HomeMy WebLinkAboutMISC LETTERSA BlueScope Steel Company
1q!9- oy43
BUTLER MANUFACTURING COMPANY
1540 Genessee • Kansas City, MO 64102
Post Office Box419917
Kansas City, MO 64141-6917
Phone: (816) 958-3000
Butler Order No ............ 19-016052
Builder .......................... RK Davis
Project ........................... Missionary Flights Intl.
Bldg. Location .............. Fort Pierce, FL
RE: Upflift Capacity of VSR panel clips.
To Whom It May Concern:
RECEIVED
DEC 112019
ST. Lucie County, Permitting
December 10, 2019
SCANNED
BY
St. Lucie County
If an S-5 clamp is correctly attached to Butler's VSR panels, then it should not become detached unless the ribs of
the VSR panel are deformed due to failure. The uplift capacity of VSR panels with clips spaced at 2'-6" on center
is 106 psf. Since the VSR panel is 16" wide, the approximate uplift force each VSR clip can resist on this project
before failure is 350 lbs.
If you have any questions, please contact me 816-968-3613.
an-NTNs document has
uli.ciF:,iir�pm�ically signed and
sealed 0yle schiCd, PE
Sincerely, rMane
.pelliKyle SchliciPIE",'
Pn a copies
6c� antaan,t
-0mnsldere,, signed alM sealed,
end [be igytature must to
+re. t: carry elecVOno copy.
°9aI6f261§12.1013:37.09-06'00'
Kyle Schlicht
Project Engineer
�1+utnuitii
`,.` i�ORE10V Sc8
No 85798 yA
q STATE OF
ZONALENG`��`
12/10/2019
1540 GENESSEE STREET
KANSAS CITY, MO 64102
FLORIDA, PE 985798
BUTL ati::ANUFACTURING COMPANY
BUTLER 1540 Genessee • Kansas City, MO 64102
m Post Office Box419917
A BlueScope Steel Company Kansas City, MO 64141-6917
Phone: (816) 968-3000
Butler Order No............ 19-016052
Builder .......................... RK Davis
Project ........................... Missionary Flights Intl.
Bldg. Location .............. Fort Pierce, FL
RE: Load supported on VSR panel clips.
To Whom It May Concern:
December 3, 2019
Butler Manufacturing has tested and approved for gravity loads to be applied to the VSR panel system and
transferred through the VSR panel clip. The load needs to be applied to an S5 clamp attached to the panel ribs. In
order to avoid bending of the panel rib, it is best if the S5 clamp is directly above the VSR clip, but the clamp may
be located on the panel ribs up to 6" away from the panel clip. The load capacity for this condition is 525 lbs. of
gravity load at each panel clip location.
If you have any questions, please contact me 816-968-3613.
Sincerely,
ReasonThls document has
been electroriwlly signed and
sea ad by.Kyle Schlicht. PE
ug nn 1. b4ital Signature with
PnSeal affixed. Printed copies
Kyle Schlich , REof isdocur ant are not
Kyle Schlicht wnsidem.,ssigned and sealed,
and the sig2pture must be
verified,c apy electronic copy.
Project Engineer Oate: 2019 2.03
i9radsv�na n
\\\11111111II/
`PNpPEW .....
No 85798
.p STATE OF
�10`•.,. ..: •4 ice:
tcsS'ONAL'.. ,o
''�/111111111\\
12/03/2019
KYLE ANDREW SCHLICHT
1540 GENESSEE STREET
KANSAS CITY, MO 64102
FFLORIDA, PE #85798
-Ll (6,-vL4s-13
'6/V wide
11718 SE Federal Hwy.. #373
Hobe Sound, FL 33455
(772) 546-5823
Cell: (772) 618-3437
Fax: (772) 545-3734
E-mail: awieder@Wiederenginee(ng.com
December 11, 2019
Stephan Claren
Claren Architecture & Design, Inc
6400 Congress Ave, Suite 2150
Boca Raton, FL 33487
Re: Missionary Flights - Dormitory Building
Permit #: 19-10-0443
Subject: Service Platform Attachment to Roof Panels
To whom it may concern:
RECEIVED
DEC 112019
5T. Lucie County, Permitting
I have reviewed the letter from Kyle Schlicht, PE of Butler Manufacturing Company, dated
December 10, 2019. The capacity of the roof clip used to attach the service platform to
the roof panels (maximum spacing of 2'-6"o.c.) exceed the design uplift loading for the
project and therefore is acceptable.
Please contact my office should you have any questions.
Wieder Engineering, Inc.
F ;5
'. �aninp. rMj
Allen Wiede'r, PE, SECB
FL 43444
r Digitallyslgnedby Allen Weeder,
Allen F� 1 tJ PEFL43444
PE.
$ DN:m=Allen Weeder, PE FL
Weeder, PE)A11444, o=Weeder Engineering,
u' m ou.
,4£y.,,.elialt=awieder@wiederenglneed
FL43444,i Mte:2019.12.11 l0fl35-05'00'
'a,� �•ls h E-
E.- WorkUsUssionwy Flights- Claren ArchitecturelConsboction Adrdnlstration\Bdmust Clips to RoofngVRoe/ Clips at Service Pladormxpd
R _ _ R SHEETMETAL WORKS.
905 WAGNER PLACE FT. PIERCE, FL 34982
PHONE (772) 465-2459 FAX (772) 465-8221
rrsheetmetalwork@gmail.com
December 2, 2019
St. Lucie County
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
RE: Missionary Flights International
3163 Hammond Road Fort Pierce, FL 34946
Permit No. 1910-0443
GENERAL COMMENTS:
Comment on 10/24/2019
See attached new plan that provides framing, construction and attachment details for
rooftop service platform and access to rooftop exhaust fan.
r
en2 on 24f20t duct to a wrappe with Fyre wrap Elite 1.5 Duct Insulation — Grease Duct
E2336, see revised drawing and also see product information sheet provided.
Sincerely,
faW14"-Ov
Richard D. Williams
President/Qualifier
R J SHEETMETAL WORKS, )J„
905 WAGNER PLACE FT. PIERCE, FL 34982
PHONE (772) 465-2459 FAX (772) 465-8221
rrsheetmetalwork@gmail.com
December 2, 2019
St. Lucie County
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982-
RE: Missionary Flights International
3163 Hammond Road Fort Pierce, FL 34946
Permit No. 1910-0443
GENERAL COMMENTS:
Co n_'0%2' /24' 01`9
ee attached new plan that provides framing, construction and attachment details for
rooftop service platform and access to rooftop exhaust fan.
Comment on 10/24/2019
Exhaust duct to be wrapped with Fyre wrap Elite 1.5 Duct Insulation — Grease Duct
ASTM E2336, see revised drawing and also see product information sheet provided.
Sincerely,
AZOIII �`�
Richard D. Williams
President/Qualifier
R `. SHEETMETAL WORKS. Il' `,
905 WAGNER PLACE FT. PIERCE, FL 34982
PHONE (772) 465-2459 FAX (772) 465-8221
rrsheetmetalwork@gmail.com
November 7, 2019
St. Lucie County
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
RE: Missionary Flights International
3163 Hammond Road Fort Pierce, FL 34946
Permit No. 1910-0443
GENERAL COMMENTS
1. See amended plan that identifies the appliance type which is being exhausted by the
Type I Hood. See attached cut sheet with dimensions of the appliance.
2. See amended plan for the dimension from the inside lower edge of the hood to the top
horizontal surface of the appliance in compliance with FMC Section 507.4.1
3. See amended plan that provides framing, construction and attachment details for
rooftop service platform and access to rooftop exhaust fan.
4. See amended plan and cut sheet for clearance reduction system NFPA 96
Figure A.4.2 (h)
Sincerely, �"✓ /
fi4o�
Richard D. Williams
President/Qualifier
FiVED
NOV 12 2019
I Permitting Der�artment
county
St. Lucie , FL