ST LUCIE COUNTY FIRE DISTRICT
BUREAU OF FIRE PREVENTION
PLAN REVIEW
( )Tenant Improvement ( )Addition
SLC
Mets Stadium
527 NW Peacock Blvd
Rodda Construction, Inc.
2128 E. Edgewood Dr., Suite 109
Florida
Jack L. Gordan Architects
Assembly
24,000 addition
Telephone: 772-462-83 06
FAX: 772-462-8466
)Renovationlalterations
( )Shell Only
F.P.B.:
B-03-288
Building Dept:
23071241
Number of stories:
Phone #
863-669-0990
City:
Lakeland
Zip Code:
33803
Phone #
212-633-0909
Review Date:
8/27/2003
Automatic sprinklers:
Required
Net sq ft: ,
Based On:
SBCCI Type: IV unp
NOTE
1. All revisions must be in compliance before the final inspection.
2. The Fire Marshal requires 24 hour notice on all inspections.
3. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
4. Permit fees are required to be paid in full prior to any inspections.
5. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. A copy of the required revision/s have been transmitted to the Architect () Contractor ( ).
7. Penetrations through rated assemblies shall be of proper UL design.
8. UL design criteria shall be submitted with the construction plans.
9. Fire Alarm Panels shall be located indoors.
THE FLORIDA FIRE PREVENTION CODE, 2001 EDITION IS CURRENTLY ENFORCED.
REVISIONS REQUIRED
ACCESS BOX IS REQUIRED ( ) ° ACCESS KEY SWITCH REQUIRED ( )
i
1. A separate permit is required for the addition or alteration of the fire sprinkler system.
2. A separate permit is required for the alteration or addition of the fire alarm system:
3. While under construction all means of egress shall be maintained at all times.
The fire guards as indicated shall not move from their post unless relieved by another fire guard.
4. A separate permit is required for the installation of the fixed fire equipment systems.
5. Replace the gravel with a more suitable walking surface for ramp "A" exit # 1.
6. Emergency lighting indicated may be insuffcient. A preliminary illumination test is suggested.
__7._P-r6vide portable fire protection throughout if not already present.
8. Provide flame spread ratings for all canopy materials.
Reviewed by:T Date: 8/27/2003