HomeMy WebLinkAboutFL ENERGT EFFICIENCY CODEFlorida Energy Efficiency Code. For Building Construcfion ;
Florida Department; of Community;Affairs
FLA/COM 2004 V2.5, EffectiVe Dec 8, 2006 -- Form 400A 2004R� ,
Method A Whole Building Performance Method for.Commercial Bu''ildings
v
PROJECT SUMMARY
Short Desc: Sleep City Description: Sleep City Mattress
Owner: Sleep City Mattress
Addressl: Kitterman & US I City: Port St. Lucie
Address2: State: FL
Zip: 0
Type: Retail Class: New Finished building
Jurisdiction: PORT ST LUCIE, ST LUCIE COUNTY, FL (661200)
Conditioned Area: 3136 SF Conditioned & UnConditioned Area:
No of Stories: 1 Area entered from Plans
Permit No: 0 Max Tonnage
If different, write in:
SCgN��
Sr, Cuci� County
3136 SF
0 SF
8
EnergyGauge Summit@ v3.20 Incorporating Florida Energy Code Version - FI.A/COM 2004 v2.5 Effective Dec 8, 2006
2/25/2009 Page I of 7
1
Component
Gross Energy Cost
Summary
Design
4,157.9
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
rtfS1
y �
rw.
Y
Criteria Result
5,628.8 PASSES
PASSES
None Entered
PASSES
None Entered
None Entered
None Entered
Yes/No/NA
EnergyGauge Summit@) v320 Incorporating Florida Energy Code Version - FWCOM 2004 v2.5 Effective Dec 8, 2006
2/25/2009 Page 2 of 7
CERTIFICATIONS
I hereby certify that the plans and specifications covered by this calculation are in compliance with the
Florida Energy Code
Prepared By: Eric J. Svoboda, PE Building Official:
Date: 2- Z-5 .0 Date:
I certify that this building is in co ce w' the FLorida Energy Efficiency Code
Owner Agent: Date:
If Required by Florida law, I hereby ertify (*) that the system design is in compliance with the FLorida
Energy Efficiency Code
Architect: Reg No:
Electrical Designer: Reg No:
Lighting Designer: eg o:
Mechanical Designer: OReg o:
Plumbing Designer: Reg No:
(*) Signature is required where F Aa a re 'F s design to be performed by registered design
professionals. Typed names and rea ers may be used where all relevant information is
contained on signed/sealed plans.
EnergyGauge Summit® v3.20 Incorporating Florida Energy Code Version - FLAICOM 2004 v2.5 Effective Dec 8, 2006
2/25/2009 Page 3 of 7
Project: Sleep City
Title: Sleep City Mattress
Type: Retail
(WEA File: DAYTONABEACH.TMY)
Buildine End Uses
Design
Reference
Total 278.70
380.90
$4,158
$5,629
ELECTRICITY(MBtulkWhl$)
278.70
81528
$4,158
380.90
111462
$5,629
AREA LIGHTS
92.20
121.50
27010
35576
$1,378
$1,797
MISC EQUIPMT
69.00
69.00
20174
20174
$1,029
$1,019
PUMPS & MISC 0.20
0.20
3
32
$2
SPACE COOL
8
4
28110
31851
$1,434
$1,608
SPACE HEAT 4.00
3.80
1153
1124
$59
$57
VENT FANS 17.20
77.60
5046
22705
$257
$1,147
& Penalties (if any): Modified Points: = 278.31
PASSES
EnergyGauge Summit@ v3.20 Incorporating Florida Energy Code Version - FLAICOM 2004 v2.5 Effective Dec 8, 2006
2/25/2009 Page 4 of 7
External Lighting Compliance
Description Category Tradable? Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (W)
(Sgft or ft)
None
Project: Sleep City
Title: Sleep City Mattress
Type: Retail
(WEA File: DAYTONABEACH.TMY)
Lighting Controls Compliance
Acronym Ashrae Description Area Design Min Compli-
ID (sq.ft) CP CP ance
PrOZo1Sp1 25,001 Sales Area 3,136 6 2 PASSES
PASSES
Project: Sleep City
Title: Sleep City Mattress
Type: Retail
(WEA File: DAYTONABEACH.TMY)
System Report Compliance
PrOSyl System 1 Co olu Nad No. of Units
Sy em 1
Component Category &Ii6ttsign Eff Design IPLV Comp-
Eff Criteria IPLV Criteria liance
Cooling System Air Conditioners Air Cooled 13.00 I0.30 8.00 PASSES
65000 to 135000 Btu/h
Cooling Capacity
Heating System Electric Furnace 1.00 1.00 PASSES
Air Handling Air Handler (Supply) - 0.20 0.90 PASSES
System -Supply Constant Volume
Air Distribution ADS System 6.00 3.50 PASSES
System
PASSES
EnergyGauge Summit@ v3.20 Incorporating Florida Energy Code Version - FLA/COM 2004 v2.5 Effective Dec 8, 2006
2/25/2009 Page 5 of 7
Plant Compliance
Description Installed Size Design Min Design
No Eff Eff IPLV
Min Category Comp
IPLV Hance
None
Water Heater Compliance
Description Type Category Design Min
Eff Eff
Design Max Comp
Loss Loss Hance
None
Piping System Compliance
Category Pipe Dia Is Operating Ins Cond Ins Req Ins Compliance
[inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in]
[F] SF.F]
WO
None
LU
EnergyGauge Summit® v3.20 Incorporating Florida Energy Code Version - FLAICOM 2004 v2.5 Effective Dec 8, 2006
2/25/2009 Page 6 of 7
.t: Sleep City
Sleep City Mattress
Retail
File: DAYTONABEACH.TMY)
Other Required Compliance
Category Section Requirement (write N/A in box if not applicable) Check
Report 13-101 Input Report Print -Out from EnergyGauge F1aCom attached
Operations Manual 13-102.1, Operations manual provided to owner
13-410,13413
Windows & Doors 13406.AB.1.1 Glazed swinging entrance & revolving doors: max. 1.0 cfin/ft'; all
other products: 0.4 cfm/ft'
Joints/Cracks 13-406.AB.1.2 To be caulked, gasketed, weather-stripped or otherwise sealed
Dropped Ceiling Cavity 13-406.AB.3 Vented: seal & insulated ceiling. Unvented seal & insulate roof &
side walls
System 13-407 HVAC Load sizing has been performed
Reheat 13-407.B Electric resistance reheat prohibited El
HVAC Efficiency 13-407, 13-408 Minimum efficiences: Cooling Tables 13-407.AB.3.2.1A-D;
Heating Tables 13-407.AB.3.2.IB, 13-407.AB.3.2.ID,
13-408.AB.3.2.IE, 13408.AB.3.2F
HVAC Controls 13-407.AB.2 Zone controls prevent reheat (exceptions); simultaneous heating
and cooling in each zone; combined HAC deadband of at least 5°F
(exceptions)
Ventilation Controls 13-409.AB.3 Motorized dampers regd, exce t g ers OK in: 1) exhaust
systems and 2) syste wi d intake or exhaust
capacity < 0 c
ADS 13-410 t-anically
i�g,�nd 'sign p ormed
HVAC Ducts 13-410.AB ctttjngs, mec anical equipment & plenum chambers shall
attached, sealed, insulated & installed per Sec.
13-410 Air Distribution Systems
Balancing 13-410.AB.4 HVAC distribution system(s) tested & balanced. Report in
construction documents
Piping Insulation 13-41 LAB In accordance with Table 13-41 LAB.2
Water Heaters 13-412.AB Performance requirements in accordance with Table 13412.AB.3.
Heat trap required
Swimming Pools 13-412.AB.2.6 Cover on heated swimming pools: Time switch (exceptions);
Readily accessible on/off switch
Hot Water Pipe 13-41 LAB.3 Table 13-41 LAB.2 for circulating systems, first 8 feet of outlet
Insulation pipe from storage tank and between inlet pipe and heat trap
Water Fixtures 13-412.AB.2.5 Shower hot water flow restricted to 2.5 gpm at 80 psi. Public
lavatory fixture how water flow 0.5 gpm max; if self -closing valve
0.25 gallon recirculating, 0.5 gallon non recirculating
Motors 13-414 Motor efficiency criteria have been met
Lighting Controls 13-415.AB Automatic control required for interior lighting in buildings >5,000
s.f.; Space control; Exterior photo sensor; Tandom wiring with 1 or
3 linear fluuorescent lamps>30 W
EnergyGauge Summit® v3.20 Incorporating Florida Energy Code Version - FLAICOM 2004 v2.5 Effective Dec 8, 2006
2/25/2009 Page 7 of 7
Project Name: Sleep City
Project Title: Sleep City Mattress
Address: Kitterman & US 1
State: FL
Zip: 0
Owner: Sleep City Mattress
EnergyGauge Summit® v3.20
0 Orientation: East
Building Type: Retail
g Classification: New Finished building
o.of Stories: 1
GrossArea: 3136 SF
Zones
No Acronym Description Type
Area
[sf]
Multiplier
Total Area
[sf]
1 PrOZol Zone 1 CONDITIONED
3136.0
1
3136.0 ❑
Spaces
No Acronym Description Type Depth
[ft]
Width Height Multi
IN [ft] plier
Total Area
[sf]
Total Volume
[cf]
2/25/2009
EnergyGauge Summit® Q.20
1
rione*zporls
1P
Zo0SP1 Sales Area
49.00
64.00
12.00 1 3136.0
37632.0 ❑
Lighting
No
Type Category
No. of
Watts per
Power Control Type
No.of
Luminaires
Lumihaire
[W]
Ctrl pts
In Zone: PrOZol
In Space: Pr0Zo1Sp1
1
Compact Fluorescent General Lighting
1
5000 Manual On/Off
6 ❑
Walls
No Description
Type Width H (Effec) Multi
Area
irecti Conductance
Heat
Dens. R-Value
[ft]
[ft] plier
[sf]
[Btu/hr. sf F]
Capacity
[lb/cf] [h.sEF/Btu]
[Btu/sf.F]
In Zone: PrOZol
1 PrOZol Wal
5/8" stucco 64.00
12.00 1
768.0
0.2067
5.731
34.65 4.8 ❑
/8"CMU/3/4"ISO
BTWN24"oc/.5"
Gyp
2 PrOZOlWa2
5/8"stucco 64.00
12.00 1
768.0
We91067
5.731
34.65 4.8 ❑
/8"CMU/3/4"ISO
BTWN24"oc/.5"
Gyp
Windows
No
Description Type Shaded
U SHGC Vis.Tra
W H (Effec)
Multi
Total Area
[Btu/hr sf F]
IN [ft]
plier
[sf]
In Zone: PrOZol
In Wall: East
1
PCOZolWalWil UserDefined No
1.2500 0.82 0.76
3.00 7.00
11
231.0 El
2/25/2009 EnergyGauge Summit® v3.20
Doors
No Description
Type
Shaded? Width H (Effec) Multi
Area
Cond. Dens. Heat Cap.
R-Value
Vt] [ft]
plier
[sf]
[Btu/hr. sE F] [lb/cf] [Btu/sf.
F]
[h.sf.FBtu]
In Zone: PrOZol
In Wall: West
1 PrOZoI Wa2Dr1 Solid core flush
No
3.00 7.00
1 21.0
0.3504 0.00
0.00
2.85
❑
(2.25)
Roofs
No Description
Type
Width
H (Effec) Multi
Area
*&Virt
Cond. Heat Cap
Dens.
R-Value
[ft]
[ft] plier
[sf]
jde9
tsii PPhPPh��333333
Btu/hr. Sf. F] [Btu/sE F]
[lb/cf]
[h.sEFBtu]
In Zone: PrOZol
I PCOZolRfl
Mtl Bldg Roof/R-19
64.00
49.00 1
3136.0
0.00
0.0492 1.34
9.49
20.3
❑
Batt
Skylights
No Description Type
U SHGC Vis.Trans
W
ffec) Multiplier
Area
Total Area
[Btu/hr sf F]
A
[ft]
[Sf]
[sf]
In Zone:
In Roof:
Floors
No Description
Type
Width
H (Effec) Multi
Area
Cond. Heat Cap. Dens.
R-Value
[ft]
[ft] plier
[sf]
[Btu/hr.
sf. F] [Btu/sf. F] [lb/cf]
[h.sf.F/Btu]
In Zone: PrOZol
1 PrOZo1F11
1 ft. soil, concrete
64.00
49.00 1
3136.0 0.2681 34.00 113.33
3.73
❑
floor, carpet and
rubber pad
2/25/2009 EnergyGauge Summit® v3.20
Systems
PrOSyl System 1
Constant Volume Packaged System
No. Of Units 1
Component Category
Capacity
Efficiency IPLV
1 Cooling System
2 Heating System
3 Air Handling System -Supply
4 Air Distribution System
96000.00
48000.00
2880.00
0 8.00
7.1700
❑
❑
Plant
Ice
4
Equipment
Category Size
NaMfNo Eff.
IPLV
Water Heaters
W-Heater Description
Description
Rt
Capacit3Cap.Unit UP Rt.
Eff
LossEl
Ext-Lighting
Description Category No. of Watts per Area/Len/No. of units Control Type Wattage
Luminaires Luminaire [sVft/No] [W]
2/25/2009 EnergyGauge Summit® v3.20
Piping
No Type Operating Insulation Nomonal pipe Insulation Is Runout?
Temperature Conductivity Diameter Thickness
[F] [ BtmWAffl [in] fnl
u
Fenestration Used
Name Glass Type No. of CoGlass
nductance SHGC 'VLT
Panes [Btu/h.sf.F] VA
ASHULSgIClrAlI User Defined 1 1.2500 0.8200 0.760 ❑
Frm
Materials Used
Only R-Value
RValue Thickness
Conductivity
Density
SpecificHeat
Mat No
Acronym
Description
Used
[h.sf.FBtul
IN
[Btu/h.ft.Fl
[lb/cfl
[Btu/Ib.FI
187
MatI187
GYP OR PLAS
No
BOARD,1/2IN
178
Mat1178
CARPET W/RUBBER PAD
Yes
1.2300
❑
265
MatI265
Soil, 1 ft
No
2.0000
1.0000
0.5000
100.00
0.2000
❑
48
Mat148
6 in. Heavyweight concrete
No
0.5000
0.5000
1.0000
140.00
0.2000
❑
268
Mat1268
0.625" stucco
No
0.1302
0.0521
0.4000
16.00
0.2000
❑
42
Mat142
8 in. Lightweight concrete
No
2.0212
0.6670
0.3300
38.00
0.2000
❑
block
269
Mat1269
.75" ISO BTWN24" oc
No
2.2321
0.0625
0.0280
4.19
0.3000
❑
23
Mat123
6 in. Insulation
No
20.0000
0.5000
0.0250
5.70
0.2000
❑
94
MatI94
BUILT-UP ROOFING,
No
0.3366
0.0313
0.0930
70.00
0.3500
❑
3/81N
2/25/2009 EnergyGauge Summit® v3.20 5
Constructs Used
No
Name
Simple
Massless Conductance
Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sLFJ
[Btu/sf.FJ
[lb/cfJ
[h.sf.F/Btu]
1011
5/8" stucco /8"CMU/3/4"ISO No
No 0.21
5.73
34.65
4.8
❑
BTWN24"oc/.5"
Gyp
Layer
Material
Material
Th Framing
No.
Factor
1
268
0.625"stucco
0.0 1
0.000
El
2
42
8 in. Lightweight concrete block
0.667
0.000
❑
3
269
.75" ISO BTWN24" oc
0.062
0.000
❑
4
187
GYP OR PLAS BOARD,1/21N
0.0417
0.000
❑
No
Name
Simple
Massless C d t ce
Heat Capacity
Density
RValue
Construct
Construct [ ]
[Btulsf.F]
[Ib/cfJ
[hsf.F/Btu)
1056
Mtl Bldg Roof/R-19
Batt
No
No
1.34
9.49
20.3
❑
®
Layer
Material
Material
Thickness
raming
No.
[ft]
Factor
1
94
BUILT-UP ROOFING, 3/81N
0.0313
0.000
❑
2
23
6 in. Insulation
0.5000
0.000
❑
No
Name
Simple
Massless Conductance
Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.F]
[Btu/sf.FJ
[Ib/cfJ
[h.sf.F/Btu]
1057
1 ft. soil, concrete floor, carpet and rubber pad No
No 0.27
34.00
113.33
3.7
❑
Layer
Material
Material
Thickness Framing
No.
[ft]
Factor
1
265
Soil, 1 ft
1.0000
0.000
❑
2
48
6 in. Heavyweight concrete
0.5000
0.000
❑
3
178
CARPET W/RUBBER PAD
0.000
❑
2/25/2009 EnergyGauge Summit® v3.20
No Name Simple Massless Conductance Heat Capacity Density RValue
Construct Construct [Btu/h.sLF] [Btu/sEF] [lb/ct] [h.sEFBtu]
1058 Solid core flush (2.25) No Yes 0.35 2.9 ❑
Layer Material Material
Thickness
Framing
No.
[ft]
Factor
1 279 Solid core flush (2.25")
0.000
2/25/2009 EnergyGauge Summit® v3.20 7
El