Re: Response to Comments on Permit # 1: Prestige Mobil
Concrete, 3825 Selvitz Rd, Ft. Pierce, Florida
Sir:
This letter is in response to your review comment #2.
The tank has emergency vents sized per NFPA 30 Section 22.7.
These vents prevent the internal pressure of both the outer and
inner from exceeding 2.5 P.S.I.G..
NFPA 30A Table 4.3.2.4 requires a minimum distance of 25 feet
from a lot line that is or can be built upon and a protected
tank (ul-2085). However the western property line shares a
boarder with an FEC right-of-way. Based upon our research (see
attached) we determined that a right-of-way is not a buildable
property but rather land used for transportation purposes.
Therefore the 25-foot restriction does not apply. We hope you
agree.
The tank will be outside the 20-foot utility easement and there
is a concrete block wall between it and the property line.
Please
You
Y. uMarsha] 1,;'.
have any questions.
ROBERT W. MARSHALL, P.E.
672 LAWSON STREET
SEBASTIAN, FLORIDA 32958
(772)581-8727
January 9, 2020
St. Lucie County
Planning and Development Services
Building and Code Regulation Division
2300 Virginia Avenue
Fort Pierce, Florida 34982
Re: Response to Review Comments for Prestige Mobile Concrete
Permit Number: 1910-0413
Dear Sir or Madam:
We are submitting the attached plan to address Plan Reviewer
Comment 2.
Please contact us if you have any other questions.
Yours
� truly,,
Y l
Robert W. Marshall, P.E.
Planning & Developmental Services Department
Building R Code Regulations Division,
DEFERRED SUBMITTAL
1910-0413
DEFERRED SUBMITTAL OF DOCUMENTS REQUIRED BEFORE THE FIRST INSPECTION IS CALLED.
1) PROVIDE INFORMATION ON WHAT WILL BE USED TO ADHERE DOWELS INTO EXISTING SLAB. SHEET
F2, TANK FOOTING DETAIL.
2) UPDATE THE GROUNDING SCHEMATIC, PROVIDE THE COMPLETE BONDING AND GROUNDING
SYSTEM.
3) PROVIDE THE CALCULATION FOR THE VOLUME OF CONTAINMENT.