Loading...
HomeMy WebLinkAboutSOIL COMPACT TESTHeadquarters To' C 1 t ENGINEER' � 1345 U S. Highway 1 # PO Box 78-1'377 Sebastian, FL. 32958 j%% AND TESTINa Sebastian, FL. 3278 Orlando Phone: 772 589 0712 723 Progress Way C.A.# 5693 Sanford, FL. 32771 SOIL COMPACTION REPORT KSMengineering.net ASTM D 1557 and ASTM D 2922 DATE TESTED: January 22, 2020 KSM JOB #: 200298-5d/MH/jo PERMIT #: CONTRACTOR: JOB LOCATION: 1911-0035 Grande Construction 13400 Palmetto Village Bldg 6 Palm City, Florida SCNNSD ;t. Lucie County ITEM TESTED: Compacted Foundation Fill TEST LOCATION DEPTH PEN DRY MAX. DRY PERCENT OF SAMPLE READ DENSITY PROCTOR VALUE (P,GF) COMPACTION 1. N.W. 2. Center 3. S.E. Soil Description: Brown Sand with traces of Rock In Place Moisture: 6.2% Optimum Moisture: 11.0% Max. Dry Density: P.C.F. 113.9 0" -12" @ Test Locations The Density & Penetrometer Readings indicate the Degree of Compaction Meets Minimum Required for Staked Foundation m 50 108.8 113.9 95.5% " 111.1 " 97.5% " 110.3 " 96.8% 115.0 W I E I I I I I G114.0 ................. H 1 I f I I I T 113.01—.._.�_..— _.._�._.. .._..1.._..! P I 1 1 I C I I I I I 112.0 F I I I • I I I I I D 111.0.._.1_.._.I._.._r._..y.._..t..—..: R I I I I I Y I I I I I 8 9 10 11 12 13 14 Moisture - % of Dry Weight Disclaimer: Contractor is responsible to maintain the tested area in the condition that KSM completed the indicated passed compaction test. KSM is not responsible if the tested area has been altered from the approved inspected condition. Email to: greg@grandefl.com Proudly Serving Florida since 1990