Loading...
HomeMy WebLinkAboutwind load design pressureEXPRESS ENGININING Ffle CwO RECEIVED k.f9 _..._�PY- FEB 20 "027 Order (Ref) #: 59501(43870-7846180556) Project Details: VISIONS C0 I�DQMIeN�o nty, Permitting Contractor: CWS INC. 4000 N HI 11735 LANE PARK ROAD TAVARES, FL HUTCHINSON ISLAND / FORT PIERCE, FL Subject: Wind Load Design Pressure Calculations (Components & Cladding) Site Information Building Classification: enclosed Wind Speed (V It): 160 mph Exposure Category: d Roof Type: monoslope Roof Slope (0): 0.0 deg Mean Roof Height (h): 140.0 ft Min. Building Dimension (L): 85.0 ft Parapet >: 3 feet? No General Calculation Directionality Factor (Kd): 1 Gust' Effect Factor (G): 0.85 Internal Pressure Coefficient (GCP; ): ± 0.18 Topographical Factor (Kt): 1.0 Velocity Pressure Exposure Coefficient ( nK): 1.52 Velocity Pressure (qh): 99.57 psf End Zone (a): 8.5 ft ASD Method: P = 0.6w Mark Qty Elev (ft) Size: W x H (in) Zone Shutter. Area (ft2) K, (Kh) q, (q h) GCP, JGCP_ Pressures (psf) mb (1) 140.0 113.0 x 77.0 4 No 60.4 1.52 99.57 0.80 %0.83 +58.4 / -60.6 mb (1) 140.0 33.0 x 77.0 4 No 17.6 1.52 99.57 0.90 -0.90 +64.5 /-64.5 Ir (1) 140.0 202.0x92.0 5 No 129.1 1.52 99.57 0.73 -1.34 +54.1/-90.6 Ir (1) 140.0 107.0 x 92.0 5 No 68.4 1.52 99.57 0.79-1.49 +57.7 /-100.0 Ir (1) 140.0 59.0 x 65.0 4 No 26.6 1.52 99.57 0.87 -0.88 +62.9 /-63.6 gp (1) 140.0 39.0 x 94.0 4 No 25.5 1.52 99.571 0.88 -0.89 +63.2 / -63.8 gp (1) 140.0 39.0 x 94.0 4 No 25.5 1.52 99.57 0.88 -0.89 +63.2 / -63.8 Id (1) 140.0 100.0 x 59.0 5 No 41.0 1.52 99.57 0.83 r-1.62 +60.5 / -107.6 Id (1) 140.0 60.0 x 92.0 5 No 38.3 1.52 99.57 0.84 -1.64 -108.6 gb (1) 140.0 84.0 x 92.0 4 No 53.7 1.52 99.57 0.81 059. / 6,:l,.0 G�;.•~ uc '•.ag ; NOTES: Design is in accordance with ASCE 7-10 (ASD method) and the Florida Building Code Sixth Edition (2017). Results; �} fit'_ F` are not valid for use unless approved via original signature and raised engineer seal of a PE from Engineering Express. = valfd Only th ised/Statrrrfld Results are based on contractor -supplied data and shall be field verified by others prior to use. Selection & installation -of- Engirt r ' '� products shall be approved using these dimensions and pressures as verified by others. Note: For openings to be properly rated in Zone 4, no pa o t e opening shal a within 5 feet of any building corner. �� •'F� • 1 . 0 This engineer has not field visited this location and if this cannot be clearly identified by others, the opening shall be re- &0 rCD evaluated prior to Installation of any fenestration. All other information provided above Including mean roof height, S r building minimum dimensions, opening sizes, & other supporting data was provided by others. For definitions of the above terms; visit EngineeringExpress.com/WikREVIEWED FOR #9885 59501(43870-7846180556) b U eA6 &(4 fq.) 55200U16"LNkAxX(954) 354-0443 AutoPrint �) kiff�EER�'77E G2 � 8�1A PAGE 1 OF 1 Visions Condominium — Design Pressures Dimensions Design Pressure EFCO Design Pressure Width x.Height Requirement Model / Configuration Rating Inch PSF O = fixed, X = operable PSF Master Bedroom: Picture Window 113 x 77 +59 / -61 5FXT / 00 +120 / -140 Sash Window 33 x 77 +65 / -65 663 / OX +73 / -90 Living Room: Sliding Glass Door 202 x 92 +55 / -91 5XPT / OXXO +120 / -120 Storefronf Wiiidow 107 x 92 +58 / -100 5FXT / 00 +120 / -140 Picture Window 59 x 65 +63 / -64 5FXT / 0 +120 / -140 Glassed Patio: Out -Swing Door East 39 x 94 +64 / -64 3501 / X +100 / -100 Out -Swing Door West 39 x 94 +64 / -64 3501 / X +100 / -100 Library / Den: Picture Window 100 x 59 +61 / -108 5FXT / 00 +120 / -140 _.--Sliding Glass Door- __ _m_ . _60x.92..,v_-_ �. _—+61J-r-109.—_—_.a_5XPT/XO __— _:.___+155J.:.155 Guest Bedroom: Sliding Glass Door 84 x 92 +59 / -61 5XPT / XO +155 / -155 Design pressure requirements were calculated at 14th floor and are valid for all lower floors. �J C