HomeMy WebLinkAboutMISC LETTERSA BlueScope Steel Company 1q!9- oy43 BUTLER MANUFACTURING COMPANY 1540 Genessee • Kansas City, MO 64102 Post Office Box419917 Kansas City, MO 64141-6917 Phone: (816) 958-3000 Butler Order No ............ 19-016052 Builder .......................... RK Davis Project ........................... Missionary Flights Intl. Bldg. Location .............. Fort Pierce, FL RE: Upflift Capacity of VSR panel clips. To Whom It May Concern: RECEIVED DEC 112019 ST. Lucie County, Permitting December 10, 2019 SCANNED BY St. Lucie County If an S-5 clamp is correctly attached to Butler's VSR panels, then it should not become detached unless the ribs of the VSR panel are deformed due to failure. The uplift capacity of VSR panels with clips spaced at 2'-6" on center is 106 psf. Since the VSR panel is 16" wide, the approximate uplift force each VSR clip can resist on this project before failure is 350 lbs. If you have any questions, please contact me 816-968-3613. an-NTNs document has uli.ciF:,iir�pm�ically signed and sealed 0yle schiCd, PE Sincerely, rMane .pelliKyle SchliciPIE",' Pn a copies 6c� antaan,t -0mnsldere,, signed alM sealed, end [be igytature must to +re. t: carry elecVOno copy. °9aI6f261§12.1013:37.09-06'00' Kyle Schlicht Project Engineer �1+utnuitii `,.` i�ORE10V Sc8 No 85798 yA q STATE OF ZONALENG`��` 12/10/2019 1540 GENESSEE STREET KANSAS CITY, MO 64102 FLORIDA, PE 985798 BUTL ati::ANUFACTURING COMPANY BUTLER 1540 Genessee • Kansas City, MO 64102 m Post Office Box419917 A BlueScope Steel Company Kansas City, MO 64141-6917 Phone: (816) 968-3000 Butler Order No............ 19-016052 Builder .......................... RK Davis Project ........................... Missionary Flights Intl. Bldg. Location .............. Fort Pierce, FL RE: Load supported on VSR panel clips. To Whom It May Concern: December 3, 2019 Butler Manufacturing has tested and approved for gravity loads to be applied to the VSR panel system and transferred through the VSR panel clip. The load needs to be applied to an S5 clamp attached to the panel ribs. In order to avoid bending of the panel rib, it is best if the S5 clamp is directly above the VSR clip, but the clamp may be located on the panel ribs up to 6" away from the panel clip. The load capacity for this condition is 525 lbs. of gravity load at each panel clip location. If you have any questions, please contact me 816-968-3613. Sincerely, ReasonThls document has been electroriwlly signed and sea ad by.Kyle Schlicht. PE ug nn 1. b4ital Signature with PnSeal affixed. Printed copies Kyle Schlich , REof isdocur ant are not Kyle Schlicht wnsidem.,ssigned and sealed, and the sig2pture must be verified,c apy electronic copy. Project Engineer Oate: 2019 2.03 i9radsv�na n \\\11111111II/ `PNpPEW ..... No 85798 .p STATE OF �10`•.,. ..: •4 ice: tcsS'ONAL'.. ,o ''�/111111111\\ 12/03/2019 KYLE ANDREW SCHLICHT 1540 GENESSEE STREET KANSAS CITY, MO 64102 FFLORIDA, PE #85798 -Ll (6,-vL4s-13 '6/V wide 11718 SE Federal Hwy.. #373 Hobe Sound, FL 33455 (772) 546-5823 Cell: (772) 618-3437 Fax: (772) 545-3734 E-mail: awieder@Wiederenginee(ng.com December 11, 2019 Stephan Claren Claren Architecture & Design, Inc 6400 Congress Ave, Suite 2150 Boca Raton, FL 33487 Re: Missionary Flights - Dormitory Building Permit #: 19-10-0443 Subject: Service Platform Attachment to Roof Panels To whom it may concern: RECEIVED DEC 112019 5T. Lucie County, Permitting I have reviewed the letter from Kyle Schlicht, PE of Butler Manufacturing Company, dated December 10, 2019. The capacity of the roof clip used to attach the service platform to the roof panels (maximum spacing of 2'-6"o.c.) exceed the design uplift loading for the project and therefore is acceptable. Please contact my office should you have any questions. Wieder Engineering, Inc. F ;5 '. �aninp. rMj Allen Wiede'r, PE, SECB FL 43444 r Digitallyslgnedby Allen Weeder, Allen F� 1 tJ PEFL43444 PE. $ DN:m=Allen Weeder, PE FL Weeder, PE)A11444, o=Weeder Engineering, u' m ou. ,4£y.,,.elialt=awieder@wiederenglneed FL43444,i Mte:2019.12.11 l0fl35-05'00' 'a,� �•ls h E- E.- WorkUsUssionwy Flights- Claren ArchitecturelConsboction Adrdnlstration\Bdmust Clips to RoofngVRoe/ Clips at Service Pladormxpd R _ _ R SHEETMETAL WORKS. 905 WAGNER PLACE FT. PIERCE, FL 34982 PHONE (772) 465-2459 FAX (772) 465-8221 rrsheetmetalwork@gmail.com December 2, 2019 St. Lucie County Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 RE: Missionary Flights International 3163 Hammond Road Fort Pierce, FL 34946 Permit No. 1910-0443 GENERAL COMMENTS: Comment on 10/24/2019 See attached new plan that provides framing, construction and attachment details for rooftop service platform and access to rooftop exhaust fan. r en2 on 24f20t duct to a wrappe with Fyre wrap Elite 1.5 Duct Insulation — Grease Duct E2336, see revised drawing and also see product information sheet provided. Sincerely, faW14"-Ov Richard D. Williams President/Qualifier R J SHEETMETAL WORKS, )J„ 905 WAGNER PLACE FT. PIERCE, FL 34982 PHONE (772) 465-2459 FAX (772) 465-8221 rrsheetmetalwork@gmail.com December 2, 2019 St. Lucie County Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982- RE: Missionary Flights International 3163 Hammond Road Fort Pierce, FL 34946 Permit No. 1910-0443 GENERAL COMMENTS: Co n_'0%2' /24' 01`9 ee attached new plan that provides framing, construction and attachment details for rooftop service platform and access to rooftop exhaust fan. Comment on 10/24/2019 Exhaust duct to be wrapped with Fyre wrap Elite 1.5 Duct Insulation — Grease Duct ASTM E2336, see revised drawing and also see product information sheet provided. Sincerely, AZOIII �`� Richard D. Williams President/Qualifier R `. SHEETMETAL WORKS. Il' `, 905 WAGNER PLACE FT. PIERCE, FL 34982 PHONE (772) 465-2459 FAX (772) 465-8221 rrsheetmetalwork@gmail.com November 7, 2019 St. Lucie County Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 RE: Missionary Flights International 3163 Hammond Road Fort Pierce, FL 34946 Permit No. 1910-0443 GENERAL COMMENTS 1. See amended plan that identifies the appliance type which is being exhausted by the Type I Hood. See attached cut sheet with dimensions of the appliance. 2. See amended plan for the dimension from the inside lower edge of the hood to the top horizontal surface of the appliance in compliance with FMC Section 507.4.1 3. See amended plan that provides framing, construction and attachment details for rooftop service platform and access to rooftop exhaust fan. 4. See amended plan and cut sheet for clearance reduction system NFPA 96 Figure A.4.2 (h) Sincerely, �"✓ / fi4o� Richard D. Williams President/Qualifier FiVED NOV 12 2019 I Permitting Der�artment county St. Lucie , FL