HomeMy WebLinkAboutSUBMITTED PAPERS_2GG�OGG�f� STANDARD PRE -CAST CONCRETE EQUIPMENT SHELTER ANALYSIS Revision 7: March 10, 1998 CLARK ENGINEERS MW, INC. 111 N.E. Jefferson Avenue Peoria, IL 61602-1227 PROJECT STATEMENT Analyze and prepare calculations suitable for submission to building officials of pre- fabrecated pre -cast concrete equipment shelters as manufactured by UNR-Rohn. Design shall include details, notes, specifications, and drawings for complete review. This analysis is for buildings in widths of 8'-4", 10'-4", 12'-0" and lengths up to 364". Compliance with BOCA, SSBC, and UBC is required. Design shall be comprehensive to cover placement of shelters in all 50 states. APPROVED .By 00 Jul ON-, 0 9 998 I 6 PAGE DATE INDEX ITEM PAGE -EXT DATE REMARKS Design Criteria 1 March 10, 1998 Design Criteria 2 March 10 1998 Design Criteria 3 March 10, 1998 Roof Design 4 March 10, 1998 -- Roof Design 5 March 10, 1998 Roof Design 6 March 10, 1998 Roof Design 7 March 10, 1998 Roof Design 8 March 10, 1998 Walls 9 March 10, 1998 Walls 10 March 10, 1998 Walls 11 March 10, 1998 Walls 12 March 10, 1998 Floor 13 March 10, 1998 Floor 14 March 10, 1998 Floor 15 March 10, 1998 �Floor 16 March 10, 1998 DATE JUL p 9 CERT. NO,��� -m�5 Lateral 17 March 10, 1998 Lateral 18 March 10, 1998 NUMBER ' Lateral 19 March 10, 1998 PLAN _P-j2kh.2-G6<,L--� Lateral 20 March 10, 1998 APP YED BY CHARLES A. OSTERDAY, JR. Lateral 21 March 10, 1998 Lateral 22 March 10, 1998 Lateral 23 March 10, 1998 Foundations 24 March 10, 1998 nature sy nature Mg Foundations 25 March 10, 1998 ��-- 26 March 10, 1998 Foundations 27 March 10, 1998 Foundations 28 March 10, 1998 APPROVED BY -' Foundations 29 March 10, 1998 Foundations 30 March 10, 1998 Foundations 31 March. 10, 1998 Foundations 32 March 10, 1998 Foundations 33 March 10, 1998 Foundations 34 March 10, 1998 Foundations 35 March 10, 1998 Foundations 36 March 10, 1998 Foundations 37 March 10, 1998 Foundations 38 March 10, 1998 Foundations 39 March 10, 1998 Foundations 40 March 10, 1998 Foundations 41 March 10, 1998 Foundations 42 March 10, 1998 Foundations 43 March 10, 1998 Foundations 44 March 10, 1998 .Foundations 45 March 10, 1998 Foundations 46 March 10, 1998 Foundations 47 March 10, 1998 Connections 48 March 10, 1998 Connections i 49 March 10, 1998 PAGE DATE INDEX ITEM PAGE EXT DATE Connections 50 March 10, 1998 Connections 51 March 10, 1998 Connections 52 March 10, 1998 Connections 53 March 10, 1998 Connections 54 March 10, 1998 Connections 55 March 10, 1998 Connections 56 March 10, 1998 Connections 57 March 10, 1998 Connections 58 March 10, 1998 Connections 59 March 10, 1998 Connections 60 March 10, 1998 Connections 61 March 10, 1998 Connections 62 March 10, 1998 Connections 63 March 10, 1998 Connections 64 March 10, 1998 Connections 65 March 10, 1998 Connections 66 March 10, 1998 Shelter Transport 67 March 10, 1998 Foundation Design 68 March 10, 1998 Foundation Design 69 March 10, 1998 Foundation Design 70 March 10, 1998 Foundation Design 71 March 10, 1998 Foundation Design 72 March 10, 1998 Foundation Design 73 March 10, 1998 Foundation Design 74 March 10, 1998 Foundation Design 75 March 10, 1998 Foundation Design 76 March 10, 1998 Fire Rating 77 March 10, 1998 Thermal Efficiency 78 March 10, 1998 Wall Openings 79 March 10, 1998 Wall Openings 80 March 10, 1998 Wall Openings 81 March 10, 1998 Wall Openings 82 March 10, 1998 Wall Openings 83 March 10, 1998 Wall Openings 84 March 10, 1998 Wall Openings 85 March 10, 1998 Wall Openings 86 March 10, 1998 Appendix'A' 87 February 6, 1990 Appendix'A' 88 February 6, 1990 Appendix'A' 89 February 6, 1990 L1UNRN0012\QPR0\C0NCT0C. W B2 L REMARKS DATF AL 0 9 1 Cbr T. Nv 5'^nP - O IS PLAN NUMBER, APPR VED BY CHARLES A. OS T ERDAY, J R. (JU14 ( signature j APPROVE® BlY 1. DESIGN CRITERIA a. Concrete (shelter) Sand lightweight concrete mix obtaining a 4000 psi minimum compressive strength in 28 days. (foundation) Normal weight concrete mix obtaining a 3000 psi minimum compressive strength in 28 days. b. Concrete Reinforcement ASTM A615 grade 60 (fy = 60 ksi) ASTM A185 smooth welded wire fabric C. Connections Plates, bars, etc... : ASTM A36 (F„ = 36 ksi) Welding electrodes : E70XX Headed studs : ASTM A108 (Ft = 60 ksi) d. Loads Floor Live Load R21 140 psf (min) to 200 psf (max) ., Wind Check for worst code based on 120 mph (EXP. C) 1 = 1.0 BOCA P = P„IKGCP Pv = 36.9 P' APPROVED By 1'w ? F �'• � 1 Exposure coeff. (K) = 0.80 INC. Gust response factor (G) = 1.32 Wall pressure coeef. (CP) = 0.8 + 0.5 = 1.3 Roof pressure coeef (Cd _ -0.7 P = 36.9 (1.0)0.8 (1.32) 1.3 = 51P' P„ = 36.9 (1.0)0.8 (1.32)-0.7 = 27P" w 1 March 10, 1998 1. DESIGN CRITERIA (cont'd) d. Loads (cont'd) Wind (cont'd) SBC Velocity pressure q = 0.00256V2(H/33)2" q = 0.00256(120)2 (15/33)217 = 29.4Ps' Use factor = 1.0 GCP Coeff = 1.2 (lateral) P = 29.4(1.0)(1.2) = 35 GCP Coeff = 1.4 (uplift) PU = 29.4(1.0)(1.4) = 41 UBC Basic wind speed 120 MPH Ce = 1.06 Cq = 1.3 (lateral) Cq = -0.7 (uplift) I = 1.0 QS = 36.9Ps' Lateral P = CeCq Qs 1 = 1.06(1.3)36.9(1.0) = 51 P1 Uplift PU = 1.06(-.07)36.9(1.) = 27P' Seismic BOCA & SBC V = CS W CS = 2.5 Aa R A. = 0.4 R = 1 4.5 CS = 2.5(0.) = 0.222 4.5 V = 0.222 W APPROVED_ ''r 1998 KIP, INC., 6 March 10, 1998 1. DESIGN CRITERIA (cont'd d. Loads (cont'd) Seismic (cont'd) UBC V = 2.5C� I W R I = 1.0 Na = 1.5 Ca = 0.36(1.5) = 0.54 Na = 1.1 Ca = 0.44(1.1) = 0.48 R = 4.5 V = 2.5(0.54)1.0 W = 0.30W 4.5 APPROVED BY 1141 rr, JUL INC 3 March 10, 1998 2. ROOF I_ I a. Code Requirements r- j f - Assumptions: f, = 4000 psi fy = 60,000 psi 4" roof: 4" @ edge -and 5.5" @ ridge Design roof for snow load and wind uplift. - Try to use only 4" thick roof panels. per ACI 318- P,,,;,, (temperature and shrinkage) = 0.0018 1/4 r- 4° 1 i I AS= 4.5°(12) .0018 = 0.0972 IN2/FT V@12 �.376.� ;668 a - Concrete cover = 2" at middle 3/4" at end 4pBY pROVED O N �'INC 4 March 10, 1998 2. ROOF (cont'd) b. Loads Dead Load 4" concrete (4.75 / 12)118 = 46.7 Psf roofing = 0.5 Psf ceiling = 1.0 Psf miscellanous = 1.5 Psf 49.7 P' x 1.4 = 70 Psf ,APPROVED BY L0-9 1998 5 March 10, 1998 'd) 2. ROOF (cant 1 _ c. Member Design �( Shear d = 4 - 1.75 = 2.25 b=12" 4" cpv, = 0.85(2) SQRT(4000)(12)2.25 = 2903#''x 0.85 = 24681 Wu = 2468 = 448 Ps' 11 /2 W, _ (448 -.70) 11.7 = 222 Ps' say okay for 50 Psf snow APPROVEDBY 0 0 !4� �. 6 March 10, 1998 2. ROOF (con t'd) c. Member Design (cont'd) Flexure f� = 4000 Ps' fy = 60 ks' l - Try #4 at maximum spacing Maximum spacing = 3 x slab thickness < 18" 4" spacing = 3 x 4.5 = 13.5 - 12" 4" Roof d=43/4"-3/4-3/4-1/4=3.0" #4012" p=0.2/3.Ox12=.00556 TMn = 0.9(60).00556(12)(3. 0)2(1 - 8.85 x .00556) = 30.81"' W„=(49.7x1.4+50x1.7)=155P' M„= 155x(11.3)2/8=29.7'<qM" Check for Wind Uplift Wu=49.7x0.9+1.3(-41)=-8.6Psf #4 12 d =.75 x 2 + 5/16 = 1.81" p = .2 = .00921 12 x 1.81 cpMC _ .9(60).00921(12)(1.81)2 (1 - 8.85 x .00921) = 18.01 M„ = 0.0086(11.33)2/8 = 0.138" x 12 = 1.66" okay 7 March 10, 1998 2. ROOF (cont'dl c. Member Design (cont'd) Deflections f, = 7.5 sgrt (4000) = 474 psi x 0.85 = 403 P" E = 42.3 sgrt (4000) = 2675"' max span = 11.33' defl = 5wl4 384(E 1) (4") Ig = (4.75)3 12 / 12 = 107.2 "4/R Mcr = 403(107.2) = 18.19k" 2.375 Deflections 4" slab (assume 52 P' live load for 2 Psf of water ponding) reinf. Ma DL Ma (LL=52 PS') a Ic" kr k"P #4@12 9.52 9.96 0.88 12.47 reinf. Mcr/Ma s 1. LL defl DL defl LL defl LL cr. above cr. #4@12 0.81 89.6 .064 .058 .078 Total DL I.t. mult. = 2 (5 year or more) 60 psf LL I.t. mutt. = 1 (3 months) * look at long term deflection of LL = 52 P' defl = .064 x (2 + 1) + (.058 + .078) (1 +. 1) = .46" = 1 / 296 initial slope of roof = 1/4" per foot Therefore assume a 1 1/2" rise in the roof, so maximum ponding is 0.46 - 1.5 = 0.264" Therefore no ponding -.50 Psf < 52 Psf oka APPROVED BY "°• ' u �3 8 March 10, 1998 3. WALLS Wind Pressure Resistance Two criteria: 1. max load - 120 mph wind-Exp. C I = 1.0 2. minimum reinf to be used is 4x4-W4.OxW4.0 WWF P 4 • WWF = o A. 2„ 21 W x o Q— Wind Pressure P=51 P' M„=51(10)2/8x1.3x12=9.9k"' Vu = 51(10/2) x 1.3 = 0.33k"r Shear cpVc _ .85(2) SQRT(4000)(12)(2) = 2580#r x .85 = 2193' V. > Vu * THEREFORE SHEAR IS OKAY Deflections By comparison to roof and the temporary nature of the load s—X okay. Axial and Flexure j,,PFpOVF—D B'Y w/o Axial Load 50'- ='_g 4x4xW4.OxW.4.0 WWF (As = 0.12 '" IN p = .12 = .005 2(12) cpMc = .9(60).005(12)(2)Z (1 - 8.85 x .005) = 12.39' M„ = 9.9k"f * THERFORE FLEXURE IS OKAY 9 March 10, 1998 3. WALLS (ont'd) Wind Pressure Resistance (cont'd) W/Axial Load Pd = 49.7x12'/2+4/12(118)(10) = 495" P, = 50x12/2=300' Psi = 1212 x 27 Psf = 162' AppROVED BY 10 March 10, 1998 - 3. WALLS (cont'd) Wind Pressure Resistance (cont'd) w/ Axial Load (cont'd) Combinations 1. D+S w=o P = 495 (1.4) + 300(1.7) = 1203#r 2. D+S+W/2(ExpD) w = 51 P'/2x.75x1.7=33#r P = 495 x 1.4 = 693 300 x 1.7 = 510 } 1065 x .75 = 799#r -162 / 2 x 1.7 = -138 3. D+W w = 51 x 1.3 = 66.3#r P = 495 x .9 = 446 } 235:r -162 x 1.3 = -211 4. D+S/2+W w = 51 x .75 x 1.7 = 65#r p = 495 x 1.4 = 693 ' 300 / 2 x 1.7 = 255 } 673 x .75 = 505' -162 x 1.7 = -275 By INC. 11 March 10, 1998 3. WALLS (cont'd) Wind Pressure Resistance (cont'd) r- w/Axial Load (cont'd) - Re: "Design of Concrete Structures" by Winter/Nilson (Vh edition) page 314 -- Pd = cpPn = cp.85 f,' bd [-pu + 1 - e' + SQRT(1 - e')Z + 2 e' u d d d u = 60,000 / .85(4000) = 17.65 - d=2" fc=4ks' b=12" d=2" cp=.87 li —` Pd = 71.0 [-17.65p + 1 - e' + SQRT[(1 - e')Z + 17.65 pe']] 2 2 Comb. M(W) P(k) e' P Pd 1 0 1.2 ---- ---- Pa„ _ .55(1.7)4(48) [1. - .88] = 8.87k' ok 2 5:0 .80 6.25 .005 2.6 ok 3 9.9 .24 41.3 .005 .30 ok 4 9_9 . 11 19.4 .005 .66 ok Summary 4" concrete wall reinforced with 4x4 - W4.0 x W4.0 WWF is okay. 12 March 10, 1998 4. FLOOR a. LOADS LL = 140 P"TO 200 PS' DL = > STRUCT - 34 P" VINYL TILE - 1 Ps' MISC - 1 Psf 36 P" WT = 2241 x 118 = 39.3 144 6(4L x118 =19.7 144 (2)6(5) x 118 x 1.67 = 7.5 144 11 67 = 34 P' APPROVED BI � 9 INC 13 March 10, 1998 4. FLOOR (cont'd) b. RIB DESIGN FLANGE: AS = 2(12).0018 = 0.043 '" 2/ft. Use W2.9 x W2.9-6x6 WWF. RIB: Since Rib is less than 4" wide - design as beam Shear re: ACI 11.5.5.1 total depth < 10", or 21/2(2) = 5" or, 1/2 x 3 = 1 1/2" TVA = 0.85(2)(4000)12 (4)(8-1.25) = 2903" x 0.85 = 2467# Vu Wu(11 -1.46) / 2 - 6.75 / 12) = 2467# W„ = 586#''/2'-0 Rib Spacing = 293P' LL = (293 - 36 x 1.4) / 1.7 = 140 P' (No stirrups) APPROVED INC Jul 14 March 10, 1998 4. FLOOR (cont'd) b. rib design (cont'd) If LL = 20OPSF• W„=(52 x 1.4 + 200 x 1.7)2 = 826"t _ Vu = 826 ((11 -1.46) / 2 - 6.75) = 34754 > 2467# 12 Provide Shear Reinf. Min. A„-50bwS/fy=>Av/S=50x4/60000=.00333 SmAx = d / 2 = 6.75 / 2 = 3.375' @S=3" Av=.01 in2/3" VS = (3894 - 2467) = 1975# = A„ fy d .85 x .85 S Av/S = 1.975 = .00488 #3 @ 3" Reinf. 60(6.75) DIST. 3894# - 826(x) = 2467# x = 1.73 x 12 = 20.7" LL = 200 Psf For 21" out use #3 Cagy 3" or W2.5 x W2.5 - 3x3 WWF LL = < 140 Ps' no shear reinforcing Rib SPAN = 11.0' LL (PSF> W (KII) M (K-) P A (" 2) BOTT. 150 .58 105 .00241 0.39 #6 200 .77 140 .0032 0.51 #7 p= m = m .9(60)24(6.75)2(1 - 8.85p) 59,049(1 - 8.85p) .UA omen/n rno rrRAVITY IN -SITU APPROVE® BY (PSF) a 1998 BAR ALLOW LL 6 140 Ni INC. #7 200 15 March 10, 1998 4. FLOOR (cont'd) b. rib design (cont'd), CONCENTRATED LOADS 2000 P' Over 6.25' Area per ASCE 7-99 2.5' x 2.5' If concentrated load has 2-1/2' x 2-1/2' dimension then load will sit on a rib .•. Shear is OK Flexure M->34(1.4)(11)2x12=8639"" 8 Per PCI Handbook Pg 4-57 a Concentrated Load Has a Effective Width Of 0.5L. If L=11'-0", Effective Width =5'-6". Therefore 2 Joists Are Effective. 2000(1.7)11 x 12 = 56,100" 4 x 2 joist M„ = 64,7390" < ON=105'`" ok APPROVED By 16 March 10, 1998 5. LATERAL a. LOADS - Worst Case - Long, High & Narrow WIND Base Shear = 51(36.3)(11.1) = 20.5k BTM OF SHELTER T/FND WALL LINE GRADE LINE APPROVF-0 By j INC 17 March 10, 1998 j 5. LATERAL (cont'd) a. Loads (cont'd) l SEISMIC , BOCA Structure Wt: Roof: (4.75/12)(12 * 36.3)(118) = 2034611 Side Wall: (4/12)(11.1 * 35.3)(118)2 = 308244 End Wall: (4/12)(11.1 * 12)(118)2 = 10478 Floor: (2/12)118(12)2 = 472 (4x6/144)10.67x 118 = 210 2(5/12)(1.67) x 118 = 164 2(9x6)/144 x 2 x 118 = 177 10230 / 2xl2 = 42.Vf 42.6[12x(36.3-1.67)] = 17703 , 1.67 x 12 x 118 = 2365 81,716# Wall Cover 2.5 psf x 11.1(12 + 36.3)2 2,681# i Floor 1.0 psf 12(36.3) = 436 Roof 1.0 psf 12(36.3) = 436 85,269# Snow 50.0 psf 12(36.3) = 21.780 107,049# PPRC)VE® BY Floor live load: 0.25 (200)(10.67)(35.0) = 18673# .k .��99� Base Shear: see design criteria$ V = 0.30 W V = 0.30 W V = 0.30 (107,049 + 18673) = 37.7' W = 0.3(20346 + 30824 + 10478 + 2681 + 436 + 21780) = 19366# 2 2 2 W = W = 19366 = 530' 36.3 36.3 18 March 10, 1998 5. LATERAL (cont'd) b. ROOF DIAPHRAGM' W Mu = 0.534(36.3)� x 1.43 = 126" 8 36.3' Vu = 0.534(36.3), x 1.43 = 13.9' 2 i Flexure p = 126 x 12 = 1 = .00077 0.9(60)4.0(96)2 (1-8.85p) 1316(1-8.85p) AS = 0.00077(4/3) 4 (96) = 0.39 in2 (1) #6 Around Perimeter Shear cpV, = 0.85 SQRT(4,000)(96)4 x .85 = 17.5k > V„ =13.9k No Shear Reinf Read APPRO`/F-D By pm ZINC 19 March 10, 1998 5. LATERAL (cont'd) c. END WALL DESIGN Vu = 13.9 KIPS U FLEXURE MU = 13.9X 11.1 = 154 K' P = 154 X 12 .9(60)4(140)2 (1-8.85 P) 1 2290(1 -8.85 P) P = .00044 X 4/3 = .00058 AS = .00058(140)4 = 0.322IN 1 #5 @ PERIMETER SHEAR 0 VC = 0.85 4000 (4)96 X .85 = 25.6 KIPS > Vu OK For distribution to floor slab, assume side wall takes the moment. Assume the shear load is resisted by floor plates. Wall plates: V„ = (154)1(11' x 5 PL) = 2.8' Floor plates: V, = 13.9/5 PL = 2.8k 20 APPROVED By P. March 10, 1998 5. LATERAL (cont'd) c. End Wall (cont'd) Check wall for combined wind. (2 way plate for out -of -plane loads) 51 x 0.7+0.25 1.3 37.3 PSF beff = 4t + 5" (plate width) a/b = 1.5 WORST B = .485 r = .485(37.3)(8)2/(.33)2 = 10.63 KSF MU = 10.63(1.3)(.332/6) = 0.251 K'/'x12 = 3.0 K"/' PU = 14 K P = 24 = .01 m = .60 = 17.64 12 2) .85 4) e' = 0.16" c..UAIJ — I4.0 TPN = cp0.55 f c Ag [1 - (kl )2] 32h CPPN = 132 x (1 - 0.57) TPN = 55.6"> P„ = 14.0' OK Ref. "Design of Concrete Structure" by Winter & Nelson PU = 18.5k M„ = 3.0k"' e= 0.16" qPn = 121 k' OK Armin = 0.002-% = .002(4 x 12) = 0.0961" 2A okav Use4x4-W4xW4WWF Check side wall for it's contribution Embeds = 3.7k Compression Side: Ry = 14.Ok -- Assume it gets distributed for width = to height. w = 11.1' APPROVED BY minimum of 3 embed platesa .•. REMBED = 14.0/5 = ± 2.8k 21 March 10, 1998 41 5. LATERAL (cont'd) c. End Wall (cont'd) CHECK SIDE WALL CONTRIBUTION Po = 495' x 0.9 = 466"1 Pup = 27 (12) / 2 =162' x 1.3 = 2104" Comp. Side P = 446 x 4 + 2800 - 210 x 4 = 37440 Tension Side P„ = (446 - 210)4 - 2800 = -1856* Wu = (51)1.3 = 66 P' MU = 6.6(121 / 12)2 / 8 = 839` x 12 = 10.1 k" P = 10.1 = 1 = .00405 0.9(60)(2)2(12)(1-8.85p) 256(1-8.85p) As = .00405(2)12 = 0.097in2 A.Pmv = 0.12(WWF) okay AS = 1.86 = .01 .9(60)(4) ASTOT = 0.107in2 < ASPmv okaX Check for P-D Effects cQ PC => Ec = 2675s' Ig = 64in4l Bd = 0 1 = 68480'"1 Pc = Tr2 6( 8480) = 46.2' Sb = 1 = 1.09 1212 (1 - 2_ 8 .7(46.2) Ma = 58.7 (121/12)2/8 fr = 7.5 SQRT(4000) = 474 P" Ma = 746#'r Mcr=47443=15.17'`•r 2 12 Ma < Mcr = 1264' .•. cracking doesn't occur Defl.=.(0.746)10.082(180) = 0.08" 2675 (64) AFFRO`Vet) BY 0 6. AL;, 22 March 10, 1998 �5. LATERAL (cont'd) c. End Wall (cont'd) Check Side Wall Contribution (cont'dl P-Delta Effect: i - ` Mu = 20.4 + 0.08 (2.8)1.09 = 20.6'" P„ = 2.8' e' = 7.36" qP" = 0.87(.85)4(21)2[-.01(17.64)+1-7.36/2+SQRT{(1-7.36/2)2 +2(7.36)(.01)17.64}] 2 ` = 6.93" > P„ = 2.8" OK Side Wall is Okay as Designed For Component Wind Pressure 4. SIDE WALL Okay for lateral force by comparison to end wall and a small area to pick up wind load. i APPFtOVEO BY �Q ��. , It, � q L• � 1` 23 March 10, 1998 6. FOUNDATIONS a. DETERMINE LOAD COMBINATIONS FOR CONCRETE DESIGN Per ACI 318 U=1AD+1.7L U = 0.75 (1.4D+1.7L+1.7W) } with wind U = 0.9 D + 1.3 W U = 0.75 (1.4D+1.7L+1.87E) } with seismic U = 0.9D +.1.43E b. DETERMINE LOAD COMBINATIONS i FOR BUILDINGS & OTHER STRUCTURES DEAD PLUS FLOOR LIVE PLUS ROOF LIVE (OR SNOW) DEAD PLUS FLOOR LIVE PLUS WIND (OR SEISMIC) 1.4 DEAD PLUS FLOOR LIVE PLUS WIND PLUS 1/2 SNOW DEAD PLUS FLOOR LIVE PLUS SNOW PLUS 1/2 WIND DEAD PLUS FLOOR LIVE PLUS SNOW PLUS SEISMIC 1.4 " Snow loads 30pf or less are not req'd. to be combined with seismic. TMaX = .625 Ab = 8x8 = 64 p = -1 AFFROVI ®�� Pmin = 1.0:v SEISMIC = pEh + E„ Where p = 1.0, E„ = 0 ' a. ~' ��'�• Per BOCA DEAD PLUS FLOOR LIVE PLUS ROOF LIVE (OR SNOW) DEAD PLUS WIND (OR SEISMIC) DEAD PLUS FLOOR LIVE PLUS ROOF LIVE (OR SNOW) PLUS WIND (OR SEISMIC) Seismic = + 1.0 Qe ± 0.5 AD PER SBC DEAD PLUS FLOOR LIVE PLUS ROOF LIVE (OR SNOW) DEAD PLUS FLOOR LIVE PLUS WIND (OR SEISMIC) DEAD PLUS FLOOR LIVE PLUS WIND + 1/2 SNOW DEAD PLUS FLOOR LIVE PLUS 1/2 WIND + SNOW DEAD PLUS FLOOR LIVE PLUS SNOW + SEISMIC UBC Seismic of 0.3W divided by 1.4 is approximately equal to SBC & BOCA Seismic of 0.22W Therefore use UBC load combination for seismic loads. 24 March 10, 1998 6. FOUNDATIONS (cont'd) c. DETERMINE SNOW LOADS FOR FLAT ROOF PER UBC (A) Pf = Ce I P9 (Contiguous U.S.) Ce=0.9 Dense Forest -- I =1.10 All others j' assume smallest P. = 5Psf PfMIN = 1.2(1.10)5 P' = 6.0P51 < 20PI min. roof live load PfMIN = 20Psf PfDESIGN = 50Psf APPROVED By j JUL 0 9 1990 Y [IN� 25 March 10; 1998 6. FOUNDATIONS (cont'd) d. load distribution DETERMINE DISTRIBUTION OF LOADS TO FOUNDATION DEAD LOAD (SELF WT) (1) Roof (4.75"/12")W(118#/CF) = 23.35W 2 (2) Roof (4.75"/l2")W(118#/CF) = 7.78W 6 (3) Walls (4/12)H (118#/CF) = 39.31-1 (4) (from floor design) 42.6PSF (—W) = 21.3W 2 .•. FOR ANY SHELTER WIDTH WL FTG.(A) WoL = 23.35W + 21.3W + 39.31-1 = 44.65°`fl2 W + 39.31-1 <— Unfactored FTG.(B) WoL = 7.78W + 39.3H <—Unfactored LIVE LOAD (SNOW) FTG.(A) WSL = W PSL <— Unfactored 2 FTG•(B) WSL = VV PSL <— Unfactored 6 LIVE LOAD (INTERIOR FLR) FTG.(A) WLL = W PLL <— Unfactored 2 FTG.(B) WLL = 0 DETERMINE DEAD LOAD FOR EACH WIDTH 81-4" W = 44.65(8.33') + 39.31-1 = 371.Vx + 39.3H 10'-4" W = 461.2" + 39.31-1 12'-0" W = 536' + 39.31-1 4PPROVED BV jut 0 S. �g9 26 March 10, 1998 6. FOUNDATIONS (cont'M d. load distribution (cont'd) DETERMINE LIVE LOAD FOR EACH WIDTH UNIFORM LIVE LOAD 50 psf I_ 81-411 WLL = 8.33'(50") 2 = 208.25�'ft 10'-4". WLL = 258.25*'ft 12'-0" WLL = 300.0am e Multiply WLL by 2.8 for 140PSF LIVE LOAD WLL by 4.0 for 20OPSF LIVE LOAD DETERMINE DEAD LOAD FOR EACH HEIGHT 9'-5" W = 44.65W + 39.3 (9.42') = 44.65W + 370.2#1" 10'-5" W = 44.65W + 409.5" 11'-1" W = 44.65W + 435.6" APPROVED e v 27 March 10, 1998 6. FOUNDATIONS (cont'dj e. DETERMINE SHELTER DEAD LOAD DISTRIBUTED TO FTG "A" FOR EACH WIDTH & HT. Width 8'-4" HT 9-15" WpL = 371.9#"ft + 370.2" = 742.11 10'-5" Wog = 371.9#"t + 409.5" = 780.54m 11'-1" Wog = 371.99m + 4350m = 807.501ft Width 10'-4" HT 9'-5" WpL = 461.2*R + 370.2" ft = 831.4" 10'-5" WOL = 461.2#m + 409.5*m = 870.7" 11'-1" WpL = 461.2#"t + 435.E*m = 896.8111 Width 12'-0" HT 9'-5" Wog = 536#`ft + 370.2" = 906.2#"t 10'-5" WpL = 536" + 409.5" = 945.5" 11'-1" WDL = 536" + 4350m = 971.6m TABLE 1 APPROVED By F �IlkFill �998 ,4 INC. 28 March 10, 1998 a 6. FOUNDATIONS (cont'dj f. CREATE A MATRIX FOR FLOOR LL FOR ALL WIDTHS AND HEIGHTS 140Psf 200 Psf WIDTH/HEIGHT LIVE LOAD LIVE LOAD W 12'-0" 840 pif 1200 pif W 10'-4" 723.1 pif 1033 pif W 81-4" 583.1 pif 833 plf TABLE 2 g. DETERMINE SNOW LOAD ON FTG "A" FOR EACH WIDTH WSJ = 50W 2 Pf Wsl(W=8.331 WSL(W=10.33') WSL(W=12'-0" ) 50 208.3pif 258.3plf 300.Opif TABLE3 APPROVEO By 4, 29 March 10, 1998 6. FOUNDATIONS (cont'd) h. wind distribution DISTRIBUTION OF LOADS TO FOOTING WIND LOAD - COUPLE METHOD (FOR 11'-1"HT) = (11.1' / 2) = 5.55 PWIND _ (11.1'/2 + 0.5'/2) 5.80 PWiND 5.55 PWiND (L OR W) 5.80 PWiND (L OR W) FTG(A) Wwl_ = [5.55PWND L(13.6') + 5.80 PWId L(2.5')]/(WxL) = PWiND(89.98)M FTG(B) W,M = [5.55 PWiND W(13.6') + 5.80 PWIND W(2.5')]/(WxL) PWIND(89.98)/L 30 March 10, 1998 6. FOUNDTIONS (cont'd) h. wind distribution fcont'd) SECTION MODULUS METHOD q = M S SW = (L+1) (W+1)3-(L-1)f W-1)3 6(W+1) 'I SL _ (L+1)3(W+1)-(L-1)3(W-1) 6(L+1) WIND LOAD ON LONG SIDE PWIND 0 N q = M = PWIND(L)78.88 FT2 SW f(L+1)(W+1)3-(L-1)(W-1) 1 6(W+1) WIND LOAD ON SHORT SIDE q = M = PwIND(W)78.88 FT2 SL [(L+1)3(W+1)-(L-1)3(W-1)1 6(L+1) W+i, H [ASSUME BOX ACTS AS SHORT COLUMN] M = (PWIND(L)11.6)(13.672) = PWIND(L)78.88 FT2 M = (PWIND(W)11.6)(13.6) 2 PWIND in 0 PWIND(W)78.88 ft2 APPROVED 8Y Z, 4 Is o 31 March 10, 1998 6. FOUNDATIONS (cont'd) h. wind distribution (cont'd) COMPARING METHODS FOR FTG (A) Assume 10' width x 30' length Assume 100 PSF wind pressure Assume 11.1' height COUPLE METHOD: W,,,L = 100PSF(89.98) = 899.80 10.0' SECTION MODULUS METHOD: WDL = 100PSF(30.0')78.88 FTZ f (31.0')(11.0')3-(29.0,)(9.0')31 6(11.0') 776.3 psf (FOR 1'-0" FTG WIDTH) THEREFORE, USE COUPLE METHOD TO FACILITATE CALCULATIONS SINCE ONLY TWO UNKNOWNS VS THREE AND MORE CONSERVATIVE USING COUPLE METHOD DETERMINE LOADS TO FTG FOR 9'-5" HIGH SHELTER & 10'-5" HIGH SHELTER H = 9.43' ABOVE FTG i (A) WvvL = EWINd(9.42'/2)L(11.92')+(9.42'/2+0.5'/2)L(2.51)1 (W) (L) = PWIN 68.54 W (B) WWL = EWIN QU-4- L H = 10.43' ABOVE FTG (A) WWL = P,vINDF(10.42/2)L(12.92')+(10.42/2+0.5'/2)L(2.5'),1 (L) (W) EWIN 8D ` 0.96) APPROVED By W 000 �u L (B) WWL = EWIN 80.96 �, , ` . •. L H = 11.08' ABOVE FTG (A) WWL = PWIND(89.98)/W (calculated previously) (B) WWL = PWIND(89.98)/L (calculated previously) -- 32 March 10, 1998 6. FOUNDATIONS (cont'dd) h. wind distribution (conM WIND PRESSURES FOR 120mph WIND SPEED WALLS: P = 51 psf or P = 35 psf ROOF: U = 27psf or P = 41 psf 51 psf lateral & 27psf uplift condition controls. DETERMINE LOAD ON FOOTING "A" FROM WIND LOAD FOR ALL WIDTHS & HEIGHTS For H = 9.42' WvvL = ± 51 psf(68.541 - 27psf W W 2 For H = 10.42' WvvL = ± 51 psf(80.961 - 27psf W W 2 For H = 11.1' WvvL = + 51 osf(89.981- 27psf W W 2 SHELTER WIDTH WWL(H=9.42') WWL(H=10.42') 8'-4" +307/-532plf +383/-608pif 101-4" +199/-478plf +260/-539p[f 12'-0" +129/-458plf +182/-506plf TABLE 4 WWL(H=11.1') +438/-663plf +305/-583plf +220/-544p[f APPROVED BY j s 33 March 10, 1998 -'I 6. FOUNDATIONS (cont'd) 1. seismic PER UBC I DETERMINE LOAD DISTRIBUTION TO FTG "A" V = 2.5C_I W � R = 1.0 R = 4.5 V = 2.5C 1( 0) W = 0.556C.W 4.5 [8'-4" WIDE X 1 V-1" HIGH X 8'-4" LONG] WpL = Roof + Walls = [49.7psf(8.33')2 + 39.3psf(4))8.33') 11.1' 2 = 10,7W .ZONE 4: Ca = 0.54 (see load calcuations) V = 0.556(0.54)(10716' = 3217# WseisMic = 3217* (13.6) 1 = 631plf 8.33 8.33 [10'-4" WIDE X 1 T-1" HIGH X 10'-4" LONG] Wog = 49.7psf(10.331)2 + 39.3psf(4)(11.1'/2)(10.33') = 14,316" ZONE 4: V = 0.556(0.54)(1431 e) = 429V is WseisMic = 4298# (13.6) 1 = 548 10.33 10.33 APPROVED BY ITJUL 41NCO 34 March 10, 1998 6. FOUNDATIONS (cont'd) i. seismic (cont'd) Per UBC [12'-0" WIDE X 11'-1" HIGH X 12'-4" LONG] Wog = 49.7psf(12.0')(12.33) ,I + 39.3psf(2)(1 1. 1'12)[12.0'+ 12.33] = 17,96r ZONE 4: V = 0.556(0.59)(17967) = 5394# WSEISMic = 5394 x 13.6 x 1112.33 = 496*ft 12 - DETERMINE FACTORS TO MULTIPLY WITH FOR OTHER HEIGHTS - FOR UBC 8'-4" WIDTH FOR 9'-5" HEIGHT W = 9616* 9616 = 0.897 10716 (9.42'+2.5) 1 = 0.172 8.33 8.33 i 0.172 = 0.878 0.196 FACTOR = 0.897(0.878) = 0.788 FOR 10'-5" HEIGHT FACTOR = 0.91 APPFIOVEO By. +3 INCw 35 March 10, 1998 6. FOUNDATIONS (cont'd) i. seismic (cont'd) Per UBC (cont'd) 10'-4" WIDTH FOR 9'-5" HEIGHT FACTOR = 0.793 10'-5" HEIGHT FACTOR = 0.913 12'-0" WIDTH FOR 9'-5" HEIGHT FACTOR = 0.798 10'-5" HEIGHT FACTOR = 0.916 UBC 8'-4" WIDTH 10'-4" WIDTH 12'-0" WIDTH ZONE 9'-5" 10'-5" 11'-1" 9'-5" 10'-5" 11'-1" 9'-5" 10'-5" 11'-1" 4 497 574 631 435 500 548 396 454 496 TABLE 5a * Footing load (±) for DL of shelter for additional load due to floor live load and snow see following pages 36 March 10, 1998 6. FOUNDATIONS (cont'd) 1 i. seismic PER BOCA DETERMINE LOAD DISTRIBUTION TO FTG "A" V = 2.5A_ W R R = 4.5 V = 2.5A� W = 0.556Aa W 4.5 [8'-4" WIDE X 11'-1" HIGH X 8'-4" LONG] Wog = Roof + Walls = [49.7psf(8.33')2 + 39.3psf(4)(8.33') 11.1' 2 = 10,71e ZONE 4: A. = 0.4 V = 0.556(0.4)(107W) = 2383# WseisMic = 2383# (13.6) 1 = 467plf 8.33 8.33 [10'-4" WIDE X 11'-1" HIGH X 10'-4" LONG] Wog = 49.7psf(10.33')2 + 39.3psf(4)(1 1. 1'/2)(10.33') = 14,316* ZONE 4: V = 0.556(0.4)(14316*) = 3184" APPROVED BY WseisMic = 318e (13.6) 1 = 405" 10.33 10.33JUL [12'-0" WIDE X 1 T-1" HIGH X 12'-4" LONG] INC. Wog = 49.7psf(12.0')(12.33') + 39.3psf(2)(1 1.1'/2)[12.0'+ 12.33'] 17, 967" ZONE 4: V = -0.556(0.4)(17967) = 3996# WSEISMic = 3996 x 13.6 x 1 /12.33 = 367#/ft 12 See UBC Seismic calculations for factors for shelters of other heights. 37 March 10, 1998 6. FOUNDATIONS (cont'd i. seismic (ont'd) Per BOCA (cont'd) i BOCA 8'-4" WIDTH 10'-4" WIDTH 12'-0" WIDTH ZONE 9'-5" 10'-5" 11'-1 9'-5" 10'-5" 11'-1" 9'-5" 10'-5" 11'-1" 4 368 425 467 320 369 405 292 334 367 TABLE 5b * Footing load W for DL of shelter for additional load due to floor live load and snow see following pages Per UBC TO DETERMINE FOOTING LOADS (±) DUE TO ADDITION OF FLOOR LIVE LOAD 1. DETERMINING SHEAR AT FLOOR LEVEL DUE TO SEISMIC LATERAL MOVEMENT PER 50Ps' OF FLOOR LIVE LOAD 2. DETERMINE HEIGHTMIDTH FACTORS V = FLOOR LIVE (WIDTH) 2.5C, R UBC DETERMINE FOOTING LOADS FOR FLOOR LIVE LOAD IN SEISMIC EVENT - 50PSF INCREMENTS. (25% OF LOAD SHALL BE CONSIDERED.) 8'-4" WIDTH (ZONE 4) V = 1(50PSf)(8.33)(0.556)(0.54) 4 10'-4" WIDTH (ZONE 4) V = 1.24 (31.26) = 38.76#KvsoP' 12'-0" WIDTH (ZONE 4) V = 1.44 (31.26) = 45.02"P' = 31.26"Pl APPROVED IN Q 38 March 10, 1998 6. FOUNDATIONS (cont'd ti i. seismic (cont'd) HEIGHT/WIDTH FACTORS Per UBC 8'-4" 2.5 / 8.33 = 0.30 10'-4" 2.5 / 10.33 = 0.24 12'-0" 2.5 / 12.0 = 0.21 WSEISMic SL = [V x HEIGHT / WIDTH FACTOR](LL / 50psD 8'-4" WIDTH 140 psf ZONE 9'-5" 10'-5" 11'-1" 4 26 26 26 10'-4" WIDTH 140 psf ZONE 9'-5" 10'-5" 11'-1" 4 26 26 26 12'-0" WIDTH 140 psf ZONE 9'-5" 10'-5" 11'-1" 4 26 26 26 TABLE6a 200 psf ZONE 9'-5" 10'-5" 4 38 38 38 200 psf ZONE 9'-5" 10'-5" 4 38 38 38 200 psf ZONE 9'-5" 10'-5" 4 38 38 38 W V FLOOR LIVE RIF AppFtOVED By JUL 0 as 39 March 10, 1998 6. FOUNDATIONS (cont'dl �I i. seismic (cont'd) Per BOCA TO DETERMINE FOOTING LOADS (±) DUE TO ADDITION OF FLOOR LIVE LOAD. 1. DETERMINING SHEAR AT FLOOR LEVEL DUE TO SEISMIC LATERAL MOVEMENT PER 50Ps' OF FLOOR LIVE LOAD 2. DETERMINE HEIGHT/WIDTH FACTORS V = FLOOR LIVE (WIDTH) 2.5A_ R BOCA DETERMINE FOOTING LOADS FOR FLOOR LIVE LOAD IN SEISMIC EVENT - 50P' INCREMENTS. (25% OF LOAD SHALL BE CONSIDERED.) 8'-4" WIDTH (ZONE 4) V = 1(50Psf)(8.33')(0.556)(0.40) = 23.16 M50psr 4 10'-4" WIDTH (ZONE 4) V = 1.24 (23.16) = 28.72#rcusoPsr 12'-0" WIDTH (ZONE 4) V = 1.44 (23.16) = 33.35#ffueoPsr W V FLOOR LIVE APPROVED. E�Y J u9 N4Q 40 March 10, 1998 1r 6. FOUNDATIONS (cont'dj i. seismic (cont'd) HEIGHT/WIDTH FACTORS Per BOCA WseisMICSL = [V x HEIGHT / WIDTH FACTOR](LL / 50psf 8'-4" WIDTH 140 psf 200 psf ZONE 9'-5" 10'-5" 11'-1" ZONE 9'-5" 10'-5" 11'-1" 4 19 19 19 4 27 27 27 10'-4" WIDTH 140 psf 200 psf ZONE 9'-5" 10'-5" 11'-1" ZONE 9'-5" 10'-5" 11'-1" 4 19 19 19 4 27 27 27 12'-0" WIDTH 140 psf 200 psf ZONE 9'-5" 10'-5" 11'-1" ZONE 9'-5" 10'-5" lit-ill4 19 19 19-- 4- 27 - 27 27 TABLE6b APPROVED a* Iv ENS. 2 41 March 10, 1998 6. FOUNDATIONS (cont'd) i. seismic (cont'd) Per UBC TO DETERMINE FOOTING LOADS (±) DUE TO ADDITION OF SNOW ON ROOF 1. DETERMINING SHEAR AT ROOF LEVEL DUE TO SEISMIC LATERAL MOVEMENT PER 10Ps'OF SNOW ON ROOF 2. DETERMINE HEIGHT/WIDTH FACTORS V = SNOW (WIDTH) 2.5C R UBC DETERMINE FOOTING LOADS FOR SNOW LOAD IN SEISMIC EVENT - 10PSF INCREMENTS. 8'-4" WIDTH (ZONE 4) V = 10P'(8.33')(0.556)(0.54) = 25.01#rc 'Psr 10'-4" WIDTH (ZONE 4) V = 1.24 (25.01) = 31.01#rr 'Pst 12'-0" WIDTH (ZONE 4) V = 1.44 (25.01) = 36.03#rr 'P" W SNOW 42 March 10, 1998 6. FOUNDATIONS (cont'd i. seismic ,cont'd) HEIGHT/WIDTH FACTORS Per UBC 8'-4" x 9'-5" (9.42 + 2.5) / 8.33 = 1.43 10'-5" (10.42 + 2.5) / 8.33 = 1.55 1 l'-l" (11.1 + 2.5) / 8.33 = 1.63 10'-4" x 9'-5" (11.92) / 10.33 = 1.15 10'-5" (12.92) / 10.33 = 1.25 1l'-l" (13.6) / 10.33 = 1.32 12'-0" x 9'-5" (11.92) / 12.0 = 0.99 10'-5" (12.92) / 12.0 = 1.08 1l'-l" (13.6) / 12.0 = 1.13 WseisMic SL = [V x HEIGHT / WIDTH FACTOR](50 psf/ 10psf) WIDTH ZONE 9'-5" 10'-5" 11'-1" 81-4" 4 178.88 193.83 203.83 WIDTH ZONE 9'-5" 10'-5" 11'-1" 10'-4" 4 178.31 193.81 204.67 WIDTH ZONE 9'-5" 10'-5" 11'-1" 12'-0" 4 178.35 194.56 203.57 TABLE7a APPROVED By 'I INC 43 March 10, 1998 6. FOUNDATIONS (cont'd) i. seismic (cont'd) -' Per BOCA TO DETERMINE FOOTING LOADS (±) DUE TO ADDITION OF SNOW ON ROOF 1. DETERMINING SHEAR AT FLOOR LEVEL DUE TO SEISMIC LATERAL I MOVEMENT PER 10Ps' OF SNOW ON ROOF 2. DETERMINE HEIGHTIWIDTH FACTORS V = SNOW (WIDTH) 2.5A_ R BOCA DETERMINE FOOTING LOADS FOR SNOW LOAD IN SEISMIC EVENT - 1OP5' INCREMENTS. 8'-4" WIDTH (ZONE 4) V = 10P5'(8.33')(0.556 0.40 = 18.53"HV10PI 10'-4" WIDTH (ZONE 4) V = 1.24 (18.53) = 22.97""'P" 12'-0" WIDTH (ZONE 4) V = 1.44 (18.53) = 26.68#/t1 P" W SNOW ti APPROVED BY jul- 0 9 1998 INC. 44 March 10, 1998 6. FOUNDATIONS (cont'dj i. seismic (cont'd) HEIGHT/WIDTH FACTORS Per BOCA 8'-4" x 9'-5" (9.42 + 2.5) / 8.33 = 1.43 10'-5" (10.42 + 2.5) / 8:33 = 1.55 1 V-1" (11.1 + 2.5) / 8.33 = 1.63 10'-4" x 9'-5" (11.92) / 10.33 = 1.15 10'-5" (12.92) / 10.33 = 1.25 1 V-1" (13.6) / 10.33 = 1.32 12'-0" x 9'-5" (11.92) / 12.0 = 0.99 10'-5" (12.92) / 12.0 = 1.08 11'-1" (13.6) / 12.0 = 1.13 ti. WSEISMic SL = [V x HEIGHT / WIDTH FACTOR](50psf / 10psf) WIDTH ZONE 9'-5" 10'-5" 11'-1" 81-4" 4 132.49 143.61 151.02 WIDTH ZONE 9'-5" 10'-5" 11'-1" 10'-4" 4 132.08 143.56 151:60 WIDTH .ZONE 9'-5" 10'-5" 11'-1" 12'-0" 4 132.07 144.07 150.74 TABLE7b 45 March 10, 1998 6. FOUNDATIONS (cont'd) k. summary of load tables The following computer output is the tabulation of the loading combinations and the associated load to soil. Based on these values, the required width of 4 foundation wall is able to be established. By adding up the required widths, the proper overall foundation width is available. APPROVED By jul, 1998 k, INC 46 March 10, 1998 6. FOUNDATIONS (cont'd) I. slab on grade foundation 1. Criteria: use slab on grade w/ 8" of washed gravel for foundation. 2. Where frost is a concern extend the washed gravel down to frost depth. 3. Since shelter doesn't have overturning problems, the foundation is the same as the perimeter beams for the bearing pressures. Provide a turned down edge to provide proper edge distance for expansion anchors. The turned down edge width will be the same as the perimeter beam which depends on the floor loads. 4. Longitudinal Steel: pmin = 0.0018 AS = 0.0018(10x14) = 0.252 in USE 2#4 bars Temp steel in slab: AS . = 0.0018(6x18) = 0.194 in2/18" USE #4 @ 18" APPROVED 1998 47 March 10, 1998 I 7. CONNECTIONS a. Roof to Side and End Walls 1. Wind Uplift Pu = 27 psf roof wt. _ (4.75/12)118 = 46.7 psf »» Max. load per conn. _ (27 - 46.7)6(4) no load due to uplift okay by inspection -- other conditions will control 2. Wind lateral (120 MPH) Note that lateral loads acting in the short direction will control due to the fewer number of plates at the roof to endwall connection. P = 51 psf (See Wind Calculations) V = 51 x 11.1 x 36 = 5095* 2 2 There are six plates in endwalls, therefore Vpl = 509511 = 84991P' 6 Seismic Lateral DL: Roof (4.75)118(12) = 561 pif 12 Wall L4)118(9.67 / 2)2 = 380ur 12 WE) = 941#r LL: Snow 50 psf x 12 Ws = 60r Wn = 1541 #r V = 0.556(0.54)WQ6) = 8330' 2 Vpl = 8330 = 1390' 6 Therefore seismic controls ppROVED BY JUL qu, � 48 March 10, 1998 7. CONNECTIONS (cont'dj- a. Roof to Side and End Walls (cont'd) Re: PCI Design Handbook Weld "A" V = 139W IW = 2" (min per PCI) Tw = 0_5 in = 0.1 (effective throughout) 5 LW = 0.9411 = 0.66" min. 0.3(70ksi)(0.1 ") Plate "B" use 3" min. weld i 0 Shear: 1.1(1.3)(1390) = 1988# Reaction: 1988 (2.5 in) = 1656# 3 in APPROVED By i" (3, 0 49 March 10, 1998 a 7. CONNECTIONS (cont'd) a. "Roof to Side and End Walls (cont'd) Anchor: Vah = min 10330# (0.85) (Nelson Stud Design) . Manual 0.85(800)(0.2in2)(0.85) 4000 psi (PCI) 878091 = min ( 73110 / Controls Vah = min (8720 - 5800)# (0.85) (Nelson Stud Design) Manual 0.85(2)(- r)(2.5 in2)(0.85) 4000 psi (PCI) 2482* l = min ( 1794* / f Controls 2 2 IC = ( (0.85(1998)/2(7311)) + ( ( 0.85(1656)/1794))1/0.85 = 0.74 < 1.0 o.k. Plate: V = 1390' Fv = 139W = 890 psi (NEGLIGIBLE) 5 in (5/16 in) Plate 5/16 x5x5 w/ (2) 1/2" DIA x 2" HAS APPROVF-0 By ' JUi 50 March 10, 1998 7. CONNECTIONS (cont'd) a. Roof to Side and End Walls (cont'M 2. lateral (cont'd) plate "C" shear: VU = 1.988, Plate and studs will be adequate by comparison to Plate B. use Plate 5/16 x3x5 w/ (2) 1/2" DIA x 2" HAS WELD /'A 1 3 I lr� APPROVIED S' JUL INC. 51 March 10, 1998 4. 7. CONNECTIONS (cont'd) b., SIDE WALL TO END WALL 1. WIND SUCTION ON END WALL Since wall is approx. square, it will act as a 2-way PL. p = 51psf 1' 8" 5 plates along Ht. of wall R = 51(10.08)(11.67)/4 = 1500#- RmAx = 1500 = 3V 5 M noff I LD- -A-APPROVED BY J ot ! WELD "A" R = . 30V lw--3"(min) fw=300/3 = 100' Fw = 2.11/in OK 3" Iona weld 52 March 10, 1998 7. CONNECTIONS (cont'd) b. Side Wall to End Wall (cont'd) PL "B" TRY (2)1/2" Dia x 2 HAS. edge dist. = 4" Pullout Pc = 0.85(4)(0.85),14000 (3+2x2)(0+2x2) = 5.1 k IC = 1/.85 [(0.3x1.3)/5.1] = 0.09 < 1.0 OK PL "C" Shear Vu = 0.3 x 1.3 = 0.39k cpVc = 0.85(800)(0.2) .85 SQRT(4000) = 7.3k cpV'c = 0.85(12.5)(2.5)" 0.8514000 = 2.26k 3 Cw = l 1 + 3.5(2.5) 1 = 1.34 Ct = 4 1.0 1.3(2.5) Cc 1.0 cpVc = 2.26(1.34) = 3.0' > V,, = 0.36k cpVc > V. = 0.36" OK PL. Thick = 2/3 x 1/2 DIA = 1/3 _ 5/16" PL. PL "B" & "C" PL 5/16x5x5 W/(2) 1/2"Diax2 HAS e APPROVE® OV 00. t & . 53 March 10, 1998 7. CONNECTIONS (cont'd) 2. UPLIFT OF BLDG. & SUCTION ON END WALL Wall suction: P = 0.7(36.9)(1.06)1.0 = 27.4P" See Part 1. - Modify Reaction R = 300(27.4/51) = 161 # x 1.3 = 0.21 k Uplift: when uplift tries to occur it will lift the back wall and 1/2 the roof and 1/2 the floor. Therefore, design wall connections to transfer load to end wall. Side Wall = 4/12(11.1 x36.3)118 = 15849 * Roof = 4.75/12(12x36.3)118/2 = 10173 Floor = (17703+2365)/2 = 10034 Misc. = (2681+436x2)/2 = 1777" 37, 833# Ru = 1.84 K 0.21 K = VU 77. • O I 00. F„c„ �wELD "A" FE "B" 54 March 10, 1998 7. CONNECTIONS (cont'd) b. Side Wall to End Wall (cont'd) 2. Uplift of Bldg. & Suction on End Wall (cont'd) Seismic V _> Roof (4.75)118(8.33)36.33 = 14135 12 Wall (4)118(36.33+8.33)11.1(2) = 38997 12 Floor (52)(7.33)(35.33) = 13466 66599# Snow 50(8.33)(36.3) = 15119 W/o Snow: V=.0.3W M 4241 10.33 43810 11699 5.17 60484 4040 .33 1333 19979# 10562r 4536 10.33 46854r 152,481 #' MRES = 66,599(8.33 / 2) = 277,385v > 105,6270' okay W/ Snow: MRES = (66,599 + 15,119)(8.33 / 2) = 340,355? > 152,481#r okay no uplift in connections due to seismic Wind APPROVED By PH = 51 psf �s Pu = 27psfs MOT = 51(36.3)(11.1)2 + 27(8.33)2(36.3) = 148053F 2 2 MRES = 66,599(8.33) / 2 = 277,385v > 1.5 MOT no overturning Req'd holddown force (F) (subtract out end walls) 4 F = 148,053 - (12)118(8.33)(11.1)2(8.33)/2 = 14,137# 8.33 55 March 10, 1998 7. CONNECTIONS (cont'd) b. Side Wall to End Wall (cont'd) 5 Connections per side (2 sides) R/Conn. = 14,13r/(5 x 2) = 1.41 k 1.3 1.84k WELD "A" R = 1.41 k V = .16k R' = SQRT[(1.41)2+(.16)2] = 1.4k Iw = 1.4 x .75 = 0.5" SAY 3" LG. WELD 2.1 PL. B" 1.8e ' �0.21K Vu, = 0.21 + 1.84 x 2.5 = 1.64k 2 3 Vu2 = 1.84k (PVC'PER = 0.85(12.5)(2.5)1•5 0.85 ,r4000 = 2.26k BY PPF�C3\/E� A CW = 1'' z , Ce — 1 (PVC'PER — 2.26k � N� � _ • (PVC'PAR 2 (PVC'PER = 4.52k IC =1 ( 1.64 x .85/2.26) + (1.84 x .85/4.52 ) ) 1/0.85 = 0.59 , 1.0 OK 5 Plates each W/(2) 1/2" DIA bolts 56 March 10, 1998 7. CONNECTIONS (cont'd) b. Side Wall to End Wall (cont'd) PL "B" thickness = 2/3 x 1/2" = 1/3 _ 5/16" PL x 5 x 11 PL "C" 1 R„ = 1.84k anchor bolt edge dist. = 4" V„ = .21 k ' I cpVc = 0.85(0.85) 800(.2) SQRT(4000) = 7.31 k = Min edge dist. = 7 1/2" - Controls cpVs = 45000 (0.2) x .85 = 9.0k cpPc = 0.85(4).85 14000 (3+2x2)(0+2x2) = 5.2 IC = [(1.84/7.31)2 + (.21/5.2)2]1/0.85 = 0.08 < 1.0 OK IC = [(1.84/7.31x2)5'3 + (.21/(5.2)513] = 0.11 < 1.0 OK (2) 1/2" Dia Bolts PL=1/2x2/3 _ 5/16"PL3x5 57 APPROVED By J� 9 1998 March 10, 1998 7. CONNECTIONS (cont'd) c. Side Wall to Floor DL & LL Case L = P F'L n B„ 1. LOADS: DL: Roof = 4.75112(6)(118) = 2801 2.5(6) = 15 Wall = 4/12(11.1)118 = 436.6 2.5(11.1) = 28 760#f x 4' = 3040# x 1.4 = 4256 LL: Snow = (50.x 6) = 300#r x 4' = 12W x 1.7 = 2040# 424V 6296# MAX. CONN. SPACING = 4'-0 P = 4240# (6296#) 0,FF)RD''F-D BY INC i March 10, 1998 7. CONNECTIONS (cont'd) c. Side Wall to Floor WELD "A" Fw = 2.1 Grp' V = 4240* J Iw = 4.24/2.1 = 2.02" weld length = 3" min. i PL "B" Vu = 6.3" j, cpV� _. 0.85(0.85) 800(.2) SQRT(4000) = 7.31 k = 0.85(12.5)(7.5)1-5 .85d4000 = 11.7k - controls CW = 1 + 3 = 1.11 3.5(7.5) Ct = 4 = 0.41 1.3(7.5) Cc = 1.0 cpVc = 11.7(1.11)0.41 = 5.32' 1 cpVS = 45000(.2) = 9.0k Vu = 6.3" . . PL 1/2 x 2/3 - 5/16 PL5/16x5x5 _ w/(2) 1/2" Dia studs @ 5.3/6.3 x 48" = 31-4" j PL "C" Vu = 6.3" 1 i qVc = 0.85(0.85)800(0.2) SQRRT(4000) = 7.31 k -' = 0.85(12.5)(4)1-5 (.85) d4000 = 4.6' Controls CW = 1 + 3 = 1.2 3.5(4) t Ct = 8 0.1.0 1.3(4) Cc — 1.0 cpVc = 1.2(4.6) = 5.5'` L 5x1 1/2 x 5/16 x 0'-5 w/(2)1 /2" Dia x4" HAS & (1) 1/2" Dia x 2" @ 5.5 x 48" = 3'- 6" Use 3'-4" 6.3 APPROVED BY 11998 JUL 0 59 March 10, 1998 7. CONNECTIONS (cont'd) c. Side Wall to Floor (cont'd) 2. DL + SNOW + WIND CASE Note that wind uplift is conservatively neglected DL + SNOW = 4240" (6296* x .75 = 4722#) = P (Pu) WTOT = 51 psf WSW = 51 (0_5) = 19.6 psf 1.3 H = 19.6(11.1)/2 x 4' = 435* x 1.7 x 0.75 = 55511 WELD "A" V = SQRT[(435)2 + (4240)2] = 4262 FW = 2.1"' Iw = 4.26/2.1 = 203 x 0.75 = 1.52" 3" of weld length req'd. APPROVED By A.- 'li iyV '�% � � •ems 60 March 10, 1998 a 7. CONNECTIONS (cont'd) c. Side Wall to Floor (cont'd) PL "B" cpVc = 5.3k (see DL + LL section) cpPc = (4.33-1.22)(0.85) = 2.64k _ JJ 2 IC = 1(0.85x(0.56)2 /2(2.64)) + (0.85 x (4.72)/5.3) ) 1/0.85 = PL 5/16 x5 w/ (2) 1/2" Dia x 0'-2 Studs PL "C" Anchor l2) Vu = 4.72' 4.72 K = P qVc = 5.51 > Vu OK 1 0.56 K _ Anchor 1 u Hu = 0.56' components V„ = .707(0.56)=0.4k R„ = .707(0.56)=0.4k TVA = 0.85(0.85) 12.5(1.41)1-5 SQRT(4000)=956* �n N ro cpRc = 0.85(0.85)(4)(3.2x2)SQRT(4000)=1170# Try (1) 1/2" Dia x 0'-2 HAS. IC = ((0.85x(400)/956 ) Z+ (0.85 x (400)/1170) 21 1/0.85 = 0.25 =1.0 OK 0.68 < 1.0 OK (1)1/2"Dia x 0'-2 Bolts w/ L 5 x 1 1/2 x 5/16 x 0'-5" 61 March 10, 1998 7. CONNECTIONS (cont'd) c. Side Wall to Floor (cont'd) 3. DL + WIND CASE 1P H (THIS FORCE IS TAKEN THROUGH BEARING) FOUNDATIONS LOADS: Hold down for uplift forces. MOT = 51 (11.1)(11.1)1/2(36) + 27 (36)(8.33)(8.33)1/2 = 147'`' DLREs = ROOF (4.75/12)118(36)(8.33) = 14.0 WALL (11.1)(4/12)118(36 + 8.0)2 = 38.4 52.41 MRES = 52.4 (8.33 / 2) = 218' Hold Down Force @ PL (FHo) FHo = (147-218) 8.33 Therefore Floor Weight Is Not Required To Holddown The Building Ju '996 RN 62 March 10, 1998 7. CONNECTIONS (cont'd), d. End Wall to Floor See lateral - end wall design section for load RYs = RYo = 9.7" x 1.3 x 1.1 = 13.9" WELD "A" Vtot = 9.7" Consider 4 plates active when endwall has door opening. V/pl = 9.7/4 = 2.42" WELD FW = 2.1r Iw = (2.42 / 2.1) x 0.75 = 0.87" use 3" min weld 13.9K PLATE "B" Vu = 13.9/4 = 3.48' cpVc = 0.85(0.85)800(0.2)SQRT(4000) = 7.31 k cpVs = 10.33 (0.85) = 8.78k # Of Anchors = 3.5 / 7.31 = 0.5 - (2) 1/2" Dia x 0'-2 Anchors Min edge dist. = 7 1/2") PLATE "C" Vu = 3.48" R = 3.48' K73") = 4.64k cpVc = 7.31 k cpRc _ (8.72 - 2.87)(0.85) = 5.0k 0.85(2)(Tr)(4 in)Z(0.85) -14000 psi = 4.6k R // C // FOUNDATIONS z z1 IC = ((0.85 x (3.48)/2(7.31)) + ( 0.85 x (4.64)/4.6) / 1/0.85 = 0.92 � 1.0 OK (2) 1/2" DIA x 0'-4 Anchors (Min. Edge dist = 7 1/2") APPROVED BY JUL G U INC. 63 March 10, 1998 7. CONNECTIONS (cont'd) e. Floor to Foundation Look at 8'-4" wide x 36'-4" long shelter because it will overturn easier Shelter DL --> roof - 8.33(36.3)4.75(118) = 14,124 12 side wall - (4/12)118(36.3)(11.1)(2) = 31,697 end wall - (4/12)118(8.3)11.1(2) = - 7,248 floor - 42.6(8.3)36.3 = 12.835 WT = 65,904' MRES = 65.90(4.16)x2/3 = 182.8' Wind P = 51 psf MOT = 51 11.1 z (36.3) = 114.0 k' 2 27 (36.3)(8.33)Z/2 = 34.0 k' 148.0 k' OK Seismic W = 14,124 + 31697 + 7248 = 33,596* 2 2 V = 0.556 (0.54)(33,596) = 10.091, MOT 10.09k. (11.1) = 112.0' (No uplift) w/50 psf snow nW = 50 (36.33)8.33 = 15.1 k V = 0.556 (0.54)(33.6 + 15.1) = 14.6k MOT = 14.6 (11.1) = 162' MRES . = 182.8 + 15.1(4.16)2/3 = 224.7' OK Therefore no overturning APPROVED By JUL 0 c(5� 64 March 10, 1998 7. CONNECTIONS (cont'd) 1 e. Floor to Fnd (cont'd) Lateral Sliding Resistance Net Wt = 65,904 - 27(36.3x8.33) = 57,740# Use 3" x 3" brg pads If spacing = 4'-0 oc : # of pads = (36.3+8.3)2/4 = 23 Wt/Pad = 57,740/23 = 2510 lb Comp. Stress = 2510/(3x3) = 279 psi < 8000 psi (pad) OK Fp = 0.7 (0.85)(3 ksi) = 1785 psi (concrete) OK APPROVED .65 March 10, 1998 h, 7. CONNECTIONS (cont'd) e. Floor to Fnd (cont'd)- Lateral Sliding Resistance (cont'd) a- Ve = 120 mph: p = 51 psf V = 20,549 lb Coefficient of friction = 0.2 Vnet = 20,549 - 0.2 (57,740) 9,000 lb Seismic V = 0.3(15,100) = 24,300lb. Vnet = 24,300 - 0.2 (15,100) = 8100" Plate 3/1 6 x 9 x 9 S = (3/16)Z x 9/6 = 0.0527 in M = 0.0527(27)4/3 = 1.898'" V = M/1" = 1898" # of Plates Req'd = 9000/1898 = 4.74 plates therefore spacing = 36.3/4.74 = 7.66' use: 6'-0 min. spacing and a minimum of (2) plates per side wall use: Plate 3/16 x 9 x 9 w/ (2)1/2 dia. exp. bolts @ 6'-0 oc with 3x3 pads @ V-0 oc for seismic zones 3 & 4 and wind speeds > 95 mph. <�M jul 1 k.4 .R 5' 'LPJ v� / 66 March 10, 1998 8. SHELTER TRANSPORT Analysis & design of shelter for handling & shipping Determine Panel Weights End: 8'-4" x 9'-5" [118 (4" )](8.33')(9.42') = 3086" 12 x 10'-5" 39.3(8.33')(10.42') = 3411* x 11'-1" 39.3(8.33')(11.1') = 3634* 10'-4" x 9'-5" 39.3(10.33')(9.42') = 3824" x 10'-5" 406(10.42') = 42310 x 11'-1" 406(11.1') = 4507# , APPRC)VF-D BY 12'-0" x 9'-5" 39.3(12.0')(9.42') — 4442#NC x 10'-5" 471.6(10.42') = 4914* "' e x 11'-1" 471.6(11.1') = 5235* Side: 9'-5" ht 39.3(9.42') = 370#r 10'-5" ht 39.3(10.42') = 406" 11'-1" ht 39.3(11.1') = 472#r 67 March 10, 1998 8. SHELTER TRANSPORT (cont'd) .analysis & design of shelter (cont'd) Roof: 8'-4" width [118(4_5)](8.33) = 369' 12 10'-4" width 44.25(10.33') = 457' 12'-0" width 44.25(12.0') = 531' Floor: 8'-4" width 52(8.33') = 4330' 10'-4" width 52(10.33') = 537" 12'-0" width 52(12.0') = 624#r See attached computer outputs for analysis and design of handling and shipping stresses. P,PPROVED By e10 F%.tce 68 March 10, 1998 8. Shelter Transport (cont'd) Lifting Plate load capacity Design for 8 1/2 ton & 12 ton fc = 4,000psi (28 day); for handling use fci = 3,000psi Re: PCI DESIGN HANDBOOK & ACI-349 Handling factor =1.2 8 1/2 ton design P = 17' assume angle = 70° P = 17 x 1.2 = 20.4 7.42K 20.4K 20- 21.7 K 70' rod & clevis: Use 1"(8 1/2 ton) clevis Re: M'MASTER'S CATALOG pg 426 (1989) 3/ V = 21.7/2 = 10.85K M = 21.7 / 2 x (4 - 3 11116) = 1.70K." 2 A = 0.7854"2 1"'dia bar I = 0.049ir%4 S = 0.098"s '/16„ F„ = 0.22 FU f, = 10.85 / 0.7854 = 13.81 ksi Fb = 0.75 Fy fb = 1.70 / 0.098 = 17.35ksi F,, > 13.81 / .22 = 62.8ksi Fy > 17.35 / .75 = 23.13ksi l`!�9$ Use A572 GR. 50 1 dia rod,�a 69 March 10, 1998 1 8. Shelter Transport cont'd Lifting Plate (cont'd) 8 1/2 ton design (cont'd) shear capacity horizontal shear classify lifting plate as an insert V„ = 1.4(7.42) = 10.4K 13 a" 7" 3 a' cpV. _ (0.85)(0.85)4 sgrt(3000)(3 1/2) (8.75 + 13.75)2 = 24.9K M r cpV, _ > V, therefore OK vertical shear r--- FAILURE PLANE I AFFROVED By JUL i Vu = 20.4(1.4) = 28.6K shear friction: A„ = 0.44 + 0.12(7 + 8.5)1/12 = 0.60'"2 cpVn = 0.60(60){(1.4 x 0.85) Sin 45 + Cos 451 = 55.7K cpV„ = 55.7K > 0.2(3) 7 + 8.5 4 = 52.6K Sin 45 cpVn = 0.85(52.6) = 44.7K > V, 70 March 10, 1998 8. Shelter Transport cont'd Lifting Plate (cont'd) 8 1 /2 ton design (cont'd) try shear friction: V„ = A„ fy u A„ = 2(0.31) + (0.44) + 0.12(18.5) = 1.25 12 fy = 60ksi u = 1.4(.85) =1.19 V„ = 1.25(60)11.19 (Sin 45) + 803.451 = 116" > Vn = 0.2(3) (5.5 +5.5 + 18.5)4 = 81.5" sin 45 cpV„ = 0.85(81.5) = 69.2" > V„ = 28.6" OK 71 APPROVED BY JUL March 10, 1998 8. Shelter Transport (cont'd) Lifting Plate (cont'd) 8 1 /2 ton (cont'd) bearing pressure vertical P = 20.4" fc = 3,000psi Fp = 0.7(0.85 x 3,000 x A,) / 1.4 = 1.28 Al AREQ = 20.4 / 1.28 = 15.9in2 APRov = 3 7/8 x 4 3/4 = 18.4in2 > AREQ OK check plate P = 17x1.2 = 20.4" ; = 20.4 / 18.4 = 1.11 ksi t = 0.61" Use 5/8" plate horizontal P = 7.4 x 1.2 = 8.9" AREQ = P / 1.28 = 7in2 APRov = 1 1/8(12)2 = 2712 OK fp = 8.9 / 27 = 0.33ksi M = 0.33(1.125)2 / 2 = 0.21 ""r S = 0.0077in3r t = 0.22" .•. use 3/8 plate T = R b2 t2 T = 0.56( .11)(412 = 27ksi t2 APPROVED By JUL 72 March 10, 1998 8. Shelter Transport (cont'd) Lifting Plate (cont'd) 8 1/2 ton (cont'd) welds vertical - 1" dia bar to side_plate: j P = 21.7/2 = 10.85' circum. 1" dia bar = 3.14" fw = 10.85 / 3.14 = 3.451 1 /4" fillet side plate to top plate: P = 10.2" w = 3 1/2" w = 2.9w" 1/4" fillet weld horizontal side plate to back plate: P = 7.42/2 = 3.71" Iw = 12 fw = 0.31 Kr 3/16" fillet 73 March 10, 1998 s 8. Shelter Transport (cont'd) Lifting Plate (cont'd) 12 ton 10.5K P = 24K —i P = 24 x 1.2 = 28.8K 30.6K 28.8K 20' . rod & clevis use 1 1/4" shackle (12 ton) Re: M°MASTER CATALOG pg 426 (1989) 5 �/4 V = 30.6K / 2 = ,�— M = 15.3(4.625 - 4.5)(1/2) _ 1 1/4" dia pin A = 1.227in2 [:Up I = 0.1198'n4 S = 0.1918in3 f„ = 15.3 / 1.227 = 12.5ksi fb = 0.96 / 0.1918 = 4.99ksi Use 1 1/4" dia rod. A572. GR. 50 steel F„ = 65(.22) = 14.3ksi V = 17.5K Fb = 50(.75) = 37.5ksi M = 7.19' APPROVED BY ra I N 15.3K 0.96K" 74 March 10, 1998 8. Shelter Transport (cont'd) Lift Plate (cont'd) 12 ton (cont'd) horizontal V„ = 10.5x1.4 = 14.71 cpVc = 24.9' > V„ OK vertical V„ = 28.8K x 1.4 = 40.3K (pVn = 44.7K > V„ OK bearing pressure vertical P = 28.8 A = 28.8 / 1.28 = 22.5'n2 APROx = 3 7/8 x 5 7/8 = 22.8'n2 fP = 28.8 / 22.8 = 1.27ksi plate: M = 1.27(0.56)(4.625)2 = t2 27ksi t = 0.75" horizontal P = 10.5K AREQ = 10.5 / 1.28 = 8.2in2 < APROV = 271n2 fP = 10.5 / 27 = 0.39ksi M = 0.39(1.125)2 / 2 = 0.247Kr S = 0.091 in3 t = 0.23" Use 3/8" plate Use 3/4" plate APPROVED BY , LI! 199 75 March 10, 1998 8. Shelter Transport (cont'd) lift Plate (cont'd) 12 ton (cont'd) welds vertical 1 1/4" dia bar: P = 30.6K / 2 = 15.3K circum. = 3.927" = Iw fH, = 3.9Kr 5/16" fillet side plate to top plate: P = 14.4K lw = 3.5" fW = 4.1 KP 5/16" fillet horizontal side plate to back plate: P = 10.5K / 2 = 5.25K IW = 12 fW = 0.44' 3/16" fillet 4PPIROVF-t) By JUL 14�� 76 March 10, 199P 9. Fire Ratina UBC requires 3.8" thick sand - lightweight concrete for a 2 hour fire rating. The shelter has a 4" thick walls and roof. Therefore the 2 hour rating is provided in the roof and wall members. APPROVED VED BY "A Jul i►99 77 March 10, 1998 10. Thermal Efficiency Wall 1" thick insulation outside air film 4" sand-It.wt. conc 0.19x4 1" foam board insulation 3/4" fiberglass faced plywood inside air film 1 1/2" thick insulation outside air film 4" sand-It.wt. conc 0.19x4 1 1/2" foam board insulation 3/4" fiberglass faced plywood inside air film 2" thick insulation outside air film 4" sand-It.wt. conc 0.19x4 2" foam board insulation 3/4" fiberglass faced plywood inside air film 2 1/2" thick insulation outside air film 4" sand-It.wt. conc 0.19x4 2 1/2" foam board insulation 3/4" fiberglass faced plywood inside air film 3" thick insulation outside air film 4" sand-It.wt. conc 0.19x4 3" foam board insulation 3/4" fiberglass faced plywood inside air film Roof outside air film 4" sand-It.wt. conc. 0.19x4 4" foam board insulation 3/4" fiberglass faced plywood inside air film = 0.17 = 0.76 = 5.0 = 0.94 = 0.68 R = 7.55 U = 1/R = 0.132 = 0.17 = 0.76 = 7.5 = 0.94 = 0.68 R = 10.05 U = 1/R=0.100 = 0.17 = 0.76 = 10.0 = 0.94 = 0.68 R = 12.55 U = 1 /R = 0.080 = 0.17 = 0.76 = 12.5 = 0.94 = 0.68 R = 15.05 U = 1 /R = 0.066 = 0.17 = 0.76 = 15.0 = 0.94 = 0.68 R = 17.55 U = 1 /R = 0.057 = 0.17 = 0.76 = 20.0 = 0.94 = 0.68 R = 22.55 U = 1 /R = 0.044 AppROVED BY a 78 March 10, 1998 11. Wall Openings 1. Opening Sizes �Door: T-0" x T-0" T-6" x T-0" 4'-0" x T-0" 6'-0" x T-0" AC Window Unit: 18"high x 28"wide HVAC: case supply return space betw. opn'as 1 8 x 20 12 x 20 20 .2 8x28 14x28 18 3 10x30 16x30 30 Wave Guide Plate: 4 x 12 -17"high x 20 3/4"wide 4 x 8 - 11 "high x 20 3/4"wide 4 x 4- 4"high x 20 3/4"wide Exhaust Fan: (one high/one low) -� 12" sq. -12 1/2" x 12 1/2" 16" sq. -16 1/2" x 16 1/2" 18" sq. -18 1/2" x 18 1/2" 20" sq. - 20 1/2" x 20 1/2" Louver: (no other openings in combination with louver) 42 1 /2"wide x 50 1 /2"high w 91 APPROVED ICI JUL A^; INC 79 March 10, 1998 11. WALL OPENINGS (cont'd)_ 2. Opening Combinations - Door and AC - Door and Exhaust - (2) HVAC and Wave Guide - Maximum allowable blockout available - 3. End Wall Sizes HEIGHT W 8'-0" 91-019 91-811 8'-0" x x x D 9'-0" x x x E 11'-8" x x x x - indicates the shelter is available in that size 4. Out of plane design for end wall 4.1 w/ door max. wind load = 51 psf Ht. = 9'-8" M/ft. = 51 x (9.67)2 = 596' 8 flexure: door size = 6'-0" 8'-0" wide shelter M = 596 x 8/2 = 2384v x 1.3 = 3100v p = 3.1x12 = 1 .9(60)12(2)2(1-8.85 x p) 69.7(1-8.85 x p) p = 0.01686 As = 0.40 in2/ft ' 10'-0" wide shelter M = 596 x 10/4 = 149V x 1.3 = 193r p = 1.937 x 12 = 1 .9(60)12(2)2(1-8.85 x p) 111.5(1-8.85 x pi)F'PF8®VED BY P =0.00982 As = 0.24 in2/ft t; t , JI,� r, 12'-0" wide shelter M = 596 x 12/6 = 1192 r x 1.3 = 1550 � $ � ° p = 1.55x12 = 1 .9(60)12(2)2(1-8.85 x p) 139.4(1-8.85 x p) p = 0.0077 As = 0.18 i in2/ft - 80 March 10, 1998 11. WALL OPENINGS (cont'dl _ shear: (PVC = (.85)22 x sgrt(4000) x 2(12) = 2190* -' V/ft = 51(1.3)9.67/2 = 321 V = 321 x 8/2 = 1282' < cpV„ = 21 W okav 4.2 w/ penetrations max. load: j 0.75 Pba1 = 0.75(0.85)2(4/60)87(87 + 60) = 0.02138 AS = 0.513 in2/ft Man = 0.9(60)12(2)2(0.02138)(1-8.85x0.02138) = 44.91 Wall = 44.9 x 8 = 246* t = 51 psf x 4.8' 12 x 1.3 x (9.67)2 Therefore 3/4 of the shelter width may be openings (max). 10 11 12 O � 7 7 8 8 9 ' 1 O 4 5 6 4" THICK 1 3.5' MEM dam" ,Z A@2!j I in4 1 10 40 333 2 10 40 333 3 10 40 333 4 10 40 333 5 10 40 333 6 10 40 333 7 12 48 576 8 12 48 576 9 12 48 576 10 12 48 576 13.9 K (SEE ENDWALL DESIGN) D 3.68 4.48 6.46 6.34 3.75. 4.78 3.56 4.22 5.81 7.05 4.53 5.30 2.94 5.41 3.40 6.40 2.13 4.22 2.60 5.30 Ai?PROVF-D BY kj JUL See Attached Computer Output For Model of In -Plane loads. 81 March 10, 1998 11. WALL OPENINGS (cont'dl 4 x 10 section: VU = 6.46' MU = 7.05k' cpV. _ (0.85)2(2) {sgrt(4000)}(4)8.5 = 3107" shear: cpV, = 0.85L0.041(60)(8.5) = 43351 4 qV„ = 3107 + 4335 = 7442" >V„ = 64W Therefore 4x4 - W4xW4 WWF is okay flexure: p = 7.05 x 12 = 1 .9(60)4(8.5)2(1-8.85 x p) 184(1-8.85 x p) p = 0.00517 As = 0.19 in 4 x 12 section: V„ = 3.40k Mu = 6.40k' shear: cpV, _ (0.85)2(2)1 SQRT(4000)14(10.5) = 3.84 k > V„ Min. Shear Reinf. Is Available Therefore 4 x 4 - W4 x W4 WNF is okay flexure: p = 6.40x12 = 1 - .9(60)4(10.5)2(1-8.85 x p) 310(1-8.85 x p) p = 0.00332 As = 0.00332(4)10.5 = 0.14 in APPROVED BY JUL !99 82 March 10, 1998 11. WALL OPENINGS (cont'dl 4. Out - of - Plane (cont'd) 4.3 Determine Allowable Amount of Openings W1 Various Wind Speeds If ratio of concrete to openings = 1 : 1.5 w 6) Assume: *5/ft AS = 0.31 inZ/ft —> p = 0.311(2)(12) = 0.01292 (or 244) Flexure Mall = 0.9(60)(2)212(0.0129)(1-8.85 x .0129) = 29.6" Wall = 29.6 x 8 = 162' 12 x 1.3 (9.67)2 p = 51 psf 162 = 3.17 51 Use 1:2 Ratio Of Concrete To Openings Shear qV, = (0.85)2(2)4'4000 (2)(12) = 2193' WsH = 2.19 x 2 = 348' > Wnex 1.3 9.67 flexure controls APPROVED BY # 2 Jul 1998 INC 83 March 10, 1998 11. WALL OPENINGS (cont'd) 4. Out - of - Plane cont'd 4.4 Check in - Plane Loads Wind Shear @ top P (psf) of wall k 51 x 36.3 x 11.1 / 4 x 1.3 = 6.68k Seismic —> Use narrowest width since that allows the least concrete available to resist load. HEIGHT roof wt = 8.33(36.3)(4.75)118 = 14.12 9'-0" 10'-0" 10'-8" 12 snow = 50 x 8.33(36.3) = 15.12 wall = (H)/2(4/12)118(36.3)2 = 12.85 14.28 15.23 W = 42.09 43.52 44.47 Zone 4 V = 0.556(0.54)(W/2)(1.1)(1.3) _ 9.03k 9.34k 9.54k 84 March 10, 1998 11. WALL OPENINGS (cont'd) 5. In plane design of end wall 5.1 w/ door opening 8'-0" wide x 8'-0" (+12") high end wall: 4'-0" wide door (Re. computer output attached) flexure: ' I MU = 33.2k' X 12 = 398'" j p = 398 = 1 = 0.00377 .9(60)4(22.5)2(1-8.85 x p) 275.5(1-8.85 x p) ATOT = (Asm = 0.38) + (At = 2.00 x 1.3 / 54 x 2) = 0.40in2 #6 (or 244) - p = 398 = 1 = 0.00723 .9(60)4(16.5)2(1-8.85 x p) 148 (1-8.85 x p) , - , ATOT = (As,,, = 0.27) + (At = 5.1 x 1.3 / 54 x 2) = 0.33in2 #6(or 244) MU = 3.24" x 12 = 38.9k" p = 38.9 = 1 = 0.00973 .9(60)4(4.5)2(1-8.85 x p) 112(1-8.85 x p) APPROVED By Jul ATOT = (As = 0.08) + (At = 2 x 1.3 / 54 x 2) = 0.104in2.,•.: #5(or 244) -r r , shear: k� � member 1 & 2 Vu = 4.561 cpVc _ (.85)SQRT(4000)4(22.5).85 = 4.1' (A)s) = (bv,)50/fy = 0.0033 s = 4" Av = 0.0133 use 4x4 - W4xW4 WWF for shear reinforcement member 3 V„ = 10.97' cpVc = (.85)SQRT(4000)4(16.5)(.85)(2) = 6.0k cpV,, = 0.85(0.04 (60)(16.5) = 8.42k 4 Ovn = 6 + 8.42 = 14.42k > V„ use 4x4 - W4xW4 WWF for shear reinforcement 41 See Attached Computer Output For Model Of In -Plane Loads 85 March 10, 1998 11. Wall Openings (cont'd) J 5. In plane design of end wall (cont'dl 5.1 w/ door opening (cont'd) I; member 4 V� = 0.38 x 1.3 = 0.5k cpVt = (0.85)ZSQRT(4000)4(6.5) = 1.19' j use 44 - W4xW4 WWF for shear reinforcement 8'-0" wide x 9'-0" (+12") high: _ flexure: MU = 37.55' x 12 = 451 k" p = 451 = 1 = 0.00429 9(60)4(22.5)1(1-8.85 x p) 242(1-8.85 x p) ATOT = (Asm = 0.25) + (At = 4.8 x 1.3 / 54 x 2) = 0.31 in' #6(or 244) AREA = 0.00429(4) 22.5 = 0.39"' shear: member 1 & 2 V„ = 4.74k cpV, = (.85)2 SQRT(4000)4(22.5) = 4.1 k (A,/s)mo = 50b,, /fy = 0.00333 s = 4 A„ = 0.0133 x3 0.0400 in2/ft use 4x4 - W4xW4 WWF member 3 V„ = 12.32k cpV. = (.85)2 (2) {SQRT(4000)}4(28.5) = 10.4k cpV, = 0.85 0.04 (60)(28.5) = 14.5k 4 cpV,, = 10.4+14.5 = 24.9k>V„ use 4x4 - W4xW4 WWF 8'-0" wide x 9'-8" (+12"): flexure: MU = 38.91 k' x 12 = 467k" p = 467 = 1 = 0.00445 .9(60)4(22.5)2(1-8.85 x p) 234(1-8.85 x p) ATOT =. (As,,,= 0.23) + (At = 4.3 x 1.3 / 54 x 2) = 0.29in2 #6(or 244) APFRCV _® BY AREA = 0.00445 (4) 22.5 = 0.40in1 86 March 10, 1998 APPENDIX "A" APPROVED BY JUL 0 9 1998 INa 87 February 6, 1990 �l J PFS Corporation S PF= 114 SOUTH WESTGATE DRIVE GREENSBORO. NORTH CAROLINA 27407 TELEPHONE: (919) 854-994 PROJECT: Bullet Resistance Test ` DATE: February 6, 1990 Reported To: UNR-Rohn P.O. Box 2000 Peoria, Illinois 62656 i On January 16, 1990, our representative, Melvin Johnson arrived at Van Doren Industries., Hays, Kansas and was met by Mr. Richard°Malmberg, General Manager. Mr. Malmberg and our representative discussed the bullet test procedures to be followed before conducting the actual tests. The bullet resistance test was to be conducted on a wall assembly of the Standard Rohn Concrete Shelter. The tests were designed as closely as possible to meet U.L. 752 weapon and ammunition specifications. The test procedure followed the U.L. listed l specifications as shown below. 1) Range - 15 feet or less 2) Sample - Rigidly mounted with corrugated cardboard 18" behind 3) High Powered Rifle - Based on Sample resistance to one shot. 4) Tes.ts Conducted - At room temperature, 22 degrees + 3 degrees C. (71.6 degrees + 5 degrees F). There must be no penetration of projectile through test sample, and no spalling of material on projected site to extent tha agments imbed in or damage cardboard. APPROVED �� p 1998 Our re resentative witnessed the test as follows : ::.:'=�:' Test Panel - Side panel of subject enclosure (�• Material of Panel - 4" thick concrete - 112 density - 4000 psi composed of expanded shale light weight coarse aggregate with regular weight sand fines back surface of panel - 11" foam board and 1/2" plywood fastened to panel. Bullet Test Weapon/Ammunition - (1) high power rifle 24" barrel (2) Remington bullets -30-06 rifle -high velocity - 220 grain soft point core Lokt-R 30067. Test Sample - Material was of commercial construction as noted above. The six test shots were fired from a distance of 15 feet and in a grid pattern with cardboard indicator, approximately 1/8" thick, double face, was placed at a distance of 18 inches behind the protected side of the test panel. Observation - Using the designated rifle and ammunition, shots were placed at various locations on the test panel to allow penetration of the projectile with sufficient force to imbed into the panel. It was found in all six samples, that the projectile was imbedded into the panel approximately 1 1/2 inches. There was no -, penetration of the wall section by the projectile or of any other material. There was no debris released into the interior as the result of the impact and there were 88 February 6, 1990 no visible signs on the interior surface of the projectiles' impact. Conclusion - The above referenced, as modified, Bullet Resistance Test was conducted using UL 752-tas the criteria. None of the six (6) samples witnessed allowed- the bullet allowed the bullet to penetrate through the test specimen. The samples prevented any debris or damage as required. Thank You. .Sincerely, Ken W. Houglan ..General Manager, Southeast Region cc: Rick Malmberg Melvin Johnson Larry Beineke APPROVED 89 February 6, 1990 REINFORCED CONCRETE. FIRE RESI;STANCE Prepared under the Direction of the CRSI Engineering Practice Committee by The CRSI Committee on Fire Ratings J. A. Gustafson, Chairman .. .. . ........... The Ceco Corporation R. D. Bay . ....... .. . . . . .......... Laclede Steel Company T. C. Creed .... ..... . . . . .. ....... Florida Steel Corporation E. G. Opbroek ..... .... . . . . ......... . . . . . . Armco Inc. F. I. Skog . . .. ..... . . . . . .... .... Cowin & Company, Inc. D. P. Gustafson, Editor . .. . . . .. . .... . ... . . . . . . . . . . CRSI And Reviewed by the CRSI Task Group on Design for Fire Resistance W. C. Black . . . . . . . . . . . . . . . . . . . Bethlehem Steel Corporation L. P. Flibotte . . . . . . . . . . . . . . . . . . • . Barker Steel Company, Inc. B. K. Thoritley, Jr. ..... . . . ... ..... Florida Steel. Corporation Special Consultant Armand H. Gustaferro, Consulting Engineer. The Consulting Engineers Group, Inc.; Glenview, Iilinois CONCRETE REINFORCING STEEL INSTITUTE 180 NORTH LA SALLE STREET, CHICAGO, ILLINOIS 60601 APPROVED BY - . CHAPTER 3-FIRE ENDURANCE .DETERMINED ,BY HEAT TRANSMISSION REQUIREMENTS OF ASTM E119 3.1 Introduction The fire endurance of concrete floors, roofs, and walls is often governed by the criteria for temperature rise of the unexposed surface rather than by structural considerations. The ASTM El19 criteria for temperature rise of the unexposed surface, referred to as "heat transmission" requirements, limit the rise to an average of 250°F or a maximum at any one point of 325°F. The purpose of these criteria is to guard against ignition of combustibles in contact with the unexposed surface. Some building codes waive or modify the heat transmission criteria for certain conditions. For example, the Wisconsin Administrative Code modifies the criteria in Section Ind 51.042—General Requiremen= "(5) The heat transmission requirements of A=Vf E119 (25b). with the exception of high hazard areas penal and health care facilities and warehouses for combustible materials. may be reduced to one-half (�2) of the hourly rating ►equired by this code. but not less than one hour. (a) The fire -resistive rating for structural integrity required by this code shall be maintained where the heat transmission criteria has been reduced " For many years other codes have classified concrete floors with slab thick- nesses of 2, 3, and 4 in., as 2, 3, and 4 hours, respectively. Even though such requirements are more liberal than those of ASTM E 119, no known fire problems have resulted. 3-2 Single Course SIabs Fire ;tests of concrete slabs have shown that the temperature rise of the unexposed surface is mainly a function of the slab thickness and the type of aggregate, as shown in Fig. 3.1. The curves in Fig. 3.1 can be expressed approxi- mately: R = Ctn . (3.1) 3-2 s STRUCTURAL CONCRETES 4 LI 3HTWEIGHt = 3: SANDED- IGRnYEIGH w Z w AIR-COOL D 9LAG w U_ I CAR ONATE ILICEO S 0' , 2 3 �•8�� 4 S 6 7 S THICKNESS, IN. Fig. 3.1 Fire Endurance of Concrete Slabs --Effect of Thickness and Type of Aggregate —based on Heat Transmission Where R = the fire endurance in minutes C= a constant for a given concrete type; values as low as 6 have been reported for siliceous aggregate concrete and as high as 11 for light- weight concrete t = the slab thickness in inches n = an exponent, usually about 1.8, but values between 1.65 and 2.0 have been reported. The data. in Fig. 3.1 represent concretes typical of those used in building construc- tion. The data are based on fire tests of concrete slabs made with a variety of aggregates as noted. For the normal weight concretes, the maximum aggregate size was 3/4 in. and the air content was about 6%. For the structural lightweight concretes, the maximum aggregate size was slightly less than 3/4 in. and the air content was about 7%. In all cases, fire tests were conducted when the mid -depth relative humidities of the slabs were 75%. It was noted above that slab thickness and aggregate type are the main factors affecting heat transmission. Other factors that affect fire endurance are moisture. condition, unit weight, air content, and maximum aggregate size. Within the usual ranges, water -cement ratio, strength, and age have only insignifi- cant effects. .3.2.1 Effect :of Moisture The effect of moisture conditions on the fire endurance as determined by heat transmission is illustrated in Fig. 3.2, which shows the temperature of the unexposed surface of three hypothetical specimens during fire tests. All specimens were made of the same concrete and were the same thickness. Speci- APPROVED BY C7.