HomeMy WebLinkAboutHVAC LOAD CALCULATIONSSFP 2 4 M9
ST, Wde
Harbour Ridge REM-ENCL f
HVAC Load Calculations
for
Harbour Ridge POA
13404 HARBOUR RIDGE BLVD 2A
PALM CITY. FLORIDA 34990
SC'gAt . .
St 4gy �u
"Cie
nr`nfY
SHGC WARNING:
The window performance values consist of the u-factor for the frame,
and Solar Heat Gain Coefficient (SHGC) for the glass. These values have
a huge Impact on the building thermal envelop and may have a significant
Impact on the following:
• the size of the HVAC system(a), $$$
• the duct work layout and design, $$
• delays with permitting, $$$$
• Inspector comments or failed Inspections $$
It Is Important to us that your project stay on schedule and if there are
any changes to the design base It may impact any of the bullet points
above. KO Enemy Design must be contacted immediately at
info enkoenemydesion.com or (561) 327-7272 to help support any
changes to your project Information.
Prepared By:
Karen
KO Ener(
1470 N Conglq
West Palm
Wednesday,
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
�® �G
e d®
&er4, 2019
®�klGJOB
,Rhvac -Residential &tight Commercial HVAC.Loads
-Elite Software Development, Inc.
KO Enerav Design LLC �;.
�11
• Harbour Ridqe REM-ENCL 13404.
1
Pro'ed Report
Ll
G6neraIiPro'ect'Informati6nse '1ZZK'` :ice ME3
'•'`
Project Title: Harbour Ridge REM-ENCL 13404
Designed By: Karen Oliver
Project Date: Wednesday, July 3, 2019
Client Name: Harbour Ridge POA
Client Address: 13404 HARBOUR RIDGE BLVD 2A
Client City: PALM CITY, FLORIDA 34990
Company Name: KO Energy Design
Company Representative: Karen Oliver
Company Address: 1470 N Congress Ave, Ste 106A
Company City: West Palm Beach, FL
Company Phone: 561-327-7272
Company E-Mail Address: info@koenergydesign.com
Company Website: www.koenergydesign.com
Permit Number(s): Jurisdiction: 661000
Desi nData
Reference City: Fort Pierce, Florida
Building Orientation: Front door faces West
Daily Temperature Range: Medium
Latitude: 27 Degrees
Elevation: 25 ft.
Altitude Factor: 0.999
Outdoor Outdoor Outdoor Indoor Indoor
Bulb
Grains
Difference
Deb Wat Bulb RAIHijm BeLHum Dry
Winter: 42 39.4 n/a n/a 70
n/a
Summer: 90 78 59% 50% 75
61
s•
rChec Ei` fires '��;:'.P
Total Building Supply CFM: 1,293 CFM Per Square ft.:
0.739
Square ft. of Room Area: 1,749 Square ft. Per Ton:
624
Volume (ft3): 14,551
Buildin 'Loads a ;?' �w n i :.: r ` ':E* "1, r"tom ""
fiif
Total Heating Required Including Ventilation Air: 26,155 Btuh 26.155
MBH
Total Sensible Gain: 28,429 Btuh 85
%
Total Latent Gain: 5,205 Btuh 15
%
Total Cooling Required Including Ventilation Air: 33,634 Btuh 2.80
Tons (Based On Sensible + Latent)
`Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J Bth Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's
performance data at
your design conditions.
C:\ ... \13404 Harbour Ridge Blvd-MJ.rh9 Wednesday, September 4, 2019, 2:32 PM
RfivaomResidential 8 Light Commercial HVAC MOMM
`,_O7EnerpV�De�sign LLG
Elite Software Development, Inc.
Harbour Ridga REM-ENCL 13404
e'i `
m.
Load Preview Report
Ne
ft.
Sa
La
Ne
Se
Htg
Cg
Al,Duct
Scope
To
/ro
Are
(Se
Gai
Gal
Loss
CFM
CFM
CFM
SiZ
Buildino
2.80
624 1,749
28,429
5.205
93,634
26.155 340. 1,293 1,293
System 1
2.80
6241,749
28,429
5,205
33,634
26,155 3401M 1,293 0'
SuoDly Duct Latent
1,284
1,284
_
Zone 1
1.749
28,429
3,921
32,350
26,155 340 1,293
1-Existing
1,559
17,316
2,944
20.260
14,763 192 788 4-0
2-Back Enclosure
122
7,643
505
8,148
6,448 84.348 2-0
3-Fmnt Enclosure
68
3.470
472.
3,942
4,943 64® 158 1-0
CA ...M404 Harbour Ridge Blvd-MJ.rh9 Wednesday, September 4, 2019, 2:32 PM
Rhvac -Re idential & Light Commercial HVAC Loads
Elite 5oftwareMevelopment, Inc.
KO Energv Design LLC
Harbour Ridge:REM-ENCL 13404:
'West Palm DeaOFL,: .....
P
Total Building Summaty Loads
Component An°�. Lt,
en�, �Tdtalr
y `d3"
Descri t'on a.
s :r,
Gam,
. Gai�fi
1A-hw-o: Glazing -Single pane, operable window, heat-
133.2 3,358
0
5,415 5,415
absorbing, wood frame, U-value 0.9, SHGC 0.48
NSISGD770: Glazing-NSI Windows & Doors SDG770
190.8 5,932
0
7,853 7,853
Gray Tint, U-value 1.11, SHGC 0.43
11 D: Door -Wood - Solid Core, U-value 0.39
20 219
0
203 203
13A-5ocs: Wall -Block, board insulation only, R-5 board
927.1 3,246
0
1,773 1,773
insulation, open core, siding finish, U-value 0.125
12E-Osw: Wall -Frame, R-19 insulation in 2 x 6 stud
30.7 58
0
36 36
cavity, no board insulation, siding finish, wood studs,
U-value 0.068
16E-30:Roof/Ceiling-Under Attic with Insulation on Attic
1582.6 1,418
0
1,266 1,266
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Light Tile,
Slate or Concrete, R-30 insulation, U-value 0.032
16B-30: Roof/Ceiling-Under Attic with Insulation on Attic
190 170
0
304 304
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark
Asphalt Shingles or Dark Metal, Tar and Gravel or
Membrane R-30 insulation U-value 0.032
Subtotals for structure:
14,401
0
16,850 16,850
People:
4
800
920 1,720
Equipment:
0
4,873 4,873
Lighting:
0
0 0
Ductwork:
7,351
1,284
4,548 5,832
Infiltration: Winter CFM: 143, Summer CFM: 75
4,403
3,121
1,238 4,359
Ventilation: Winter CFM: 0 Summer CFM: 0
0
0
0 0
Total Building Load Totals:
26,155
5,205
28,429 33,634
s "
CheckFi re'
Total Building Supply CFM: 1,293
CFM Per Square ft.:
0.739
Square ft. of Room Area: 1,749
Square ft. Per Ton:
624
Volume (ft'): 14,551
i a xMn , ,
.Bu'I 'n' '•Loads
;hP .'Sa",H'S.r R"-.'�'*�.Q+ �.! =' '�';7_..„" . a�;,. s: ,.
n, OF 3
Total Heating Required Including Ventilation Air:
26,155 Btuh 26.155
MBH
Total Sensible Gain:
28,429 Btuh 85
%
Total Latent Gain:
5,205 Btuh 15
%
Total Cooling Required Including Ventilation Air:
33,634 Btuh 2.80
Tons (Based On
Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturers performance data at
your design conditions.
C:\ ... \13404 Harbour Ridge Blvd-MJ.rh9 Wednesday, September 4, 2019, 2:32 PM
Wall 13%
Glass 36%
Glass 39%
Roof 6%
Roof 5%
Wall 5%
Infiltration 17%
Ductwork 28%
Door 1 %
Infiltration 13%
Door 1 % People 5%
Ductwork 17%
Equipment 14%
CA ...M404 Harbour Ridge Blvd-MJ.rh9 Wednesday, September 4, 2019, 2:32 PM
Rhvae - Residential &tight Commercial HVAC Loads '
Elite Software Development, Inc.
KO Energy Design LLC .
�..
� Harbour,Ridge REM
ENCL 13404,
W 411
4111!
System 1 System #1 Summmy Loads
Component'
Area
Sen
r
Son
Totals
=Des'' c }do
uan
Loss
i
Gain
Gai"`
1A-hw-o: Glazing -Single pane, operable window, heat-
133.2
3,358
0
5,415
5,415
absorbing, wood frame, U-value 0.9, SHGC 0.48
NSISGD770: Glazing-NSI Windows & Doors SDG770
190.8
5,932
0
7,853
7,853
Gray Tint, U-value 1.11, SHGC 0.43
11 D: Door -Wood - Solid Core, U-value 0.39
20
219
0
203
203
13A-5ocs: Wall -Block, board insulation only, R-5 board
927.1
3,246
0
1,773
1,773
insulation, open core, siding finish, U-value 0.125
12E-Osw: Wall -Frame, R-19 insulation in 2 x 6 stud
30.7
58
0
36
36
cavity, no board insulation, siding finish, wood studs,
U-value 0.068
16E-30: Roof/Ceiling-Under Attic with Insulation on Attic
1582.6
1,418
0
1,266
1,266
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Light Tile,
Slate or Concrete, R-30 insulation, U-value 0.032
16B-30: Roof/Ceiling-Under Attic with Insulation on Attic
190
170
0
304
304
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark
Asphalt Shingles or Dark Metal, Tar and Gravel or
Membrane R-30 insulation U-value 0.032
Subtotals for structure:
14,401
0
16,850
16,850
People:
4
800
920
1,720
Equipment:
0
4,873
4,873
Lighting:
0
0
0
Ductwork:
7,351
1,284
4,548
5,832
Infiltration: Winter CFM: 143, Summer CFM: 75
4,403
3,121
1,238
4,359
Ventilation: Winter CFM: 0 Summer CFM: 0
0
0
0
0
System 1 System #1 Load Totals:
26,155
5,205
28,429
33,634
Check,
Supply CFM: 1,293
CFM Per Square ft.:
0.739
Square ft. of Room Area: 1,749
Square ft. Per Ton:
624
Volume (ft3): 14,551
Total Heating Required Including Ventilation Air:
26,155 Btuh
26.155
MBH
Total Sensible Gain:
28,429 Btuh
85
%
Total Latent Gain:
5,205 Btuh
15
%
Total Cooling Required Including Ventilation Air:
33,634 Btuh
2.80
Tons (Based On Sensible + Latent)
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and
ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according
to the manufacturer's performance
data at
your design conditions.
C:\ ...\13404 Harbour Ridge Blvd-MJ.rh9 Wednesday, September 4, 2019, 2:32 PM
Rhvac - Residential & Light .Commercial 'HVAC Loads
KO EnergPDesign LLC
West Palm Beach FL -33411,
Elite Software Development, Inc.
Harbour Ridge REM-ENCL13404
_ 7
S stem 1 Room Load Summa
Room
No Name "`�'•'SF'
Htg Min
Area Senses ''Htg
.Btuh"^'-GFM
Run Run r 4,ItZg' Clg Min ,
Duch DuctSens Lat�t Cig a
Size "tw-?�•Vel `Btuhtir•f•Btuh'# �.,CFMi:•
Act
Sys
CFMi
--Zone 1--
1 Existing
1,559 14,763 192
4-0
0 17,316 2,944 788
788
2 Back Enclosure
122 6,448 84
2-0
0 7,643 505 348
348
3 Front Enclosure
68 4,943 64
1-0
0 3,470 472 158
158
Duct Latent
1.284
System 1 total
1,749 26,155 340
28,429 5,205 1,293
1,293
Cooling System Su ma
<,
*Cooking , ,Sensible/Latent'" 3
Tons S Id
Semen ble ,r Latent
Btuh "'Btuh r ^
Total`
Btuh
Net Required:
2.80 85% / 15%
28,429 5,205
33,634
CA ...\13404 Harbour Ridge Blvd-MJ.rh9 I Wednesday, September 4, 2019, 2:32 PM
KO Energy Design
561 327-7272
Field Verification Requirement
Project Information
Designed by:
Karen Oliver
Project date:
Wednesday, July 3, 2019
Client name:
Harbour Ridge POA
Client address:
13404 HARBOUR RIDGE BLVD 2A
Client city:
PALM CITY, FLORIDA 34990
Company name:
KO Energy Design
Company phone:
561-327-7272
Field Verification Requirement
All inputs/defaults/building characteristics used for the ACCA Manual J Version 8
calculations must be verified by the Homeowner and/or must be verified by the builder/owner/contractor verifying that what
is built is consistent with the builder's/owners project components used in this report. All data used for Manual J sizing
report is based on RFI received via customer.. K.O. Energy Design must be notified in writing of any said changes to RFI.
Equipment Selection
Equipment selected below was carefully chosen to meet or exceed the FL Energy Efficiency Code. Alternate equivalent
equipment selection shall also meet the attached Energy Code Requirements. Any change in SEER or size of equipment will
require approval and plan revision. K.O. Energy Design must be notified in writing of any said changes.
Manual D Duct Sizing
Duct sizing has been carefully engineered at the stated s.p. Any deviance in duct sizing could impact the performance and
efficiency of selected equipment. Any change or alteration in duct sizing will require approval and possible plan revision.
K.O. Energy Design must be notified in writing of any said changes. Duct sealing Air Distribution System Test to be
performed and made available for Rough Duct Inspection, if required.