HomeMy WebLinkAboutENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTIONENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Community Affairs
EnergyGauge FlaCom vl.22 FORM 40OA-2001
Whole Building Performance Method for Commercial Buildings
L Jurisdiction: PORT ST LUCIE, ST LUCIE COUNTY, FL (661200)
Short Desc:
Mets Stadium
Project:
Mets Stadium
Owner:
Address:
•
525 NW Peacock Blvd.
City:
Port St. Lucie
State:
FL
PermitNo:
0
Zip:
34986
Storeys:
4
Type:
Office (Business)
GrossArea:
19117
Class:
Addition to existing Building
Net Area:
19117
Max Tonnage: 50 (if different, write in)
Compliance Summary
Component Design Criteria Result
Gross Energy Use 92.85 100.00 PASSES
Other Envelope Requirements - A PASSES
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
PASSES
PASSES
PASSES
PASSES
PASSES
PASSES
Yes/No/NA
IMPORTANT NOTE. An b4Put report Print -Out from EnergyGauge FlaCom of
this design building must be submitted along with this Compliance Report.
SCANNED
BY
St. Lucie County
7/17/2003
EnergyGauge FlaCom FLCCSB v1.22
I
COMPLIANCE CERTIFICATION:
I hereby certify that the plans • and
specifications covered by this calculation are
in compliance with the Florida Energy
Efficiency Code.
PREPARED BY• D uee M_ caniniley, PE
DATE:
Review of the plans and specifications covered by this
calculation indicates compliance with the Florida Energy
Code. Before construction is completed, this building will be
inspected for compliance in accordance with Section
'553.908, F.S.
BUILDING OFFICIAL:
DATE:
I hereby certify that this building is in compliance
with the Florida Energy Efficiency Code.
OWNER AGENT -
DATE:
If required by Florida law, I hereby certify
(') that the system design is in
compliance with the Florida Energy Code.
REGISTRATION
No.
ARCHITECT:
ELECTRICAL SYSTEM DESIGNER:
Darcee Mcaninley, PE
Florida/58108
LIGHTING SYSTEM DESIGNER:
Darcee Mcaninley, PE
Florida/58108
MECHANICAL SYSTEM DESIGNER:
Darcee Mcaninley, PE
Florida/58108
PLUMBING SYSTEM DESIGNER:
David A Wojcieszak, PE
Florida/58108
(') Signature is required where Florida Law requires design to be performed by registered design professionals.
Typed names and registration numbers may be used where all relevant information is contained on signed/sealed
plans.
7/17/2003
EnergyGauge FlaCom FLCCSB v1.22
2
Project: Mets Stadium
Title: Mets Stadium
Type: Office (Business)
Location: PORT ST LUCIE, ST LUCIE COUNTY, FL (661200)
(WEA File: DAYTONABEACILTM
Whole Building Compliance
Design Reference
Total 90.41 100.00
ELECTRICITY 90.41 100.00
AREA LIGHTS
11.08
22.84
HEAT REJECT
7.02
7.00
MISC EQUIPMT
0.73
0.73
PUMPS & MISC
3.09
2.89
SPACE COOL
43.67
41.71
VENT FANS
24.82
24.83
Credits & Penalties (if any):
Reheat Penalty: 1.027
Modified Points: = 92.85 '
PASSES
7/17/2003
EnergyGauge FlaCom FLCCSB v1.22
3
z
Project: Mets Stadium
Title: Mets Stadium
Type: Office (Business)
Location: PORT ST LUCIE,
ST LUCIE COUNTY, FL (661200)
(WEA File: DAYTONABEACILTM
Other Envelope Requirements
Item Zone
Description
Design
Limit
Meet Req.
Storage Roof AHU NI
Exterior Roof - Max Uo Limit
0.05
0.09
Yes
Conference Ro AHU N3
Exterior Roof - Max Uo Limit
0.05
0.09
Yes
Laundry Roof AHU N4
Exterior Roof - Max Uo Limit
0.05
0.09
Yes
Ticket Roof AHU N5
Exterior Roof - Max Uo Limit
0.05
0.09
Yes
Electric Room AHU N7
Exterior Roof - Max Uo Limit
0.05
0.09
Yes
Skybox Roof AHU NI 1
Exterior Roof - Max Uo Limit
0.05
0.09
Yes
Storage Roof AHU N2
Exterior Roof - Max Uo Limit
0.05
0.09
Yes
Skybox Roof AHU N12
Exterior Roof - Max Uo Limit
0.05
0.09
Yes
Skybox Roof AHU N13
Exterior Roof- Max Uo Limit
0.05
0.09
Yes
Meets Other Envelope Requirements
External Lighting Compliance
Description Category Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (W)
(Sgft or ft)
None
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22
Project: Mets Stadium
Title: Mets Stadium
Type: Office (Business)
Location: PORT ST LUCIE, ST LUCIE COUNTY, FL (661200)
(WEA File: DAYTONABEACH.TM
Lighting Controls Compliance
Acronym Ashrae
Description
Area
No. of
Design
Min
Compli-
ID
(sq.ft)
Tasks
CP
CP
ance
Storage Nl 46
Storage & Warehouse - Fine Active
982
1
3
2
PASSES
Storage
Conference 132
Conference/meeting(Multiple
5,187
1
18
4
PASSES
Functions)
Laundry 87
Laundry - Ironing & Sorting
1,032
1
2
2
PASSES
Tickets 132
Conference/meeting (Multiple
9,316
1
20
7
PASSES
Functions)
Electric Room 4
Electrical Mechanical Equipment
179
1
2
2
PASSES
Room - General
AHU N11 133
Banquet/Multi purpose (Multiple
480
1
2
2
PASSES
Functions) Alt 78
Storage N2 46
Storage & Warehouse - Fine Active
982
1
2
2
PASSES
Storage
AHU N12 133
Banquet/Multi purpose (Multiple
480
1
2
2
PASSES
Functions) Alt 78
AHU N13 133
Banquet/Multi purpose (Multiple
480
1
2
2
PASSES
Functions) Alt 78
PASSES
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22
Project: Mets Stadium
Title: Mets Stadium
Type: Office (Business)
Location: PORT ST LUCIE, ST LUCIE COUNTY, FL (661200)
(WEA File: DAYTONABEACH.TM
System Report Compliance
AEU NI System 1
Variable Air Volume Built-up No. of Units
System
1
Component Category
Capacity Design Eff Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System Compliance Not Applicable
PASSES
Air Handling Air Handler (Supply) -
1.25 1.25
PASSES
System -Supply Variable Volume
AHU N2 System 2
Variable Air Volume Built-up No. of Units
System
1
Component Category
Capacity Design Eff Design IPLV
Comp-
Eff Criteria IPLV - Criteria
liance
Cooling System Compliance Not Applicable
PASSES
Air Handling Air Handler (Supply) -
1.25 1.25
PASSES
System -Supply Variable Volume
AHU N3 System 3
Variable Air Volume Built-up No. of Units
System
1
Component Category
Capacity Design Eff Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System Compliance Not Applicable
PASSES
Air Handling Air Handler (Supply) -
1.25 1.25
PASSES
System -Supply Variable Volume
AHU N4 System 4
Variable Air Volume Built-up No. of Units
System
1
Component Category
Capacity Design Eff Design IPLV
Comp-
,
Eff Criteria IPLV Criteria
liance
Cooling System Compliance Not Applicable
PASSES
Air Handling Air Handler (Supply) -
1.25 1.25
PASSES
System -Supply Variable Volume
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22
AHU N5 System 5
Variable Air Volume Built-up No. of Units
System
1
Component
Category
Capacity'Design Eff Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System
Compliance Not Applicable
PASSES
Air Handling
Air Handler (Supply) -
1.25 1.25
PASSES
System -Supply
Variable Volume
AHU N7 System 7
Variable Air Volume Built-up No. of Units
System
1
Component
Category
Capacity
Design Eff Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System
Compliance Not Applicable
PASSES
Air Handling
Air Handler (Supply) -
1.25 1.25
PASSES
System -Supply
Variable Volume
AHU N11 System 11
Variable Air Volume Built-up No. of Units
System
1
Component
Category
Capacity
Design Eff Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System
Compliance Not Applicable
PASSES
Air Handling
Air Handler (Supply) -
1.25 1.25
PASSES
System -Supply
Variable Volume
AHU N12 System 12
Variable Air Volume Built-up No. of Units
System
1
Component
Category
Capacity
Design Eff Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System
Compliance Not Applicable
PASSES
Air Handling
Air Handler (Supply) -
1.25 1.25
PASSES
System -Supply
Variable Volume
•
I
AHU N13 System 13
Variable Air Volume Built-up No. of Units
System
1
Component
Category
Capacity
Design Eff Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System
Compliance Not Applicable
PASSES
Air Handling
Air Handler (Supply) -
1.25 1.25
PASSES
System -Supply
Variable Volume
7/17/2003 EnergyGauge FlaCom FLCCSB vl.22
PASSES
Plant Compliance
Description Installed Size
Design Min Design Min
Category Comp
No
Eff Eff IPLV IPLV
liance
Open reciprocating 1 50
2.7 2.7 2.8 2.8
Water Chilling Pkg PASSES
chiller
(Reciprocating) Elec.
Operated <=150
PASSES
Project: Mets Stadium
Title: Mets Stadium
Type: Office (Business)
Location: PORT ST LUCIE, ST LUCIE COUNTY, FL
(661200)
(WEA File: DAYTONABEACH.TM
Water Heater Compliance
Description Type
Category Design
Eff
Min Design Max Comp
Eff Loss Loss liance
Water Heater I Non Storage Water
All ratings 0.85
0.80 PASSES
heaters - Gas
Water Heater 2 Non Storage Water
All ratings 0.85
0.80 PASSES
heaters - Gas
PASSES
Project: Mets Stadium
Title: Mets Stadium
Type: Office (Business)
Location: PORT ST LUCIE, ST LUC
Piping System Compliance
Category Pipe Din Is Operating Ins Cond Ins Req Ins Compliance
linches] Runout? Temp [Btu-in/hr Thick [in] Thick [in]
[F] SF.F]
Cooling Systems (Chilled Water, Brine
3.00 False 45.00 0.28 2.00 1.29 PASSES
and Refrigerant)
PASSES
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22
A: Mets Stadium
Mets Stadium
Office (Business)
on: PORT ST LUCIE, ST LUC
Other Required Compliance
0
Category
Section
Requirement (write N/A in box if not applicable)
Check
Infiltration
406.1
Infiltration Criteria have been met
El
System
407.1
HVAC Load sizing has been performed
❑
Ventilation
409.1
Ventilation criteria have been met
ADS
410.1
Duct sizing and Design have been performed
T & B
410.1
Testing and Balancing will be performed
Electrical
413.1
Metering criteria have been met
Motors
414.1
Motor efficiency criteria have been met
Lighting
415.1
Lighting criteria have been met
❑
O & M
102.1
Operation/maintenance manual will be provided to owner
Roof/Ceil
404.1
R-19 for Roof Deck with supply plenums beneath it
Report
101
Input Report Print -Out from EnergyGauge F1aCom attached?
G
7/17/2003
EnergyGauge FlaCom FLCCSB v1.22
J
� • l
ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Community Affairs
EnergyGauge MaCom v1.22
INPUT DATA REPORT
Project Name: Mets Stadium
Project Title: Mets Stadium
Address: 525 NW Peacock Blvd.
State: FL
Zip: 34986
Owner:
Proiect Information
Orientation: North
Building Type: Office (Business)
Building Classification: Addition to existing Building
No.of Storeys: 4
GrossArea: 19117
Zones
No
Acronym
Description
Type
Load Profile
Area
Multiplier
Total Area
[sf]
[sf]
1
AHU Nl
Zone 1
CONDITIONED
Uses Building Load
981.8
1
981.8
❑
Profile
2
AHU N3
Zone 2
CONDITIONED
Uses Building Load
5187.0
1
5187.0
❑
Profile
3
AHU N4
Zone 3
CONDITIONED
Uses Building Load
1032.0
1
1032.0
❑
Profile
4
AHU N5
Zone 4
CONDITIONED
Uses Building Load
9316.0
1
9316.0
❑
Profile
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22 1
5 AHU N7
Zone 5
CONDITIONED
Uses Building Load
178.5
1
178.5
❑
Profile
6 AHU N11
Zone 6
CONDITIONED
Uses Building Load
480.0
1
480.0
❑
Profile
7 AHU N2
Zone 2
CONDITIONED
Uses Building Load
981.8
1
981.8
❑
Profile
8 AHU N12
Zone 8
CONDITIONED
Uses Building Load
480.0
1
480.0
❑
Profile
9 AHU N13
Zone 9
CONDITIONED
Uses Building Load
480.0
1
480.0
❑
Profile
Spaces
No Acronym
Description
Type
Depth Width
Height
Multi
Total Area
Total Volume
•
[ft] [ft]
[ft]
plier
[sf]
[cf]
In Zone: AHU N1
1 Storage N1
Storage
Storage & Warehouse - Fine
17.00 57.75
9.00
1
981.8
8835.8
❑
Active Storage
In Zone: AHU N3
1 Conference
ZoOSpl
Conference/meeting
57.00 91.00
9.00
1
5187.0
46683.0
❑
(Multiple Functions)
In Zone: AHU N4
1 Laundry
ZoOSP1
Laundry - Ironing & Sorting
43.00 24.00
9.00
1
1032.0
9288.0
❑
In Zone: AHU N5
1 Tickets
Store/Conference
Conference/meeting
137.00 68.00
9.00
1
9316.0
83844.0
❑
(Multiple Functions)
In Zone: AHU N7
1 Electric Room Electric Room
Electrical Mechanical
17.00 10.50
9.00
1
178.5
1606.5
❑
Equipment Room - General
In Zone: AHU N11
1 AHU N11
ZoOSp 1
Banquet/Multi purpose
16.00 30.00
8.00
1
480.0
3840.0
❑
(Multiple Functions) Alt 78
In Zone: AHU N2
1 Storage N2
Storage
Storage & Warehouse - Fine
17.00 57.75
9.00
1
981.8
8835.8
❑
Active Storage
In Zone: AHU N12
1 AHUN12
Zo0Sp1
Banquet/Multipurpose
16.00 30.00
8.00
1
480.0
3840.0
❑
(Multiple Functions) Alt 78
In Zone: AHU N13
7/17/2003
EnergyGauge FlaCom FLCCSB v1.22
2
1 AHUN13 Zo0Spl Banquet/Multipurppose
16.00 30.00
8.00 1 480.0
3840.0
(Multiple Functions) Alt 78
Lighting
No Type
Power
Control Type
No.of
[W]
Ctrl pts
In Zone: AHU Nl
In Space: Storage N1
1 Recessed Fluorescent - No vent
1600.00
Manual On/Off
3
❑
In Zone: AHU N3
In Space: Conference
,
1 Recessed Fluorescent - No vent
5632.00
Manual On/Off
18
•
In Zone: AHU N4
In Space: Laundry
1 Recessed Fluorescent - No vent
1152.00
Manual On/Off
2
In Zone: AHU N5
In Space: Tickets
1 Recessed Fluorescent - No vent
10472.00
Manual On/Off
20
El
In Zone: AHU N7
In Space: Electric Room
1 Recessed Fluorescent - No vent
64.00
Manual On/Off
2
In Zone: AHU Nll
In Space: AHU N11
1 Recessed Fluorescent - No vent
832.00
Manual On/Off
2
❑
In Zone: AHU N2
In Space: Storage N2
1 Recessed Fluorescent - No vent
1600.00
Manual On/Off
2
0
In Zone: AHU N12
In Space: AHU N12
1 Recessed Fluorescent - No vent
884.00
Manual On/Off
2
In Zone: AIIU N13
In Space: AHU N13
1 Recessed Fluorescent - No vent
936.00
Manual On/Off
2
❑
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22
Walls
No
Description
Type
Width H (Effec) Multi
Area
DirectionConductance
Heat
Dens.
R-Value
[ft]
[ft]
plier
[sf]
[Btu/hr.
sf. F]
Capacity
[]b/cf]
[h.sf.FBtu]
[Btu/sf.F]
In Zone: AHU NI
1
NE Wall
Partition wall, 0.75
57.75
9.00
1
519.8
NorthEast
0.8350
2.5000
100.00
1.20
in. gyp, airspace,
0.75 in. g
2
SE Wall
Partition wall, 0.75
17.00
9.00
1
153.0
SouthEast
0.8350
2.5000
100.00
1.20
in. gyp, airspace,
0.75 in. g
3
SW Wall
0.5 Ply/35/8" Mtl
57.75
9.00
1
519.8
SouthWes
0.0798
0.5388
7.98
12.54
•
std@24"oc/Rll/0.5"
t
Cyp
4
NW Wall
0.75 in. stucco,
17.00
9.00
1
153.0
NorthWes
0.0838
11.2245
50.24
11.94
2"styro 8"CMU,lx2
t
x24"oc,airspace,
In Zone: AHU N3
1
PrOZo2Wal
0.5 Ply/35/8" Mtl
8.00
9.00
1
72.0
NorthWes
0.0798
0.5388
7.98
12.54
std@24"oc/Ri 1/0.5"
t
Gyp
2
PrOZo2Wa2
0.5 Ply/35/8" Mtl
36.00
9.00
1
324.0
NorthEast
0.0798
0.5388
7.98
12.54
std@24"oe/RI I/0.5"
Gyp
3
PrOZo2Wa3
0.5 Ply/35/8" Mtl
91.00
9.00
1
819.0
NorthWes
0.0798
0.5388
7.98
12.54
std@24"oc/Rl l/0.5"
t
Gyp
4
PrOZo2Wa4
0.5 Ply/35/8" Mtl
37.00
9.00
1
333.0
SouthWes
0.0798
0.5388
7.98
12.54
std@24"oc/Rl 1/0.5"
t
Gyp
5
PrOZo2Wa5
0.5 Ply/35/8" Mtl
12.00
9.00
1
108.0
SouthEast
0.0798
0.5388
7.98
12.54
std@24"oc/Rl 1/0.5"
Gyp
6
PrOZo2Wa6
0.5 Ply/35/8" Mtl
16.00
9.00
1
144.0
SouthWes
0.0798
0.5388
7.98
12.54
std@24"oc/Rl 1/0.5"
t
Gyp
7
PrOZo2Wa7
Partition wall, 0.75
10.00
9.00
1
90.0
SouthEast
0.8350
2.5000
100.00
1.20
in. gyp, airspace,
0.75 in. g
7/17/2003
EnergyGauge
FlaCom
FLCCSB
vl.22
4
8
PrOZo2Wa8
0.5 Ply/35/8" Mil
29.00
9.00 1
std@24"oc/Rl 1/0.5"
Gyp
9
PrOZo2Wa9
Partition wall, 0.75
18.00
9.00 1
in. gyp, airspace,
0.75 in. g
In Zone: AHU N4
1
PrOZo3WaI
0.5 Ply/35/8" Mtl
24.50
9.00 1
std@24"oc/Rl 1/0.5"
Gyp
2
PrOZo3Wa2
0.5 Ply/35/8" Mtl
11.00
9.00 1
std@24"oc/Rl 1/0.5"
Gyp
3
PrOZo3Wa3
0.5 Ply/35/8" Mtl
8.00
9.00 1
std@24"oc/R11/0.5"
Gyp
In Zone: AHU N5
0
1
PrOZo4Wa1
0.5 Ply/35/8" Mtl
52.00
9.00 1
std@24"oc/Rl 1/0.5"
Gyp
2
PrOZo4Wa2
0.5 Ply/35/8" Mtl
51.00
9.00 1
std@24"oc/Rl l/0.5"
Gyp
3
PrOZo4Wa3
0.5 Ply/35/8" Mtl
4.00
9.00 1
std@24"oc/Rl l/0.5"
Gyp
4
PrOZo4Wa4
0.5 Ply/35/8" Mtl
5.00
9.00 1
std@24"oc/Rl 1/0.5"
Gyp
5
PrOZo4Wa5
0.5 Ply/35/8" Mtl
9.00
9.00 1
std@24"oc/Rl 1/0.5"
Gyp
6
PrOZo4Wa6
0.5 Ply/35/8" Mtl
4.00
9.00 1
std@24"oc/Rl 1/0.5"
Gyp
7
PrOZo4Wa7
0.5 Ply/35/8" Mtl
49.00
9.00 1
std@24"oc/Rl 1/0.5"
Gyp
8
PrOZo4Wa8
0.5 Ply/35/8" Mtl
49.00
9.00 1
std@24"oc/Rl l/0.5"
Gyp
261.0 SouthWes 0.0798 0.5388 7.98 12.54 Ej
t
162.0 NorthEast 0.8350 2.5000 100.00 1.20 ❑
220.5 SouthWes 0.0798 0.5388
7.98 12.54 ❑
t
99.0 SouthEast 0.0798 0.5388
7.98 12.54 ❑
72.0 SouthWes 0.0798 0.5388
7.98 12.54
t
468.0
NorthWes
0.0798
0.5388
7.98
12.54
❑
t
459.0
North
0.0798
0.5388
7.98
12.54
❑
36.0
NorthWes
0.0798
0.5388
7.98
12.54
❑
t
45.0
NorthEast
0.0798
0.5388
7.98
12.54
❑
81.0
NorthWes
0.0798
0.5388
7.98
12.54
t
36.0
North
0.0798
0.5388
7.98
12.54
❑
441.0
NorthWes
0.0798
0.5388
7.98
12.54
t
441.0
SouthWes
0.0798
0.5388
7.98
12.54
❑
t
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22 5
9
PrOZo4Wa9
0.5 Ply/35/8" Mtl
89.00
9.00
1
801.0
South
0.0798
0.5388
7.98
12.54
❑
std@24"oc/Rl 1/0.5"
Gyp
10
PrOZo4Wa10
0.5 Ply/35/8" Mtl
990.00
9.00
1
8910.0
SouthEast
0.0798
0.5388
7.98
12.54
std@24"oc/Rl 1/0.5"
Gyp
11
PIOZo4Wal1
0.5 Ply/35/8" Mtl
22.00
9.00
1
198.0
North
0.0798
0.5388
7.98
12.54
std@24"oc/Rl l/0.5"
Gyp
12
PIOZo4Wal2
0.5P1y/35/8"Mt1
29.00
9.00
1
261.0
NorthEast
0.0798
0.5388
7.98
12.54
std@24"oc/RI 1/0.5"
Gyp
In Zone: AHU N11
1
PrOZo6Wa1
0.5 Ply/35/8" Mtl
30.00
8.00
1
240.0
South
0.0798
0.5388
7.98
12.54
`
std@24"oe/Rll/0.5"
Gyp
2
PrOZo6Wa3
00.5 Ply/35/8" Mtl
30.00
8.00
1
240.0
North
0.0798
0.5388
7.98
12.54
❑
std@24"oc/Rl 1/0.5"
Gyp
3
PrOZo6Wa4
0.5 Ply/35/8" Mtl
16.00
8.00
1
128.0
West
0.0798
0.5388
7.98
12.54
std@24"oc/Rl l/0.5"
Gyp
In Zone: AHU N2
1
NE Wall
Partition wall, 0.75
57.75
9.00
1
519.8
NorthEast
0.8350
2.5000
100.00
1.20
in. gyp, airspace,
0.75 in. g
2
SE Wall
Partition wall, 0.75
17.00
9.00
1
153.0
SouthEast
0.8350
2.5000
100.00
1.20
in. gyp, airspace,
0.75 in. g
3
SW Wall
0.5 Ply/35/8" Mtl
57.75
9.00
1
519.8
SouthWes
0.0798
0.5388
7.98
12.54
std@24"oc/Rl l/0.5"
t
Gyp
4
NW Wall
0.75 in. stucco,
17.00
9.00
1
153.0
NorthWes
0.0838
11.2245
50.24
11.94
2"styro 8"CMU,lx2
t
x24"oc,airspace,
In Zone: AHU N12
1
PrOZo8Wa1
0.5 Ply/35/8" Mtl
30.00
8.00
1
240.0
North
0.0798
0.5388
7.98
12.54
std@24"oc/Rl l/0.5"
Gyp
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22 6
2 South Wall 0.5 Ply/35/8" Mtl 30.00
8.00 1
240.0
South
0.0798
0.5388
7.98
12.54
std@24"oc/Rl l/0.5"
Gyp
In Zone: AHU N13
1 PrOZo9Wa1 0.5 Ply/35/8" Mtl 30.00
8.00 1
240.0
North
0.0798
0.5388
7.98
12.54
std@24"oc/Rl l/0.5"
Gyp
2 PrOZo9Wa2 0.5 Ply/35/8" Mtl 16.00
8.00 1
128.0
East
0.0798
0.5388
7.98
12.54
std@24"oc/Rl 1/0.5"
Gyp
3 PrOZo9Wa3 0.5 Ply/35/8" Mtl 30.00
8.00 1
240.0
South
0.0798
0.5388
7.98
12.54
std@24"oc/R11/0.5"
Gyp
Windows
No Description Type Shaded
UCen
Sc Vis.Tr
W
H (Effec)
Multi
Total Area
[Btu/hr sf F]
IN
[ft]
plier
[sf]
In Zone: AHU N11
In Wall: North Wall
3 PrOZo6Wa3Wi3 SINGLE CLEAR
No
1.0018
0.95
0.88
25.00
6.00
1
150.0
In Zone: AHU N12
In Wall: North Wall
1 PrOZo8WalWi1 SINGLECLEAR
No
1.0018
0.95
0.88
25.00
6.00
1
150.0
In Zone: AHU N13
In Wall: North Wall
1 PrOZo9WalWll SINGLE CLEAR
No
1.0018
0.95
0.88
25.00
6.00
1
150.0
In Zone: AHU N5
In Wall: S Wall
1 PIOZo4Wa9Wil SINGLE CLEAR
No
1.0018
0.95
0.88
37.00
6.00
1
222.0
In Wall: SE Wall
1 PrOZo4WalOWi1 SINGLE CLEAR
No
1.0018
0.95
0.88
37.00
6.00
1
222.0
In Wall: SW Wall
1 PrOZo4Wa8Wil SINGLE CLEAR
No
1.0018
0.95
0.88
25.00
6.00
1
150.0
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22
Doors
No Description Type Shaded? Width H (Effec) Multi Area Cond. Dens. Heat Cap. R-Value
IN [ft] plier [sf] [Btu/hr. sf. F] [lb/cf] [Btu/sf. F] [h.sf.F/Btu]
Zone: AHU NI
In Wall:
SW Wall
1
PrOZolWa3DIl
Polystyrene core
No
(18 ga steel) 2
2
PrOZolWa3Dr2
Polystyrene core
No
(18 ga steel) 2
3
PrOZolWa3D13
Polystyrene core
No
(18 ga steel) 2
Zone: AHU N3
In Wall:
NW Wall
1
PrOZo2WalDI1O
Polystyrene core
No
(18 ga steel) 1
In Wall:
NE Wall
1
PiOZo2Wa2Drl
Polystyrene core
No
(18 ga steel) 1
In Wall:
NW Wall
1
PIOZo2Wa3DIl
Polystyrene core
No
(18 ga steel) 1
In Wall:
SW Wall
1
PIOZo2Wa4Drl
Polystyrene core
No
(18 ga steel) 2
In Wall:
SW Wall
1
PrOZo2Wa6DIl
Polystyrene core
No
(18 ga steel) 2
Zone: AHU N4
In Wall:
SW Wall
1
PrOZo3Wz3DIl
Polystyrene core
No
(18 ga steel) 1
Zone: AHU N11
In Wall:
South Wall
1
PrOZo6WalDrl
Polystyrene core
No
(18 ga steel) 1
Zone: AHU N2
In Wall:
SW Wall
1
PrOZo7Wa3DIl
Polystyrene core
No
(18 ga steel) 2
6.00
7.00
1
42.0
0.3849
0.00
0.00
2.60
ED
6.00
7.00
1
42.0
0.3849
0.00
0.00
2.60
❑
3.00
7.00
1
21.0
0.3849
0.00
0.00
2.60
❑
3.00
7.00
1
21.0
0.4982
0.00
0.00
3.00
7.00
1
21.0
0.4982
0.00
0.00
3.00
7.00
1
21.0
0.4982
0.00
0.00
6.00
7.00
1
42.0
0.3849
0.00
0.00
6.00
7.00
1
42.0
0.3849
0.00
0.00
3.00
7.00
1
21.0
0.4982
0.00
0.00
3.00 7.00 1 21.0 0.4982 0.00 0.00
6.00 7.00 1 42.0 0.3849 0.00 0.00
2.01
2.01
2.01 ❑
2.60 ❑
2.60 ❑
2.01 ❑
2.01
2.60
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22 8
2 PrOZo7Wa3Dr2 Polystyrene core
No
6.00
7.00
1
42.0
0.3849
0.00
0.00
2.60
❑
(18 ga steel) 2
3 PrOZo7Wa3Dr3 Polystyrene core
No
3.00
7.00
1
21.0
0.3849
0.00
0.00
2.60
❑
(18 ga steel) 2
In Zone: AHU N12
In Wall: South Wall
1 PrOZo8Wa2DIl Polystyrene core
No
3.00
7.00
1
21.0
0.4982
0.00
0.00
2.01
❑
(18 ga steel) 1
In Zone: AHU N13
In Wall: South Wall
1 PrOZo9Wa3Drl Polystyrene core
No
3.00
7.00
1
21.0
0.4982
0.00
0.00
2.01
❑
(18 ga steel) 1
Roofs
No Description •Type
Width
H (Effec)
Multi
Area
Tilt
Cond.
Heat Cap
Dens.
R-Value
[ft]
IN
plier
[sf]
[deg]
[Btu/hr. Sf. F]
[Btu/sf. F]
[lb/cf]
[h.sf.F/Btu]
In Zone: AMU NI
1 Storage Roof Cone Tile/l/2"WD
17.00
57.75
1
981.8
0.00
0.0474
2.15
16.45
21.12
❑
Deck/WD
Truss/6"Batt/Gyp
In Zone: AHU N3
1 PrOZo2Rf1 Cone Tile/l/2"WD
91.00
57.00
1
5187.0
0.00
0.0474
2.15
16.45
21.12
❑
Deck/WD
Truss/6"Batt/Gyp
In Zone: AHU N4
1 PrOZo3Rf1 Cone Tile/1/2"WD
24.00
43.00
1
1032.0
0.00
0.0474
2.15
16.45
21.12
❑
Deck/WD
Truss/6"Batt/Gyp
In Zone: AHU N5
1 PrOZo4Rf1 Cone Tile/l/2"WD
68.00
137.00
1
9316.0
0.00
0.0474
2.15
16.45
21.12
❑
Deck/WD
Truss/6"Batt/Gyp
In Zone: AHU N7
1 PrOZo5Rf1 Cone Tile/1/27M
17.00
10.50
1
178.5
0.00
0.0474
2.15
16.45
21.12
❑
Deck/WD
Truss/6"Batt/Gyp
In Zone: AHU NI I
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22
1
PrOZo6Rf1
Cone Tile/1/2"WD
30.00
16.00 1
480.0
0.00 0.0474
2.15
16.45 21.12
❑
Deck/WD
Truss/6'Batt/Gyp
In Zane:
AHU N2
I
Storage Roof
Cone Tile/l/2"WD
17.00
57.75 1
981.8
0.00 0.0474
2.15
16.45 21.12
❑
Deck/WD
Truss/6'Batt/Gyp
In Zone:
AHU N12
1
PrOZo8Rf1
Cone Tile/l/2"WD
30.00
16.00 1
480.0
0.00 0.0474
2.15
16.45 21.12
❑
Deck/WD
Truss/6'Batt/Gyp
In Zane:
AHU N13
1
PrOZo9Rf1
Cone Tile/1/2"WD
30.00
16.00 1
480.0
0.00 0.0474
2.15
16.45 21.12
❑
Deck/WD
Truss/6'Batt/Gyp
Skylights
No Description Type
UCen Shading Vis.Trans
W H (Effec) Multiplier
Area Total Area
[Btu/hr sf F] Coeff
IN IN
[Sf] [Sf]
In Zone,
In Roof:
Floors
No Description
Type
Width
H (Effec) Multi
Area
Cond. Heat Cap. Dens.
R-Value
[ft]
[ft] plier
[sf]
[Btu/hr. sL F] [Btu/sf. F]
[lb/cf]
[h.sLFBtu]
In Zone:
AHU NI
1
Storage Floor
Concrete floor,
17.00
57.75 1
981.8
0.5987 9.33
140.00
1.67
❑
carpet and rubber
pad
In Zone:
AHU N3
1
PrOZo2F11
Concrete floor,
91.00
57.00 1
5187.0 0.5987 9.33
140.00
1.67
❑
carpet and rubber
pad
In Zone:
AHU N4
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22 10
I Pr0Zo3Fll Concrete floor, 24.00
43.00 1 1032.0 0.5987 9.33
140.00 1.67
0
carpet and rubber
pad
In Zone: AHU N5
1 Pr0Zo4Fll Concrete floor, 68.00
137.00 1 9316.0 0.5987 9.33
140.00 1.67
Q
carpet and rubber
pad
In Zone: AHU N2
1 Storage Floor Concrete floor, 17.00
57.75 1 981.8 0.5987 9.33
140.00 1.67
ED
carpet and rubber
pad
Systems
AHU N1 System 1
•
Variable Air Volume Built-up System
No. Of Units 1
Component Category
Capacity Efficiency IPLV
1 Cooling System (Compliance Not Applicable)
6650.00
2 Air Handling System -Supply (Air Handler (Supply) -
300.00 1.25
El
Variable Volume)
AHU N2 System 2
Variable Air Volume Built-up System
No. Of Units 1
Component Category
Capacity Efficiency IPLV
1 Cooling System (Compliance Not Applicable)
6666.00
ED
2 Air Handling System -Supply (Air Handler (Supply) -
300.00 1.25
ED
Variable Volume)
AHU N3 System 3
Variable Air Volume Built-up System
No. Of Units 1
Component Category
Capacity Efficiency IPLV
1 Cooling System (Compliance Not Applicable)
150951.00
2 Air Handling System -Supply (Air Handler (Supply) -
4000.00 1.25
Variable Volume)
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22 11
AHU N4
System 4
Variable Air Volume Built-up System
No. Of Units 1
Component
Category
Capacity Efficiency 1PLV
1
2
Cooling System (Compliance Not Applicable)
Air Handling System -Supply (Air Handler (Supply) -
Variable Volume)
26337.00
1000.00 1.25
El
AHU N5
System 5
Variable Air Volume Built-up System
No. Of Units 1
Component
Category
Capacity Efficiency IPLV
1
2
Cooling System (Compliance Not Applicable)
Air Handling System -Supply (Au Handler (Supply) -
Variable Volute)
177889.00
5200.00 1.25
❑
❑
AHU N7
•
System 7
Variable Air Volume Built-up System
No. Of Units 1
Component
Category
Capacity Efficiency 1PLV
1
2
Cooling System (Compliance Not Applicable)
Air Handling System -Supply (Air Handler (Supply) -
Variable Volume)
80889.00
3300.00 1.25
❑
AHU N11
System 11
Variable Air Volume Built-up System
No. Of Units 1
Component
Category
Capacity Efficiency IPLV
1
2
Cooling System (Compliance Not Applicable)
Air Handling System -Supply (Au Handler (Supply) -
Variable Volume)
30113.00
800.00 1.25
El
ED
AHU N12
System 12
Variable Air Volume Built-up System
No. Of Units 1
Component
Category
Capacity Efficiency IPLV
1
2
Cooling System (Compliance Not Applicable)
Air Handling System -Supply (Air Handler (Supply) -
Variable Volume)
29816.00
800.00 1.25
El
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22 12
AHU N13 System 13
Variable Air Volume Built-up System No. Of Units 1
Component Category
Capacity
Efficiency IPLV
1 Cooling System (Compliance Not Applicable)
2 Air Handling System -Supply (Air Handler (Supply) -
Variable Volume)
30194.00
800.00
1.25
❑
❑
Plant
Equipment
Category
Size
Inst.No Eff. IPLV
1 Open reciprocating chiller
Cooling Equipment
50.0 [Tons]
1 2.70 [COP] 2.80
'
Water Heaters
W-Heater Description
Capacit Cap.Unit
I/P Rt.
Efficienc Loss
1 Non Storage Water heaters - Gas
2 Non Storage Water heaters - Gas
[Not Req]
[Not Req]
650000 [Btu/h]
650000 [Btu/h]
0.8500 [Et] [Not Req]
0.8500 [Et] [Not Req]
❑
❑
Ext-Lighting
Description
Categories.
Area/Len/No. of units
Wattage
[sVft/No]
[W]
El
Piping
No Type
Operating Insulation
Nomonal pipe
Insulation Is Runout?
Temperature Conductivity
Diameter
Thickness
[F] [ Btu-in/h.sf.F]
[in]
[in]
1 Cooling Systems (Chilled Water, Brine and
45.00 0.28
3.00
2.00 No ❑
Refriger
7/17/2003 EnergyGauge F1aCom FLCCSB v1.22 13
Fenestration Used
Name Glass Type No. of Glass SC T
Frame
Frame
Panes Conductance
Conductance
Absorptance
[Btu/h.sf.F]
[Btu/h.sf.F]
ApLbWndl SINGLE CLEAR 1 1.0018 0.9500 0.8810
0.4340
0.7000 ❑
Materials Used
at No
Acronym
Description
Only R-Value
Used
RValue
[h.sf.FBtu]
Thickness
IN
Conductivity
[Btu/h.ft.F]
Density
[lb/cf]
SpecificHeat
[Btu/lb.F]
18
Mat118
2 in. Wood
No
2.3857
0.1670
0.0700
37.00
0.3900
❑
264
Mat1264
ALUMINUM, 1/16IN
No
0.0002
0.0050
26.0000
480.00
0.1000.
❑
214
Mat1214
POLYSTYRENE, E-NP.,
No
5.2100
0.1042
0.0200
1.80
0.2900
❑
1-1/4IN,
187
Matll87
GYP OR PLAS
No
0.4533
0.0417
0.0920
50.00
0.2000
❑
BOARD,1/2IN
206
Mat1206
CELLULOSE,FILL,5.5IN,R-
No
20.8318
0.4583
0.0220
3.00
0.3300
❑
20
151
Matll51
CONC HW, DRD, 140LB,
No
0.4403
0.3333
0.7570
140.00
0.2000
❑
4IN
178
Mat1178
CARPET W/RUBBER PAD
Yes
1.2300
❑
265
Mat1265
Soil, 1 ft
No
2.0000
1.0000
0.5000
100.00
0.2000
❑
48
Mat148
6 in. Heavyweight concrete
No
0.5000
0.5000
1.0000
140.00
0.2000
❑
123
Matll23
CONC BLOCK
No
1.7227
0.6667
0.3870
53.00
0.2000
❑
MW,8IN,HOLLOW
159
Mat1159
CONC
No
0.3202
0.3333
1.0410
140.00
0.2000
❑
HW-UNDRD-140LB41N
57
Mat157
3/4 in. Plaster or gypsum
No
0.1488
0.0625
0.4200
100.00
0.2000
❑
72
Mat172
AIR LAYER, 314IN OR
Yes
0.9000
❑
LESS, VERT. WALLS
267
Mat1267
0.75" stucco
No
0.1563
0.0625
0.4000
16.00
0.2000
❑
266
Mat1266
2x4@16" oc+Rl1 Batt
No
8.3343
0.2917
0.0350
9.70
0.2000
❑
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22 14
215
Mat1215
POLYSTYRENE, EXP.,
No
8.3350
0.1667
0.0200
1.80
0.2900
❑
2IN,
105
MatI105
CONC BLK HW, 8IN,
No
1.1002
0.6667
0.6060
69.00
0.2000
❑
HOLLOW
256
Mat1256
WOOD, SOFT, 1-1/2IN
No
1.8939
0.1250
0.0660
32.00
0.3300
❑
268
Mat1268
0.625" stucco
No
0.1302
0,0521
0.4000
16.00
0.2000
❑
42
Mat142
8 in. Lightweight concrete
No
2.0212
0.6670
0.3300
38.00
0.2000
❑
block
269
MatI269
.75" ISO BTWN24" oc
No
2.2321
0.0625
0.0280
4.19
0.3000
❑
86
MatI86
BRICK, COMMON, 4IN
No
0.8012
0.3333
0.4160
120.00
0.2000
❑
211
Mat1211
POLYSTYRENE,EXP.,1/2I
No
2.0850
0.0417
0.0200
1.80
0.2900
❑
N,
12
Mat112
3 in. Insulation
No
10.0000
0.2500
0.0250
2.00
0.2000
❑
218
Mat1218
POLYURETHANE,EXP.,1/2
No
3.2077
0.0417
0.0130
1.50
0.3800
❑
IN,
23
Mat123
6 in. Insulation
No
20.0000
0.5000
0.0250
5.70
0.2000
❑
4
Matl4
Steel siding
No
0.0002
0.0050
26.0000
480.00
0.1000
❑
271
Mat1271
2x4@24" oc+RII Batt
No
10.4179
0.2917
0.0280
7.11
0.2000
❑
272
Mat1272
Panel with 7/16" panels
Yes
0.9044
❑
273
Mat1273
Hollow core flush (1.375")
Yes
1.2777
❑
274
Mat1274
Solid core flush (1.375")
Yes
1.7141
❑
275
Matl275
Panel with 7/16" panels
Yes
1.0019
❑
(1.375")
276
Mat1276
Hollow core flush (1.75")
Yes
1.3239
❑
277
Mat1277
Panel with 1-1/8" panels
Yes
1.7141
❑
(1.75")
278
Mat1278
Solid core flush (1.75")
Yes
1.6500
❑
279
Mat1279
Solid core flush (2.25")
Yes
2.8537
❑
280
Mat1280
Fiberglass/Mineral wool core
Yes
0.8167
❑
281
Mat1281
Paper Honeycomb core
Yes
0.9357
❑
282
Mat1282
Solid Urethane foam core
Yes
1.6500
❑
283
Mat1283
Solid mineral fiberboard core
Yes
1.7816
❑
284
Mat1284
Polystyrene core (18 ga steel)
Yes
2.0071
❑
1
285
Mat1285
Polyurethane core (18 ga
Yes
2.5983
❑
steel) 2
286
Mat1286
Polyurethane core (24 ga
Yes
2.5983
❑
steel) 1
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22 15
287
Mat1287
Polyurethane core (24 ga
Yes
4.1500
❑
steel) 2
288
Mat1288
Solid Urethane foam core
Yes
4.1500
❑
81
Matl81
ASPHALT -ROOFING,
Yes
0.1500
❑
ROLL
244
Mat1244
PLYWOOD, 1/2IN
No
0.6318
0.0417
0.0660
34.00
0.2900
❑
185
Matl185
CLAY TILE, PAVER, 3/8IN
No
0.0301
0.0313
1.0410
120.00
0.2000
❑
82
Mat182
ASPHALT -SHINGLE AND
Yes
0.4400
❑
SIDING
11
Matlll
2 in. Insulation
No
6.6800
0.1670
0.0250
2.00
0.2000
❑
47
Matl47
2 in. Heavyweight concrete
No
0.1670
0.1670
1.0000
140.00
0.2000
❑
95
Mat195
CONC BLOCK
No
0.7107
0.3333
0.4690
101.00
0.2000
❑
HW-4IN-HOLLOW
248
Mat1248
ROOF GRAVEL OR
No
0.0500
0.0417
0.8340
55.00
0.4000
❑
SLAGI/2IN
94
Mat194
BUILTAUP ROOFING,
No
0.3366
0.0313
0.0930
70.00
0.3500
❑
3/81N
Constructs Used
No
Name
Simple
Construct
Massless Conductance
Construct [Btu/h.sf.F]
Heat Capacity
[Btu/sf.F]
Density
[lb/cf]
RValue
[h.sf.FBtu]
1004
Concrete floor, carpet and rubber pad
No
No
0.60
9.33
140.00
1.6703
❑
Layer
Material Material
Thickness
Framing
No.
[ft]
Factor
1
151 CONC HW, DRD,
140LB, 4IN
0.3333
0.00
❑
2
178 CARPET W/RUBBER PAD
0.00
❑
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22 16
No
Name
Simple
Construct
Massless Conductance Heat Capacity
Construct [Btu/h.sf.F] [Btu/sf.F]
Density
[Ib/cf]
RValue
[b.sf.FBtul
1008
Partition wall, 0.75
in. gyp, airspace,
0.75 in. No
No 0.83
2.50
100.00
1.1976
❑
gyp
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
57
3/4 in. Plaster or gypsum
0.0625
0.00
❑
2
72
AIR LAYER, 3/4IN OR LESS, VERT.
0.00
❑
WALLS
3
57
3/4 in. Plaster or gypsum
0.0625
0.00
❑
No
Name
0
Simple
Construct
Massless Conductance Heat Capacity
Construct [Btu/h.sf.F] [Btu/sf.F]
Density
[Ib/cf]
RValue
[h.sf.FBtul
1010
0.75 in. stucco,
No
No 0.08
11.22
50.24
11.9386
❑
2"styro,8"CMU,lx2x24"oc,airspace,0.5"gyp
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
267
0.75" stucco
0.0625
0.00
❑
2
187
GYP OR PLAS BOARD,1/21N
0.0417
0.00
❑
3
215
POLYSTYRENE, EXP., 2IN,
0.1667
0.00
❑
4
105
CONC BLK HW, 81N, HOLLOW
0.6667
0.00
❑
5
256
WOOD, SOFT, 1-1/2IN
0.1250
0.00
❑
No
Name
Simple
Construct
Massless Conductance
Construct [Btu/h.sf.F[
Heat Capacity
[Btu/sf.F]
Density
[lb/cf]
RValue
[h.sf.FBtul
1015
0.5 Ply/35/8" Mtl std@24"Oc/RI1/0.5" Gyp No
No 0.08
0.54
7.98
12.5383
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
211
POLYSTYRENE,EXP.,1/2IN,
0.0417
0.00
❑
2
12
3 in. Insulation
0.2500
0.00
❑
3
187
GYP ORPLASBOARD, 1/2IN
0.0417
0.00
❑
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22 17
No
Name
Simple
Massless
Conductance Heat Capacity
Density
RValue
Construct
Construct
[Btu/h.sLF]
[Btu/sf.F]
[lb/cf]
Ih.sf.FBtu]
1033
Polystyrene core (18
ga steel) 1 No
Yes
0.50
2.0071
❑
Layer
Material
Material
Thickness
Framing
No.
IN
Factor
1
284
Polystyrene core (18 ga steel) 1
0.00
❑
No
Name
Simple
Massless
Conductance Heat Capacity
Density
RValue
Construct
Construct
[Btu/h.sf.F]
[Btu/sf.F]
[Ib/cf]
[h.sf.FBtu]
1034
Polystyrene core (18 ga steel) 2 No
Yes
0.38
2.5983
❑
Layer
MaPerial
Material
Thickness
Framing
No.
IN
Factor
1
285
Polyurethane core (18 ga steel) 2
0.00
❑
No
Name
Simple
Massless
Conductance Heat Capacity
Density
RValue
Construct
Construct
[Btu/h.sf.F]
[Btu/sf.F]
[lb/cf]
[h.sf.FBtu]
1041
Cone Tile/l/2"WD Deck/WD No
No
0.05
2.15
16.45
21.1151
❑
Truss/6'Batt/Gyp
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1_
185
CLAY TILE, PAVER, 3/81N
0.0313
0.00
❑
2
244
PLYWOOD, 1/2IN
0.0417
0.00
❑
3
187
GYP OR PLAS BOARD,1/2IN
0.0417
0.00
❑
4
23
6 in. Insulation
0.5000
0.00
❑
7/17/2003 EnergyGauge FlaCom FLCCSB v1.22 18
General Project Data Input
Project file name:
Project title:
Designed by:
Project date:
Project location:
Client name:
Client address:
Cient city:
Client phone:
Client fax:
Company name:
Company representative:
Company address:
Company city:
Company phone:
Company fax:
Company e-mail address:
Company website:
Mats Stadium
Darcee A. McAninley, P.E.
June 23,2003
FORT PIERCE, FLORIDA, USA
Jack L. Gordon Architects, P.C., AIA
43 West 23rd Street
New York, NY 10010
212-633-0909
212-633-2085
Wojcieszak & Associates, Inc.
Darcee A. McAninley, P.E.
833 East 5th Street
Stuart, FL 34994
772-286-8696
772-286-4521
darcee@dwojo.com
dwojo.com
Barometric pressure: 29.894 in.wg.
Altitude: 25 feet
Latitude: 27 Degrees
Mean daily temperature range: 15 Degrees
Starting & ending time for HVAC load calculations: Sam -11 pm
Floor heat loss coefficient: 0.62 Btuh per foot of slab
Number of unique zones in this project: 52
Lighting requirements:
0.00
Watts per square foot
Equipment requirements:
0.00
Watts per square foot
People sensible load multiplier:
245
Btuh per person
People latent load multiplier:
155
Btuh per person
Zone sensible safety factor:
0
%
Zone latent safety factor:
0
%
Zone heating safety factor:
0
%
People diversity factor:
100
%
Lighting profile number:
0
Equipment profile number:
0
People profile number:
0
.Building default ceiling height: •
0.0
feet
Building default wall height: a
0.0
feet
Internal Operating Load Profiles C = 100
hr
I hr
I hr
I hr
hr
hr
hr
hr
hr
hr
I hr
I hr
hr
hr
hr
hr
hr
hr
hr
hr
hr
hr
hr
hr
1
2
3
1 4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
1
C
C
C
C
C
C
C
20
30
50
50
C
C
C
C
C
C
C
C
C
C
C
50
20
2
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
c
C
C
C
C
C
C
C
3
C
C
C
C
C
C
C
C
c
C
C
C
C
C
C
C
c
c
c
C
C
C
C
C
4
C
C
C
C
C
C
c
C
C
c
C
C
C
c
C
C
C
C
C
C
C
C
C
C
5
C
C
C
c
c
C
C
C
C
C
C
C
C
C
C
C
C
C
c
C
C
C
C
C
6
C
c
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
7
c
c
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
8
C
C
C
c
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
c
C
C
C
9
C
C
C
C
C
C
c
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
101
cl
C
C
ci
cl
ci
cl
cl
ci
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C:1Documents and 8ettingsMarceelDesldop123026 METS.CHV Thursday, July 17, 2003, 3:21 PM
CHVAC - Full Commercial HVAC Loads Calculation Program
Wolcieszak 8 Associates, Inc.
Stuart, FL 34994-2401
Elite
Software Development, Inc.
Mets Stadium
Page
General Project Data input cont'd
Building -Level Design Conditions
Design Outdoor Outdoor
Month Dry Bulb Wet Bulb
Indoor
Rel.Hum
Indoor
Dry Bulb
Grains
Diff
In/Outdoor
Correction
August 90 78
Winter 42
50%
72
70
67.38
4
Master Roofs
Roof ASHRAE
No. Roof#
Roof
U-Fac
Dark
Color
Susp.
Ceil
1 6
0.034
No
Yes
Master Walls
Wall ASHRAE
No. Group.
Wall
U-Fac
Wall
Color
1 D
0.122
L
Master Partitions
Partition Partition
No. U-Factor
Cool
T-D
Heat
T-D
1 0.355 8 18
Partition #1 Description: 8 inch concrete block partition wall, adjoining shipping and receiving area
2 0.034 8 18
Master Glass
Glass Summer Winter Glass
No. U-Factor U-Factor Shd.Coef.
Interior
Shading
Interior
Shd.Coef
Room
Const
Glass
Width
Glass
Height
1 0.900 0.910 0.700
2
0.000
M
1.000
1.000
C:\Documents and Settings\Darcee1DesktopN23026 METS.CHV Thursday, July 17, 2003, 3:21 PM
CH AC -Full Commercial HVAC Loads Calculation Program
Elite Software Development, Inc.
Wojeieszak & Associates, Inc.
Mets Stadium
StuartFL 34994-2401
Page
Building Summary Loads
Building peaks in August at 5pm.
Bldg Load Area
Sen
%Tot
Let
Sen
Net
%Net
Descriptions Quan
Loss
Loss
Gain
Gain
Gain
Gain
Roof 21,299
20,328
12.68
0
19,728
19,728
3.90
Wall 6,112
20,879
13.03
0
14,728
14,728
2.91
Glass 1,044
26,601
16.60
0
49,802
49,802
9.84
Floor Slab 678
11,770
7.34
0
0
0
0.00
S4in Loads
79,577
49.65
0
84,258
84,258
16.64
Lighting 14,712
0
0.00
0
50,199
50,199
9.92
Equipment 32,800
0
0.00
0
111,918
111,918
22.11
People 268
0
0.00
41,540
65,660
107,200
21.18
Partition 2,194
14,020
8.75
0
6,231
6,231
1.23
Cool. Pret. 97
0
0.00
0
0
0
0.00
Heat. Pret. 97
0
0.00
0
0
0
0.00
Cool. Vent. 2,267
0
0.00
105,545
36,843
142,387
28.13
Heat. Vent. 2,267
66,670
41.60
0
0
0
0.00
Cool.lnfil. 0
0
0.00
0
0
0
0.00
Heat.lnfil. 0
0
0.00
0
0
0
0.00
Draw-Thru Fan 0
0
0.00
0
4,048
4,048
0.80
Blow-Thru Fan 0
0
0.00
0
0
0
0.00
Reserve Cap. 0
0
0.00
0
0
0
0.00
Reheat Cap. 0
0
0.00
0
0
0
0.00
Supply Duct 0
0
0.00
0
0
0
0.00
Return Duct 0
0
0.00
0
0
0
0.00
Misc. Supply 0
0
0.00
0
0
0
0.00
Misc. Return 0
0
0.00
0
0
0
0.00
Building Totals 160,267
100.00
147,085
359,157
506,242
100.00
Building Sen
%Tot
Lat
Sen
Net
%Net
Summary Loss
Loss
Gain
Gain
Gain
Gain
Ventilation 66,670
41.60
105,545
36,843
142,387
28.13
Infiltration 0
0.00
0
0
0
0.00
Pretreated Air 0
0.00
0
0
0
0.00
Zone Loads 93,597
58.40
41,540
318,266
359,806
71.07
Plenum Loads 0
0.00
0
0
0
0.00
Fan & Duct Loads 0
0.00
0
4,048
4,048
0.80
Building Totals 160,267
100.00
147,085
359,157
506,242
100.00
•
Check Figures
0
Total Building Supply Air (based on a 18°
TD):
16,912
CFM
Total Building Vent. Air (13.41 % of Supply):
2,267
CFM
Total Conditioned Air Space:
21,201
Sq.ft
Supply Air Per Unit Area:
0.7977
CFM/Sq.ft
Area Per Cooling Capacity:
502.5506
Sq.ffron
Cooling Capacity Per Area:
0.0020
Tons/Sq.ft
Total Heating Required With Outside Air:
160,267
Btuh
Total Cooling Required With Outside Air:
42.19
Tons
C:1Documents and SettingsUarceeTesktop123026 METS.CHV Thursday, July 17, 2003, 3:21 PM
' CH AC - Full Commercial HVAC Loads Calculation Program
Elite Software Development, Inc.
Wojcieszak & Associates, Inc.
it
Mets Stadium
Stuart, FL 34994-2401
Page
Air Handler #1 Total Load Summaify
Air Handler Description: AHU-N1 Variable Air Volume
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.02 HP
Fan Input: 0% motor and fan efficiency with 0 in.
water across the fan
Sensible Heat Ratio: 1.00
— This system occurs 1 time(s) in the building. —
Air System Peak Time: 8pm in August.
Outdoor Conditions: 83° DB, 77° WB, 128.64 grains
Summer: Ventilation controls outside air, — Winter:
Ventilation controls outside air.
Zone Space sensible loss: 7,760
Btuh
Infiltration sensible loss: 0
Btuh
0
CFM
Outside Air sensible loss: -261
Btuh
48
CFM
Supply Duct sensible loss: 0
Btuh
Return Duct sensible loss: 0
Btuh
Return Plenum sensible loss: 0
Btuh
Total System sensible loss:
7,499 Btuh
Heating Supply Air: 7,760 / (.999 X 1.08 X 30) =
240
CFM
Winter Vent Outside Air (20.2% of supply) =
48
CFM
Zone space sensible gain: 4,617
Btuh
Infiltration sensible gain: 0
Btuh
Draw-thru fan sensible gain: 60
Btuh
Supply duct sensible gain: 0
Btuh
Reserve sensible gain: 0
Btuh
Total sensible gain on supply side of coil:
4,677 Btuh
Cooling Supply Air: 4,677 / (.999 X 1.1 X 17) =
250
CFM
Summer Vent Outside Air (19.4% of supply) =
48
CFM
Return duct sensible gain: 0
Btuh
Return plenum sensible gain: 0
Btuh
Outside air sensible gain: 160
Btuh
48
CFM
Blow-thru fan sensible gain: 0
Btuh
Total sensible gain on return side of coil:
160 Btuh
Total sensible gain on air handling system:
4,836 Btuh
Zone space latent gain: 0
Btuh
Infiltration latent gain: 0
Btuh
Outside air latent gain: 1,814
Btuh
Total latent gain on air handling system:
1,814 Btuh
Total system sensible and latent gain:
6,650 Btuh
Check Figures
Total Air Handler Supply Air (based on a 170
):
250
CFM
Total Air Handler Vent. Air (19.36% of Suppe):
48
CFM
Total Conditioned Air Space:
969
Sq.ft
Supply Air Per Unit Area:
0.2583
CFM/Sq.ft
Area Per Cooling Capacity:
1,748.5310
Sq.ft/Ton
Cooling Capacity Per Area:
0.0006
Tons/Sq.ft
Total Heating Required With Outside Air:
7,499
Btuh
Total Cooling Required With Outside Air:
0.55
Tons
C:1Documenls and Settings1Darcee1Desktop123026 METS.CHV Thursday, July 17, 2003, 3:21 PM
CH AC - Full Commerclal HVAC Loads Calculation Program
Elite Software Development, Inc.
Wojcieszak if Associates, Inc. ,��
p
Mats Stadium
Stuart, FL 34994-2401 �LL�
Pace 8
Air Handler #2 Total Load Summafy
Air Handler Description: AHU-N2 Variable Air Volume
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.02 HP
Fan Input: 0% motor and fan efficiency with 0 in.
water across the fan
Sensible Heat Ratio: 1.00
— This system occurs 1 time(s) in the building. —
Air System Peak Time: 8pm in August.
Outdoor Conditions: 83° DB, 77° WB, 128.64 grains
Summer: Ventilation controls outside air, — Winter: Ventilation controls outside
air.
Zone Space sensible loss: 6,476 Btuh
Infiltration sensible loss: 0 Btuh
0
CFM
Outside Air sensible loss: -261 Btuh
48
CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Stuh
Total System sensible loss:
6,214 Btuh
Heating Supply Air: 6,476 / (.999 X 1.08 X 30) =
200
CFM
Winter Vent Outside Air (24.2% of supply) =
48
CFM
Zone space sensible gain: 4,632 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 60 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
4,692 Btuh
Cooling Supply Air: 4,692 / (.999 X 1.1 X 17) =
251
CFM
Summer Vent Outside Air (19.3% of supply) =
48
CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 160 Btuh
48
CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
160 Btuh
Total sensible gain on air handling system:
4,852 Btuh
ZoOe space latent gain: 0 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 1,814 Btuh
Total latent gain on air handling system:
1,814 Btuh
Total system sensible and latent gain:
6,666 Btuh
Check Figures
Total Air Handler Supply Air (based on a 170j ):
251
CFM
Total Air Handler Vent. Air (19.30% of Supply'):
48
CFM
Total Conditioned Air Space:
969
Sq.ft
Supply Air Per Unit Area:
0.2591
CFM/Sq.ft
Area Per Cooling Capacity:
1,744.5010
Sq.ft/fon
Cooling Capacity Per Area:
0.0006
Tons/Sq.ft
Total Heating Required With Outside Air:
6,214
Btuh
Total Cooling Required With Outside Air:
0.56
Tons
C:tDocuments and SettingslDarceelDesktop123026 METS.CHV Thursday, July 17, 2003, 3:21 PM
'CH AC -Full Commercial HVAC Loads Calculation Program
Wojcieszak & Associates, Inc. J�
Stuart. FL 34994-2401 ���LLLJJt���l
fh
j
Elite Software Development, Inc.
Mats Stadium
Paqe 10
Air Handler #3 Total Load Summafy
Air Handler Description: AHU-N3 Variable Air Volume
Supply Air Fan: Draw-Thru with program estimated horsepower of
0.46 HP
Fan Input: 0% motor and fan efficiency with 0 in.
water across the fan
Sensible Heat Ratio: 0.77
— This system occurs 1 time(s) in the building. --
Air System Peak Time: 8pm in August.
Outdoor Conditions: 83° DB, 77° WB, 128.64 grains
Summer: Exhaust controls outside air, — Winter: Exhaust controls outside air.
Zone Space sensible loss: 20,656 Btuh
Infiltration sensible loss: 0 Btuh
0
CFM
Outside Air sensible loss: 0 Btuh
0
CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
20,656 Btuh
Heating Supply Air: 20,656 / (.999 X 1.08 X 30) =
638
CFM
Winter Vent Outside Air (0.0% of supply) =
0
CFM
Zone space sensible gain: 89,353 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 1,160 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
90,513 Btuh
Cooling Supply Air: 90,513 / (.999 X 1.1 X 17) =
4,845
CFM
Summer Vent Outside Air (0.0% of supply) =
0
CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 0 Btuh
0
CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
0 Btuh
Total sensible gain on air handling system:
90,513 Btuh
Zone space latent gain: 27,280 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 0 Btuh
Total latent gain on air handling system:
27,280 Btuh
Total system sensible and latent gain:
117,793 Btuh
Check Figures
Total Air Handler Supply Air (based on a 17113):
4,845
CFM
Total Air Handler Vent. Air (0.00% of Supply):
0
CFM
Total Conditioned Air Space:
6,977
Sq.ft
Supply Air Per Unit Area:
0.6944
CFM/Sq.ft
Area Per Cooling Capacity:
710.7751
Sq.ft/Ton
Cooling Capacity Per Area:
0.0014
Tons/Sq.ft
Total Heating Required With Outside Air:
20,656
Btuh
Total Cooling Required With Outside Air:
9.82
Tons
C:1Documents and SettingsUarcee1Desktopt23026 METS.CHV Thursday, July 17, 2003, 3:21 PM
CH AC - Full Commercial HVAC Loads Calculation Program
Elite Software Development, Inc.
Wojcieszak 8 Associates, Inc. Jf��
Mats Stadium
StuartFL 34994-2401 a'k1
Page 12
Air Handler #4 Total Load Summary
Air Handler Description: AHU-N4 Constant Volume - Proportion
dupply Air Fan: Draw-Thru with program estimated horsepower of 0.09 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 1.00
— This system occurs 1 time(s) in the building. --
Air System Peak Time: 5pm in August.
Outdoor Conditions: 89° DB, 78- WB, 128.26 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in August at 8pm is different
from the total system peak time, hence the air system CFM was computed
using a zone sensible load of 16,980.
Summer: Ventilation controls outside air, — Winter: Ventilation controls outside air.
Zone Space sensible loss: 2,609 Btuh
Infiltration sensible loss: 0 Stuh
0 CFM
Outside Air sensible loss: 4,337 Btuh
144 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
6,946 Btuh
Heating Supply Air: 2,609 / (.999 X 1.08 X 17) =
144 CFM
Winter Vent Outside Air (100.0% of supply) =
144 CFM
Zone space sensible gain: 16,699 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 220 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
16,920 Btuh
Cooling Supply Air: 17,200 / (.999 X 1.1 X 17) =
921 CFM
Summer Vent Outside Air (15.6% of supply) =
144 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 2,524 Btuh
144 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
2,524 Btuh
Total sensible gain on air handling system:
19,444 Btuh
Zone space latent gain: 0 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 6,893 Btuh
Total latent gain on air handling system:
6,893 Btuh
Total system sensible and latent gain: !
26,337 Btuh
Check Figures
Total Air Handler Supply Air (based on a 17' TD):
921 CFM
Total Air Handler Vent. Air (15.59% of Supply):
144 CFM
Total Conditioned Air Space:
957 Sq.ft
Supply Air Per Unit Area:
0.9620 CFM/Sq.ft
Area Per Cooling Capacity: 436.0475 Sq.ft/Ton
Cooling Capacity Per Area:
0.0023 Tons/Sq.ft
Total Heating Required With Outside Air:
6,946 Btuh
Total Cooling Required With Outside Air:
2.19 Tons
C:tDocuments and Sett1ngslDarceelDesktop123026 METS.CHV Thursday, July 17, 2003, 3:21 PM
CH AC - Full Commercial HVAC Loads Calculation Program
Wojcieszak 8 Associates, Inc.
Elite Software Development, Inc.
Meta Stadium
StuartFL 34994-2401
Pace 16
Air Handler #5 Total Load Summary
Air Handler Description: AHU-N5 Variable Air Volume
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.50 HP
Fan Input: 0% motor and fan efficiency with 0 in.
water across the fan
Sensible Heat Ratio: 0.92
— This system occurs 1 time(s) in the building. —
Air System Peak Time: 4pm in August.
Outdoor Conditions: 90° DB, 78° WB, 126.54 grains
Summer: Ventilation controls outside air, — Winter: Ventilation controls outside air.
Zone Space sensible loss: 38,774 Btuh
Infiltration sensible loss: 0 Btuh
0
CFM
Outside Air sensible loss: 33,838 Btuh
1,120
CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
72,612 Btuh
Heating Supply Air: 38,774 / (.999 X 1.08 X 30) =
1,198
CFM
Winter Vent Outside Air (93.5% of supply) =
1,120
CFM
Zone space sensible gain: 98,215 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 1,275 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
99,489 Btuh
Cooling Supply Air: 99,489 / (.999 X 1.1 X 17) =
5,325
CFM
Summer Vent Outside Air (21.0% of supply) =
1,120
CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 22,156 Btuh
1,120
CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
22,156 Btuh
Total sensible gain on air handling system:
121,645 Btuh
Zone space latent gain: 8,680 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 51,278 Btuh
Total latent gain on air handling system:
59,958 Btuh
Total system sensible and latent gain:
181,603 Btuh
Check Figures
Total Air Handler Supply Air (based on a 17' ):
5,325
CFM
Total Air Handler Vent. Air (21.03% of Supply):
1,120
CFM
Total Conditioned Air Space:
9,702
Sq.ft
Supply Air Per Unit Area:
0.5489
CFM/Sq.ft
Area Per Cooling Capacity:
641.0919
Sq.ft/ron
Cooling Capacity Per Area:
0.0016
Tons/Sq.ft
Total Heating Required With Outside Air:
72,612
Btuh
Total Cooling Required Wdh Outside Air:
15.13
Tons
C:1Documents and Settings\DarceelDesktop123026 METS.CHV Thursday, July 17, 2003, 3:21 PM
C JAC - Full Commercial HVAC Loads Calculation Program
Elite Software Development, Inc.
Woicieszak 8 Associates, Inc.
Mats Stadium
Stuart, FL 34994-2401
Pape 18
Air Handler #7 Total Load Summaty
Air Handler Description: AHU-N7 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.31 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 1.00
— This system occurs 1 time(s) in the building. —
Air System Peak Time: 5pm in August.
Outdoor Conditions: 89- DB, 78" WB, 128.26 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time
in August at 8pm is different
frd)m the total system peak time, hence the air system CFM was computed using a zone sensible load of 71,797.
Summer: Ventilation controls outside air, — Winter: Ventilation controls outside air.
Zone Space sensible loss: 229 Btuh
Infiltration sensible loss: 0 Btuh
0
CFM
Outside Air sensible loss: 7,264 Btuh
187
CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
7,493 Btuh
Heating Supply Air: 229 / (.999 X 1.08 X 1) =
187
CFM
Winter Vent Outside Air (100.0% of supply) =
187
CFM
Zone space sensible gain: 71,778 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 790 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
72,568 Btuh
Cooling Supply Air: 72,587 / (.999 X 1.1 X 20) =
3,302
CFM
Summer Vent Outside Air (5.7% of supply) =
187
CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 1,644 Btuh
187
CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
1,644 Btuh
Total sensible gain on air handling system:
74,212 Btuh
Zone space latent gain: 0 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 6,677 Btuh
Total latent gain on air handling system:
6,677 Btuh
Total system sensible and latent gain: r
80,889 Btuh
Check Figures
Total Air Handler Supply Air (based on a 20° TD):
3,302
CFM
-
Total Air Handler Vent. Air (5.66% of Supply):
187
CFM
Total Conditioned Air Space:
187
Sq.ft
Supply Air Per Unit Area:
17.6598
CFM/Sq.ft
Area Per Cooling Capacity:
27.7416
Sq.ftrron
Cooling Capacity Per Area:
0.0360
Tons/Sq.ft
Total Heating Required With Outside Air:
7,493
Btuh
Total Cooling Required With Outside Air:
6.74
Tons
C'Mocuments and SettingslDarceelDesktop123026 METS.CHV Thursday, July 17, 2003, 3:21 PM
'CH AC - Full Commercial HVAC Loads Calculation Program
J$
Elite Software Development, Inc.
Wojcieszak & Associates, Inc. ,II
I
Mats Stadium
StuartFL 34994.2401 i4J!$1
Page 20
Air Handler #ll Total Load Summaty
Air Handler Description: AHU-N11 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.06 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.87
-- This system occurs 1 time(s) in the building. —
Air System Peak Time: 5pm in August.
Outdoor Conditions: 89° DB, 78° WB, 128.26 grains
Because of the diversity in zone, plenum and ventilation loads, the zone
sensible peak time
in August at 6pm is different
from the total system peak time, hence the air system CFM was computed using a zone sensible load of 12,517.
Summer: Ventilation controls outside air, — Winter: Ventilation controls outside air.
Zone Space sensible loss: 5,843 Btuh
Infiltration sensible loss: 0 Btuh
0 CFM
Outside Air sensible loss: 7,251 Btuh
240 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
13,095 Btuh
Heating Supply Air: 5,843 / (.999 X 1.08 X 23) =
240 CFM
Winter Vent Outside Air (100.0% of supply) =
240 CFM
Zone space sensible gain: 12,346 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 162 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
12,509 Btuh
Cooling Supply Air: 12,679 / (.999 X 1.1 X 17) =
679 CFM
Summer Vent Outside Air (35.4% of supply) =
240 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 4,220 Btuh
240 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
4,220 Btuh
Total sensible gain on air handling system:
16,729 Btuh
Zone space latent gain: 1,860 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: t 11,524 Btuh
Total latent gain on air handling system:
13,384 Btuh
Total system sensible and latent gain: r
30,113 Btuh
Check Figures
Total Air Handler Supply Air (based on a 17° TD):
679 CFM
Total Air Handler Vent. Air (35.37% of Supply):
240 CFM
Total Conditioned Air Space:
480 Sq.ft
Supply Air Per Unit Area:
1.4138 CFM/Sq.ft
Area Per Cooling Capacity: 191.2819 Sq.ftrron
Cooling Capacity Per Area:
0.0052 Tons/Sq.ft
Total Heating Required With Outside Air:
13,095 Btuh
Total Cooling Required Wdh Outside Air:
2.51 Tons
C:VDocuments and SettingslDarceetDesktopV3026 METS.CHV Thursday, July 17, 2003, 3:21 PM
H AC - Full Commercial HVAC Loads Calculation Program
Elite Software Development, Inc.
Wojcieszak & Associates, Inc.
Mats Stadium
StuartFL 34994-2401
Pace 22
Air Handler #12 Total Load Summafy
Air Handler Description: AHU-N12 Constant Volume - Proportion
dupply Air Fan: Draw-Thru with program estimated horsepower of 0.06 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.87
— This system occurs 1 time(s) in the building. --
Air System Peak Time: 5pm in August.
Outdoor Conditions: 89° DB, 78° WB, 128.26 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time
in August at 6pm is different
from the total system peak time, hence the air system CFM was computed using a zone sensible load of 12,164.
Summer: Ventilation controls outside air, — Winter: Ventilation controls outside air.
Zone Space sensible loss: 5,406 Btuh
Infiltration sensible loss: 0 Btuh
0 CFM
Outside Air sensible loss: 7,251 Btuh
240 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
12,657 Btuh
Heating Supply Air: 5,406 / (.999 X 1.08 X 21) =
240 CFM
Winter Vent Outside Air (100.0% of supply) =
240 CFM
Zone space sensible gain: 12,054 Btuh
Infiltration sensible gain: 0 • Btuh
Draw-thru fan sensible gain: 158 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
12,212 Btuh
Cooling Supply Air: 12,322 / (.999 X 1.1 X 17) =
659 CFM
Summer Vent Outside Air (36.4% of supply) =
240 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 4,220 Btuh
240 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
4,220 Btuh
Total sensible gain on air handling system:
16,433 Btuh
Zone space latent gain: 1,860 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: * 11,524 Btuh
Total latent gain on air handling system:
13,384 Btuh
Total system sensible and latent gain: if
29,816 Btuh
Check Figures
Total Air Handler Supply Air (based on a 17° TD):
659 CFM
Total Air Handler Vent. Air (36.39% of Supply):
240 CFM
Total Conditioned Air Space:
480 Sq.ft
Supply Air Per Unit Area:
1.3740 CFM/Sq.ft
Area Per Cooling Capacity: 193.1841 Sq.ftrTon
Cooling Capacity Per Area:
0.0052 Tons/Sq.ft
Total Heating Required With Outside Air:
12,657 Btuh
Total Cooling Required,With Outside Air:
2.48 Tons
C:\Documents and Settings\DarceeXDesktop123026 METS.CHV Thursday, July 17, 2003, 3:21 PM
off AC - Full Commercial HVAC Loads Calculation Program
Elite Software Development, Inc.
Waicieszak & Associates, Inc.
A
Mets Stadium
Stuart FL 34994-2401
Pace 24
Air Handler #13 Total Load Summaty
yir Handler Description: AHU-N13 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.06 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.87
-- This system occurs 1 time(s) in the building. —
Air System Peak Time: 5pm in August.
Outdoor Conditions: 89- DB, 78° WEI, 128.26 grains
Because of the diversity in zone, plenum and ventilation loads, the zone
sensible peak time in August at 6pm is different
foom the total system peak time, hence the air system CFM was computed using a zone sensible load of 12,537.
Summer: Ventilation controls outside air, — Winter: Ventilation controls outside air.
Zone Space sensible loss: 5,843 Btuh
Infiltration sensible loss: 0 Btuh
0 CFM
Outside Air sensible loss: 7,251 Btuh
240 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
13,095 Btuh
Heating Supply Air: 5,843 / (.999 X 1.08 X 23) =
240 CFM
Winter Vent Outside Air (100.0% of supply) =
240 CFM
Zone space sensible gain: 12,428 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 163 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
12,590 Btuh
Cooling Supply Air:12,700 / (.999 X 1.1 X 17) =
680 CFM
Summer Vent Outside Air (35.3% of supply) =
240 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 4,220 Btuh
240 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
4,220 Btuh
Total sensible gain on air handling system:
16,810 Btuh
Zone space latent gain: 1,860 Btuh
Nifltration latent gain: 0 Btuh
Outside air latent gain: 11,524 Btuh
Total latent gain on air handling system:
13,384 Btuh
Total system sensible and latent gain:
30,194 Btuh
Check Figures
Total Air Handler Supply Air (based on a 17' TD):
680 CFM
Total Air Handler Vent. Air (35.31 % of Supply):
240 CFM
Total Conditioned Air Space:
480 Sq.ft
Supply Air Per Unit Area:
1.4161 CFWSq.ft
Area Per Cooling Capacity: 190.7659
Sq.ft/Ton
Cooling Capacity Per Area:
0.0052 Tons/Sq.ft
Total Heating Required With Outside Air:
13,095 Btuh
Total Cooling Required With Outside Air:
2.52 Tons
C:1Documents and Settings1DarceelDesktop123026 METS.CHV