HomeMy WebLinkAboutSUBMITTED PAPERSST. LUCIE COUNTY -FT PIERCE FIRE DISTRICT BUILDING PLAN REVIEW P. O. BOX 3030 Telephone: 661-462.2312 Ft. Pierce, FL 34948-3030 FAX: 561-462-2326 JURISDICTION: St Lucie County FPB #: 6570 PROJECT NAME: New Horizons - Detox_ BLDG DEPT #: 96070095 CONTRACTOR: Proctor Construction_ PHONE #: 561-234-8164 ARCHITECT: Hill/Krieg PHONE #: 941-482-4761 BUILDING OWNER: New Horizons REVIEW DATE: 7-15-96 BUILDING LOCATION: 4500 Midway Rd # OF STORIES: 1 OCCUPANCY TYPE: Institutional AUTO SPKLS: Yes X No GROSS SQ FOOTAGE: 7200 sq ft NET SQ FT: OCCUPANT LOAD: BASED ON: sq ft per person net CONSTRUCTION TYPE: NFPA #220 _III (211) SBCCI _V_(pro) NEW CONSTRUCTION _X_TENANT IMPROV RENOVATION ADDITION SHELL ONLY ALL REVISIONS LISTED MUST BE IN COMPLIANCE BEFORE THE FINAL INSPECTION. The Fire Marshal requires 24 hour notice on all inspections. The Building Department schedules all final inspections. ****************************************************************************************************************** DETOX BUILDING 1. A separate permit is required from the Fire Marshal for the installation of the automatic sprinkler system and the fire alarm system. (See attached requirements.) REVIEWED BY: DATE: Sheet — of 8T. LUCIE COUNTY FIRE PRE VENTIt.N BUR:tr'.AU % FIRE ALARM REQUIREMENTS A'separate permit is required'-fr-on-., the Fire Marshal's -Office fo r� the installation ofafire alarm syttern. Installation shill be by p­Florlda Certified Alarm Systems,: retractor 1, and Must have Ic 1 1-9 EF. prbfixinu,tf :9-c6-tK_ation.Nu..-' lier,.Pr a Florida Certified Electrical Contractor (Master), With EC. In the certification -Nuri-iber.* The contractor !:hall furnish a.copv.of his State Certification upon making application. Ap.aqqati2jL'for an oermit shall include the following: 1. 'rhe r;rjntractcrs name,,r4dress, pfione. number,' and license Number. The job'sit--i address and OCCLI 'anCy r: y pe. P ; 3. UL..'HZ;.,.;_,ng end manufactures sr�ecific'ations on all appliances. .4. Standard -bah C .,Ic,.!Iations. S. Voltage'� ,�iop Calculations. 6. Floor plan, showing.,alFlocatioiis of appliances. 7. Drawing -shall incl'Oe the location of devices, wire runs, zones, end of line resistors a n d/ typical wiring method"e"7used on the devices. 8. All rooms shall be labeled and show dimensions. 9. When duct,type smoke de _--tors are installed for automatic fan shut down, the,KA.c.p. or Remote F.A.C.P. shall be I '_` Le,, oTmally occupied area. -A supervisory trouble signal shall be indicated audibih, and visually in the panel or a genera Mgnal I eVacuatio:i shall be initiated. - Th e. Co Htra cto r s h a 1 1 be responsible for obtaining a St.. Lucie County ALqri,!,; Users Permit in*.the form of a decal, frorh thk! County Tax Collectors Office, 2306 Virginia Ave. Ft. Piercd,*Fi. The ,Building Cbi-vrier must sign i-qn the permit• application. When the, building is -i-otectsd,wifil a supervised automatic Sprinkler sysfarn,. then the fire alarm system shs.11 a -so be supervised by a receiving station approved by the Fire Marshal. A Knox Box shall be installed and shall b6 located per'directior, of te Fire Marshal. The Knox Bo:, shall contain an access key (s)-so entry can be gained by eme,-gency personal to access the automatic sprinkler controls and fire alarm control panel. Tha- Knox Box shall be mounted near an entrance ncu accessing the automatic sp'rinicler controls ar i or fire alarm control panel - .The Department of Community Affairs, Florida Board of Building Codes And Standards, Accessibility requirements are mandated for fire alarm requirements and the American with Disabilities Act (ADA) is Federal Law and is presently used for litigation purposes. page The, Fire Alarm requirements in the Florida Accessibility Manual and the Americans With Disabilities Act (ADA)are included below. It is the responsibility of the building architect and or engineer to design.these requirements in to the building fire alarm system. AMERICANS WITH DISABILITIES ACT (ADA) The rules and regulations for the Americans with Disabilities Act (ADA) were published, in the Federal Register with an effective date of July 26, 1992. The requirements for visible and audible indi.cattng appliances, for manual fire alarm boxes will apply when a fire protective signaling system or single station detectors are provided for: When a,specific occupancy requires the installation of a fire alarm or detection system as referenced in the National -Fire Protection Association (N.F.P.A.) Standard 101, The Southern Standard Building Code, -or if a 'building ovrner chooses to install an alarm system not required by code, then the system must be installed and comply with the provisions of N.F.P.A. No. 72, National Fire Alarm Code. If a specific occupancy chapter of N.F.P.A. 101 or the Southern Standard Building Code Chapter 903 does not require a fire alarm system then an alarm or detection system need not be installed. Note, that each occupancy requirements differ from each other and each occupancy chapter of N.F.P-.A 10.1 has it's own requirements. The requirements for visible and audible indicating appliances, and a maximum mounting height for manual firer alarm boxes will apply when a fire protective signaling system or single station detectors are provided for: A. All new construction, excluding non -transient residential occupancies (e.g., apartrnents, condominiums, dormitories and one and two family -dwelling units), designed and constructed for occupancy after January 26,1993. and, B. Any alteration to a place of public accommodation or a commerci,-.11facility after January 26,1992. C. - To be classified as a place of public accommodation, a facility must be operated by a private entity; its operation must effect commerce, and must fall within. one of these 12 categories: 1. Place of lod-ging. 2. Establishments serving food or drink 3 Places of exhibition or entertainment. 4. Places of public gathering 5 Sales or rental establishments. 6. Service establishments. 7. Stations used for'bublic 10. Places of education. 11. Social service center establishments.-A2. Places of exercise or recreation. page 2. D. Commercial facilities are those facilities that are intended for non-residential use by a private entity and whose operation effect commerce. Included in this cateaory are factories warehouses, office buildings, and other buildings in which Employment may occur. E. Requirements that are effected: 1. Controls and operating mechanisms. 2. Visual signals. 3. Visual signals appliances. 4. Audible emergency alarms. F. The requirements effect the location and height of control mechanisms. The color, intensity and location of visual and audible signals. G If provided, electrically powered internally illuminated exit signs shall flash as a visual emergency alarm in conjunction with audible emergency alarms. The flash frequency of visible alarm devices shall be not less than 5 Hz. If such alarms use electricity from the building, as a power source, then they shall be installed on the same systems as the audible alarm signals. In lieu of flashing the exit signs. visible alarm devices may be mounted adiacent to the exit signs H. Visual signal appliances shall be provided in buildings and facilities in each of the following areas: Rest rooms and any other general usage areas: (e.q, meeting rooms), hallways, lobbies, and any other area of common use .I. Visual signals shall be integrated into the building or facility alarm system. If a single station audible alarms are provided then single station visible alarm signals shall be provided. J. Where Are Visible Alarms Not Required: 1. Areas used only by employees as work areas are not required to be constructed or equipped to be accessible. Thus, visible alarms are not required in individual employee offices and work stations, unless the individual employee is deaf or hard of hearing. 2. If the occupancy is not required to provide a manual alarm. or detection system. 3. If a manual alarm system is not required for a specific occupancy, the electrical illuminated exit signs are not required to flash, nor is a visual indicating appliance, (strobe light) required in lieu of the flashing exit sign. K. CONTROLS AND OPERATING MECHANISMS 1. Controls and operating mechanisms in accessible spacc, and accessible' routs , as specified in N.F.P.A. 10'I shall have the highest operable part not more than 48 inches above the floor for forward approach and 54 inches if the floor space allows for parallel approach by a person in a wheel chair. page 3. 2. Controls and operating mechanisms shall be operable with one hand and shall no require tight grasping, pinching or twisting of the wrist. The maximum force required to activcte the controls shall be no greater than 5 lbs. 3. Visual signal appliances shall be l:;rovided in general use areas and rest rooms, corridors, hallways,lobbies and 6ther-areas of common use. 4. Required visual alarms shall be integrated into the building alarm system and shall have the following minimum photometric and location features. a. The lamp shall be xenon strobe type or equivalent. b. The color shall be clear or normal white. c. The intensity shall be a minimum of 1 Hz, and a maximum of 3 Hz. d. The appliance shall be placed 80 inches above the highest floor level within the space or 6 incht?s' below the ceiling which ever is lower. e. No place in any room- or space required to have a visual signal shall be more than 50 ft. from a signal (Horizontal Plane). f. Visual signals may be insalled in large rooms or spaces exceeding 100 ft across without obstructions 6 ft. above the finished floor. Devices may be placed 100 ft. apart in lieu of suspending appliances from the ceiling. g. Common corridors*or hallway appliances shall be placed so as a person is no more than 50 it. from a visual signal. h. Accassible sleeping rooms in hotels, motels, inns, boarding houses, dormitories, resorts and ;other places to transient lodging are required to' have a visible alarm which can be actuated by a signal from the building alarm system. H.R.S. REQUIREMENTS: H.R.S. requirements will differ with some occupancies, such as Child' Day Care Centers and Adult Congregate Living Facilities. These type facilities are reviewed and inspected under State Fire Marshal Rule 4-A, and are inspected by W.R.S. for compliance. page 4. ST. LUCIE COUNTY BUREAU OF FIRE. PREVENTION TELEPHONE: (407).462-2312 FAX: (407)-462-2325 AUTOMATIC FIRE SPRINKLER SYSTEMS The St. Lucie County Fire. Prevention Bureau enforces State Fire Marshal Rule 4-A-3.012 which requites compliance to Florida Statutes, Chapter 553.79 (6), (c). The following requirements are necessary for compliance when submitting automatic fire sprinkler plans for approval by the St. Lucie County Fire Prevention *Bureau. a 1. ENGINEER OF RECORD: The Florida Registered Professional Engineer for the automatic fire id sprinkler system shall develop the sprinkler system design criteria, piping system d concept for the system, perform the required engineering analysis, and .be,responsible for the �p preparation and sealing of the fire sprinkler system construction documents. 2. The building architect shall furnish the St. Lucie County Fire Marshal a letter stating who the engineer of record will be. The architect is responsible for the entire building construction. 3. SPECIALTY ENGINEER: A Florida Registered Professional Engineer, not the Engineer of Record for the sprinkler system, may design a portion .of the sprinkler system not within the expertise of the Engineer of Record, such as electrical controls, etc. 4.' The engineer of record shall be responsible for the sprinkler design criteria, piping system concept, and the point of interface or the point of service which meets the requirements of the fire sprinkler system and applicable codes as defined in Florida Statutes 633.021,,.meaning that point at which the underground piping for the sprinkler system using water as the extinguishing agent becomes exclusively for the sprinkler system. The point of service shall be designated by the engineer of record who sealed the plans for a system of 50 or more heads. NO PERMIT WILL BE ISSUED --UNTIL TWF POINT of RFRVICE HAS BEEN DESIGNATED ON THE SITE PLAN OF THE UNDERGROUND, � PIPING SYSTEM. S. The seal of a- Registered Professional Engineer is not required for the design of additions,. alterations or new fire sprinkler systems of 49 or fewer heads. 6. Fire sprinkler construction documents must be prepared by the engineer of record and shall include as a minimum all the items indicated by FS. 61-G15-32.903. 7. FIRE SPRINKLER SYSTEM PLAN SUBMITAL. The Automatic Sprinkler Contractor shall submit the required permitting documents to the respective building departments which are located in St. Lucie County. Forward all plans, calculations, and specifications directly to the building departments of the City of Ft. Pierce, the City of Port St. Lucie, and the St. Lucie County Building Department.. They will forward all documents to the fire prevention bureau for review. 8. Three sets of plans specifications and calculations are required for permitting. The Engineer of Record shall be responsible for all necessary revisions as required. 1. 1 9. Specifications submitted with the automatic sprinkler system documents shall include the required listing of materials and devices essential to, the successful, system operation as indicated in N.F.P.A. 13-2.1.1. The listing as published in the Underwriters Laboratories, Inc. Fire Resistance Directory, 1995 edition may be used as proof of compliance, or The Factory Mutual Listing may be used. The manufactures name and product category guide designation number shall be indicated or a separate manufactures specification presented at the time of permitting. 10 The Engineer of Record shall sign, seal and date each page all drawings, the first page of specifications and the cover page of the hydraulically calculations. 11. The automatic sprinkler contractor shall obtain a permit from the respectful building department after review by the Fire Marshal's Office. 12. A separate permit is required from the Fire Marshal's Office by the automatic sprinkler contractor. The contractor shall furnish a copy of his/her state certification upon making application for the permit. 13. When the review is completed by the Fire Marshal's Office, the contractor must sign the Fire Prevention Bureau permit and submit the pink copy to the respective building department to receive their permit and the reviewed plans . 14. The automatic sprinkler company qualifier shall sign for the permit or a notarized letter must be presented at -the time of making application stating the.name of the person who may sign for the permit. 15. Renovations or alterations to an existing system requires a separate permit from the Fire Marshal's Office when additional piping is added, changed or modified. 16. INSTALLATION: A. Installation shall be by a Florida licensed Fire Protection Contractor I or 11. A certified contractor V is permitted to install the underground portion of the system from the point of service to one (1) foot above the finished floor. NOTE: A certified underground utilities = contractor is not permitted to install any portion -of a automatic sprinkler system. B. The fire protection systems contractor I or II installing the system shall supervise and be responsible for the complete system, except that a contractor V installing the underground piping shall supervise and be responsible only for that portion that he installs. C. If the above ground piping is installed by a contractor other than the one that installed the underground, the above ground contractor shall be'responsible to obtain a copy of the . underground test certificate from the underground contractor. D. Upon completion of the final inspection of the above ground piping, the contractor shall conduct tests and maintain on file the contractor's material and test certificate for the above ground piping as specified in N.F.P.A. # 13. E. The above ground systems contractor shall present copies of the test certification to theFire Marshall upon competition of the hydrostatic test. -F. The hydrostatic test shall be conducted for two (2) hours at 200 psi. G. The Fire Marshall requires 24 hour notice on all inspections. 2. 17. Duct tile iron, copper piping or polyvinyl chloride (PVC), AWWA-C-900 shall meet the minimum requirements of DR-14 Class 200 for critical use in fire lines. Underground piping shall be UL.or FM listed. NOTE: C-900 DR -18. Class 150 is not permitted for underground sprinkler piping. 18. Compliance to N.F.P.A. 231 is required for: A. Occupancies storing materials representing the broad range of combustibles up to 30 feet in height. B. Storage of plastics (Groups B and C - all configurations Group A - free flowing only) upto 30 feet in height. • C. Storage of Group A plastics (except free flowing up to 25 feet in height). D. New buildings and existing buildings that are converted to storage occupancy. 19. Compliance to N.F.P.A. 231C is required for: A. The storage of materials representing the broad range of combustibles stored over 12 feet in height on racks. B. For storage height of 12 feet or less see N.F.P.A.13. 20. All component parts and their UL listing information shall be submitted for approval upon applying for a permit. 21. Monitoring of sprinkler systemsj. A. All automatic sprinkler systems shall be monitored by a Central Station Facility or LocalAlarm Receiving Station approved by the St. Lucie County Fire Marshal. Exception: N.F.P.A. 13-D systems are not required to be monitored. 22. Knox Box A. A Knox Box shall be installed and shall be located per direction of the Fire Marshal. The Knox Box shall contain an access key (s) so entry can be gained by emergency personnel to access the automatic sprinkler system controls. and the fire alarm control panel. 3.