Loading...
HomeMy WebLinkAboutEVALUATION REPORT0 SCANNED BY St. Lucie County ENGINEER EVALUATE EVALUATION REPORT Polyglass USA, Inc. 1111 West Newport Center Drive Deerfield Beach, FL 33442 (954)233-1230 NEMO j etc. Certificate of Authorization #32455 353 Christian Street, Unit #13 Oxford, CT 06478 (203)262-9245 TEST CONSULT CERTIFY Lion Report P12060.02.09-1124 �L52_S9�R28 T Date of Issuance:02/24/2009 Revision 24: 01/24/2018 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the 6h Edition (2017) Florida Building Code sections noted herein. DESCR PilOgfLsfa RuofiJaderiayinents LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the product(s), the Quality Assurance or the production facilitylocation(s). NEMO Ietc. requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by:the words "NEMOIetc. Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report -is. displayed, then it shall be done TJJLmt rre1&"V INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user y the m�a�;yf�JJje�r,°, �r i distributors and shall be available for inspection at the job site at the request of the Building Official"J�(i`— t/d This Evaluation Report consists of pages 1 through 14. REV'E Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59166, Florida DCAAN£1983 CODE COMPLIANCE ST. LUCIEPP��C,,�cOUNTY BOCC The facsimile seal appearing was authorized by Robert Nieminen, P.E. on 01/24/2018. This does not serve as an electronically signed document. CERTIFICATION OF INDEPENDENCE: 1. NEMOietc. does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. NEMOJ etc. is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. 5. This is a building code evaluation. Neither NEMO I etc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was,used for permitting or design guidance unless retained specifically for that purpose. 0-NEM0 I etc. ROOFING COMPONENT EVALUATION: 1. SCOPE: Product Category: Roofing Sub -Category: Underlayment Compliance Statement: Roof Underlayments, as produced by PDlyglass USA, Inc., have demonstrated compliance with the following sections of the a Edition (2017) Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Prove Standard Year 1504.3.1 Wind Uplift FM 4474 2011 1504.3.1 Wind Uplift UL1897 2012 1507.2.3 / 1507.1.1 Physical Properties ASTM D226 2009 1507.2.4 / 1507.1.1, 1507.2.9.2 Physical Properties ASTM D1970 2015 1507.3.3 Physical Properties FRSA/TRI April 2012 2012 1507.11.2 Physical Properties ASTM D6164 2011 1507.11.2 Physical Properties ASTM D6222 2011 TAS 110 - Accelerated Weathering ASTM D4798 2011 3. REFERENCES: int4y Examination Reference Date FM Approvals (TST 1867) Wind Uplift 3004091 01/12/2000 PRI (TST 5878) Physical Properties PRI01111 04/08/2002 PRI (TST 5878) ' Physical Properties PUSA-005-02-01 01/31/3002 PRI (TST 5878) Physical Properties PUSA-013-02-01 12/23/2002 PRI (TST 5878) Physical Properties PU5A-013-02-02 12/23/2002 PRI (TST 5878) Physical Properties PUSA-013-02-03 12/23/2002 PRI (TST 5878) Physical Properties PUSA-018-02-01 07/14/2003 PRI (TST 5878) Physical Properties PUSA-028-02-01 07/13/2005 PRI (TST 5878) Physical Properties PUSA-033-02-01 01/12/2006 PRI (TST 5878) Physical Properties PUSA-035-02-01 09/29/2006 PRI (TST 5878) Physical Properties PUSA-055-02-02 12/10/2007 PRI (TST 5878) Physical Properties PUSA-061-02-02 01/28/2008 PRI (TST 5878) Physical Properties PUSA-076-02-01 02/22/2008 PRI (TST 5878) Physical Properties PUSA-083-02-01 04/14/2008 PRI (TST5878) Physical Properties PUSA-088-02-01 07/29/2009 MTI (TST 2508) Physical Properties JX20H7A 04/01/2008 MTI (TST 2508) Physical Properties RX14E8A 01/29/2009 ERD (TST 6049) Physical Properties 11752.09.99-1 02/08/2000 ERD (TST 6049) Wind Uplift 11757.08.01-1 08/13/2001 ERD (TST 6049) Wind Uplift 11776.06.02 01/16/2003 ERD (TST 6049) Physical Properties 02200.07.03 07/14/2003 ERD (TST 6049) Wind Uplift 'P1740.01.07 01/04/2007 ERD (TST 6049) Physical Properties P5110.04.07-1 04/11/2007 ERD (TST 6049) Wind Uplift P9260.03.08 03/21/2008 ERD (TST 6049) Physical Properties P13450.08.09 08/13/2009 ERD (TST 6049) Wind Uplift P30540.11.09-R1 11/30/2009 ERD (TST 6049) Physical Properties P11030.11.09-1 11/30/2009 ERD (TST 6049) . Wind Uplift P11030.11.09-2 11/30/2009 ERD (TST 6049) Physical Properties P11030.11.09-3 11/30/2009 ERD (TST 6049) Physical Properties P33360.06.10 06/25/2010 ERD (TST 6049) Physical Properties P33370.03.11 03/02/2011 ERD (TST 6049) Physical Properties P33370.04.11 04/26/2011 ERD (TST 6049) Physical Properties P37300.10.11 10/19/2011 NEMO ETC, LLC. Evaluation Report P32060.02.09-R24 Certificote of Aothor.'wtion#32455 6' EDITION (2017) FBC NON-HVH2 EVALUATION FL5259-R28 Polyglass Roof Underlayments; (9S4) 233-1230 Revision 24: 01/24/2018 Page 2 of 14 ONEMOjetc. Enti Examination Reference Date ERD (TST 6049) Physical Properties P40390.08.12-1 08/06/2012 ERD (TST 6049) Physical Properties P40390.08.12-2 08/07/2012 ERD (TST 6049) Physical Properties C41420.09.12-3 - 09/11/2012 ERD (TST 6049) Wind Uplift P39680.03.13 03/04/2013 ERD (TST 6049) Physical Properties P45370.04.13 04/26/2013 ERD (TST 6049) Wind Uplift P1738.02.07-R2 04/29/2013 ERD (TST 6049) Wind Uplift 11757.04.01-1-R1 04/30/2013 ERD (TST 6049) Wind Uplift 'P41630.08.13 08/06/2013 ERD (TST 6049) Wind Uplift P11751.05.03-R1 11/26/2013 ERD (TST 6049) Wind Uplift P11781.11.03-R1 11/26/2013 ERD (TST 6049) Physical Properties P45270.05.14 05/12/2014 ERD (TST 6049) Physical Properties 6020.07.14-1 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-2 09/08/2014 ERD (TST 6049) . Physical Properties 6020.09.14-3 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-4 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-5 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-6 09/08/2014 ERD (TST 6049) Physical Properties P46520.10.14 10/03/2014 ERD (TST 6049) Physical Properties P43290.10.14 10/17/2014 ERD (TST 6049) Physical Properties PLYG-SC7550.03.15 03/24/2015 ERD (TST 6049) Physical Properties P40390.04.15 04/03/2015 ERD (TST 60,19) Physical Properties P44360.10.14-R1 05/18/2015 ERD (TST 6049) Physical Properties PLYG-SC8080.05.15-1 05/20/2015 ERD (TST 6049) Wind Uplift PLYG-SC8905.05.16-1 05/17/2016 ERD (TST 6049) Physical Properties PLYG-SC8080.07.16 07/16/2016 ERD (TST 6049) Wind Uplift PLYG-SC12025.10.16 10/12/2016 ERD (TST 6049) Physical Properties PLYG-SC13040.12.16 12/27/2016 ERD (TST 6049) Physical Properties PLYG-SC11900.03.17 03/10/2017 ERD (TST 6049) Physical Properties PLYG-SC12115.08.17 08/08/2017 ICC-ES(EVL 2396) IBC Compliance ESR-1697 11/01/2014 Miami -Dade (CER 1592) HVHZ Compliance NOA 14-0717.08 01/22/2015 Polyglass USA Manufacturing Affidavit Products Current 02/18/2009 Polyglass USA P/L Affidavit Mule -Hide Cross Ltg 03/01/2008 Polyglass USA Materials Affidavit Polystick SA Compound 08/18/2011 UL, I.I.C. (QUA9625) Quality Control Service Confirmation Exp. 10/05/2018 4. PRODUCT DESCRIPTION: 4.1.1 Elastobase is a fiberglass reinforced, SBS modified bitumen base sheet. 4.1.2 Elastobase P is a polyester -reinforced, SBS modified bitumen base sheet. 4.1.3 Polyglass G2 Base is a fiberglass -reinforced, asphaltic base sheet. 4.1.4 Polyglass APP Base is a fiberglass -reinforced, APP modified bitumen base sheet. 4.2.1 Polystick MTS or Polystick MTS PLUS is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, surfaced with polyolefinic film surface; meets FRSA/TRI April 2012. 4.2.2 Po(ysfick IR-Xe is arnominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with an aggregate surface; meets ASTM D1970. 4.2.3 Polystick TU Plus is a nominal 80-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. NEMO ETC, LL[. Evaluation Report P12060.02.09-R24 Certifrcare ofAuthorizotian #32455 67"EDITION(2017)FBC NON-HVHZ EVALUATION FLS259-R29 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 3 of 14 'ON I etc. 4.2.4 Polystick TU P is a nominal 130-mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester reinforced, with a granular surface; meets FRSA/TRI April 2012. 4.2.5 Polystick TU Max is a nominal 60-mil thick rubberized asphalt waterproofing membrane with a 190 g/m2 polyester fabric surface; meets ASTM D3970 and FRSA/TRI April 2012. 4.2.6 Polyflex SAP, Polyflex SAP FIR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR) are polyester reinforced, APP modified bitumen cap sheets; meet FRSA/TRI April 2012. 4.2.7 Polystick Dual Pro' is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyester fabric surface; meets ASTM D3970. 4.2.8 Polystick Tile Pro' is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. 4.2.9 Polystick MU-X is a nominal 54-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polypropylene film surface; meets AC188 and physical requirements of ASTM D1970 (See Section 5.8). 4.3.1 Elastoflex G TU is a polyester reinforced, modified bitumen tile underlayment composed of a sand -surfaced SBS modified bitumen back -side and granule -surfaced APP modified bitumen top -side. Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System' from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or Hot Asphalt applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. 4.3.2 Elastoflex S6 G and Eiastoflex S6 G FIR are polyester reinforced, SBS modified bitumen cap sheets; meet ASTM D6164. Elastoflex S6 G and Elastoflex S6 G FIR are for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. Elastoflex 56 G is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Elastoflex S6 G FIR is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. 4.3.3 Polyflex G and Polyflex G FIR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222. Polyflex G is for use as an alternate to Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Polyflex G FIR is for use as an alternate to Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. S. LIMITATIONS: 5.1 This is a building code evaluation. Neither NEMOIetc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in the HVHZ. 5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire ratings of this product. 5.4 Polyglass Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering. NEMO ETC, U.C. Evaluation Report P12060.02.09-R24 Certificate of Authorization H32455 6'" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments; (9541 233-1230 Revision 24: 01/24/2018 Page 4 of 14 IAL "FI Nenno l etc. 5.5 Allowable Roof Covers: �fii*..mF;t,� `'v.�.?x'..rt.sY, k�*?",..�` o: fs.s�s.�r.-`'"���:a"�TABLE L�ROOF [OVER OR770NS*4z ,� .:.. 2' )•' �`�*"_,e a�� 'fif�..>-.�ci+e;�}"_ Underlayment Asphalt Shingles Nall -On Tile Foam -On Tile Metal wood Shakes & Shingles Slate Elastobase Yes Yes (Base Sheet in 2-ply rystem) Yes (Base Sheet in 2-ptysys[em) Yes Yes Yes Elastobase P Yes Yes (Base Sheet In 2-ply system) Yes (Base Sheet in 2-ply system) Yes Yes Yes PolyglaSS G2 Base No Yes (Base Sheet in 2-ply rystem) yes (Base Sheet In 2-ply system) No No No yglass APP Base NoYes (ease Sheet in 2-ply system) (Base ShW net -ply system) No No No stick NITS or MTS PLUS Yes Yes No Yes Yes Yes ystick lR-Xe Yes No No No Yes Yes ystick TU Na Yes Yes (See 5.5.1) Na No Na stick TU Plus Yes Yes Yes (See 5.5.1) Yes Yes Yes stick TU Max No Yes Yes (See 5.5.1) Yes No Na stick Dual Pro yes No No Ves Yes Yes stick Tile Pro CoYes Yes Yes Yes (See S.S.1) Yes Yes Yes stick MU-X Yes No No Yes Yes Yes toflex S6G Yes Yes Yes (See 5.5.1) No Yes Yes toflex S6 G FR Yes Yes No No Yes Yes toflex G TU Yes Yes Yes (See 5.5.1) No Yes Yes flexG Yes Yes Yes (See 5.5.1) No Yes Yes Polyflex FR Yes Yes No No Yes Yes flex SAP cr SAP FR Yes Yes Yes (See 5.5.1) No Yes Yes e-Hide SA-APP Cap Sheet A-APP Cap Sheet (FR) Yes Yes Yes (See 5.5.1) No Yes Yes 5.5.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / underlayment combinations. TABLE IA.IU OW!{9,LET{tEADHESIVE"(UNDE(tUITRAFNT �.3-s•? , OM9INATIOrd$ is+: »r i-.-��'- .e�.. i. _. u - Adhesive Florida Product Approval Underlayments DAP Foam Touch'n Seal StormBond Roof Tile Adhesive FL14506 Polystick TU Plus, Polystick TU Max Dow TileBondt" FL22525 Polystick TU P,-Polystick TU Plus, Polyp" SAP or Tile Pro Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro, ICP Adhesives Polyset® AH-160 FL6332 Elastoflex G TU, Elastoflex 56 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR, Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro, ICP Adhesives Polyset® RTA-1 FL6276 Elastoflex G TU, Elastoflex 56 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR, • Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) 'Refer to Tile Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance. NEMO ETC, U.C. Evaluation Report P120E0.02.09-R24 Cenificore ojAurhprrzatipn rl32455 eEDITION(20171 FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments; (9S4) 233-1230 Revision 24: 01/24/2018 Page 5 of 14 ONEMOletc. 5.6 Allowable Substrates: 5.6.1 Direct -Bond to Deck: Polystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: ➢ New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing plywood; New or existing, unprimed OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed Southern Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods "ZIP System" Panels (designed and installed to meet wind loads for project). Nate: Polyglass does not require priming of new or existing plywood or OSB sheathing. New or existing plywood or OSB sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ ASTM D41 primed structural concrete. Polyflex G or Polyflex G FR torch -applied to: ➢ ASTM D41 primed structural concrete. 5.6.2 Bond -to -Insulation: Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: ➢ ASTM C1289, Type II, Class 1 polyisocyanurate or Type V polyisocyanurate-composite insulation; Dens Deck DuraGuard; Dens Deck Prime; orSECUROCK Gypsum -Fiber Roof Board. Elastoflex G TU, Elastoflex S6 G or Elastoflex 56 G FR in hot asphalt to: ➢ Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. Polyflex G or Polyflex G FR torch -applied to: ➢ ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on tile systems, insulation attachment shall be designed by a qualified design professional and installed based on testing of the insulation/underlayment system in accordance with FBC Section 1504.3.1. 5.6.3 Bond to Mechanically Attached Base Laver: Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or Tile Pro self -adhered to: ➢ ASTM D226, Type I or II felt; Elastobase; Elastobase P or Mule -Hide Nail Base. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ ASTM D226, Type I or II felt; Elastobase; Elastobase P, Mule -Hide Nail Base or Polyglass G2 Base. Polyflex G or Polyflex G FR torch -applied to: ➢ Elastobase; Elastobase P, Mule -Hide Nail Base, Polyglass G2 Base or Polyglass APP Base. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For installations under foam -on tile systems, base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein, or as tested in accordance with FBC Section 1504.3.1. NEMO ETC, U.C. Evaluation Report P12060.02.09-R24 Certi/irate afAuthorrzotion#33455 EDITION (2017) F8C NON-HVH2 EVALUATION FL5259-R28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 6 of 14 IONenno l etc. 5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12) does not address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not addressed in FRSA/TRI April 2012 (04-12) and are used in foam -on tile applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04- 12), Appendix A, Table 1A or FBC 1609 for determination of design wind loads. #1 Maximum Design Pressure=-90 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: None Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #2 Maximum Design Pressure =-97 5 osf- Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x 1Y" ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-inch o.c. #3 Maximum Design Pressure =-105 osf., Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: WB-3000 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x 1%" ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-Inch o.c. #4 Maximum Design Pressure=-135 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: (Optional) PG100 or ASTM D41 Base Ply: .(Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Joints: Min. 4-inch wide strips of Elastoflex SA-V over all plywood joints. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #5 Maximum Design Pressure=-315 osf: Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Tile Pro, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #6 Maximum Design Pressure = -622 5 osf: Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #7 Maximum Design Pressure=-3b.0 osf': Deck: Min. 15/32-inch OSB to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 1.25-inch long x 1-inch head diameter round metal cap nails Spacing: Cinch o.c. at the 3-inch wide side laps and 6-inch O.C. at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. NEMO ETC, LLC. Evaluation Report P32060.02.09-1124 Certificate ofAuthorrzation N32455 e EDITION (2017) FBC NON-HVH2 EVALUATION FL5259-R28 Polygla% Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 7 of 14 ONEMOletc. #8 Maximum Design Pressure =-37.5 osf': Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: it ga. x 1.25-inch long x 1-inch head diameter round metal cap nails Spacing: 6-inch o.c. at the 3-inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #9 Maximum Design Pressure =-37 5 osf': Deck: Min.19/32-Inch plywood to meet project requirementsto satisfaction of Authority Having Jurisdiction. Base Sheet: One (1) or two (2) layers ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-inch Idng x 1-inch head diameter round metal cap nails Spacing: 6-inch o.c. at the 3-inch wide side laps and 12-inch c.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt. #10 Maximum Design Pressure =-45 osf': Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: One (1) layer ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diametertin caps Saacing: 4-inch o.c. at the 2-inch wide side laps and 4-inch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional; for use with self -adhering underlayment only) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU, applied in full mopping of hot asphalt. #11 Maximum Design Pressure=-45 osf'- Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Two (2) layers ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-Inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 9-inch o.c. at the 2-inch wide side laps and 9-inch o.c. at two (2) equally spaced staggered center rows. Base Ply.f (Optional; for use with self -adhering underlayment only) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt. #12 Maximum Design Pressure =-45 osf Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 9-inch o.c. at the 2-inch wide side laps and 18-inch o.c. at two (2) equally spaced staggered center rnws. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #13 Maximum Design Pressure =-52 5 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 9-inch o.c. at the 2-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #14 Maximum Design Pressure =-525osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: Simplex Original Cap Nails Spacing: 6-inch o.c. at the 3-inch wide side laps and 6-Inch o.c. at four (4) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. NEMO ETC, LLC Evaluation Report P12060.02.09-R24 CenlJ@ote of Authorization#32455 e EDITION (2017) FBC NON-HVH2 EVALUATION FL5259-R28 Polyglass Roof Underlayments; ISM) 2333230 Revision 24: 01/24/2018 Page 8 of 14 ONEMOletc. #15 Maximum Design Pressure =-52.5 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex Original Cap Nails Spacing: 6-inch o.c. at the 3-inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or Polyflex G, torch -applied. #16 Maximum Design Pressure =-60 osf: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: 11 ga. x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 8-inch o.c. at the 4-inch wide side laps and 8-inch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #17 Maximum Design Pressure =-60 osf: Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: OMG #12 Standard Roofgrip with OMG Flat Bottom Metal Plates Spacing: 12-inch o.c. at the 4-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #18 Maximum Design Pressure =-67 5 osf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underloyment) Fasteners: 12 ga. x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 8-inch o.c. at the 4-inch wide side laps and 8-inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #19 Maximum Design Pressure=-75 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underloyment) Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG 3 Galvalume Steel Plates, OMG Roofgrip #14 with OMG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-inch Insulation Plates or Simplex MAX% Cap Fasteners Spacing: 10-inch o.c. at the 4-inch wide side laps and 10-inch c.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mapping of hot asphalt or torch -applied or Polyflex G, torch - applied. #20 Maximum Design Pressure =-90 osf Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-inch o.c. at the 2-inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #21 Maximum Design Pressure = -90 osf: Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal Plates Spacing: 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #22 Maximum Design Pressure =-90 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having 2 insdiction. Base Sheet: Elastobase (sanded top surface) Fasteners: Trufast #12 DP or Trufast#14 HD with Trufast 3" Metal Insulation Plates Spacing: 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt. NEMO ETC, U.C. Evaluation Report P12060.02.09-R24 Cedilcate ofAuthorizotion N32455 6n"EDITION (2017) FBC NON-HVH2 EVALUATION FL6259-R28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 9 of 14 ONEMOletc. #23 Max!mLtm Design Pressure=-900sf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underloyment) Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG 3" Galvalume Steel Plates, OMG Roofgrip #14 with OMG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-inch Insulation Plates or Simplex MAXX Cap Fasteners Spacing: 9-inch o.c. at the 4-inch wide side laps and 9-inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #24 Maximum Design Pressure =-97.5 osf Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 4-inch o.c. at the 4-inch wide side laps and 4-inch o.c. at four (4) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hilo SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #25 Maximum Design Pressure=-105 osf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-inch o.c. at the 2-inch wide side laps and 6-inch c.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #26 Maximum Design Pressure =-112 5 osf: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga, x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 6-Inch D.C. at the 4-inch wide side laps and 6-Inch c.c. at four (4) equally spaced staggered center rows. Primer: PG100 or ASTM D41 primer at all tin -caps Base Ply: Polystick MTS or Polystick MTS PLUS, self -adhered Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #27 Maximum Design Pressure = -120 Dsf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal Plates Spacing: 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at five (5) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #28 Maximum Design Pressure =-120 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface) Fasteners: Trufast #12 DP or Trufast #14 HD with Trufast 3" Metal Insulation Plates Spacing: 6-Inch o.c. at the 4-inch wide side laps and 6-inch o.c. at five (5) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt. 5.6.4.1 All other direct -deck, adhered Polyglass underlayment systems beneath foam -on tile systems carry a Maximum Design Pressure of -45 psf. NEMO ETC, I.I.C. Evaluation Report P32060.02.09-1124 - certlf)cate of Authorization#32455 e EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28 Potyglass Roof Underlayments; (994) 233-1230 Revision 24: 01/24/2018 Page 10 of 14 ONEMOletc. 5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table IA. Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density designed by a qualified design, professional to resist the elevated pressure criteria. Commorly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk` carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. 5.7 Exposure Limitations: Elastobase, Elastobase P, Polyglass G2 Base or Polyglass APP Base shall not be left exposed for longer than 30-days after installation. Folystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 90-days after installation. Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Dual Pro, Tile Pro or Elastoflex G TU shall not be left exposed for longer than 180-days after installation. Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure limitation, unless the prepared roof covering is to be adhesive -set tile, in which case the maximum exposure is 30 days. Elastoflex S6 G or Elastoflex S6 G FR or Polyflex G or Polyflex G FR does not have an exposure limitation, unless the prepared roof covering is to be adhesive -set tile (Elastoflex S6 G or Polyflex G only), in which case the maximum exposure is 180 days. 5.8 Polystick MU-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226 roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as set forth in Section 4.3, Note 1 ofASTM D1970-15, should be established as to slip resistance. 5.9 Tile Slippage Limitations (FRSA/TRI Aoril 2012 (04-12)), When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles ���, .s "" a r„au3�.a4a�'�'r.At+tEZ'iTLLESEt{�!AG�d.tAAIT�T[pF�i4Hr�IREC[i'�ECK Underlayment Tile Profile TIII: �NSTAtfAtAONs; �" Staging Method �� '�a� �, Maximum Slope Elastoflex G TU Flat SO -tile stack 7:12 Lugged 8-tile stack (6 over 2) 6:12 Elastoflex S6 G or 56 G FR Flat or Lugged 6-tile stack (4 over 2) 4:12 Polystick MTS or MTS PLUS Flat 6-tile stack (4 over 2) 5:12 Lugged 6-tile stack (4 over 2) 4:12 Polystick Tile Pro Flat or Lugged 6-tile stack (4 over 2) 7:12 Polystick TU Max Flat 6-tile stack (4 over 2) or 10-tile stack 7:12 Lugged 6-tile stack (4 over 2) 7:12 Lugged 10-tile stack 6:12 Polystick TU P Flat 6-tile stack (4 over 2) 6:12 Lugged 6-tile stack (4 over 2) 4:12 Polystick TU Plus Flat or Lugged 6-tile stack (4 over 2) 7:12 Flat or Lugged 10-tile stack 6:12 Polyflex G or G FR Flat or Lugged 6-tile stack (4 over 2) q:12 Polyflex SA P or SA P FR Flat or Lugged 6-tile stack (4 over 2) 4:12 NEMO ETC, U.C. Evaluation Report P32060.02.09-R24 Cenifitote ajAuth.rk&im#32455 6n'EDITION (2017)F8C NON-HVHZ EVALUATION FL5259-R29 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 11 of 14 ONEIVIO I etc. 6. INSTALLATION: 6.1 Polyglass Roof Underlayments shall be installed in accordance with Polyglass published installation requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application, and prime the substrate (if applicable). 6.3.1 Non -Tile Applications: Shall be installed in compliance with the codified requirements for ASTM D226, Type II underlayment in FBC Table 1507.1.1 for the type of prepared roof covering to be installed. Elastobase, Elastobase P or Mule -Hide Nail Base may be covered with a layer of Polystick, Polyflex SAP, Polyflex SA P FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR), self -adhered, Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt or Polyflex G or Polyflex G FR, torch applied. Roof cover limitations are those are those associated with the top -layer underlayment, as set forth in Table 1. 6.3.2 Tile Applications: Elastobase, Elastobase P or Mule -Hide Nail Base are limited to use as a mechanically attached base sheet in the "Two Ply System" from FRSA/TRI April 2012 (04-12). Reference is made to Table 1 and Section 5.6.4 herein, coupled with FRSA/TRI April2012 (04-12) Installation Manual. 6.4.2 u,nLan=u ,,, LUMpuance wim me comnea requirements for ASTM D1970 (except Polystick TU P) underlayment in FBC Table 1507.1.1 for the type of prepared roof covering to be installed. Direct -to -Deck with Mechanically Fastened Roof Covers, All self -adhering materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP FR and Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) should be back -nailed in selvage edge seam in accordance with Polyglass / Mule - Hide back nailing guidelines. Nails shall be corrosion resistant, 11 gauge ring -shank type with a minimum 1-inch diameter metal disk or Simplex -type metal cap nail, at a minimum rate of 12" o.c. Polystick TU Plus should be back - nailed using the above noted fasteners and spacing, in area marked "nail area, area para clavar" on the face of membrane. The head lap membrane is to cover the area being back -nailed. All seal -lap seams (selvage laps) must be [k, firmly rolled with a minimum 28 lb. hand .+ 4:x 4 roller to ensure full contact and adhesion. For Dual Pro and Tile Pro, align the edge of the top sheet to the end of the glue pattern (the sheet will overlap the fabric). View of Ovelap Seam of Dual Pro and Tile Pro All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PG5o0 Modified Cement applied in between the application of the lap. Polystick TU Plus, Dual Pro and Tile Pro may not be used in any exposed application such as crickets, exposed valleys, or exposed roof to wall details NEMO ETC, LLC. Evaluation Report P32060.02.09-R24 Certificate of Authoraotion#32455 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL5259-RZ8 Polyglass Roof Undedayments; 1954) 233-1230 Revision 24: 01/24/2018 Page 12 of 14 *NEMO I etc. Repair of Polystick membranes is to be accomplished by applying Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PG500 Modified Cement to the area in need of repair, followed by a minimum 6 x 6 inch patch of the Polystick material of like kind, set and hand rolled in place over the repair area. Patch laps, if needed, shall be installed in a water shedding manner. All Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a minimum of 40-lb weighted -roller or, on steep slopes, use of a stiff broom with approximately 40-lbs of load applied for the field membrane. Hand rollers are acceptable for rolling of patches, laps (min. 28 lb roller) or small areas of the roof that are not accessible to a large roller or broom. 6.4.3 Tile Applications (not allowed for Polystick Dual Pro, IR-XeorPolystick MU-& Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions noted above as a guideline. For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base Sheet fastening shall be not less than FRSA/TRI April 2012 (04-12), Table 1. For adhesive -set tile applications, refer to Section S.6.4 herein. 6.4.4 Two (2) Ply Underlayment Systems• Polystick MTS or MTS PLUS followed by Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Tile Pro, MU-X or Polyflex SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with the top -layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired. Polystick MTS or MTS PLUS followed by Polystick TU P, TU Plus, TU Max, Tile Pro or Polyflex SAP is allowable for use under foam -on tile systems. Limits of use are those associated with the top -layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired. - 6.5.1 Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FIR shall be installed in -compliance with current Polyglass published installation requirements. For use in tile applications: ✓ Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 G is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof. systems or the Hot Asphalt applied "Cap Sheet" in the 'two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 G FIR is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. 6.5.2 For hot -asphalt -applications, Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR shall be fully asphalt -applied to the substrates noted in Section 5.6. Side laps shall be minimum 3-inch and end -laps minimum 6-inch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully adhered in a complete mopping of hot asphalt with asphalt extending approximately 3/8-inch beyond the lap edge. 6.6.1 Polyflex G or Polyflex G FIR shall be installed in compliance with current Polyglass published installation requirements. For use in tile applications: ✓ Polyflex G is for use as an alternate to the Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems (Base Sheet Limited per 5.6.3). ✓ Polyflex G FIR is for use as an alternate to the Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems (Base Sheet Limited per 5.6.3). NEMO ETC, U.C. Evaluation Report P12060.02.09-R24 Certificate of Authorizotion#32455 6"'EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-RZB Polyglass Roof Underlayments; 1954) 233-1230 Revision 24: 01/24/2018 Page 13 of 14 • ONEMO I etc. 6.6.2 Polyflex G or Polyflex G FR shall be fully torch -applied to the substrates noted in Section 5.6. Side laps shall be minimum 3-inch and end -laps minimum 6-inch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully heat -welded and inspected to ensure minimum 3/8-inch flow of modified compound beyond the lap edge. 6_7 Tile Staging: 6.7.1 Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the underlayment. Refer to Table 2 herein, and Polyglass published requirements for tile staging. 6.7.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TRI April 2012 (04-12) must be used on all roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of battens or sail- boards, to prevent tile sliding and/or damage to the underlayment during the loading process. 6.7.3 Polyglass specifies the minimum cure time after installation of self -adhering membranes and before loading of roofing tiles is forty-eight (48) hours. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. B. MANUFACTURING PLANTS: Contact the noted QA agency for information on product locations covered for F.A.C. 611520-3 CA requirements. The following plants have qualified products under their respective physical properties specifications. 9. Fernley, NV, Hazleton, PA & Winter Haven, FL ASTM D1970 Polystick MU-X Hazleton, PA M-D 13-0004 Elastoflex G TU Hazleton, PA &Winter Haven, FL ASTM D1970 Polystick IR-Xe ASTM D1970 & FRSA/TRI April 2012 Polystick TU Plus ASTM D1970 & FRSA/TRI April 2012 Pol stick TU Max Tuscaloosa, AL ASTM D4601, Type II Polyglass G2 Base Winter Haven, FL ASTM D226 (physicals) Elastobase, Elastobase P ASTM D6509 Polyglass APP Base FRSA/TRI April 2012 Polystick MTS, Polystick MTS PLUS FRSA/TRI April 2012 Polystick TU P FRSA/TRI April 2012 Polyflex SAP, Polyflex SA P FR ASTM D1970 Polystick Dual Pro ASTM D1970 & FRSA/TRI April 2012 Polystick Tile Pro ASTM D6164 Elastoflex S6, Elastoflex 56 G FR ASTM D6222 PolyFlex G, Polyflex G FR tYrihYXri�1v3lTl;f_tPq�� 111�'A UL, LLC—QUA9625; (314) 578-3406; k.chancellor@us.ul.com -END OF EVALUATION REPORT - NEMO ETC, LLC. Evaluation Report P12060.02.09-R24 certificate of Authorization#32455 6'"EDITION (20171 FBC NON-HVH2 EVALUATION FLS259-1128 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 14 of 14 SCANNED BY :t Lucie County NOV 0 6 "0I119 9T, 6ugle teunty, Permitting NEone I etca Certlflcate ofAuthorlratlon #32455 353 Christian Street, Unit il13 Oxford, CT 06478 (203)252.9245 MIN€ER EVALUATE U§T €OWULT CERTIFY One Owens Corning Parkway FL10674-R35 Toledo, OH 43659 Date of Issuance: 02/06/2012 (740) 404.7829 Revision 10: 08/15/2019 SCOPE: This Evaluation Report Is Issued under Rule 6113120.3 and the applicable rules and regulations governing the use of construction materials In the State of Florida. The documentation submitted has been reviewed by Robert Nleminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume, The products described herein have been.evaluated for compliance with the 6th Edition (2017) Florida Building Code sections noted herein, DESCRIPTION: Owens Corning Asphalt Roof Shingles LABELING: Labeling shall be In accordance with the requirements of the Accredited Quality Assurance Agency noted herein and FBC 1507.2.7.1 / R905.2.6.1 CONTINUED COMPLIANCE: This Evaluation Report Is valid until the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change, Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nleminen, P.E. of any changes to the product(s), the Quality Assurance or the production facility location(s), NEW Ietc. requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle, ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMOietc, Evaluated" may be displayed In advertising literature, If any portion of the Evaluation Report is displayed, than It shall be done In Its aentirety, INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to thepile/ p]eq a turer or Its distributors and shall be available for inspection at the job site at the requ�i�(theEB, uilldinn Offiicc® q�i ae This Evaluation Report consists of pages 1 through 10, CO®� Prepared by: -= COMPLIANCE ST. LUCIE COUNTY BOCC � EAT€ flf a Robert J,M.Nieminen P.E. *,g. yt The facsimllosaalaPPoaringwaaauthorized bVRobert ^� +' Nlaminen,RE. on 08/15/2019, This deal not servo as an Florida Registration No, 59166, Florida DCA ANE1983 %! Iimg electronically slgnod document, CERTIFICATION OF INDEPENDENCE: 1, NEMOletc. does not have, nor does it Intend to acquire, or will It acquire, a financial Interest In any company manufacturing or distributing products It evaluates. 2, NEMOIatc, Is not owned, operated or controlled by any company manufacturing or distributing products It evaluates, S. Robert Nleminen, P.E. does not have nor will acquire, a financial Interest In any company manufacturing or distributing products for which the evaluation reports are being Issued, 4. Robert Nleminen, P.E. does not have, nor will acquire, a financial Interest In any other entity Involved In the approval process of the product. S. This Is a building code evaluation, Neither NEMOI etc, nor Robert Nleminen, P.E, are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, Is/was used for permitting or deslgn guidance unless retained specifically for that purpose. 02028, NEMO ETC, LLC NNEM0 I ae° ROOFING SYSTEMS EVALUATION! Sub -Category: Asphalt Shingles Compliance Statement! Owens Corning Asphalt Roof Shingles, as produced by Owens Corning, have demonstrated compliance with the following sections of the 61h Edition (2017) Florida Building Code and Florida Building Code, Residential Volume through testing In accordance with the following Standards. Compliance Is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein, 1507,24 R905.2.3 1507.2.5, R905.2,4 15071,7A, R905.2.6,1 1507,2.7,1, R905,2,6,1 Physical Properties Physical Properties Wind Resistance Wind Resistance ASTM D1970 ASTM D3462 ASTM D3162 ASTM 07158 2015 2010 2026 2011 IBM Refereoce Data Owens Corning Declaration Equivalency Declaration 08/06/2019 PRI(TST5878) ASTM D1970 OCF-382.02.01 10/24/2017 UL LLC (CER9626) Physicals & Wind Resistance File R2453, Vol, 3 02/15/2007 UL LLC (CER9626) Physicals & Wind Resistance 20120516-R2453 05/16/2012 UL LLC (TST9628) Physical Properties OSCA20263 04/18/2006 UL LLC (TST9628) Wind Resistance 11CA34308 02/18/2012 UL LLC (TST9628) Physicals & Wind Resistance 4786093137 02/01/2014 UL LLC (TST9628) Wind Resistance 4786126532 02/10/2014 UL LLC (TST9628) Physical Properties Classification letter 02/13/2014 UL LLC (TST9628) Physical Properties Classification letter 10/02/2015 Miami -Dade (CER3592) FBC HVHZ Compliance Various NOAs Various PRI (QUA9110) Quality Control Service Confirmation 04/05/2020 d. PRODUCT DESCRIPTION: 4.1 ACCESSORY STARTERS: 4.1.1 Starter Strip Shingle, Starter strip Plus and SRS TopShield Starter are starter strips for asphalt roof shingles. Meets AD I M U9492. 4.1.2 Starter Shingle Roll Is a mineral -surfaced, fiberglass-relnforced, self -adhering SBS modified bitumen starter strip, nominal 7.2-Inch wide x 33-ft 4-Inch long roll, for use with asphalt shingles, Meets ASTM D1970, 4,2 A4ptiAtTSHINGLES: 4.2.1 Classic' and Supreme' are fiberglass reinforced, 3-tab asphalt roof shingles. Meets ASTM D3462. 4.2.2 Berkshire' are fiberglass reinforced, 4-tab asphalt roof shingles, Meets ASTM D3462, 4.2.3 Duration, TruDefinitlon' Duration, Duration' Premium Cool, TruDefinitlon Duration' Designer Color Collection, TruDefinitlon' Oakridge , Oakridge' and WeatherGuard' HP are fiberglass reinforced, laminated asphalt roof shingles, Meets ASTM D3452, 4.3.1 Berkshire' Hip & Ridge Shingles with Sealant, DuraRldge® Hip & Ridge Shingles with Sealant, ProEdgee Hip & Ridge Shingles and WeatherGuard' HP Hip & Ridge Shingles are fiberglass reinforced, hip and ridge asphalt roof shingles. Meets ASTM D3462. NEMid iff€, LL€ Evaluation Report 037940.02.12•1130 Certftata orAuthon:ation#32455 9ra €Bifm(mil F66 N®N=HVH2 €VALUATION fL10E14-ffi§ Owens Corning Asphalt Roof Shingles Revision 10: 08/15/2019 Page 2 of 10 ONEM010ca 5.1 This Is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nleminen, P.E, are, In any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, Is/was used for permitting or design guidance unless retained specifically for that purpose, 5.2 This Evaluation Report Is not for use In FBC HVHZ jurisdictions, 5.3 Fire Classification Is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire ratings of this product, 5 Wind Classification: 5.4.1 The Owens Corning asphalt shingles noted In Section 4.2 are Classified In accordance with FBC Tables 1507.2.7.1 and R905,2.6,1 to ASTM D3161, Class F and/or ASTM D7158, Class H, Indicating acceptable use In all wind zones up to Va,d =150 mph (Vult =194 mph), Refer to Section 6 for Installation requirements to meet this wind rating. Note: Classification by ASTM D7158 applies only to exposure category B or C, as defined In FBC 1609.4.3, and a mean roof height of 60 feet or less. Calculations by a qualified design professional are required for conditions outside these limitations. Contact the shingle manufacturer for data specific to each shingle, 5.4.2 Starter Strip Shingle, Starter Strip Plus and SRS TopShield Starter noted In Section 4.1.1 and the Owens Corning hip & ridge shingles noted In Section 43 are Classified In accordance with FBC Tables 1507.2,7,1 and R905.2,6,1 to ASTM D3161, Class F, Indicating acceptable use In all wind zones up to Vssd = 150 mph (Vuit = 194 mph), Refer to Section 6 for Installation requirements to meet this wind rating, 5.4.3 Refer to Owens Corning published Information on wind resistance and Installation limitations. 5,S All products In the roof assembly shall have quality assurance audit In accordance with F,A,C. Rule 61G20.3, 6.1 GENERAL: 6.1.1 Roof deck, slope, underlayment and fasteners shall comply with FBC 1507.2 / R905.2 and the shingle manufacturer's minimum requirements, 6.1.2 Underlayment shall be acceptable to the shingle manufacturer and shall hold current Florida Statewide Product Approval, or be Locally Approved per Rule 61G20.3, per FBC Sections 1507.2.3, 1507,2,4 or R905.2.3, 6.1.3 Fasteners shall be In accordance with the shingle manufacturer's published requirements, but not less than FBC 1507.2.6 or R905,2.5, Staples are not permitted. 6.1.4 Owens Corning asphalt shingles are acceptable for use In reroof (tear -off) or recover applications, subject to the limitations set forth In FBC Sectlon 1511 or R908 and published In5tallation Instructions. 6.2.1 Installation of Starter Strip Shingle, Starter Strip Plus and SRS TopShleld Starter shall comply with the Corning current published Instructions, using minimum five (5) nails per strip. Figure 1: Minimum Nailing, Starter Strip Figure 2: Minimum Nailing, Starter Strip Plus NEW €t€, LL€ Evaluation Report 037940.02.12•RIb CertVicote of Authorization #32455 0 €®h10N (2011) FOE N6N=RVR2 €VALWICIN fL106i4.1t10 Owens Corning Asphalt Roof Shingles Revision 10: 08/15/2019 Page 3 of 20 ONEMOleteg 6.2.2 Installation of Starter Shingle Roll shall comply with the Owens Corning current published Instructions, Drip edge t adhesive along eaves Figure 5: Starter Shingle Roll Underiayment edge Starter Shingle Roll adhered directly to underlayment end primed drip edge 6.3 ASPHALT SHINGLES: 6.3.1 Installation of asphalt shingles shall comply with the Owens Corning current published Instructions, using minimum four (4) nails per shingle in accordance with FBC 1507.2.7 or R905.2.6, with the following exceptions: D Berkshire' shingles require minimum five (5) nalls per shingle. r0 WeatherGuard' His shingles require minimum six (6) nails per shingle. Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are required Refer to Owens Corning published Information on wind resistance and Installation limitations. 6.3.1.1 Classics & Supreme: Normal Wind. Areas Area porn vionros normaloa IAI t r 6"Bapoaurs Expostoidn Mansard or Ares pare Hlah Wlnd deavenea y Aroea vionfas fuartn T 10 x Figure 4: Minimum Nailing, Classic & Supreme (Standard Size) Normal Wind Areas Area par& vlantas normaloa a (A) x t" a00 Exposure Exposioidn Mansard or Area pare High Wind deavanos y Areas vlonros fusrrea �� z° ® t• Figure 5: Minimum Nailing, Classic & Supreme (Metric Size) NEM@ Eft, LLE Evaluation Report 037940.02,12-1110 Certocste of Autharfrallon#32455 6M 01TION(260) fK NON•NVNi@VALUAfION fL10674-ff1§ Owens Corning Asphalt Roof Shingles Revision 10: 08/15/2019 Pago 4 of 20 6.3,2.2 Berks Ire°; Figure 6: S-Nall Pattern, Berkshire ONE-moletev 81e1am Strip La Bra do 5e11edor Figure 7: 6-Nall Pattern, Berkshire 8eahmstrlp La the de tellador r, BYr' 8Yf' e'N' 8Yr' 1" t t ti ,S ti1 Aophah rooMgcement Cemanto de nahode astaha Figure 8: Mansard or Steep Slope Pattern, Berkshire IN N€M® €10, me Evaluation Report 037940.02.12-1110 Certificate of Authorization #32455 0 € fifft 12617) PH NON-HVH2 €VALUAfft Pt10674•R39 Owens Corning Asphaft Roof Shingles Revision 10: 08/15/2019 Page 5 of 10 NNEmo I ate. 6.3.1.3 Duration®, TruDefinitlone Duration, Duration® Premium Cool & TruDeflnitlono Duration' Designer Color Collection: 4-Nail Fastening Pattern SuroNail®fastening am width Nall, Typical 1" 12" I I 12" 1" .._term er -,.,_!'= n uwni •,__a.ro 4am"a4ne++'s'=.Y: 5.115" 5.5/8 ewav". Figure 9: Standard 4-Nall Pattern, Duration 6-Nell Fastening Pattern auroNali�fasunine area width. r Nall, Typical 1" IV, ' _ / 12" Rwnirca -busk+.-----',s---`.-�R ---i1 .!_arms rmr .w.rwa=:-.. 1,. 61re" 65/t° ewer.. Figure 10: 6-Nell Pattern, Duration Fastening for Slopes Greater Than 21:12 aurelialM fasFNall, width ypical 12"m Ca 6�uHAa4 1., 6+116" 5.51V + it —71" Four 1" Spots of Asphalt Roofing Cement Figure 11: Mansard or Steep Slope Pattern, Duration N€PAB €T€I LL€ Evaluation Report 037940,02.32-RSO Certificate afAvthoriratlon #32455 §fa €BITION 12110) FOE NBN•RVRS EVALUATION fU@9944RH Owens Corning Asphalt Roof Shingles Revision 10: 08/15/2019 Page 6 of 10 ONSM01atel 6.3.24 TruDeflnitlon'Oakrldae®.Oakrldee®: 4 Nall Pattern Esquema Con clavos 8 5/6" Exposuro Exposfddn de 661opulg. 12, 6 5/0" Exposure I Expas7Nan dS 5 M pulp, Figure 12; Standard 4-Nall Pattern, Oukridge 6 Nall Pattern Esquema con 6 clavos i� S 8/8" Exposuga Exposld6n de 66/8pulp, t2' 8 8/8" gxpo5um ' Exposlddn de 6618 pul6. Figure 13: 6-Nall Pattern, Oukridge WOOD Muffs ITH width P NSY, Typical POP Io Spot, ohNphoR Roofing Commit Fleure 14: Mansard or Steeo.Sleee Pnttnrn. nakrldae N€FAB €f€s LL€ Evaluation Report 037940.02.12•R10 Certificate of Authorlcotlon#32455 Of€tiffm(20111 fit N6N=WVN2 €VALUMION FU85JOA Owens Corning Asphalt Roof Shingles Revision 10: 08/15/2019 Page 7 of 10 6.3.1.5 WeatherGuard® HP: E@®�OTO u 58 rap E,P,eJ W;I r?,11 Figure 15; 6-Nall Pattern, WeatherGuard HP NNoil Pattern quemt con 41avo§ ON 11160 fromulaWluim Eap9su[� 9 Fosta�ars at�Yin�fido a Li iglu b @9pslcido de Villa pp19, 8 sine ores Poaro pow do comegof do fadi0 de0A= 1 pugad4 Figure 16: Mansard or Steep -Slope Pattern, WeatherGuard HP 6.4 HIP & RIDGE SHINGLES: 6.4.1 Installation of asphalt shingles shall comply with the Owens Corning current published Instructions. Y Berkshire' Hip and Ridge Shingles with Sealant and DuraRldge® Hip & Ridge Shingles wlth Sealant require minimum two (2) nails per shingle. 9 WeatherGuard' HP Hip and Ridge Shingles and ProEdgem Hip & Ridge Shingles require minimum four (4) nails per shingle. Refer to Owens Corning published Information on wind resistance and Installation limitations. WM6 €f€r LL€ Evaluation Report 037940.02.12•RSO Cert1flcuteofAuthorlranon#32455 §re €Bifl®N (2611) F®€ NON-HVH2 €VALUA716N F1,166744Ri§ Owens Corning Asphalt Roof Shingles Revision 10: 08/15/2019 Page 8 of 10 6.4.1.1 Berkshire® HIP & Ridge with Sealant and DuraRldgeO Hip & Ridge Shingles with Sealant: Fig. A P11®usllingWi vlonin ro4 Dlr®s41An dpl vlanta predaminante �I411a ® - —a C AVQG I I A I I I I �I I PEr�,oeurt-► Araik, M dt I M Figure 17: Isometric View, Berkshire and DuraRldae 6.4.1.2 WeatherGuarde HP Hip & Ridge Shingles: Fig. A R 4 Dir otbn Wlno A NO@ A I A I I � AA I I axpoe�uru Figure 19: Isometric View, WeatharGuard HP Hip & Ridge Fig, 0 Top view II" II" Figure 18: Plan View, Berkshire and DuraRldae Fig, C Hip & Ridge Shingle Fastening Topvw None Nails 7" 2 2" 1' t' 1 1 o g, Exposure 'I Figure 20: Plan View, WeatherGuard HP Hip & Ridge N€M@ €f€r M Evaluation Report 037940.02,12•1110 Certificate ofAarhorlcatlon #32455 0'" €BMBN 126i71 FOE NBN•HVNZ €VALUMIBN €U0074AM Owens Corning Asphalt Roof shingles Revision 10: 00/15/2019 Page 9 of 10 6.4.1.3 ProEdge° Hip & Ridge Shingles: Prevailing Wind Direction Solhor Strip 46'-' B' Etpotore 7 h' Figure 21: Isometric View, ProEdge ON'Emoletes Standard Fastening Pattern �� »• �� . r 12' Sealant 7�f' S"Etpature I�—f2°� Figure 22: Plan View, ProEdge 7.1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. 7,2 Asphalt shingle wrappers shall Indicate compliance with one of the required classifications detailed In FBC Table 1507.2.7.1 / R905.2.6.1. of this product. QA requirements, PRI Construction I or on Having Jurisdiction In order to MOMS, LLG— 4UA911U I f 3l31 b21•D, END OF EVALUATION REPORT - eva N€MO €fi€, a Evaluation Report 037840,02,12•RSO Crrtlilc0a of Authorization #32455 6'u €bifION (2617) €06 NON•RVNS €VALUMION €L166744M Owens Corning Asphalt Roof Shingles Revision 10t 08/15/2019 Pogo 10 of 10