Loading...
HomeMy WebLinkAboutOUTSIDE AIR CALCULATIONI Consulting October 18, 2019 Art Kamm, PE, LEED AP CxA �- Bradly Brown, PE, LEED AP Lon T. Carter, P.E., LEED AP Reply to: Fort Pierce Mike Pella, PE, LEED AP 1, Gordon Scott Plaza 1: Break the Bank Arcade 7173 S. US Hwy 1 Port St. Lucie, FL 34952 RE: Outside Air Calculation St. Lucie County Permit # 1907-0705 To whom it may concern, SCANNED BY St. Lucie County Below is the outside air calculation provided,as requested for the above referenced project. Space Data (from Architectural plans): 2262 sq.ft. 64 seats Per 2017 Florida Building Code — Mechanical, 6t' edition Chapter 4, Ventilation; table 403.3.1.1 epodsandamasement BeW q alleys (sealing areas) 0 10 0.12 — OB dar etlo 100 20 0.W — Pfame Thus: 2262 x 0.18 = 407.16 CFM 64 x 7.5 = 480.0 CFM 887.16 CFM of ventilation air. If you have any questions or require additional information, please contact me directly. Sincerely, KAMM CONSULTING, INC. John �Mayr, LEED AP, BD+C Project Manager 954.448.0792 Florida: 1407 West Newport Center Drive Deerfield Beach, Florida 33442 954-949-2200 954-949-2201 FAX OFFICES Florida: o, 1408 Orange Avenue Fort Pierce, Florida 34950 772.595.1744 772.595.1745 FAX www.kammconsulting.com