EVALUATION REPORT
ICP Adhesives and Sealants, Inc. Evaluati
12505 NW 44N Street I
Coral Springs, FL 33065 Pat
(888)774-1419
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulat
construction materials in the State of Florida. The documentation submitted has been revic
P.E. for use of the product under the Florida Building Code. The product described here
compliance with the 6u' Edition (2017) Florida Building Code sections noted herein.
DESCRIPTION: ICP Adhesives Polyset® AH-160 i.
r
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality
herein. i,
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(
Quality Assurance documentation changes, or provisions of the Code that relate to the prodi
this Evaluation Report by the named client constitutes agreement to notifyiRobert Nier
changes or the referenced Quality Assurance documentation changes. Trinity) ERD requires
Evaluation Report relative to updated Code requirements with each Code Cycle.'
ADVERTISEMENT: The Evaluation Report number preceded by the words'Trinity'( ERD Evalu
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be do
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the us
its distributors and shall be available for inspection at the job site at the requestjof the Buildi
This Evaluation Report consists of pages 1 through 9.
Prepared by:
r
a_• - ecE
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCAANE1983
facsimile seat
ninen. P.E. on
.............. ......
CEFmFICATION OF INDEPENDENCE:
1. Exterior Research & Design, LLC. d/b/a Trinity.) ERD does not have, nor does it intend to -,acquire or wi
in any company manufacturing or distributing products it evaluates.
2. Exterior Research & Design, L-C. d/b/a Trinity I ERD is not owned, operated or controlled by at
distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any compariy manufactur
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved
product.
5. This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are,' in any way, t
project on which this Evaluation Report, or previous versions thereof, is/wasused for permitting or d
specifically for that purpose. I
4CH & DESIGN, LLC.
ofAutborization #9503
4N STREET; UNIT 13
OXFORD, CT06478
(203)262-9245
i Report 02768.03.06-R8
FL6332-RS
of Issuance:08/08/2008
Revision 8:10/12/2017
is governing the use of
ad by Robert Nieminen,
has been evaluated for
Agency noted
changes, the referenced
:change. Acceptance of
ten, P.E. if the product,
complete review of this
d" may be displayed in
in its entirety.
by the manufacturer or
Official.
was authurmed by Robert
7. This does not serve as an
t acquire, a financial interest
company, manufacturing or
or distributing products for
i the approval process of the
Designer of Record for any
,n guidance unless retained
\! I RIN1TY ERD
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Roof Tile Adhesives
Compliance Statement: ICP Adhesives Polyset® AH-160, as produced by ICP Adhesives and Sealants, Inc., has
demonstrated compliance with the 6th Edition (2017) Florida Building Code through testing in accordance with the
Standards set forth herein. Compliance is subject to the Installation Requirements and Limitations / Conditions of
Use set forth herein.
2. STANDARDS:
Sections
Pro a
Standard
Year
1504.2.1.1
Overturning resistance
SSTD 11
1997
3. REFERENCES:
KniLty.
Examination
Reference
Date
ERD(TST 6049)
Static Uplift —SSTD 11
P39740.02.12
02/20/2012
ERD(TST 6049)
Static Uplift —SSTD 11
P39740.11.13-R1
01/02/2015
ICC-ES(EVL2396)
20121BC Compliance
ESR-1709
12/01/2016
Miami -Dade (CER 1592)
HVHZ compliance
17-0322.03
04/27/2017
PRI(TST 5878)
Static Uplift —SSTD 11
ECM-001-02-01
09/21/2001
PRI (TST 5878)
Static Uplift -SSTD 11
PFI-006-02-01
05/09/2005
,PRI (TST 5878)
Static Uplift —SSTD 11
PFI-006-02-02
05/09/2005
PRI (TST 5878)
Static Uplift —SSTD 11
PFI-007-02-01
10/11/2005
PRI (TST 5878)
Static Uplift —SSTD 11
PFI-008-02-04
02/21/2006
PRI(TST5878)
Static Uplift —SSTD 11
PFI-009-02-03
02/21/2006
PRI [TST 5878)
Static Uplift —SSTD 11
TGRI-001-02-03
10/30/2006
PRI TST 5878)
Static Uplift —SSTD 11
TGRI-001-02-03
10/30/2006
PRI (TST 5878)
Static Uplift —SSTD 11
PFPI-010-02-01
12/07/2006
PRI (TST 5878)
Static Uplift —SSTD 11
PFPI-011-02-01
12/07/2006
PRI (TST 5878)
Static Uplift —SSTD 11
PFPI-012-02-01
12/07/2006
PRI(TST5878)
Static Uplift —SSTD 11
PFPI-013-02-01
12/07/2006
PRI (TST 5878)
Static Uplift —SSTD 11
PFPI-014-02-01
12/07/2006
PRI (TST 5878)
Static Uplift—SSTD 11
ECM-003-02-01
06/13/2008
PRI (TST 5878)
Static Uplift —SSTD 11
ECM-004-02-01
06/13/2008
PRI (TST5878)
Static Uplift —SSTD 11
ECM-005-02-01
06/13/2008
PRI (TST 5878)
Static Uplift —SSTD 11
ECM-606-02-01
06/13/2008
PRI (TST5878)
Static Uplift—SSTD 11
ECM-007-02-01
06/13/2008
PRI(TST5878)
Static Uplift —SSTD 11
ECM-008-02-01
06/13/2008
UL LLC (QUA 9625)
Quality Assurance -
Service Confirmation
Exp. 06/05/2018
4. PRODUCT DESCRIPTION:
'
4.1 ICP Adhesives Polyset® AH-160 is a two -component expanding polyurethane roof tile adhesive that is mixed
and dispensed from a dispensing system provided by ICP Adhesives and Sealants, Inc. The components are
available in refillable tanks or disposable cylinders (ICP Adhesives ProPack® 30 & 100).
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity) ERD nor Robert Nieminen, P.E. are, in anyway, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for
permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
Exterior Research and Design, I.I.C. Evaluation Report 02768.03.06-R8
Certificate ofAuthariictian a9503 6'"EDITION(2017)FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyset• AH-160; (888) 774-1419 Revision 8: 10/12/2017
Page 2 of 9
(x
14
• U
TRINITY I ERD
5.3 Fire classification is not part of this evaluation. Refer to a current Roofing Materials Directory for fire ratings
of this product and FBC 1505.2.
5.4 ICP Adhesives Polyset® AH-160 can be used with flat, low and high profile tiles or any rigid, discontinuous roof
assembly having a current Florida Statewide Product Approval or approved on a local -level by the Authority
Having Jurisdiction.
5.5 Minimum underlayment shall be per FRSA/TRI April 2012 (04-12) or having a current Florida Statewide
Product Approval or approved on a local -level by the Authority Having Jurisdiction for use with ICP Adhesives
Polyset® AH-160.
5.6 Field tiles, meeting the limitations of FBC 1609.5.3, using ICP Adhesives Polyset® AH-160 are limited to
projects having an Aerodynamic Uplift Moment (M.), determined in accordance with FBC 1609.5.3 or Tables
2A and 28 of FRSA/TRI April 2012 (04-12), not greater than the following Allowable Overturning Moment
values. Refer to Section 10 and ICP Adhesives and Sealants, Inc. published installation instructions for
Adhesive Paddy Placement details. d
�iw.?�)rsz'�' �� �a�ks�>TABLEl aEIELD TILE(NI-CPADHE$IyES POLySET'�a+AH'160.r�,k�a��,
u��4�
�AfAFA�ODygpPflED
w'�'+�'N'.�,':a�".,
�"�v""'� ��.��
�e�g� � b'{�Fy 2701 GI USAF rORI OEPENO M 9P��LE01[NNpNf10U5 ]ADDY
PIACEME�yr��
s .-,., a�. iP .,.., «& .f4,iolh�fARGIN OF,SAFEfgAI,NFAOVAPpUm Poal ERD[F,END(N�ITLYO PADDy)P,IACEMEMxC
f,5�,y
«_ �`�:+" w °
Tile (FBC 1609.5.3)
Adhesive Paddy Placement
Allowable
Overturning
Type
Profile
Moment (ft-IbQ
Independent; Single Paddy, Medium (2x7-inch, "30 gram)
J
60
Clay or
Inde endent; Sin Ie Padd , Large 2x10-inch,-45 ram
P g Y g( gram)
]
112
Concrete
Flat
Interdependent; Two Paddy (4x4-inch on underlayment, 2x4-inch at'!tile
overlap)
54
Independent; Single Paddy, Medium (2x7-inch, -30 gram) J
39
Clay
Low/
Independent; Single Paddy, Large (2x10-inch,-54 gram) ]
67
Concrete
te
Medium
Interdependent; Two Paddy (44-inch on underlayment, 2x4-inch at, tile overlap)
58
Clay
High
Independent; Single Paddy, Large (2x10-inch,-45 gram) )
134
-
Independent; Single Paddy, Medium (20-inch, -30 gram) J
65
Clay
Concrete
High
Independent; Single Paddy, Large (240-inch, -63 gram) J
109
Interdependent; Two Paddy (44-Inch on underlayment, 2x4-Inch at tile overlap)
40
Clay
Barrel
2x10-inch x `35 gram for pans; 2 @ 140-inch x-17 gram for cap
J
147
Concrete
Barrel
2x10-inch x -35 gram for pans; 2 @ 140-inch x-17 gram for cap
J
107
ClayCap
atop 2x,
Independent: Continuous Paddy
p Y ("34 gram/ft)
I
135
stringer
d
Concrete
Cap atop 2x
Independent: Continuous Paddy
P Y (" 34 gram/ft)
116
stringer
Clay
Cap atop 2x
Interdependent:
stringer
Head: One (1) #10 x 2h" screw; Overlap: 1 x 6 inch (-10.5 gram)
JI
105
Concrete
Cap atop 2x
Interdependent:
76
stringer
Head: One (1) #10 x 2M" screw; Overlap: 1 x 6 inch ("10.5 gram)
5.6.1 Data in Table 1 relates to installation over a '30/90' underlayment system, as del
2012 (04-12). Alternate underlayment systems include those having a current
Approval and/or approved on a local -level by the Authority Having Jurisdiction <
Adhesives Polyseto AH-160.
5.6.2 Tile roof systems using the types or profiles other than those listed above acquiri
ICP Adhesives Polyset® AH-160 shall be tested in accordance with SSTD 11 or Te
TAS 101. For the interdependent two -paddy method, an additional 2-to-1 mar
SSTD 11 or Testing Application Standard TAS 101 shall be applied in determining
moment'.
Exterior Research and Design, LLC.
Certifitute o)Authori[otion#9503 a EDITION (2017) FBC NON-HVHZ EVALUATION
ICP Adhesives Polyset® AH-160, (888) 774-1419
the FRSA/TRI April
Statewide Product
Ily for use with ICP
acceptance for use with
ig Application Standard
above that specified in
e 'allowable overturning
Report 02768.03.06-R8
FL6332-R8
Revision 8: 10/12/2017
Page 3 of 9
\,i I RINITY ERD
5.7 Hip and ridge tiles using ICP Adhesives Polyset® AH-160 are limited to projects having hip/ridge design pressure
requirements, determined in accordance with Table 1A of FRSA/TRI April 2012 (04-12), not greater than the
following values. Refer to 1CP Adhesives and Sealants, Inc. published installation instructions for Adhesive
Paddy Placement details.
rx%,
q.,r+vii�,.,�TAeiE2Hla<IpGETILESINICPADHEiIvesPo[.rsEr0AHi60r'5�`'*rv-.
I �1 ALLOWAB[EUPUFT RESISTANCE PERFORMAL�CE DATA `�' "�' ��' - �''�' 't
ice' �'
32Ta.t,MAkGINOF5AFE7YALREADYAPPLIEa iORINaYPENDEIVT �^`
fCOMINUGUS.PADDYJ PIACEMEMr+�' +'Cy's *-
...•'aF,SAFE7YALFFADYAPPUEQ FOKIMEROEPENUEM P%AEEMEM,.yN,"
Allowable
rile Substrate Attachment Method Design Pressure
(Psf)
Clay
2x PT ridge board
Independent: Continuous Paddy (^34 gram/ft)
116
Concrete
2x PT ridge board
Independent: Continuous Paddy (^ 34 gram/ft)
107
Clay
2x PT ridge board
Interdependent: Head: One (1) #10 x 234" screw;
Overlap: 1 x 6 inch (^10.5 gram)
90
Concrete
2x PT ridge board
Interdependent: Head: One (1) #10 x 2W screw;
Overlap: 1 x 6 inch (^10.5 gram)
56
Clay or
Hip & Ridge Channel Metal (FL5374):
Concrete
galvanized only
Independent: Continuous Paddy (^34 gram/ft)
169
Clay or
Trim LockTM (FI5374): aluminum,
Concrete
galvanized,Galvalume® or stainless steel
Independent: Continuous Paddy (-34 gram/ft)
173
Clay or
Trim Lock'" Plus (FL5374): aluminum,
Concrete
galvanized, Galvalume® arstainless steel
Independent: Continuous Paddy
P y (" 34 gram/ft)
178
Clay
Top Notch (FL8095)
Independent: Continuous Paddy (^ 32 gram/ft)
125
Concrete
Top Notch (FL8095)
Independent: Continuous Paddy (^ 32 gram/ft)
146
6. INSTALLATION:
6.1 ICP Adhesives Polyset® AH-160 and the tile roof assembly shall be installed in accordance with FRSA/TRI
April 2012 (04-12) and ICP Adhesives and Sealants, Inc. published installation instructions, subject to the
limitations outlined in Section 5.
6.2 Hip and ridge boards or hip/ridge metal shall be installed in accordance with the FRSA/TRI April 2012 (04-12).
Proprietary hip and ridge metal shall be installed in accordance with the manufacturer's Florida Product
Approval.
6.3 Installation shall be performed by applicators who hold a valid Qualified Applicator Card presented by ICP
Adhesives and Sealants, Inc.
BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the
installation of this product. {
8. MANUFACTURING PLANTS:
Tomball, TX
9. QUALITY ASSURANCE ENTITY:
UL, LLC. - QUA9625; (847) 664-3623; LeAnna.Gradecki@ul.LOm
Exterior Research and Design, I.I.C. Evaluation Report 02768.03.06-118
Cerafimtea/Auth#rlrnaon#9503 0 EDITION 120171 FBC NON-HVHZ EVALUATION FL6332-RS
ICP Adhesives Polyset' AH-160; (888) 774-1419 Revision 8:10/12/2017
Page 4 of 9
i
I
I
I
10. PADDY PLACEMENT DETAILS (FROM ICP ADHESIVES AND SEALANTS, INC. PUBLISHED
I
10.1 Independent, Medium Paddy:
Nail through plastic cement Paddy (Beneath Tile)
(when required)
IUndedayment °ram
7 in. tin.
Battens optional
Gave Course
a
f
°
a
10in.
d
�2 in' Fascia
Eave Closure
Fiat/Low ProfrleTile
Exterior Research and Design, U.C.
Certificate ofAuthorimtlan #9503
I
Nall through plastic w
Paddy (Beneath Tile)
(when required)
i
Undedayment
I
71n.
2In.
Battens optional
e Sr�t
� ?y
I
Y
Y. _ Gave Course
asda
Weee
10 in. 2 in.
Gave closurosure
Drip edge,
LII.h D.M'If. Tile
6'" EDITION (20171 FBC NON-HVHZ EVALUATION
ICP Adhesives Polyseta AH-160, (888) 774.1419
TRINITY I ERD
E):
Report 02768.03.06-R8
FL6332-R8
Revision 8: 10/12/2017
Page 5 of 9
10.2 Independent, Large Paddy:
optional
Rat/Low ProfileTile
-1 TRINITY (ERD
I
plasliccement
Medium Profile Tile
Nall through plastic ce
(when required)
addy (Beneath Tile)
/
Underlayment
IIYI �
10 m.x
2 in.wide
Battens
optional
Eave Course
Fascia
Weephole
10 in. 2 in.
Eave closure
Drip edge
High ProfileTile
' Eave Closure
Fasda
Exterior Research and Design, U.C. Evaluation Report 02768.03.06-R8
Ceniilone of Authorization a9503 6'"EDITION (2017)FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyseta AH-160; (888) 774.1419 Revision 8: 10/12/2017
Page 609
a
10.3 Interdependent, Two Paddy:
Nail through plastic cement
Pad dy(between tiles)
(when required)
Battens optional
°
°
Paddy(undertile)
Singlepaddy
on top of tale
4x4in.
4
fi x.
Sing!
padd
- - -
undertil
Singlepaddy
on underlaymant
2x4in.
Min
�l in.
scia
Eave Closure
Flat/Low Profile Tile
Exterior Research and Design, LLC.
v CertlJicate of Authorization #9503
U
�1 TRINITY ERD
,
Nall through plastic cement Single paddy under file
(when required)
I. I { Paddy (between tiles)
i 1
Battens \ j /Paddy(under ale)
on
10 in.`'c
Medium
Nail through plastic ce Singlepaddyundertiie '
(when required)
\ Paddy (between ales)
p oPtional �?�}', Paddy(undertile)
nglepaddy
on underlayment
4x4in.
Single 2x4in 11i'
paddyon
top of We r .
t
z. I
_ Eave Course"
WlFascia
ephole
loin. in. Eave closure
Drip edge
High ProfileTile
(Sm EDITION (2017) FBC NON-HVHZ EVALUATION
ICP Adhesives Polyseta AH-160; (888) 774-1419
on Report 02768.03.06-R8
FL6332-R8
Revision 8: 10/12/2017
Page 7 of 9
\,ITRINITYIERD
10.4 Two Piece Barrel (Cap & Pan) Tile:
11 Place enough adhesive to achiew 65 to 70
In contact with the pantile.
21 Tum Ci M upaitc down. Place edaaalw
IQ In. b 1lnch In f um oubide edgaof cevor0le.
ImlallwvaR
Enure 201n 25 aa. In. correct ere. on
each eide or eovo.6m.
Remove topportion of the new toune owertile.Abutto secend coupe of
Pon d1ea.Emum eave end of pan and cowrtilet are flesh at cave line.
Two Piece Barrel - High Profile Tile
10.5 Hip and Ridge (independent Placement):
TO afluea hipMd6c otis, ahead pCICPPdysYPgfl-16o My
l epp5eddorm the=Wofthe hp1idgeboard mgehinbed
enne-
Exterior Research and Design, L-C. Evaluation Report 02768.03.06-R8 - -
CertiiicoteofAuthoriaodanN9503 6s"EDMON(2017)FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyseta AH-160; (888) 774-2419 Revision 8: 10/12/2017 a
Page 8 of 9
e
i P
TRINITY I ERD
10.6 Hipand Ridge (interdependent placement):
- Exterior Research and Design, LLC.
o Certifiane of Authorkadon#9503
y
e
1" X 6" Bead of ICP'
Polyset®AH-160
roof tile adhesive
i
#10 x 2-1/2" Sca ew
Code Approved)
9
Fastener
Adhere starter
tile with a 2" x 7"
Paddy placed 3"
down from head
of tile
- END OF EVALUATION REPORT -