weight of
the cement when used at the rate of 65 mL per 100kg (1 fluid ounce per 100 pounds) of cement;
and
That MasterSure Z 60 admixture meets the requirements for a Type S, Specific Performance,
Admixture as specified in Table 1 of ASTM C494/C494M and AASHTO M194, the Standard
Specifications for Chemical Admixtures for Concrete.
Richard Hubbard
Sr. Technical Marketing Specialist
BASF Corporation
Admixtures Systems MASTER"
23700 Chagrin Boulevard »BUILDERS
Cleveland,d. Ohio 44122
Telephone (216) 839-7500 SOLUTIONS