October 30, 2019
Grande Construction of Florida Inc. .
Attu. Greg Oldakowski
575 NW Mercantile Pl. # 113
Port St. Lucie, FL 34986
RE: Finished floor waiver
Dear Mr. Oldakowski:
SCANNED
BY
St. Lucie County
Please accept this letter in response to your written request received October 30, 2019 to waive
the finished floor elevation of 18" above the crown of the road. The waiver request is for 9
proposed garages for Palmetto Village, located at 13400 Harbour Ridge Blvd., Palm City.
Pursuant to Section 7.04.01(C-3) of the St. Lucie County Land Development Code, the Planning
and Development Services Director has the authority to grant administrative relief, when
topographical conditions are such that compliance with this subsection would be impracticable
or cause grade level conditions detrimental to adjacent or nearby properties, consistent with the
intent of the Flood Protection regulations and any other applicable portion of this Code.
The Planning and Development Services Director has granted your request for administrative
relief of the finished floor elevation based on the following determinations:
1. The proposed garages are located in Flood Zone X.
2. The proposed finished floor elevation will be between 11.24' NAVD (lowest) and 11.80'
NAVD (highest) which will be 0.6' —1.16, above the elevation of the crown of the road.
3. The elevation of the center line of the adjacent road is 10.90' NAVD at the entry of
Palmetto Village.
4. Raising the finished floor 18" above center line of the road would be impracticable due to
existing constraints that will not allow the finished floor elevation to meet or exceed Is'
above the center line of Harbour Ridge Blvd. The garage slabs will need to tie into varying
existing edge of pavement locations for transition and alleviation ofheight change hazards.
This approval does not in any way constitute authorization to begin construction. Prior to the
commencement of any construction on this property, an application for a specific building permit
must be obtained from this department.
Please feel free to contact me at (772) 462-2822 if you have any questions.
P
ely,
Olson, AICP
Planning and Development Services.Director
cc: Monica Graziani Building and Code Compliance Manager
Jim McGuinness, Interim Building Official
Melissa Brubaker, Zoning Supervisor
ST. LUCIE COUNTY
BOARD OF COUNTY
COMMISSIONERS
LINDA BARTZ
CHAIR
DISTRICTS
CATHY TOWNSEND
VICE -CHAIR
DISTRICT 5
CHRIS DZADOVSKY
DISTRICT 1
SEAN MITCHELL
DISTRICT 2
FRANNIE
HUTCHINSON
DISTRICT 4
HOWARD N TIPTON
COUNTY ADMINISTRATOR
DAN MCINTYRE
COUNTY ATTORNEY
MAILING ADDRESS
2300 VIRGINIA AVENUE
FORT PIERCE, FL 34982
PHONE
(772) 462-2622
TDD
(772) 462-1428
FAX
(772) 462-1581
E-MAIL
OLSONL@STLUCIECO.ORG
WEBSITE
W W W.STLUCIECO.GO V
PLANNING AND DEVELOPMENT
SERVICES DEPARTMENT
Planning Division
October 30, 2019 SCANNED
BY
Grande Construction of Florida Inc. St. Lucie County
Atm. Greg Oldakowski y
575 NW Mercantile Pl. # 113 (Ni N - _ 1
Port St. Lucie, FL 34986
RE: Finished floor waiver
Dear Mr. Oldakowski:
Please accept this letter in response to your written request received October 30, 2019 to waive
the finished floor elevation of 18" above the crown of the road. The waiver request is for 9
proposed garages for Palmetto Village, located at 13400 Harbour Ridge Blvd., Palm City.
Pursuant to Section 7.04.01(C-3) of the St. Lucie County Land Development Code, the Planning
and Development Services Director has the authority to grant administrative relief, when
topographical conditions are such that compliance with this subsection would be impracticable
or cause grade level conditions detrimental to adjacent or nearby properties, consistent with the
intent of the Flood Protection regulations and any other applicable portion of this Code.
The Planning and Development Services Director has granted your request for administrative
relief of the finished floor elevation based on the following determinations:
1. The proposed garages are located in Flood Zone X.
2. The proposed finished floor elevation will be between 11.24' NAVD (lowest) and 11.80'
NAVD (highest) which will be 0.6' —1.16' above the elevation of the crown of the road.
3. The elevation of the center line of the adjacent road is 10.90' NAVD at the entry of
Palmetto Village.
4. Raising the finished floor 18" above center line of the road would be impracticable due to
existing constraints that will not allow the finished floor elevation to meet or exceed 18'
above the center line of Harbour Ridge Blvd. The garage slabs will need to tie into varying
existing edge of pavement locations for transition and alleviation of height change hazards.
This approval does not in any way constitute authorization to begin construction. Prior to the
commencement of any construction on this property, an application for a specific building permit
must be obtained from this department.
Please feel free to contact me at (772) 462-2822 if you have any questions.
Since ely,
eslie Olson AICP
Planning and Development Services Director
cc: Monica Graziani, Building and Code Compliance Manager
Jim McGuinness, Interim Building Official
Melissa Brubaker, Zoning Supervisor
Grande Construction of Florida, Inc.
RESIDENTIAL & COMMERCIAL / DEVELOPERS / CONSTRUCTION MANAGERS
October 30, 2019
St Lucie County - Planning & Development Services
Building & Code Regulation Division
2300 Virginia Ave.
Ft Pierce, FL 34982
Attn: Ms. Leslie Olson, ATCP
Planning & Development Director
'OCT 3 0 2019
o Cr s
Re: Harbour Ridge- Palmetto Village Garage Buildings : 9 New Total
Permit # T 63y elicf of SLC Land Development Code
Please allow this correspondence to serve as request.for relief of the St Lucie Land
Development Code regarding finished floor elevation heights as referenced in said code;
Chapter 7.04.01C.
This project has existing constraints that will not allow for finished floor heights to meet or
exceed 18" above crown of adjacent road, particularly Barbour Ridge Blvd. The crown of
road varies from 12.26' to 11.33' (end -to -end) with the lowest point of 10.90' at the entry to
Palmetto Village.
The intent is to remove asphalt parking spaces in Palmetto Village and construct nine (9)
free-standing garage buildings. The concrete garage slab(s)/floor(s) must tie -into varying
existing edge of pavement locations for transition and alleviation of height change hazards.
By taking the average of existing rear points and existing front points of parking stalls, an
overall finished floor height range will be approximately 11.24' (lowest) to 11.80' (highest).
We appreciate and thank you in advance for the assistance granting relief for this unique
situation. Please do not hesitate to contact us directly with any questions regarding this
matter.
Best Regards,
/ pros•
G cg Oldakowski, President
CC: SLC Permitting/Plan Review
Harbour Ridge POA
Harbour Ridge Property Manager
Project File
575 NW Mercantile Pl. # 113 Port St. Lucie, FL 34986 Ph. 772-336-7240
T
Architectonic Inc
St. Lucie County Building Department Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Ft. Pierce, FL 34982
October 28, 2019
RE: 13400 Harbor Ridge Blvd Project
Permit # 1910-0067
To Whom It My Concern:
Please accept the following responses to the comments dated 10/24/2019 from your agency. Response shown on
plans corresponding (if required) to these comments are noted.
*PLEASE PROVIDE SEPARATE PERMIT APPLICATION FOR EACH PROPOSED GARAGE, PER 101.2 OF THE FORIDA
BUILDING CODE 6TH EDITION, 2017.
Response: CONTRACTOR TO PROVIDE
*PLEASE PROVIDE BUILDING CONSTRUCTION CLASSIFICATION OF PROPOSED GARAGES, PER 602 OF THE FLORIDA
BUILDING CODE 6TH EDTION, 2017
Response: SEE SHEET A-1
*PLEASE PROVIDE EXIT DOOR LOCATION OF EACH PROPOSED GARAGE ON SITE PLAN PER 107 OF THE FORIDA
BUILDING CODE 6TH EDITION, 2017.
Response: CONTRACTOR TO PROVIDE
*PLEASE CLARIFY WHICH CEILING DETAIL IS BEING SUBMITTED, TRUSS DESIGN DRAWINGS SHOW REGID CEILING
DIRECTLY APPLIED OR 7-1-14 OC BRACING VS. TYPICAL WALL SECTION DETAIL ON SHEET A-1 IF PLAN SET, PER 107
OF THE FORIDA BUILDING CODE 6TH EDITION, 2017.
Response: SEESHEETA-1
*PLEASE PROVIDE SOIL CAPACITY, PER 1808 AND 107 OF THE FORIDA BUILDING CODE 6TH EDITION, 2017.
Response: SEESHEETA-1
*PLEASE PROVIDE DECAY AND TERMITE POROTECTION FOR WOOD MATERIAL, PER 2303.1.9.1 OF THE FORIDA
BUILDING CODE 6TH EDITION, 2017.
Response: SEESHEETA-1
*PLEASE PROVIDE MORTAR REQUIREMENTS FOR MASONRY CONSTRUCTION, PER 2103.2 OF THE FORIDA
BUILDING CODE 0 EDITION, 2017.
Response: SEE SHEET A-1
*PLEASE SHOW DETAIL OF EXIT DOOR GENERAL MEANS OF EGRESS PER 1003.5 OF THE FLORIDA BUILDING CODE
6TH EDITION, 2017
Response: SEESHEETA-1
806 Delaware Avenue Tel: 772 460 7751 www.architectonicinc.com
Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 1 of 2
t., Architectonic Inc
*PLEASE PROVIDE FOOTER DIMENSIONS ON TYPICAL WALL SECTION DETAIL ON SHEET A-1 OF PLAN SET PER 107
OF THE FLORIDA BUILDING CODE 6TM EDTION, 2017
Response: SEESHEETA-1
*EACH GARAGE BUILDING REQUIRES A SEPARATE PERMIT.
Response: CONTRACTOR TO PROVIDE
*ADDRESS FOR APPLICATION: 13400 HARBOUR RIDGE BLVD, PROJECT.
Response: CONTRACTOR TO PROVIDE
*PLEASE INDICATE THE PROPOSED FINISHED FLOOR ELEVATION AND THE ELEVATION OF THE CENTER LINE OF
HARBOUR RIDGE BLVDS. MIN. REQUIRED ELEVATION IS 18".
Response: CONTRACTOR TO PROVIDE
*IN CASE THE 18" ABOVE CENTER LINE OF THE ROAD IS CREATING A PROBLEM, THE PLANNING DIRECTOR MAY
GRANT RELIEF OF THE CODE. A WRITTEN REQUEST SHOULD BE DIRECTED ATTENTION LESLIE OLSEN, AICP,
DIRECTOR OF PLANNING AND DEVELOPMENT SERVICES DEPARTMENT. PLEASE INCLUDE IN YOUR LETTER THE
REASON THE REQUEST, THE PROPOSED, THE PROPOSED ELEVATION, THE ELEVATION OF THE CENTER LINE OF THE
ROAD, ADDRESS AND PERMIT NUMBER AND IF THE PROPERTY IS IN A FLOOD ZONE THE MIN. REQUIRED FLOOD
ZONE ELEVATION. PLEASE INDICATE THE REQUEST IS FOR ALL 10 GARAGES. PLEASE SUBMIT THE LETTER TO MY
ATTENTION. A $50.00 FEE IS APPLICABLE AND WILL BE ADDED TO THE PERMIT FEE.
Response: CONTRACTOR TO PROVIDE
*PLEASE BE AWARE THAT ABOVE COMMENTS ONLY REFLECTS THE ZONING REVIEW. THE PLANS EXAMINER
MIGHT HAVE ADDITIONAL COMMENTS.
Response: CONTRACTOR TO PROVIDE
806 Delaware Avenue Tel: 772 460 7751 www.architectonicinc.com
Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 2 of 2
Architectonic Inc
St. Lucie County Building Department Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Ft. Pierce, FL 34982
October 28, 2019 s,cq
RE: 13400 Harbor Ridge Blvd Project ,f RUC/Q)' COUn'
Permit # 1910-0067 fy
To Whom It My Concern:
Please accept the following responses to the comments dated 10/24/2019 from your agency. Response shown on
plans corresponding (if required) to these comments are noted.
*PLEASE PROVIDE SEPARATE PERMIT APPLICATION FOR EACH PROPOSED GARAGE, PER 101.2 OF THE FORIDA
BUILDING CODE 6TH EDITION, 2017.
Response: CONTRACTOR TO PROVIDE
*PLEASE PROVIDE BUILDING CONSTRUCTION CLASSIFICATION OF PROPOSED GARAGES, PER 602 OF THE FLORIDA
BUILDING CODE 0 EDTION, 2017
Response: SEESHEETA-1
*PLEASE PROVIDE EXIT DOOR LOCATION OF EACH PROPOSED GARAGE ON SITE PLAN PER 107 OF THE FORIDA
BUILDING CODE 6TH EDITION, 2017.
Response: CONTRACTOR TO PROVIDE
*PLEASE CLARIFY WHICH CEILING DETAIL IS BEING SUBMITTED, TRUSS DESIGN DRAWINGS SHOW REGID CEILING
DIRECTLY APPLIED OR 7-1-14 OC BRACING VS. TYPICAL WALL SECTION DETAIL ON SHEET A-1 IF PLAN SET, PER 107
OF THE FORIDA BUILDING CODE 6TH EDITION, 2017.
Response: SEESHEETA-1
*PLEASE PROVIDE SOIL CAPACITY, PER 1808 AND 107 OF THE FORIDA BUILDING CODE 6TH EDITION, 2017.
Response: SEESHEETA-1
*PLEASE PROVIDE DECAY AND TERMITE PDROTECTION FOR WOOD MATERIAL, PER 2303.1.9.10F THE FORIDA
BUILDING CODE 6TH EDITION, 2017.
Response: SEESHEETA-1
*PLEASE PROVIDE MORTAR REQUIREMENTS FOR MASONRY CONSTRUCTION, PER 2103.2 OF THE FORIDA
BUILDING CODE 6TH EDITION, 2017.
Response: SEESHEETA-1
*PLEASE SHOW DETAIL OF EXIT DOOR GENERAL MEANS OF EGRESS PER 1003.5 OF THE FLORIDA BUILDING CODE
6TH EDITION, 2017
Response: SEESHEETA-1
806 Delaware Avenue
Fort Pierce, Florida 34950
Tel: 772 460 7751
Fax: 772 460 4244
www.architectonicinc.com
FL Reg #AA26003348 1 of 2
Architectonic Inc
`PLEASE PROVIDE FOOTER DIMENSIONS ON TYPICAL WALL SECTION DETAIL ON SHEET A-1 OF PLAN SET PER 107
OF THE FLORIDA BUILDING CODE 6T" EDTION, 2017
Response: SEESHEETA-1
'EACH GARAGE BUILDING REQUIRES A SEPARATE PERMIT.
Response: CONTRACTOR TO PROVIDE
"ADDRESS FOR APPLICATION: 13400 HARBOUR RIDGE BLVD, PROJECT.
Response: CONTRACTOR TO PROVIDE
"PLEASE INDICATE THE PROPOSED FINISHED FLOOR ELEVATION AND THE ELEVATION OF THE CENTER LINE OF
HARBOUR RIDGE BLVDS. MIN. REQUIRED ELEVATION IS 18".
Response: CONTRACTOR TO PROVIDE
*IN CASE THE 18" ABOVE CENTER LINE OF THE ROAD IS CREATING A PROBLEM, THE PLANNING DIRECTOR MAY
GRANT RELIEF OF THE CODE. A WRITTEN REQUEST SHOULD BE DIRECTED ATTENTION LESLIE OLSEN, AICP,
DIRECTOR OF PLANNING AND DEVELOPMENT SERVICES DEPARTMENT. PLEASE INCLUDE IN YOUR LETTER THE
REASON THE REQUEST, THE PROPOSED, THE PROPOSED ELEVATION, THE ELEVATION OF THE CENTER LINE OF THE
ROAD, ADDRESS AND PERMIT NUMBER AND IF THE PROPERTY IS IN A FLOOD ZONE THE MIN. REQUIRED FLOOD
ZONE ELEVATION. PLEASE INDICATE THE REQUEST IS FOR ALL 30 GARAGES. PLEASE SUBMIT THE LETTER TO MY
ATTENTION. A $50.00 FEE IS APPLICABLE AND WILL BE ADDED TO THE PERMIT FEE.
Response: CONTRACTOR TO PROVIDE
'PLEASE BE AWARE THAT ABOVE COMMENTS ONLY REFLECTS THE ZONING REVIEW. THE PLANS EXAMINER
MIGHT HAVE ADDITIONAL COMMENTS.
Response: CONTRACTOR TO PROVIDE
806 Delaware Avenue Tel: 7724607751 www.architectonicinc.com
Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 2 of 2