HomeMy WebLinkAboutSOIL COMPACT TESTHeadquarters 11345 U.S. Highway 1 Sebastian, FL. 32958 Orlando 723 Progress Way Sanford, FL. 32771 DATE TESTED: PERMIT #: CONTRACTOR: JOB LOCATION T-7C 1 t ENGINEER-11 h f711VIL AND TESTINv SOIL COMPACTION REPORT ASTM D 1557 and ASTM D 2922 January 22, 2020 1911-0036 Grande Construction 13400 Palmetto Village Bldg 2 Palm City, Florida Mailing PO Box 78-1377 Sebastian, FL. 32978 Phone:772-589-0712 C.A.# 5693 KSMengineerin�g.neettt /?IIrG�-,�J KSM JOB #: 200298-2d/MH/jo SQgNNEE) St. Luc B County ITEM TESTED: Compacted Foundation Fill TEST LOCATION PEN DRY MAX. DRY PERCENT OF SAMPLE DEPTH READ DENSITY PROCTOR VALUE (P.C.F) COMPACTION 1. S.E. 0" - 12" 50 113.8 113.9 99.9% 2. Center " " 113.3 99.5% 3. N.W. 110.3 96.8% Soil Description: Brown Sand with traces 115.0 - of Rock W I I I I I I In Place Moisture: E I I I I I 6.2% G I 114.0 ..—.i—..——..—�.—. i..—.. i ..—... Optimum Moisture: H I I I I I I 11.0% T I 113.0 j—..—.i_..— Max. Dry Density: P.C.F. P 113.9 I I I I I C I @ Test Locations The 112.0 ••— I— •—•I•—••-4•—••—!••— a ••—••• Density & Penetrometer F I I I I I Readings Indicate the I I I I I Degree of Compaction Meets D 111.0 ••—•I—• — p— —r — y -- y — Minimum Required R I I I I for -Staked Foundation Y I I I I 110.0 �..—.;—..—..—..—;.—..�..—.. I ..—.., a 9 10 11 12 13 14 �s•` J�\E �' K�(� �''•, Moisture - % of Dry Weight EN • N • •[�- Disclaimer: Contractor is responsible to maintain the tested area in the condition that KSM completed the indicated passed compaction test. gD PzP•• �� KSM is not responsible if the tested area has been ' t%P �'nt• •'�NC9+�.•� altered from the approved inspected condition. 1/23/2020 Email to: greg@grandefl.com Proudly Serving Florida since 1990