STANDARD PRE -CAST CONCRETE
EQUIPMENT SHELTER ANALYSIS
Revision 7: March 10, 1998
CLARK ENGINEERS MW, INC.
111 N.E. Jefferson Avenue
Peoria, IL 61602-1227
PROJECT STATEMENT
Analyze and prepare calculations suitable for submission to building officials of pre-
fabrecated pre -cast concrete equipment shelters as manufactured by UNR-Rohn.
Design shall include details, notes, specifications, and drawings for complete review.
This analysis is for buildings in widths of 8'-4", 10'-4", 12'-0" and lengths up to 364".
Compliance with BOCA, SSBC, and UBC is required. Design shall be comprehensive to
cover placement of shelters in all 50 states.
APPROVED .By
00 Jul ON-,
0 9 998
I
6
PAGE DATE INDEX
ITEM
PAGE
-EXT DATE
REMARKS
Design Criteria
1
March 10, 1998
Design Criteria
2
March 10 1998
Design Criteria
3
March 10, 1998
Roof Design
4
March 10, 1998
-- Roof Design
5
March 10, 1998
Roof Design
6
March 10, 1998
Roof Design
7
March 10, 1998
Roof Design
8
March 10, 1998
Walls
9
March 10, 1998
Walls
10
March 10, 1998
Walls
11
March 10, 1998
Walls
12
March 10, 1998
Floor
13
March 10, 1998
Floor
14
March 10, 1998
Floor
15
March 10, 1998
�Floor
16
March 10, 1998
DATE JUL p 9 CERT. NO,��� -m�5
Lateral
17
March 10, 1998
Lateral
18
March 10, 1998
NUMBER '
Lateral
19
March 10, 1998
PLAN _P-j2kh.2-G6<,L--�
Lateral
20
March 10, 1998
APP YED BY CHARLES A. OSTERDAY, JR.
Lateral
21
March 10, 1998
Lateral
22
March 10, 1998
Lateral
23
March 10, 1998
Foundations
24
March 10, 1998
nature
sy nature
Mg
Foundations
25
March 10, 1998
��--
26
March 10, 1998
Foundations
27
March 10, 1998
Foundations
28
March 10, 1998
APPROVED BY -'
Foundations
29
March 10, 1998
Foundations
30
March 10, 1998
Foundations
31
March. 10, 1998
Foundations
32
March 10, 1998
Foundations
33
March 10, 1998
Foundations
34
March 10, 1998
Foundations
35
March 10, 1998
Foundations
36
March 10, 1998
Foundations
37
March 10, 1998
Foundations
38
March 10, 1998
Foundations
39
March 10, 1998
Foundations
40
March 10, 1998
Foundations
41
March 10, 1998
Foundations
42
March 10, 1998
Foundations
43
March 10, 1998
Foundations
44
March 10, 1998
.Foundations
45
March 10, 1998
Foundations
46
March 10, 1998
Foundations
47
March 10, 1998
Connections
48
March 10, 1998
Connections
i
49
March 10, 1998
PAGE DATE INDEX
ITEM
PAGE
EXT DATE
Connections
50
March 10, 1998
Connections
51
March 10, 1998
Connections
52
March 10, 1998
Connections
53
March 10, 1998
Connections
54
March 10, 1998
Connections
55
March 10, 1998
Connections
56
March 10, 1998
Connections
57
March 10, 1998
Connections
58
March 10, 1998
Connections
59
March 10, 1998
Connections
60
March 10, 1998
Connections
61
March 10, 1998
Connections
62
March 10, 1998
Connections
63
March 10, 1998
Connections
64
March 10, 1998
Connections
65
March 10, 1998
Connections
66
March 10, 1998
Shelter Transport
67
March 10, 1998
Foundation Design
68
March 10, 1998
Foundation Design
69
March 10, 1998
Foundation Design
70
March 10, 1998
Foundation Design
71
March 10, 1998
Foundation Design
72
March 10, 1998
Foundation Design
73
March 10, 1998
Foundation Design
74
March 10, 1998
Foundation Design
75
March 10, 1998
Foundation Design
76
March 10, 1998
Fire Rating
77
March 10, 1998
Thermal Efficiency
78
March 10, 1998
Wall Openings
79
March 10, 1998
Wall Openings
80
March 10, 1998
Wall Openings
81
March 10, 1998
Wall Openings
82
March 10, 1998
Wall Openings
83
March 10, 1998
Wall Openings
84
March 10, 1998
Wall Openings
85
March 10, 1998
Wall Openings
86
March 10, 1998
Appendix'A'
87
February 6, 1990
Appendix'A'
88
February 6, 1990
Appendix'A'
89
February 6, 1990
L1UNRN0012\QPR0\C0NCT0C. W B2
L
REMARKS
DATF AL 0 9 1 Cbr T. Nv 5'^nP - O IS
PLAN NUMBER,
APPR VED BY CHARLES A. OS T ERDAY, J R.
(JU14
( signature j
APPROVE® BlY
1. DESIGN CRITERIA
a. Concrete
(shelter) Sand lightweight concrete mix obtaining a 4000 psi minimum
compressive strength in 28 days.
(foundation) Normal weight concrete mix obtaining a 3000 psi minimum
compressive strength in 28 days.
b. Concrete Reinforcement
ASTM A615 grade 60 (fy = 60 ksi)
ASTM A185 smooth welded wire fabric
C. Connections
Plates, bars, etc... : ASTM A36 (F„ = 36 ksi)
Welding electrodes : E70XX
Headed studs : ASTM A108 (Ft = 60 ksi)
d. Loads
Floor Live Load
R21 140 psf (min) to 200 psf (max) .,
Wind
Check for worst code based on 120 mph (EXP. C) 1 = 1.0
BOCA
P = P„IKGCP
Pv = 36.9 P' APPROVED By
1'w ? F �'• � 1
Exposure coeff. (K) = 0.80 INC.
Gust response factor (G) = 1.32
Wall pressure coeef. (CP) = 0.8 + 0.5 = 1.3
Roof pressure coeef (Cd _ -0.7
P = 36.9 (1.0)0.8 (1.32) 1.3 = 51P'
P„ = 36.9 (1.0)0.8 (1.32)-0.7 = 27P"
w
1 March 10, 1998
1. DESIGN CRITERIA (cont'd)
d. Loads (cont'd)
Wind (cont'd)
SBC
Velocity pressure q = 0.00256V2(H/33)2"
q = 0.00256(120)2 (15/33)217 = 29.4Ps'
Use factor = 1.0
GCP Coeff = 1.2 (lateral) P = 29.4(1.0)(1.2) = 35
GCP Coeff = 1.4 (uplift) PU = 29.4(1.0)(1.4) = 41
UBC
Basic wind speed 120 MPH
Ce = 1.06 Cq = 1.3 (lateral)
Cq = -0.7 (uplift)
I = 1.0
QS = 36.9Ps'
Lateral P = CeCq Qs 1 = 1.06(1.3)36.9(1.0) = 51 P1
Uplift PU = 1.06(-.07)36.9(1.) = 27P'
Seismic
BOCA & SBC
V = CS W CS = 2.5 Aa
R
A. = 0.4 R = 1 4.5
CS = 2.5(0.) = 0.222
4.5
V = 0.222 W
APPROVED_ ''r
1998
KIP, INC.,
6
March 10, 1998
1. DESIGN CRITERIA (cont'd
d. Loads (cont'd)
Seismic (cont'd)
UBC
V = 2.5C� I W
R
I = 1.0
Na = 1.5 Ca = 0.36(1.5) = 0.54
Na = 1.1 Ca = 0.44(1.1) = 0.48
R = 4.5
V = 2.5(0.54)1.0 W = 0.30W
4.5
APPROVED BY
1141 rr, JUL
INC
3
March 10, 1998
2. ROOF
I_ I
a. Code Requirements
r-
j f - Assumptions: f, = 4000 psi fy = 60,000 psi
4" roof: 4" @ edge -and 5.5" @ ridge
Design roof for snow load and wind uplift.
- Try to use only 4" thick roof panels.
per ACI 318- P,,,;,, (temperature and shrinkage) = 0.0018
1/4 r-
4° 1 i I
AS= 4.5°(12) .0018 = 0.0972 IN2/FT V@12 �.376.�
;668
a
- Concrete cover = 2" at middle
3/4" at end
4pBY
pROVED
O
N
�'INC
4 March 10, 1998
2. ROOF (cont'd)
b. Loads
Dead Load
4" concrete (4.75 / 12)118 = 46.7 Psf
roofing = 0.5 Psf
ceiling = 1.0 Psf
miscellanous = 1.5 Psf
49.7 P' x 1.4 = 70 Psf
,APPROVED BY
L0-9 1998
5 March 10, 1998
'd)
2. ROOF (cant
1 _
c. Member Design
�( Shear
d = 4 - 1.75 = 2.25
b=12"
4" cpv, = 0.85(2) SQRT(4000)(12)2.25 = 2903#''x 0.85 = 24681
Wu = 2468 = 448 Ps'
11 /2
W, _ (448 -.70) 11.7 = 222 Ps'
say okay for 50 Psf snow
APPROVEDBY
0 0 !4�
�.
6 March 10, 1998
2. ROOF (con
t'd)
c. Member Design (cont'd)
Flexure
f� = 4000 Ps' fy = 60 ks'
l
- Try #4 at maximum spacing
Maximum spacing = 3 x slab thickness < 18"
4" spacing = 3 x 4.5 = 13.5 - 12"
4" Roof
d=43/4"-3/4-3/4-1/4=3.0"
#4012"
p=0.2/3.Ox12=.00556
TMn = 0.9(60).00556(12)(3. 0)2(1 - 8.85 x .00556) = 30.81"'
W„=(49.7x1.4+50x1.7)=155P'
M„= 155x(11.3)2/8=29.7'<qM"
Check for Wind Uplift
Wu=49.7x0.9+1.3(-41)=-8.6Psf
#4 12 d =.75 x 2 + 5/16 = 1.81"
p = .2 = .00921
12 x 1.81
cpMC _ .9(60).00921(12)(1.81)2 (1 - 8.85 x .00921) = 18.01
M„ = 0.0086(11.33)2/8 = 0.138" x 12 = 1.66" okay
7 March 10, 1998
2. ROOF (cont'dl
c. Member Design (cont'd)
Deflections
f, = 7.5 sgrt (4000) = 474 psi x 0.85 = 403 P"
E = 42.3 sgrt (4000) = 2675"'
max span = 11.33'
defl = 5wl4
384(E 1)
(4") Ig = (4.75)3 12 / 12 = 107.2 "4/R
Mcr = 403(107.2) = 18.19k"
2.375
Deflections
4" slab (assume 52 P' live load for 2 Psf of water ponding)
reinf.
Ma DL
Ma (LL=52 PS')
a Ic"
kr
k"P
#4@12
9.52
9.96
0.88 12.47
reinf.
Mcr/Ma s
1. LL defl DL
defl LL defl LL
cr. above cr.
#4@12
0.81
89.6 .064
.058 .078
Total DL I.t. mult. = 2 (5 year or more)
60 psf LL I.t. mutt. = 1 (3 months)
* look at long term deflection of LL = 52 P'
defl = .064 x (2 + 1) + (.058 + .078) (1 +. 1) = .46" = 1 / 296
initial slope of roof = 1/4" per foot
Therefore assume a 1 1/2" rise in the roof, so maximum ponding
is 0.46 - 1.5 = 0.264"
Therefore no ponding
-.50 Psf < 52 Psf
oka APPROVED BY
"°• ' u �3
8 March 10, 1998
3. WALLS
Wind Pressure Resistance
Two criteria: 1. max load - 120 mph wind-Exp. C I = 1.0
2. minimum reinf to be used is 4x4-W4.OxW4.0 WWF
P
4
• WWF = o
A.
2„ 21 W x o
Q—
Wind Pressure
P=51 P'
M„=51(10)2/8x1.3x12=9.9k"'
Vu = 51(10/2) x 1.3 = 0.33k"r
Shear
cpVc _ .85(2) SQRT(4000)(12)(2) = 2580#r x .85 = 2193'
V. > Vu
* THEREFORE SHEAR IS OKAY
Deflections
By comparison to roof and the temporary nature of the load
s—X okay.
Axial and Flexure j,,PFpOVF—D B'Y
w/o Axial Load 50'- ='_g
4x4xW4.OxW.4.0 WWF (As = 0.12 '" IN
p = .12 = .005
2(12)
cpMc = .9(60).005(12)(2)Z (1 - 8.85 x .005) = 12.39'
M„ = 9.9k"f
* THERFORE FLEXURE IS OKAY
9 March 10, 1998
3. WALLS (ont'd)
Wind Pressure Resistance (cont'd)
W/Axial Load
Pd = 49.7x12'/2+4/12(118)(10) = 495"
P, = 50x12/2=300'
Psi = 1212 x 27 Psf = 162'
AppROVED BY
10 March 10, 1998
- 3. WALLS (cont'd)
Wind Pressure Resistance (cont'd)
w/ Axial Load (cont'd)
Combinations
1. D+S
w=o
P = 495 (1.4) + 300(1.7) = 1203#r
2. D+S+W/2(ExpD)
w = 51 P'/2x.75x1.7=33#r
P = 495 x 1.4 = 693
300 x 1.7 = 510 } 1065 x .75 = 799#r
-162 / 2 x 1.7 = -138
3. D+W
w = 51 x 1.3 = 66.3#r
P = 495 x .9 = 446 } 235:r
-162 x 1.3 = -211
4. D+S/2+W
w = 51 x .75 x 1.7 = 65#r
p = 495 x 1.4 = 693
' 300 / 2 x 1.7 = 255 } 673 x .75 = 505'
-162 x 1.7 = -275
By
INC.
11 March 10, 1998
3. WALLS (cont'd)
Wind Pressure Resistance (cont'd)
r-
w/Axial Load (cont'd)
- Re: "Design of Concrete Structures" by Winter/Nilson
(Vh edition) page 314
-- Pd = cpPn = cp.85 f,' bd [-pu + 1 - e' + SQRT(1 - e')Z + 2 e' u
d d d
u = 60,000 / .85(4000) = 17.65
- d=2" fc=4ks' b=12" d=2" cp=.87
li
—` Pd = 71.0 [-17.65p + 1 - e' + SQRT[(1 - e')Z + 17.65 pe']]
2 2
Comb. M(W) P(k) e' P Pd
1 0 1.2 ---- ---- Pa„ _ .55(1.7)4(48)
[1. - .88]
= 8.87k' ok
2 5:0 .80 6.25 .005 2.6 ok
3 9.9 .24 41.3 .005 .30 ok
4 9_9 . 11 19.4 .005 .66 ok
Summary
4" concrete wall reinforced with 4x4 - W4.0 x W4.0 WWF is okay.
12 March 10, 1998
4. FLOOR
a. LOADS
LL = 140 P"TO 200 PS'
DL = >
STRUCT - 34 P"
VINYL TILE - 1 Ps'
MISC - 1 Psf
36 P"
WT = 2241 x 118 = 39.3
144
6(4L x118 =19.7
144
(2)6(5) x 118 x 1.67 = 7.5
144 11 67 = 34 P'
APPROVED BI
� 9
INC
13 March 10, 1998
4. FLOOR (cont'd)
b. RIB DESIGN
FLANGE: AS = 2(12).0018 = 0.043 '" 2/ft.
Use W2.9 x W2.9-6x6 WWF.
RIB: Since Rib is less than 4" wide - design as beam
Shear
re: ACI 11.5.5.1 total depth < 10",
or 21/2(2) = 5" or, 1/2 x 3 = 1 1/2"
TVA = 0.85(2)(4000)12 (4)(8-1.25) = 2903" x 0.85
= 2467#
Vu Wu(11 -1.46) / 2 - 6.75 / 12) = 2467#
W„ = 586#''/2'-0 Rib Spacing = 293P'
LL = (293 - 36 x 1.4) / 1.7 = 140 P' (No stirrups)
APPROVED
INC
Jul
14 March 10, 1998
4. FLOOR (cont'd)
b. rib design (cont'd)
If LL = 20OPSF•
W„=(52 x 1.4 + 200 x 1.7)2 = 826"t
_ Vu = 826 ((11 -1.46) / 2 - 6.75) = 34754 > 2467#
12
Provide Shear Reinf.
Min. A„-50bwS/fy=>Av/S=50x4/60000=.00333
SmAx = d / 2 = 6.75 / 2 = 3.375'
@S=3" Av=.01 in2/3"
VS = (3894 - 2467) = 1975# = A„ fy d
.85 x .85 S
Av/S = 1.975 = .00488 #3 @ 3" Reinf.
60(6.75)
DIST. 3894# - 826(x) = 2467#
x = 1.73 x 12 = 20.7"
LL = 200 Psf For 21" out use #3 Cagy 3"
or W2.5 x W2.5 - 3x3 WWF
LL = < 140 Ps' no shear reinforcing
Rib
SPAN = 11.0' LL (PSF> W (KII) M (K-) P A (" 2) BOTT.
150 .58 105 .00241 0.39 #6
200 .77 140 .0032 0.51 #7
p= m = m
.9(60)24(6.75)2(1 - 8.85p) 59,049(1 - 8.85p)
.UA omen/n rno rrRAVITY IN -SITU APPROVE® BY
(PSF) a 1998
BAR ALLOW LL
6 140 Ni INC.
#7 200
15 March 10, 1998
4. FLOOR (cont'd)
b. rib design (cont'd),
CONCENTRATED LOADS
2000 P' Over 6.25' Area per ASCE 7-99
2.5' x 2.5'
If concentrated load has 2-1/2' x 2-1/2'
dimension then load will sit on a rib
.•. Shear is OK
Flexure
M->34(1.4)(11)2x12=8639""
8
Per PCI Handbook Pg 4-57 a Concentrated Load Has a
Effective Width Of 0.5L. If L=11'-0", Effective Width
=5'-6". Therefore 2 Joists Are Effective.
2000(1.7)11 x 12 = 56,100"
4 x 2 joist
M„ = 64,7390" < ON=105'`" ok
APPROVED By
16 March 10, 1998
5. LATERAL
a. LOADS - Worst Case - Long, High & Narrow
WIND
Base Shear = 51(36.3)(11.1) = 20.5k
BTM OF SHELTER
T/FND WALL LINE
GRADE LINE
APPROVF-0 By
j INC
17 March 10, 1998
j 5. LATERAL (cont'd)
a. Loads (cont'd)
l SEISMIC
,
BOCA
Structure Wt:
Roof: (4.75/12)(12 * 36.3)(118) = 2034611
Side Wall: (4/12)(11.1 * 35.3)(118)2 = 308244
End Wall: (4/12)(11.1 * 12)(118)2 = 10478
Floor:
(2/12)118(12)2 =
472
(4x6/144)10.67x 118 =
210
2(5/12)(1.67) x 118 =
164
2(9x6)/144 x 2 x 118 =
177
10230 / 2xl2 = 42.Vf
42.6[12x(36.3-1.67)] =
17703
,
1.67 x 12 x 118 =
2365
81,716#
Wall Cover 2.5 psf x 11.1(12 + 36.3)2
2,681#
i Floor 1.0 psf 12(36.3) =
436
Roof 1.0 psf 12(36.3) =
436
85,269#
Snow 50.0 psf 12(36.3) =
21.780
107,049#
PPRC)VE® BY
Floor live load: 0.25 (200)(10.67)(35.0) =
18673#
.k
.��99�
Base Shear:
see design criteria$
V = 0.30 W
V = 0.30 W
V = 0.30 (107,049 + 18673) =
37.7'
W = 0.3(20346 + 30824 + 10478 +
2681 +
436 + 21780) = 19366#
2 2
2
W = W = 19366 = 530'
36.3 36.3
18 March 10, 1998
5. LATERAL (cont'd)
b. ROOF DIAPHRAGM'
W Mu = 0.534(36.3)� x 1.43 = 126"
8
36.3' Vu = 0.534(36.3), x 1.43 = 13.9'
2
i
Flexure
p = 126 x 12 = 1 = .00077
0.9(60)4.0(96)2 (1-8.85p) 1316(1-8.85p)
AS = 0.00077(4/3) 4 (96) = 0.39 in2 (1) #6 Around Perimeter
Shear
cpV, = 0.85 SQRT(4,000)(96)4 x .85 = 17.5k > V„ =13.9k
No Shear Reinf
Read
APPRO`/F-D By
pm
ZINC
19 March 10, 1998
5. LATERAL (cont'd)
c. END WALL DESIGN
Vu = 13.9 KIPS U
FLEXURE
MU = 13.9X 11.1 = 154 K'
P = 154 X 12
.9(60)4(140)2 (1-8.85 P)
1
2290(1 -8.85 P)
P = .00044 X 4/3 = .00058
AS = .00058(140)4 = 0.322IN
1 #5 @ PERIMETER
SHEAR
0 VC = 0.85 4000 (4)96 X .85
= 25.6 KIPS > Vu OK
For distribution to floor slab, assume side wall takes the moment. Assume the
shear load is resisted by floor plates.
Wall plates:
V„ =
(154)1(11'
x 5 PL) = 2.8'
Floor plates:
V, =
13.9/5 PL
= 2.8k
20
APPROVED By
P.
March 10, 1998
5. LATERAL (cont'd)
c. End Wall (cont'd)
Check wall for combined wind. (2 way plate for out -of -plane loads)
51 x 0.7+0.25
1.3
37.3 PSF
beff = 4t + 5" (plate width)
a/b = 1.5 WORST B = .485
r = .485(37.3)(8)2/(.33)2 = 10.63 KSF
MU = 10.63(1.3)(.332/6) = 0.251 K'/'x12 = 3.0 K"/'
PU = 14 K
P = 24 = .01 m = .60 = 17.64
12 2) .85 4)
e' = 0.16"
c..UAIJ — I4.0
TPN = cp0.55 f c Ag [1 - (kl )2]
32h
CPPN = 132 x (1 - 0.57)
TPN = 55.6"> P„ = 14.0' OK
Ref. "Design of Concrete Structure" by Winter & Nelson
PU = 18.5k M„ = 3.0k"'
e= 0.16" qPn = 121 k' OK
Armin = 0.002-% = .002(4 x 12) = 0.0961" 2A okav
Use4x4-W4xW4WWF
Check side wall for it's contribution
Embeds = 3.7k
Compression Side: Ry = 14.Ok -- Assume it gets distributed for
width = to height.
w = 11.1' APPROVED BY
minimum of 3 embed platesa
.•. REMBED = 14.0/5 = ± 2.8k
21 March 10, 1998
41
5. LATERAL (cont'd)
c. End Wall (cont'd)
CHECK SIDE WALL CONTRIBUTION
Po = 495' x 0.9
= 466"1
Pup = 27 (12) / 2 =162' x 1.3
= 2104"
Comp. Side
P = 446 x 4 + 2800 - 210 x 4 = 37440
Tension Side
P„ = (446 - 210)4 - 2800 = -1856*
Wu = (51)1.3 = 66 P'
MU = 6.6(121 / 12)2 / 8 = 839` x 12 =
10.1 k"
P = 10.1 =
1 = .00405
0.9(60)(2)2(12)(1-8.85p) 256(1-8.85p)
As = .00405(2)12 = 0.097in2
A.Pmv = 0.12(WWF) okay
AS = 1.86 = .01
.9(60)(4)
ASTOT = 0.107in2 < ASPmv okaX
Check for P-D Effects
cQ PC => Ec = 2675s' Ig = 64in4l Bd = 0 1 = 68480'"1
Pc = Tr2 6( 8480) = 46.2' Sb = 1 = 1.09
1212 (1 - 2_ 8
.7(46.2)
Ma = 58.7 (121/12)2/8 fr = 7.5 SQRT(4000) = 474 P"
Ma = 746#'r
Mcr=47443=15.17'`•r
2 12
Ma < Mcr = 1264'
.•. cracking doesn't occur
Defl.=.(0.746)10.082(180) = 0.08"
2675 (64)
AFFRO`Vet) BY 0
6. AL;,
22 March 10, 1998
�5. LATERAL (cont'd)
c. End Wall (cont'd)
Check Side Wall Contribution (cont'dl
P-Delta Effect:
i -
` Mu = 20.4 + 0.08 (2.8)1.09 = 20.6'"
P„ = 2.8' e' = 7.36"
qP" = 0.87(.85)4(21)2[-.01(17.64)+1-7.36/2+SQRT{(1-7.36/2)2
+2(7.36)(.01)17.64}]
2
` = 6.93" > P„ = 2.8" OK
Side Wall is Okay as Designed
For Component Wind Pressure
4. SIDE WALL
Okay for lateral force by comparison to end wall and a small area to pick up wind
load.
i
APPFtOVEO BY �Q
��. , It, � q
L• � 1`
23 March 10, 1998
6. FOUNDATIONS
a. DETERMINE LOAD COMBINATIONS
FOR CONCRETE DESIGN
Per ACI 318
U=1AD+1.7L
U = 0.75 (1.4D+1.7L+1.7W) } with wind
U = 0.9 D + 1.3 W
U = 0.75 (1.4D+1.7L+1.87E) } with seismic
U = 0.9D +.1.43E
b. DETERMINE LOAD COMBINATIONS
i FOR BUILDINGS & OTHER STRUCTURES
DEAD PLUS FLOOR LIVE PLUS ROOF LIVE (OR SNOW)
DEAD PLUS FLOOR LIVE PLUS WIND (OR SEISMIC)
1.4
DEAD PLUS FLOOR LIVE PLUS WIND PLUS 1/2 SNOW
DEAD PLUS FLOOR LIVE PLUS SNOW PLUS 1/2 WIND
DEAD PLUS FLOOR LIVE PLUS SNOW PLUS SEISMIC
1.4
" Snow loads 30pf or less are not req'd. to be combined with seismic.
TMaX = .625
Ab = 8x8 = 64
p = -1 AFFROVI ®��
Pmin = 1.0:v
SEISMIC = pEh + E„ Where p = 1.0, E„ = 0 ' a. ~' ��'�•
Per BOCA
DEAD PLUS FLOOR LIVE PLUS ROOF LIVE (OR SNOW)
DEAD PLUS WIND (OR SEISMIC)
DEAD PLUS FLOOR LIVE PLUS ROOF LIVE (OR SNOW) PLUS WIND (OR
SEISMIC)
Seismic = + 1.0 Qe ± 0.5 AD
PER SBC
DEAD PLUS FLOOR LIVE PLUS ROOF LIVE (OR SNOW)
DEAD PLUS FLOOR LIVE PLUS WIND (OR SEISMIC)
DEAD PLUS FLOOR LIVE PLUS WIND + 1/2 SNOW
DEAD PLUS FLOOR LIVE PLUS 1/2 WIND + SNOW
DEAD PLUS FLOOR LIVE PLUS SNOW + SEISMIC
UBC Seismic of 0.3W divided by 1.4 is approximately equal to SBC & BOCA
Seismic of 0.22W
Therefore use UBC load combination for seismic loads.
24 March 10, 1998
6. FOUNDATIONS (cont'd)
c. DETERMINE SNOW LOADS FOR FLAT ROOF
PER UBC
(A) Pf = Ce I P9 (Contiguous U.S.)
Ce=0.9 Dense Forest
-- I =1.10 All others
j'
assume smallest P. = 5Psf
PfMIN = 1.2(1.10)5 P'
= 6.0P51 < 20PI min. roof live load
PfMIN = 20Psf
PfDESIGN = 50Psf
APPROVED By
j JUL 0 9 1990
Y [IN�
25 March 10; 1998
6. FOUNDATIONS (cont'd)
d. load distribution
DETERMINE DISTRIBUTION OF LOADS TO FOUNDATION
DEAD LOAD (SELF WT)
(1) Roof (4.75"/12")W(118#/CF) = 23.35W
2
(2) Roof (4.75"/l2")W(118#/CF) = 7.78W
6
(3) Walls (4/12)H (118#/CF) = 39.31-1
(4) (from floor design) 42.6PSF (—W) = 21.3W
2
.•. FOR ANY SHELTER WIDTH WL
FTG.(A) WoL = 23.35W + 21.3W + 39.31-1
= 44.65°`fl2 W + 39.31-1 <— Unfactored
FTG.(B) WoL = 7.78W + 39.3H <—Unfactored
LIVE LOAD (SNOW)
FTG.(A) WSL = W PSL <— Unfactored
2
FTG•(B) WSL = VV PSL <— Unfactored
6
LIVE LOAD (INTERIOR FLR)
FTG.(A) WLL = W PLL <— Unfactored
2
FTG.(B) WLL = 0
DETERMINE DEAD LOAD FOR EACH WIDTH
81-4" W = 44.65(8.33') + 39.31-1
= 371.Vx + 39.3H
10'-4" W = 461.2" + 39.31-1
12'-0" W = 536' + 39.31-1
4PPROVED BV
jut 0 S. �g9
26 March 10, 1998
6. FOUNDATIONS (cont'M
d. load distribution (cont'd)
DETERMINE LIVE LOAD FOR EACH WIDTH
UNIFORM LIVE LOAD 50 psf
I_
81-411 WLL = 8.33'(50")
2
= 208.25�'ft
10'-4". WLL = 258.25*'ft
12'-0" WLL = 300.0am
e
Multiply WLL by 2.8 for 140PSF LIVE LOAD
WLL by 4.0 for 20OPSF LIVE LOAD
DETERMINE DEAD LOAD FOR EACH HEIGHT
9'-5" W = 44.65W + 39.3 (9.42')
= 44.65W + 370.2#1"
10'-5" W = 44.65W + 409.5"
11'-1" W = 44.65W + 435.6"
APPROVED
e v
27 March 10, 1998
6. FOUNDATIONS (cont'dj
e. DETERMINE SHELTER DEAD LOAD DISTRIBUTED TO FTG "A"
FOR EACH WIDTH & HT.
Width 8'-4"
HT 9-15" WpL = 371.9#"ft + 370.2" = 742.11
10'-5" Wog = 371.9#"t + 409.5" = 780.54m
11'-1" Wog = 371.99m + 4350m = 807.501ft
Width 10'-4"
HT 9'-5" WpL = 461.2*R + 370.2" ft = 831.4"
10'-5" WOL = 461.2#m + 409.5*m = 870.7"
11'-1" WpL = 461.2#"t + 435.E*m = 896.8111
Width 12'-0"
HT 9'-5" Wog = 536#`ft + 370.2" = 906.2#"t
10'-5" WpL = 536" + 409.5" = 945.5"
11'-1" WDL = 536" + 4350m = 971.6m
TABLE 1
APPROVED By
F �IlkFill
�998
,4 INC.
28 March 10, 1998
a
6. FOUNDATIONS (cont'dj
f. CREATE A MATRIX FOR FLOOR LL FOR ALL WIDTHS AND HEIGHTS
140Psf 200 Psf
WIDTH/HEIGHT LIVE LOAD LIVE LOAD
W 12'-0" 840 pif 1200 pif
W 10'-4" 723.1 pif 1033 pif
W 81-4" 583.1 pif 833 plf
TABLE 2
g. DETERMINE SNOW LOAD ON FTG "A" FOR EACH WIDTH
WSJ = 50W
2
Pf Wsl(W=8.331 WSL(W=10.33') WSL(W=12'-0" )
50 208.3pif 258.3plf 300.Opif
TABLE3
APPROVEO By
4,
29 March 10, 1998
6. FOUNDATIONS (cont'd)
h. wind distribution
DISTRIBUTION OF LOADS TO FOOTING
WIND LOAD - COUPLE METHOD (FOR 11'-1"HT)
= (11.1' / 2)
= 5.55 PWIND
_ (11.1'/2 + 0.5'/2)
5.80 PWiND
5.55 PWiND (L OR W)
5.80 PWiND (L OR W)
FTG(A) Wwl_ = [5.55PWND L(13.6') + 5.80 PWId L(2.5')]/(WxL)
= PWiND(89.98)M
FTG(B) W,M = [5.55 PWiND W(13.6') + 5.80 PWIND W(2.5')]/(WxL)
PWIND(89.98)/L
30 March 10, 1998
6. FOUNDTIONS (cont'd)
h. wind distribution fcont'd)
SECTION MODULUS METHOD
q = M
S
SW = (L+1) (W+1)3-(L-1)f W-1)3
6(W+1)
'I
SL _ (L+1)3(W+1)-(L-1)3(W-1)
6(L+1)
WIND LOAD ON LONG SIDE
PWIND
0
N
q = M = PWIND(L)78.88 FT2
SW f(L+1)(W+1)3-(L-1)(W-1) 1
6(W+1)
WIND LOAD ON SHORT SIDE
q = M = PwIND(W)78.88 FT2
SL [(L+1)3(W+1)-(L-1)3(W-1)1
6(L+1)
W+i,
H
[ASSUME BOX ACTS
AS SHORT COLUMN]
M = (PWIND(L)11.6)(13.672)
= PWIND(L)78.88 FT2
M = (PWIND(W)11.6)(13.6)
2
PWIND
in
0
PWIND(W)78.88 ft2
APPROVED 8Y
Z, 4
Is o
31 March 10, 1998
6. FOUNDATIONS (cont'd)
h. wind distribution (cont'd)
COMPARING METHODS
FOR FTG (A)
Assume 10' width x 30' length
Assume 100 PSF wind pressure
Assume 11.1' height
COUPLE METHOD:
W,,,L = 100PSF(89.98) = 899.80
10.0'
SECTION MODULUS METHOD:
WDL = 100PSF(30.0')78.88 FTZ
f (31.0')(11.0')3-(29.0,)(9.0')31
6(11.0')
776.3 psf
(FOR 1'-0" FTG WIDTH)
THEREFORE, USE COUPLE METHOD TO FACILITATE CALCULATIONS
SINCE ONLY TWO UNKNOWNS VS THREE AND MORE CONSERVATIVE
USING COUPLE METHOD
DETERMINE LOADS TO FTG FOR 9'-5" HIGH SHELTER & 10'-5" HIGH
SHELTER
H = 9.43' ABOVE FTG
i (A) WvvL = EWINd(9.42'/2)L(11.92')+(9.42'/2+0.5'/2)L(2.51)1
(W) (L)
= PWIN 68.54
W
(B) WWL = EWIN QU-4-
L
H = 10.43' ABOVE FTG
(A) WWL = P,vINDF(10.42/2)L(12.92')+(10.42/2+0.5'/2)L(2.5'),1
(L) (W)
EWIN 8D ` 0.96)
APPROVED By
W 000 �u L
(B) WWL = EWIN 80.96 �, , ` . •.
L
H = 11.08' ABOVE FTG
(A) WWL = PWIND(89.98)/W (calculated previously)
(B) WWL = PWIND(89.98)/L (calculated previously)
-- 32 March 10, 1998
6. FOUNDATIONS (cont'dd)
h. wind distribution (conM
WIND PRESSURES FOR 120mph WIND SPEED
WALLS:
P = 51 psf or P = 35 psf
ROOF:
U = 27psf or P = 41 psf
51 psf lateral & 27psf uplift condition controls.
DETERMINE LOAD ON FOOTING "A" FROM WIND
LOAD FOR ALL WIDTHS & HEIGHTS
For H = 9.42' WvvL = ± 51 psf(68.541 - 27psf W
W 2
For H = 10.42' WvvL = ± 51 psf(80.961 - 27psf W
W 2
For H = 11.1' WvvL = + 51 osf(89.981- 27psf W
W 2
SHELTER
WIDTH WWL(H=9.42') WWL(H=10.42')
8'-4" +307/-532plf +383/-608pif
101-4" +199/-478plf +260/-539p[f
12'-0" +129/-458plf +182/-506plf
TABLE 4
WWL(H=11.1')
+438/-663plf
+305/-583plf
+220/-544p[f
APPROVED BY
j s
33 March 10, 1998
-'I 6. FOUNDATIONS (cont'd)
1. seismic
PER UBC
I
DETERMINE LOAD DISTRIBUTION TO FTG "A"
V = 2.5C_I W
� R
= 1.0
R = 4.5
V = 2.5C 1( 0) W = 0.556C.W
4.5
[8'-4" WIDE X 1 V-1" HIGH X 8'-4" LONG]
WpL = Roof + Walls
= [49.7psf(8.33')2 + 39.3psf(4))8.33') 11.1'
2
= 10,7W
.ZONE 4:
Ca = 0.54 (see load calcuations)
V = 0.556(0.54)(10716' = 3217#
WseisMic = 3217* (13.6) 1 = 631plf
8.33 8.33
[10'-4" WIDE X 1 T-1" HIGH X 10'-4" LONG]
Wog = 49.7psf(10.331)2 + 39.3psf(4)(11.1'/2)(10.33')
= 14,316"
ZONE 4:
V = 0.556(0.54)(1431 e) = 429V
is
WseisMic = 4298# (13.6) 1 = 548
10.33 10.33
APPROVED BY
ITJUL
41NCO
34 March 10, 1998
6. FOUNDATIONS (cont'd)
i. seismic (cont'd)
Per UBC
[12'-0" WIDE X 11'-1" HIGH X 12'-4" LONG]
Wog = 49.7psf(12.0')(12.33)
,I
+ 39.3psf(2)(1 1. 1'12)[12.0'+ 12.33]
= 17,96r
ZONE 4:
V = 0.556(0.59)(17967) = 5394#
WSEISMic = 5394 x 13.6 x 1112.33 = 496*ft
12 -
DETERMINE FACTORS TO MULTIPLY WITH FOR OTHER HEIGHTS -
FOR UBC
8'-4" WIDTH
FOR 9'-5" HEIGHT
W = 9616* 9616 = 0.897
10716
(9.42'+2.5) 1 = 0.172
8.33 8.33
i
0.172 = 0.878
0.196
FACTOR = 0.897(0.878) = 0.788
FOR 10'-5" HEIGHT
FACTOR = 0.91
APPFIOVEO By.
+3
INCw
35 March 10, 1998
6. FOUNDATIONS (cont'd)
i. seismic (cont'd)
Per UBC (cont'd)
10'-4" WIDTH
FOR 9'-5" HEIGHT FACTOR = 0.793
10'-5" HEIGHT FACTOR = 0.913
12'-0" WIDTH
FOR 9'-5" HEIGHT FACTOR = 0.798
10'-5" HEIGHT FACTOR = 0.916
UBC
8'-4" WIDTH 10'-4" WIDTH 12'-0" WIDTH
ZONE 9'-5" 10'-5" 11'-1" 9'-5" 10'-5" 11'-1" 9'-5" 10'-5" 11'-1"
4 497 574 631 435 500 548 396 454 496
TABLE 5a
* Footing load (±) for DL of shelter for additional load due
to floor live load and snow see following pages
36 March 10, 1998
6. FOUNDATIONS (cont'd)
1
i. seismic
PER BOCA
DETERMINE LOAD DISTRIBUTION TO FTG "A"
V = 2.5A_ W
R
R = 4.5 V = 2.5A� W = 0.556Aa W
4.5
[8'-4" WIDE X 11'-1" HIGH X 8'-4" LONG]
Wog = Roof + Walls
= [49.7psf(8.33')2 + 39.3psf(4)(8.33') 11.1'
2
= 10,71e
ZONE 4:
A. = 0.4
V = 0.556(0.4)(107W) = 2383#
WseisMic = 2383# (13.6) 1 = 467plf
8.33 8.33
[10'-4" WIDE X 11'-1" HIGH X 10'-4" LONG]
Wog = 49.7psf(10.33')2 + 39.3psf(4)(1 1. 1'/2)(10.33')
= 14,316*
ZONE 4:
V = 0.556(0.4)(14316*) = 3184"
APPROVED BY
WseisMic = 318e (13.6) 1 = 405"
10.33 10.33JUL
[12'-0" WIDE X 1 T-1" HIGH X 12'-4" LONG] INC.
Wog = 49.7psf(12.0')(12.33')
+ 39.3psf(2)(1 1.1'/2)[12.0'+ 12.33']
17, 967"
ZONE 4:
V = -0.556(0.4)(17967) = 3996#
WSEISMic = 3996 x 13.6 x 1 /12.33 = 367#/ft
12
See UBC Seismic calculations for factors for shelters of other heights.
37 March 10, 1998
6. FOUNDATIONS (cont'd
i. seismic (ont'd)
Per BOCA (cont'd)
i
BOCA
8'-4" WIDTH 10'-4" WIDTH 12'-0" WIDTH
ZONE 9'-5" 10'-5" 11'-1 9'-5" 10'-5" 11'-1" 9'-5" 10'-5" 11'-1"
4 368 425 467 320 369 405 292 334 367
TABLE 5b
* Footing load W for DL of shelter for additional load due
to floor live load and snow see following pages
Per UBC
TO DETERMINE FOOTING LOADS (±) DUE TO ADDITION OF FLOOR LIVE
LOAD
1. DETERMINING SHEAR AT FLOOR LEVEL DUE TO SEISMIC LATERAL
MOVEMENT PER 50Ps' OF FLOOR LIVE LOAD
2. DETERMINE HEIGHTMIDTH FACTORS
V = FLOOR LIVE (WIDTH) 2.5C,
R
UBC
DETERMINE FOOTING LOADS FOR FLOOR LIVE LOAD IN SEISMIC EVENT -
50PSF INCREMENTS. (25% OF LOAD SHALL BE CONSIDERED.)
8'-4" WIDTH
(ZONE 4) V = 1(50PSf)(8.33)(0.556)(0.54)
4
10'-4" WIDTH
(ZONE 4) V = 1.24 (31.26) = 38.76#KvsoP'
12'-0" WIDTH
(ZONE 4) V = 1.44 (31.26) = 45.02"P'
= 31.26"Pl
APPROVED
IN Q
38 March 10, 1998
6. FOUNDATIONS (cont'd
ti
i. seismic (cont'd)
HEIGHT/WIDTH FACTORS
Per UBC
8'-4" 2.5 / 8.33 = 0.30
10'-4" 2.5 / 10.33 = 0.24
12'-0" 2.5 / 12.0 = 0.21
WSEISMic SL = [V x HEIGHT / WIDTH FACTOR](LL / 50psD
8'-4" WIDTH
140 psf
ZONE 9'-5" 10'-5" 11'-1"
4 26 26 26
10'-4" WIDTH
140 psf
ZONE 9'-5" 10'-5" 11'-1"
4 26 26 26
12'-0" WIDTH
140 psf
ZONE 9'-5" 10'-5" 11'-1"
4 26 26 26
TABLE6a
200 psf
ZONE 9'-5" 10'-5"
4 38 38 38
200 psf
ZONE 9'-5" 10'-5"
4 38 38 38
200 psf
ZONE 9'-5" 10'-5"
4 38 38 38
W
V
FLOOR LIVE
RIF
AppFtOVED By
JUL 0 as
39
March 10, 1998
6. FOUNDATIONS (cont'dl
�I
i. seismic (cont'd)
Per BOCA
TO DETERMINE FOOTING LOADS (±) DUE TO ADDITION OF FLOOR LIVE
LOAD.
1. DETERMINING SHEAR AT FLOOR LEVEL DUE TO SEISMIC LATERAL
MOVEMENT PER 50Ps' OF FLOOR LIVE LOAD
2. DETERMINE HEIGHT/WIDTH FACTORS
V = FLOOR LIVE (WIDTH) 2.5A_
R
BOCA
DETERMINE FOOTING LOADS FOR FLOOR LIVE LOAD IN SEISMIC EVENT -
50P' INCREMENTS. (25% OF LOAD SHALL BE CONSIDERED.)
8'-4" WIDTH
(ZONE 4) V = 1(50Psf)(8.33')(0.556)(0.40) = 23.16 M50psr
4
10'-4" WIDTH
(ZONE 4) V = 1.24 (23.16) = 28.72#rcusoPsr
12'-0" WIDTH
(ZONE 4) V = 1.44 (23.16) = 33.35#ffueoPsr
W
V
FLOOR LIVE
APPROVED. E�Y
J u9
N4Q
40
March 10, 1998
1r
6. FOUNDATIONS (cont'dj
i. seismic (cont'd)
HEIGHT/WIDTH FACTORS
Per BOCA
WseisMICSL = [V x HEIGHT / WIDTH FACTOR](LL / 50psf
8'-4" WIDTH
140 psf
200 psf
ZONE
9'-5"
10'-5"
11'-1"
ZONE
9'-5"
10'-5"
11'-1"
4
19
19
19
4
27
27
27
10'-4"
WIDTH
140 psf
200 psf
ZONE
9'-5"
10'-5"
11'-1"
ZONE
9'-5"
10'-5"
11'-1"
4
19
19
19
4
27
27
27
12'-0"
WIDTH
140 psf
200 psf
ZONE
9'-5"
10'-5"
11'-1"
ZONE
9'-5"
10'-5"
lit-ill4
19
19
19--
4-
27 -
27
27
TABLE6b
APPROVED a*
Iv
ENS.
2
41 March 10, 1998
6. FOUNDATIONS (cont'd)
i. seismic (cont'd)
Per UBC
TO DETERMINE FOOTING LOADS (±) DUE TO ADDITION OF SNOW ON
ROOF
1. DETERMINING SHEAR AT ROOF LEVEL DUE TO SEISMIC LATERAL
MOVEMENT PER 10Ps'OF SNOW ON ROOF
2. DETERMINE HEIGHT/WIDTH FACTORS
V = SNOW (WIDTH) 2.5C
R
UBC
DETERMINE FOOTING LOADS FOR SNOW LOAD IN SEISMIC EVENT -
10PSF INCREMENTS.
8'-4" WIDTH
(ZONE 4) V = 10P'(8.33')(0.556)(0.54) = 25.01#rc 'Psr
10'-4" WIDTH
(ZONE 4) V = 1.24 (25.01) = 31.01#rr 'Pst
12'-0" WIDTH
(ZONE 4) V = 1.44 (25.01) = 36.03#rr 'P"
W
SNOW
42
March 10, 1998
6. FOUNDATIONS (cont'd
i. seismic ,cont'd)
HEIGHT/WIDTH FACTORS
Per UBC
8'-4" x 9'-5"
(9.42 + 2.5) / 8.33
= 1.43
10'-5"
(10.42 + 2.5) / 8.33
= 1.55
1 l'-l"
(11.1 + 2.5) / 8.33
= 1.63
10'-4" x 9'-5"
(11.92) / 10.33
= 1.15
10'-5"
(12.92) / 10.33
= 1.25
1l'-l"
(13.6) / 10.33
= 1.32
12'-0" x 9'-5"
(11.92) / 12.0
= 0.99
10'-5"
(12.92) / 12.0
= 1.08
1l'-l"
(13.6) / 12.0
= 1.13
WseisMic SL = [V x HEIGHT / WIDTH FACTOR](50 psf/ 10psf)
WIDTH ZONE 9'-5" 10'-5" 11'-1"
81-4" 4 178.88 193.83 203.83
WIDTH ZONE 9'-5" 10'-5" 11'-1"
10'-4" 4 178.31 193.81 204.67
WIDTH ZONE 9'-5" 10'-5" 11'-1"
12'-0" 4 178.35 194.56 203.57
TABLE7a
APPROVED By
'I
INC
43 March 10, 1998
6. FOUNDATIONS (cont'd)
i. seismic (cont'd)
-' Per BOCA
TO DETERMINE FOOTING LOADS (±) DUE TO ADDITION OF SNOW ON
ROOF
1. DETERMINING SHEAR AT FLOOR LEVEL DUE TO SEISMIC LATERAL
I
MOVEMENT PER 10Ps' OF SNOW ON ROOF
2. DETERMINE HEIGHTIWIDTH FACTORS
V = SNOW (WIDTH) 2.5A_
R
BOCA
DETERMINE FOOTING LOADS FOR SNOW LOAD IN SEISMIC EVENT -
1OP5' INCREMENTS.
8'-4" WIDTH
(ZONE 4) V = 10P5'(8.33')(0.556 0.40 = 18.53"HV10PI
10'-4" WIDTH
(ZONE 4) V = 1.24 (18.53) = 22.97""'P"
12'-0" WIDTH
(ZONE 4) V = 1.44 (18.53) = 26.68#/t1 P"
W
SNOW
ti
APPROVED BY
jul- 0 9 1998
INC.
44 March 10, 1998
6. FOUNDATIONS (cont'dj
i. seismic (cont'd)
HEIGHT/WIDTH FACTORS
Per BOCA
8'-4" x 9'-5"
(9.42 + 2.5) / 8.33
= 1.43
10'-5"
(10.42 + 2.5) / 8:33
= 1.55
1 V-1"
(11.1 + 2.5) / 8.33
= 1.63
10'-4" x 9'-5"
(11.92) / 10.33
= 1.15
10'-5"
(12.92) / 10.33
= 1.25
1 V-1"
(13.6) / 10.33
= 1.32
12'-0" x 9'-5"
(11.92) / 12.0
= 0.99
10'-5"
(12.92) / 12.0
= 1.08
11'-1"
(13.6) / 12.0
= 1.13
ti.
WSEISMic SL = [V x HEIGHT / WIDTH FACTOR](50psf / 10psf)
WIDTH ZONE 9'-5" 10'-5" 11'-1"
81-4" 4 132.49 143.61 151.02
WIDTH ZONE 9'-5" 10'-5" 11'-1"
10'-4" 4 132.08 143.56 151:60
WIDTH .ZONE 9'-5" 10'-5" 11'-1"
12'-0" 4 132.07 144.07 150.74
TABLE7b
45 March 10, 1998
6. FOUNDATIONS (cont'd)
k. summary of load tables
The following computer output is the tabulation of the loading combinations and
the associated load to soil. Based on these values, the required width of
4 foundation wall is able to be established. By adding up the required widths, the
proper overall foundation width is available.
APPROVED By
jul, 1998
k, INC
46 March 10, 1998
6. FOUNDATIONS (cont'd)
I. slab on grade foundation
1. Criteria: use slab on grade w/ 8" of washed gravel for foundation.
2. Where frost is a concern extend the washed gravel down to frost depth.
3. Since shelter doesn't have overturning problems, the foundation is the same
as the perimeter beams for the bearing pressures. Provide a turned down
edge to provide proper edge distance for expansion anchors. The turned
down edge width will be the same as the perimeter beam which depends on
the floor loads.
4. Longitudinal Steel:
pmin = 0.0018
AS = 0.0018(10x14) = 0.252 in
USE 2#4 bars
Temp steel in slab:
AS . = 0.0018(6x18) = 0.194 in2/18"
USE #4 @ 18"
APPROVED
1998
47 March 10, 1998
I
7. CONNECTIONS
a. Roof to Side and End Walls
1. Wind Uplift
Pu = 27 psf
roof wt. _ (4.75/12)118 = 46.7 psf
»» Max. load per conn. _ (27 - 46.7)6(4)
no load due to uplift
okay by inspection -- other conditions will control
2. Wind lateral (120 MPH)
Note that lateral loads acting in the short direction will control due to the
fewer number of plates at the roof to endwall connection.
P = 51 psf (See Wind Calculations)
V = 51 x 11.1 x 36 = 5095*
2 2
There are six plates in endwalls, therefore
Vpl = 509511 = 84991P'
6
Seismic Lateral
DL:
Roof (4.75)118(12) = 561 pif
12
Wall L4)118(9.67 / 2)2 = 380ur
12 WE) = 941#r
LL:
Snow 50 psf x 12 Ws = 60r
Wn = 1541 #r
V = 0.556(0.54)WQ6) = 8330'
2
Vpl = 8330 = 1390'
6
Therefore seismic controls
ppROVED BY
JUL qu, �
48
March 10, 1998
7. CONNECTIONS (cont'dj-
a. Roof to Side and End Walls (cont'd)
Re: PCI Design Handbook
Weld "A" V = 139W
IW = 2" (min per PCI)
Tw = 0_5 in = 0.1 (effective throughout)
5
LW = 0.9411 = 0.66" min.
0.3(70ksi)(0.1 ")
Plate "B"
use 3" min. weld
i
0
Shear: 1.1(1.3)(1390) = 1988#
Reaction: 1988 (2.5 in) = 1656#
3 in
APPROVED By
i" (3, 0
49
March 10, 1998
a
7. CONNECTIONS (cont'd)
a. "Roof to Side and End Walls (cont'd)
Anchor: Vah = min 10330# (0.85) (Nelson Stud Design)
. Manual
0.85(800)(0.2in2)(0.85) 4000 psi (PCI)
878091
= min ( 73110 / Controls
Vah = min (8720 - 5800)# (0.85) (Nelson Stud Design)
Manual
0.85(2)(- r)(2.5 in2)(0.85) 4000 psi (PCI)
2482* l
= min ( 1794* / f Controls
2 2 IC = ( (0.85(1998)/2(7311)) + ( ( 0.85(1656)/1794))1/0.85
= 0.74 < 1.0 o.k.
Plate: V = 1390'
Fv = 139W = 890 psi (NEGLIGIBLE)
5 in (5/16 in)
Plate 5/16 x5x5 w/ (2) 1/2" DIA x 2" HAS
APPROVF-0 By
' JUi
50 March 10, 1998
7. CONNECTIONS (cont'd)
a. Roof to Side and End Walls (cont'M
2. lateral (cont'd)
plate "C"
shear: VU = 1.988,
Plate and studs will be adequate by comparison to Plate B.
use Plate 5/16 x3x5 w/ (2) 1/2" DIA x 2" HAS
WELD /'A
1 3
I
lr�
APPROVIED S'
JUL
INC.
51 March 10, 1998
4.
7. CONNECTIONS (cont'd)
b., SIDE WALL TO END WALL
1. WIND SUCTION ON END WALL
Since wall is approx. square, it will act as a 2-way PL.
p = 51psf
1' 8"
5 plates along Ht. of wall
R = 51(10.08)(11.67)/4 = 1500#-
RmAx = 1500 = 3V
5
M noff
I
LD- -A-APPROVED BY
J ot !
WELD "A"
R = . 30V lw--3"(min) fw=300/3 = 100'
Fw = 2.11/in OK
3" Iona weld
52 March 10, 1998
7. CONNECTIONS (cont'd)
b. Side Wall to End Wall (cont'd)
PL "B"
TRY (2)1/2" Dia x 2 HAS. edge dist. = 4"
Pullout
Pc = 0.85(4)(0.85),14000 (3+2x2)(0+2x2) = 5.1 k
IC = 1/.85 [(0.3x1.3)/5.1] = 0.09 < 1.0 OK
PL "C"
Shear
Vu = 0.3 x 1.3 = 0.39k
cpVc = 0.85(800)(0.2) .85 SQRT(4000) = 7.3k
cpV'c = 0.85(12.5)(2.5)" 0.8514000 = 2.26k
3
Cw = l 1 + 3.5(2.5) 1 = 1.34
Ct = 4 1.0
1.3(2.5)
Cc 1.0
cpVc = 2.26(1.34) = 3.0' > V,, = 0.36k
cpVc > V. = 0.36" OK
PL. Thick = 2/3 x 1/2 DIA = 1/3 _ 5/16" PL.
PL "B" & "C" PL 5/16x5x5 W/(2) 1/2"Diax2 HAS
e
APPROVE® OV
00.
t
& .
53 March 10, 1998
7. CONNECTIONS (cont'd)
2. UPLIFT OF BLDG. & SUCTION ON END WALL
Wall suction:
P = 0.7(36.9)(1.06)1.0
= 27.4P"
See Part 1. - Modify Reaction
R = 300(27.4/51) = 161 # x 1.3 = 0.21 k
Uplift:
when uplift tries to occur it will lift the back wall and 1/2 the roof and 1/2 the floor.
Therefore, design wall connections to transfer load to end wall.
Side Wall = 4/12(11.1 x36.3)118 = 15849 *
Roof = 4.75/12(12x36.3)118/2 = 10173
Floor = (17703+2365)/2 = 10034
Misc. = (2681+436x2)/2 = 1777"
37, 833#
Ru = 1.84 K
0.21 K = VU
77.
• O
I
00.
F„c„
�wELD "A"
FE "B"
54 March 10, 1998
7. CONNECTIONS (cont'd)
b. Side Wall to End Wall (cont'd)
2. Uplift of Bldg. & Suction on End Wall (cont'd)
Seismic
V _>
Roof (4.75)118(8.33)36.33 = 14135
12
Wall (4)118(36.33+8.33)11.1(2) = 38997
12
Floor (52)(7.33)(35.33) = 13466
66599#
Snow 50(8.33)(36.3) = 15119
W/o Snow:
V=.0.3W M
4241 10.33 43810
11699 5.17 60484
4040 .33 1333
19979# 10562r
4536 10.33 46854r
152,481 #'
MRES = 66,599(8.33 / 2) = 277,385v > 105,6270' okay
W/ Snow:
MRES = (66,599 + 15,119)(8.33 / 2) = 340,355? > 152,481#r okay
no uplift in connections due to seismic
Wind APPROVED By
PH = 51 psf
�s
Pu = 27psfs
MOT = 51(36.3)(11.1)2 + 27(8.33)2(36.3) = 148053F
2 2
MRES = 66,599(8.33) / 2 = 277,385v > 1.5 MOT
no overturning
Req'd holddown force (F) (subtract out end walls)
4
F = 148,053 - (12)118(8.33)(11.1)2(8.33)/2 = 14,137#
8.33
55 March 10, 1998
7. CONNECTIONS (cont'd)
b. Side Wall to End Wall (cont'd)
5 Connections per side (2 sides)
R/Conn. = 14,13r/(5 x 2) = 1.41 k
1.3
1.84k
WELD "A"
R = 1.41 k V = .16k R' = SQRT[(1.41)2+(.16)2] = 1.4k
Iw = 1.4 x .75 = 0.5" SAY 3" LG. WELD
2.1
PL. B"
1.8e
' �0.21K
Vu, = 0.21 + 1.84 x 2.5 = 1.64k
2 3
Vu2 = 1.84k
(PVC'PER = 0.85(12.5)(2.5)1•5 0.85 ,r4000 = 2.26k
BY
PPF�C3\/E�
A
CW = 1'' z ,
Ce — 1 (PVC'PER — 2.26k �
N� �
_ •
(PVC'PAR 2 (PVC'PER = 4.52k
IC =1 ( 1.64 x .85/2.26) + (1.84 x .85/4.52 ) ) 1/0.85 = 0.59 , 1.0
OK
5 Plates each W/(2) 1/2" DIA bolts
56 March 10, 1998
7. CONNECTIONS (cont'd)
b. Side Wall to End Wall (cont'd)
PL "B" thickness = 2/3 x 1/2" = 1/3 _ 5/16" PL x 5 x 11
PL "C"
1
R„ = 1.84k anchor bolt edge dist. = 4"
V„ = .21 k
' I cpVc = 0.85(0.85) 800(.2) SQRT(4000) = 7.31 k
= Min edge dist. = 7 1/2" - Controls
cpVs = 45000 (0.2) x .85 = 9.0k
cpPc = 0.85(4).85 14000 (3+2x2)(0+2x2) = 5.2
IC = [(1.84/7.31)2 + (.21/5.2)2]1/0.85 = 0.08 < 1.0 OK
IC = [(1.84/7.31x2)5'3 + (.21/(5.2)513] = 0.11 < 1.0 OK
(2) 1/2" Dia Bolts
PL=1/2x2/3 _ 5/16"PL3x5
57
APPROVED By
J� 9 1998
March 10, 1998
7. CONNECTIONS (cont'd)
c. Side Wall to Floor DL & LL Case
L = P
F'L n B„
1. LOADS:
DL: Roof = 4.75112(6)(118) = 2801
2.5(6) = 15
Wall = 4/12(11.1)118 = 436.6
2.5(11.1) = 28
760#f x 4' = 3040# x 1.4 = 4256
LL: Snow = (50.x 6) = 300#r x 4' = 12W x 1.7 = 2040#
424V 6296#
MAX. CONN. SPACING = 4'-0
P = 4240# (6296#)
0,FF)RD''F-D BY
INC
i
March 10, 1998
7. CONNECTIONS (cont'd)
c. Side Wall to Floor
WELD "A"
Fw = 2.1 Grp'
V = 4240*
J Iw = 4.24/2.1 = 2.02"
weld length = 3" min.
i
PL "B"
Vu = 6.3"
j, cpV� _. 0.85(0.85) 800(.2) SQRT(4000)
= 7.31 k
= 0.85(12.5)(7.5)1-5 .85d4000
= 11.7k - controls
CW = 1 + 3
= 1.11
3.5(7.5)
Ct = 4
= 0.41
1.3(7.5)
Cc = 1.0
cpVc = 11.7(1.11)0.41
= 5.32'
1 cpVS = 45000(.2)
= 9.0k
Vu = 6.3" . .
PL 1/2 x 2/3 - 5/16
PL5/16x5x5
_ w/(2) 1/2" Dia studs @ 5.3/6.3 x 48"
= 31-4"
j PL "C"
Vu = 6.3"
1 i qVc = 0.85(0.85)800(0.2) SQRRT(4000)
= 7.31 k
-' = 0.85(12.5)(4)1-5 (.85) d4000
= 4.6' Controls
CW = 1 + 3
= 1.2
3.5(4)
t Ct = 8
0.1.0
1.3(4)
Cc — 1.0
cpVc = 1.2(4.6)
= 5.5'`
L 5x1 1/2 x 5/16 x 0'-5
w/(2)1 /2" Dia x4" HAS
& (1) 1/2" Dia x 2" @ 5.5 x
48" = 3'- 6" Use 3'-4"
6.3
APPROVED BY
11998
JUL 0
59 March 10, 1998
7. CONNECTIONS (cont'd)
c. Side Wall to Floor (cont'd)
2. DL + SNOW + WIND CASE
Note that wind uplift is conservatively neglected
DL + SNOW = 4240" (6296* x .75 = 4722#) = P (Pu)
WTOT = 51 psf
WSW = 51 (0_5) = 19.6 psf
1.3
H = 19.6(11.1)/2 x 4' = 435* x 1.7 x 0.75 = 55511
WELD "A"
V = SQRT[(435)2 + (4240)2] = 4262
FW = 2.1"'
Iw = 4.26/2.1 = 203 x 0.75 = 1.52"
3" of weld length req'd.
APPROVED By
A.- 'li iyV
'�% �
� •ems
60 March 10, 1998
a
7. CONNECTIONS (cont'd)
c. Side Wall to Floor (cont'd)
PL "B"
cpVc = 5.3k (see DL + LL section)
cpPc = (4.33-1.22)(0.85) = 2.64k
_ JJ 2
IC = 1(0.85x(0.56)2 /2(2.64)) + (0.85 x (4.72)/5.3) ) 1/0.85 =
PL 5/16 x5 w/ (2) 1/2" Dia x 0'-2 Studs
PL "C"
Anchor l2)
Vu = 4.72'
4.72 K = P qVc = 5.51 > Vu OK
1 0.56 K _ Anchor 1
u Hu = 0.56'
components V„ = .707(0.56)=0.4k
R„ = .707(0.56)=0.4k
TVA = 0.85(0.85) 12.5(1.41)1-5 SQRT(4000)=956*
�n
N
ro
cpRc = 0.85(0.85)(4)(3.2x2)SQRT(4000)=1170#
Try (1) 1/2" Dia x 0'-2 HAS.
IC = ((0.85x(400)/956 ) Z+ (0.85 x (400)/1170) 21 1/0.85 = 0.25 =1.0 OK
0.68
< 1.0 OK
(1)1/2"Dia x 0'-2 Bolts w/ L 5 x 1 1/2 x 5/16 x 0'-5"
61 March 10, 1998
7. CONNECTIONS (cont'd)
c. Side Wall to Floor (cont'd)
3. DL + WIND CASE
1P
H (THIS FORCE IS
TAKEN THROUGH BEARING)
FOUNDATIONS
LOADS:
Hold down for uplift forces.
MOT = 51 (11.1)(11.1)1/2(36) + 27 (36)(8.33)(8.33)1/2 = 147'`'
DLREs = ROOF (4.75/12)118(36)(8.33) = 14.0
WALL (11.1)(4/12)118(36 + 8.0)2 = 38.4
52.41
MRES = 52.4 (8.33 / 2) = 218'
Hold Down Force @ PL (FHo)
FHo = (147-218)
8.33
Therefore Floor Weight Is Not Required To Holddown The Building
Ju
'996
RN
62
March 10, 1998
7. CONNECTIONS (cont'd),
d. End Wall to Floor
See lateral - end wall design section for load
RYs = RYo = 9.7" x 1.3 x 1.1 = 13.9"
WELD "A"
Vtot = 9.7"
Consider 4 plates active when endwall has door opening.
V/pl = 9.7/4 = 2.42" WELD
FW = 2.1r
Iw = (2.42 / 2.1) x 0.75 = 0.87"
use 3" min weld 13.9K
PLATE "B"
Vu = 13.9/4 = 3.48'
cpVc = 0.85(0.85)800(0.2)SQRT(4000) = 7.31 k
cpVs = 10.33 (0.85) = 8.78k
# Of Anchors = 3.5 / 7.31 = 0.5 - (2) 1/2" Dia x 0'-2 Anchors
Min edge dist. = 7 1/2")
PLATE "C"
Vu = 3.48"
R = 3.48' K73") = 4.64k
cpVc = 7.31 k
cpRc _ (8.72 - 2.87)(0.85) = 5.0k
0.85(2)(Tr)(4 in)Z(0.85) -14000 psi = 4.6k
R // C //
FOUNDATIONS
z z1
IC = ((0.85 x (3.48)/2(7.31)) + ( 0.85 x (4.64)/4.6) / 1/0.85 = 0.92 � 1.0 OK
(2) 1/2" DIA x 0'-4 Anchors
(Min. Edge dist = 7 1/2")
APPROVED BY
JUL G U
INC.
63 March 10, 1998
7. CONNECTIONS (cont'd)
e. Floor to Foundation
Look at 8'-4" wide x 36'-4" long shelter because it will overturn easier
Shelter DL -->
roof - 8.33(36.3)4.75(118) =
14,124
12
side wall - (4/12)118(36.3)(11.1)(2) =
31,697
end wall - (4/12)118(8.3)11.1(2) =
- 7,248
floor - 42.6(8.3)36.3 =
12.835
WT =
65,904'
MRES = 65.90(4.16)x2/3 = 182.8'
Wind
P = 51 psf
MOT = 51 11.1 z (36.3) = 114.0 k'
2
27 (36.3)(8.33)Z/2 = 34.0 k'
148.0 k'
OK
Seismic
W = 14,124 + 31697 + 7248 = 33,596*
2 2
V = 0.556 (0.54)(33,596) = 10.091,
MOT 10.09k. (11.1) = 112.0' (No uplift)
w/50 psf snow
nW = 50 (36.33)8.33 = 15.1 k
V = 0.556 (0.54)(33.6 + 15.1) = 14.6k
MOT = 14.6 (11.1) = 162'
MRES . = 182.8 + 15.1(4.16)2/3 = 224.7' OK
Therefore no overturning
APPROVED By
JUL 0 c(5�
64 March 10, 1998
7. CONNECTIONS (cont'd)
1
e. Floor to Fnd (cont'd)
Lateral Sliding Resistance
Net Wt = 65,904 - 27(36.3x8.33) = 57,740#
Use 3" x 3" brg pads
If spacing = 4'-0 oc : # of pads = (36.3+8.3)2/4 = 23
Wt/Pad = 57,740/23 = 2510 lb
Comp. Stress = 2510/(3x3) = 279 psi < 8000 psi (pad) OK
Fp = 0.7 (0.85)(3 ksi) = 1785 psi (concrete) OK
APPROVED
.65 March 10, 1998
h,
7. CONNECTIONS (cont'd)
e. Floor to Fnd (cont'd)-
Lateral Sliding Resistance (cont'd)
a- Ve = 120 mph: p = 51 psf V = 20,549 lb
Coefficient of friction = 0.2
Vnet = 20,549 - 0.2 (57,740) 9,000 lb
Seismic
V = 0.3(15,100) = 24,300lb.
Vnet = 24,300 - 0.2 (15,100) = 8100"
Plate 3/1 6 x 9 x 9
S = (3/16)Z x 9/6 = 0.0527 in
M = 0.0527(27)4/3 = 1.898'"
V = M/1" = 1898"
# of Plates Req'd = 9000/1898
= 4.74 plates
therefore spacing = 36.3/4.74
= 7.66'
use: 6'-0 min. spacing and a minimum of
(2) plates per side wall
use: Plate 3/16 x 9 x 9 w/ (2)1/2 dia.
exp. bolts @ 6'-0 oc with 3x3 pads
@ V-0 oc for seismic zones 3 & 4
and wind speeds > 95 mph.
<�M
jul
1 k.4 .R 5'
'LPJ v� /
66 March 10, 1998
8. SHELTER TRANSPORT
Analysis & design of shelter for handling & shipping
Determine Panel Weights
End: 8'-4" x 9'-5" [118 (4" )](8.33')(9.42') = 3086"
12
x 10'-5" 39.3(8.33')(10.42') = 3411*
x 11'-1" 39.3(8.33')(11.1') = 3634*
10'-4" x 9'-5" 39.3(10.33')(9.42') = 3824"
x 10'-5" 406(10.42') = 42310
x 11'-1" 406(11.1') = 4507# , APPRC)VF-D BY
12'-0" x 9'-5" 39.3(12.0')(9.42') — 4442#NC
x 10'-5" 471.6(10.42') = 4914* "' e
x 11'-1" 471.6(11.1') = 5235*
Side: 9'-5" ht 39.3(9.42') = 370#r
10'-5" ht 39.3(10.42') = 406"
11'-1" ht 39.3(11.1') = 472#r
67 March 10, 1998
8. SHELTER TRANSPORT (cont'd)
.analysis & design of shelter (cont'd)
Roof: 8'-4" width [118(4_5)](8.33) = 369'
12
10'-4" width 44.25(10.33') = 457'
12'-0" width 44.25(12.0') = 531'
Floor: 8'-4" width 52(8.33') = 4330'
10'-4" width 52(10.33') = 537"
12'-0" width 52(12.0') = 624#r
See attached computer outputs for analysis and design of handling and shipping
stresses.
P,PPROVED By
e10
F%.tce
68 March 10, 1998
8. Shelter Transport (cont'd)
Lifting Plate
load capacity
Design for 8 1/2 ton & 12 ton
fc = 4,000psi (28 day); for handling use fci = 3,000psi
Re: PCI DESIGN HANDBOOK & ACI-349
Handling factor =1.2
8 1/2 ton design
P = 17' assume angle = 70°
P = 17 x 1.2 = 20.4
7.42K
20.4K 20- 21.7 K
70'
rod & clevis:
Use 1"(8 1/2 ton) clevis
Re: M'MASTER'S CATALOG pg 426 (1989)
3/
V = 21.7/2 = 10.85K
M = 21.7 / 2 x (4 - 3 11116) = 1.70K."
2
A = 0.7854"2
1"'dia bar I = 0.049ir%4
S = 0.098"s
'/16„
F„ = 0.22 FU f, = 10.85 / 0.7854 = 13.81 ksi
Fb = 0.75 Fy fb = 1.70 / 0.098 = 17.35ksi
F,, > 13.81 / .22 = 62.8ksi
Fy > 17.35 / .75 = 23.13ksi l`!�9$
Use A572 GR. 50 1 dia rod,�a
69 March 10, 1998
1
8. Shelter Transport cont'd
Lifting Plate (cont'd)
8 1/2 ton design (cont'd)
shear capacity
horizontal shear
classify lifting plate as an insert
V„ = 1.4(7.42) = 10.4K
13 a" 7" 3 a' cpV. _ (0.85)(0.85)4 sgrt(3000)(3 1/2)
(8.75 + 13.75)2 = 24.9K
M
r
cpV, _ > V, therefore OK
vertical shear
r--- FAILURE PLANE
I
AFFROVED By
JUL i
Vu = 20.4(1.4) = 28.6K
shear friction:
A„ = 0.44 + 0.12(7 + 8.5)1/12 = 0.60'"2
cpVn = 0.60(60){(1.4 x 0.85) Sin 45 + Cos 451 = 55.7K
cpV„ = 55.7K > 0.2(3) 7 + 8.5 4 = 52.6K
Sin 45
cpVn = 0.85(52.6) = 44.7K > V,
70
March 10, 1998
8. Shelter Transport cont'd
Lifting Plate (cont'd)
8 1 /2 ton design (cont'd)
try shear friction:
V„ = A„ fy u
A„ = 2(0.31) + (0.44) + 0.12(18.5) = 1.25
12
fy = 60ksi
u = 1.4(.85) =1.19
V„ = 1.25(60)11.19 (Sin 45) + 803.451 = 116"
> Vn = 0.2(3) (5.5 +5.5 + 18.5)4 = 81.5"
sin 45
cpV„ = 0.85(81.5) = 69.2" > V„ = 28.6" OK
71
APPROVED BY
JUL
March 10, 1998
8. Shelter Transport (cont'd)
Lifting Plate (cont'd)
8 1 /2 ton (cont'd)
bearing pressure
vertical P = 20.4"
fc = 3,000psi Fp = 0.7(0.85 x 3,000 x A,) / 1.4 = 1.28 Al
AREQ = 20.4 / 1.28 = 15.9in2
APRov = 3 7/8 x 4 3/4 = 18.4in2 > AREQ OK
check plate
P = 17x1.2 = 20.4"
; = 20.4 / 18.4 = 1.11 ksi
t = 0.61" Use 5/8" plate
horizontal
P =
7.4 x 1.2
= 8.9"
AREQ =
P / 1.28
= 7in2
APRov =
1 1/8(12)2
= 2712 OK
fp =
8.9 / 27
= 0.33ksi
M =
0.33(1.125)2 / 2
= 0.21 ""r
S =
0.0077in3r
t =
0.22"
.•. use 3/8 plate
T = R b2
t2
T = 0.56( .11)(412 = 27ksi
t2
APPROVED By
JUL
72
March 10, 1998
8. Shelter Transport (cont'd)
Lifting Plate (cont'd)
8 1/2 ton (cont'd)
welds
vertical
- 1" dia bar to side_plate:
j P = 21.7/2 = 10.85'
circum. 1" dia bar = 3.14"
fw = 10.85 / 3.14 = 3.451
1 /4" fillet
side plate to top plate:
P = 10.2"
w = 3 1/2"
w = 2.9w"
1/4" fillet weld
horizontal
side plate to back plate:
P = 7.42/2 = 3.71"
Iw = 12
fw = 0.31 Kr
3/16" fillet
73
March 10, 1998
s
8. Shelter Transport (cont'd)
Lifting Plate (cont'd)
12 ton
10.5K
P = 24K —i
P = 24 x 1.2 = 28.8K 30.6K
28.8K 20' .
rod & clevis
use 1 1/4" shackle (12 ton)
Re: M°MASTER CATALOG pg 426 (1989)
5 �/4 V = 30.6K / 2 =
,�— M = 15.3(4.625 - 4.5)(1/2) _
1 1/4" dia pin
A = 1.227in2
[:Up I = 0.1198'n4
S = 0.1918in3
f„ = 15.3 / 1.227 = 12.5ksi
fb = 0.96 / 0.1918 = 4.99ksi
Use 1 1/4" dia rod. A572. GR. 50 steel
F„ = 65(.22) = 14.3ksi V = 17.5K
Fb = 50(.75) = 37.5ksi M = 7.19'
APPROVED BY
ra I N
15.3K
0.96K"
74 March 10, 1998
8. Shelter Transport (cont'd)
Lift Plate (cont'd)
12 ton (cont'd)
horizontal
V„ = 10.5x1.4 = 14.71
cpVc = 24.9' > V„ OK
vertical
V„ = 28.8K x 1.4 = 40.3K
(pVn = 44.7K > V„ OK
bearing pressure
vertical
P = 28.8
A = 28.8 / 1.28 =
22.5'n2
APROx = 3 7/8 x 5 7/8 =
22.8'n2
fP = 28.8 / 22.8 =
1.27ksi
plate:
M = 1.27(0.56)(4.625)2 =
t2
27ksi t = 0.75"
horizontal
P = 10.5K
AREQ = 10.5 / 1.28 = 8.2in2 < APROV = 271n2
fP = 10.5 / 27 = 0.39ksi
M = 0.39(1.125)2 / 2 = 0.247Kr
S = 0.091 in3
t = 0.23"
Use 3/8" plate
Use 3/4" plate
APPROVED BY
, LI! 199
75 March 10, 1998
8. Shelter Transport (cont'd)
lift Plate (cont'd)
12 ton (cont'd)
welds
vertical
1 1/4" dia bar:
P = 30.6K / 2 = 15.3K
circum. = 3.927" = Iw
fH, = 3.9Kr
5/16" fillet
side plate to top plate:
P = 14.4K
lw = 3.5"
fW = 4.1 KP
5/16" fillet
horizontal
side plate to back plate:
P = 10.5K / 2 = 5.25K
IW = 12
fW = 0.44'
3/16" fillet
4PPIROVF-t) By
JUL 14��
76 March 10, 199P
9. Fire Ratina
UBC requires 3.8" thick sand - lightweight concrete for a 2 hour fire rating.
The shelter has a 4" thick walls and roof. Therefore the 2 hour rating is provided in the roof
and wall members.
APPROVED VED BY
"A Jul i►99
77 March 10, 1998
10. Thermal Efficiency
Wall
1" thick insulation
outside air film
4" sand-It.wt. conc 0.19x4
1" foam board insulation
3/4" fiberglass faced plywood
inside air film
1 1/2" thick insulation
outside air film
4" sand-It.wt. conc 0.19x4
1 1/2" foam board insulation
3/4" fiberglass faced plywood
inside air film
2" thick insulation
outside air film
4" sand-It.wt. conc 0.19x4
2" foam board insulation
3/4" fiberglass faced plywood
inside air film
2 1/2" thick insulation
outside air film
4" sand-It.wt. conc 0.19x4
2 1/2" foam board insulation
3/4" fiberglass faced plywood
inside air film
3" thick insulation
outside air film
4" sand-It.wt. conc 0.19x4
3" foam board insulation
3/4" fiberglass faced plywood
inside air film
Roof
outside air film
4" sand-It.wt. conc. 0.19x4
4" foam board insulation
3/4" fiberglass faced plywood
inside air film
= 0.17
= 0.76
= 5.0
= 0.94
= 0.68
R = 7.55
U = 1/R = 0.132
= 0.17
= 0.76
= 7.5
= 0.94
= 0.68
R = 10.05
U = 1/R=0.100
= 0.17
= 0.76
= 10.0
= 0.94
= 0.68
R = 12.55
U = 1 /R = 0.080
= 0.17
= 0.76
= 12.5
= 0.94
= 0.68
R = 15.05
U = 1 /R = 0.066
= 0.17
= 0.76
= 15.0
= 0.94
= 0.68
R = 17.55
U = 1 /R = 0.057
= 0.17
= 0.76
= 20.0
= 0.94
= 0.68
R = 22.55
U = 1 /R = 0.044
AppROVED BY
a
78
March 10, 1998
11. Wall Openings
1. Opening Sizes
�Door: T-0" x T-0"
T-6" x T-0"
4'-0" x T-0"
6'-0" x T-0"
AC Window Unit: 18"high x 28"wide
HVAC: case supply return
space betw. opn'as
1 8 x 20 12 x 20
20
.2 8x28 14x28
18
3 10x30 16x30
30
Wave Guide Plate:
4 x 12 -17"high x 20 3/4"wide
4 x 8 - 11 "high x 20 3/4"wide
4 x 4- 4"high x 20 3/4"wide
Exhaust Fan: (one high/one low)
-� 12" sq. -12 1/2" x 12 1/2"
16" sq. -16 1/2" x 16 1/2"
18" sq. -18 1/2" x 18 1/2"
20" sq. - 20 1/2" x 20 1/2"
Louver: (no other openings in combination with louver)
42 1 /2"wide x 50 1 /2"high
w
91
APPROVED ICI
JUL
A^; INC
79 March 10, 1998
11. WALL OPENINGS (cont'd)_
2. Opening Combinations
- Door and AC
- Door and Exhaust
- (2) HVAC and Wave Guide
- Maximum allowable blockout available
- 3. End Wall Sizes
HEIGHT
W 8'-0" 91-019 91-811
8'-0" x x
x
D 9'-0" x x
x
E 11'-8" x x
x
x - indicates the shelter is available in that size
4. Out of plane design for end wall
4.1 w/ door
max. wind load = 51 psf
Ht. = 9'-8"
M/ft. = 51 x (9.67)2 = 596'
8
flexure: door size = 6'-0"
8'-0" wide shelter
M = 596 x 8/2 = 2384v x 1.3 =
3100v
p = 3.1x12 =
1
.9(60)12(2)2(1-8.85 x p)
69.7(1-8.85 x p)
p = 0.01686 As =
0.40 in2/ft
' 10'-0" wide shelter
M = 596 x 10/4 = 149V x 1.3
= 193r
p = 1.937 x 12 =
1
.9(60)12(2)2(1-8.85 x p)
111.5(1-8.85 x pi)F'PF8®VED BY
P =0.00982 As =
0.24 in2/ft
t;
t , JI,�
r,
12'-0" wide shelter
M = 596 x 12/6 = 1192 r x 1.3
= 1550
� $ � °
p = 1.55x12 =
1
.9(60)12(2)2(1-8.85 x p)
139.4(1-8.85 x p)
p = 0.0077 As = 0.18
i
in2/ft
- 80
March 10, 1998
11. WALL OPENINGS (cont'dl
_ shear:
(PVC = (.85)22 x sgrt(4000) x 2(12) = 2190*
-' V/ft = 51(1.3)9.67/2 = 321
V = 321 x 8/2 = 1282' < cpV„ = 21 W okav
4.2 w/ penetrations
max. load:
j 0.75 Pba1 = 0.75(0.85)2(4/60)87(87 + 60) = 0.02138
AS = 0.513 in2/ft
Man = 0.9(60)12(2)2(0.02138)(1-8.85x0.02138) = 44.91
Wall = 44.9 x 8 = 246* t = 51 psf x 4.8'
12 x 1.3 x (9.67)2
Therefore 3/4 of the shelter width may be openings (max).
10
11
12
O �
7
7
8
8
9
' 1
O
4
5
6
4" THICK
1
3.5'
MEM
dam" ,Z
A@2!j
I in4
1
10
40
333
2
10
40
333
3
10
40
333
4
10
40
333
5
10
40
333
6
10
40
333
7
12
48
576
8
12
48
576
9
12
48
576
10
12
48
576
13.9 K
(SEE ENDWALL DESIGN)
D
3.68
4.48
6.46
6.34
3.75.
4.78
3.56
4.22
5.81
7.05
4.53
5.30
2.94
5.41
3.40
6.40
2.13
4.22
2.60
5.30
Ai?PROVF-D BY
kj JUL
See Attached Computer Output For Model of In -Plane loads.
81
March 10, 1998
11. WALL OPENINGS (cont'dl
4 x 10 section:
VU = 6.46'
MU = 7.05k'
cpV. _ (0.85)2(2) {sgrt(4000)}(4)8.5 = 3107"
shear: cpV, = 0.85L0.041(60)(8.5) = 43351
4
qV„ = 3107 + 4335 = 7442" >V„ = 64W
Therefore 4x4 - W4xW4 WWF is okay
flexure: p = 7.05 x 12 = 1
.9(60)4(8.5)2(1-8.85 x p) 184(1-8.85 x p)
p = 0.00517 As = 0.19 in
4 x 12 section:
V„ = 3.40k
Mu = 6.40k'
shear:
cpV, _ (0.85)2(2)1 SQRT(4000)14(10.5) = 3.84 k > V„
Min. Shear Reinf. Is Available
Therefore 4 x 4 - W4 x W4 WNF is okay
flexure:
p = 6.40x12 = 1 -
.9(60)4(10.5)2(1-8.85 x p) 310(1-8.85 x p)
p = 0.00332
As = 0.00332(4)10.5 = 0.14 in
APPROVED BY
JUL !99
82 March 10, 1998
11. WALL OPENINGS (cont'dl
4. Out - of - Plane (cont'd)
4.3 Determine Allowable Amount of Openings W1 Various Wind Speeds
If ratio of concrete to openings = 1 : 1.5
w
6)
Assume:
*5/ft AS = 0.31 inZ/ft —> p = 0.311(2)(12) = 0.01292
(or 244)
Flexure
Mall = 0.9(60)(2)212(0.0129)(1-8.85 x .0129)
= 29.6"
Wall = 29.6 x 8 = 162'
12 x 1.3 (9.67)2
p = 51 psf
162 = 3.17
51
Use 1:2 Ratio Of Concrete To Openings
Shear
qV, = (0.85)2(2)4'4000 (2)(12) = 2193'
WsH = 2.19 x 2 = 348' > Wnex
1.3 9.67
flexure controls
APPROVED BY
# 2 Jul 1998
INC
83
March 10, 1998
11. WALL OPENINGS (cont'd)
4. Out - of - Plane cont'd
4.4 Check in - Plane Loads
Wind
Shear @ top
P (psf) of wall k
51 x 36.3 x 11.1 / 4 x 1.3 = 6.68k
Seismic
—> Use narrowest width since that allows the least concrete available to resist
load.
HEIGHT
roof wt = 8.33(36.3)(4.75)118 = 14.12 9'-0" 10'-0" 10'-8"
12
snow = 50 x 8.33(36.3) = 15.12
wall = (H)/2(4/12)118(36.3)2 = 12.85 14.28 15.23
W = 42.09 43.52 44.47
Zone 4
V = 0.556(0.54)(W/2)(1.1)(1.3) _
9.03k 9.34k 9.54k
84
March 10, 1998
11. WALL OPENINGS (cont'd)
5. In plane design of end wall
5.1 w/ door opening
8'-0" wide x 8'-0" (+12") high end wall:
4'-0" wide door (Re. computer output attached)
flexure:
' I MU = 33.2k' X 12 = 398'"
j p = 398 = 1 = 0.00377
.9(60)4(22.5)2(1-8.85 x p) 275.5(1-8.85 x p)
ATOT = (Asm = 0.38) + (At = 2.00 x 1.3 / 54 x 2) = 0.40in2
#6 (or 244)
- p = 398 = 1 = 0.00723
.9(60)4(16.5)2(1-8.85 x p) 148 (1-8.85 x p) ,
- , ATOT = (As,,, = 0.27) + (At = 5.1 x 1.3 / 54 x 2) = 0.33in2
#6(or 244)
MU = 3.24" x 12 = 38.9k"
p = 38.9 = 1 = 0.00973
.9(60)4(4.5)2(1-8.85 x p) 112(1-8.85 x p)
APPROVED By
Jul ATOT = (As = 0.08) + (At = 2 x 1.3 / 54 x 2) = 0.104in2.,•.:
#5(or 244) -r r
, shear: k� �
member 1 & 2 Vu = 4.561
cpVc _ (.85)SQRT(4000)4(22.5).85 = 4.1'
(A)s) = (bv,)50/fy = 0.0033 s = 4" Av = 0.0133
use 4x4 - W4xW4 WWF for shear reinforcement
member 3 V„ = 10.97'
cpVc = (.85)SQRT(4000)4(16.5)(.85)(2) = 6.0k
cpV,, = 0.85(0.04 (60)(16.5) = 8.42k
4
Ovn = 6 + 8.42 = 14.42k > V„
use 4x4 - W4xW4 WWF for shear reinforcement
41 See Attached Computer Output For Model Of In -Plane Loads
85 March 10, 1998
11. Wall Openings (cont'd)
J 5. In plane design of end wall (cont'dl
5.1 w/ door opening (cont'd)
I;
member 4 V� = 0.38 x 1.3 = 0.5k
cpVt = (0.85)ZSQRT(4000)4(6.5) = 1.19'
j use 44 - W4xW4 WWF for shear reinforcement
8'-0" wide x 9'-0" (+12") high:
_ flexure:
MU = 37.55' x 12 = 451 k"
p = 451 = 1 = 0.00429
9(60)4(22.5)1(1-8.85 x p) 242(1-8.85 x p)
ATOT = (Asm = 0.25) + (At = 4.8 x 1.3 / 54 x 2) = 0.31 in'
#6(or 244)
AREA = 0.00429(4) 22.5 = 0.39"'
shear:
member 1 & 2 V„ = 4.74k
cpV, = (.85)2 SQRT(4000)4(22.5) = 4.1 k
(A,/s)mo = 50b,, /fy = 0.00333 s = 4 A„ = 0.0133
x3
0.0400 in2/ft
use 4x4 - W4xW4 WWF
member 3 V„ = 12.32k
cpV. = (.85)2 (2) {SQRT(4000)}4(28.5) = 10.4k
cpV, = 0.85 0.04 (60)(28.5) = 14.5k
4
cpV,, = 10.4+14.5 = 24.9k>V„
use 4x4 - W4xW4 WWF
8'-0" wide x 9'-8" (+12"): flexure:
MU = 38.91 k' x 12 = 467k"
p = 467 = 1 = 0.00445
.9(60)4(22.5)2(1-8.85 x p) 234(1-8.85 x p)
ATOT =. (As,,,= 0.23) + (At = 4.3 x 1.3 / 54 x 2) = 0.29in2
#6(or 244)
APFRCV _® BY
AREA = 0.00445 (4) 22.5 = 0.40in1
86 March 10, 1998
APPENDIX "A"
APPROVED BY
JUL 0 9 1998
INa
87
February 6, 1990
�l
J PFS Corporation
S
PF= 114 SOUTH WESTGATE DRIVE
GREENSBORO. NORTH CAROLINA 27407 TELEPHONE: (919) 854-994
PROJECT: Bullet Resistance Test
` DATE: February 6, 1990
Reported To: UNR-Rohn
P.O. Box 2000
Peoria, Illinois 62656
i
On January 16, 1990, our representative, Melvin Johnson arrived at Van Doren
Industries., Hays, Kansas and was met by Mr. Richard°Malmberg, General Manager. Mr.
Malmberg and our representative discussed the bullet test procedures to be followed
before conducting the actual tests. The bullet resistance test was to be conducted
on a wall assembly of the Standard Rohn Concrete Shelter.
The tests were designed as closely as possible to meet U.L. 752 weapon and
ammunition specifications. The test procedure followed the U.L. listed
l specifications as shown below.
1) Range - 15 feet or less
2) Sample - Rigidly mounted with corrugated cardboard 18" behind
3) High Powered Rifle - Based on Sample resistance to one shot.
4) Tes.ts Conducted - At room temperature, 22 degrees + 3 degrees C. (71.6 degrees
+ 5 degrees F). There must be no penetration of projectile through test
sample, and no spalling of material on projected site to extent tha agments
imbed in or damage cardboard. APPROVED ��
p 1998
Our re resentative witnessed the test as follows : ::.:'=�:'
Test Panel - Side panel of subject enclosure (�•
Material of Panel - 4" thick concrete - 112 density - 4000 psi composed of expanded
shale light weight coarse aggregate with regular weight sand fines back surface of
panel - 11" foam board and 1/2" plywood fastened to panel.
Bullet Test Weapon/Ammunition - (1) high power rifle 24" barrel (2) Remington
bullets -30-06 rifle -high velocity - 220 grain soft point core Lokt-R 30067.
Test Sample - Material was of commercial construction as noted above. The six test
shots were fired from a distance of 15 feet and in a grid pattern with cardboard
indicator, approximately 1/8" thick, double face, was placed at a distance of 18
inches behind the protected side of the test panel.
Observation - Using the designated rifle and ammunition, shots were placed at
various locations on the test panel to allow penetration of the projectile with
sufficient force to imbed into the panel. It was found in all six samples, that the
projectile was imbedded into the panel approximately 1 1/2 inches. There was no
-, penetration of the wall section by the projectile or of any other material. There
was no debris released into the interior as the result of the impact and there were
88 February 6, 1990
no visible signs on the interior surface of the projectiles' impact.
Conclusion - The above referenced, as modified, Bullet Resistance Test was conducted
using UL 752-tas the criteria. None of the six (6) samples witnessed allowed- the
bullet allowed the bullet to penetrate through the test specimen. The samples
prevented any debris or damage as required.
Thank You.
.Sincerely,
Ken W. Houglan
..General Manager, Southeast Region
cc: Rick Malmberg
Melvin Johnson
Larry Beineke
APPROVED
89 February 6, 1990
REINFORCED
CONCRETE.
FIRE RESI;STANCE
Prepared under the Direction
of the
CRSI Engineering Practice Committee
by
The CRSI Committee on Fire Ratings
J. A. Gustafson, Chairman .. .. . ........... The Ceco Corporation
R. D. Bay . ....... .. . . . . .......... Laclede Steel Company
T. C. Creed .... ..... . . . . .. ....... Florida Steel Corporation
E. G. Opbroek ..... .... . . . . ......... . . . . . . Armco Inc.
F. I. Skog . . .. ..... . . . . . .... .... Cowin & Company, Inc.
D. P. Gustafson, Editor . .. . . . .. . .... . ... . . . . . . . . . . CRSI
And Reviewed by the
CRSI Task Group on Design for Fire Resistance
W. C. Black . . . . . . . . . . . . . . . . . . . Bethlehem Steel Corporation
L. P. Flibotte . . . . . . . . . . . . . . . . . . • . Barker Steel Company, Inc.
B. K. Thoritley, Jr. ..... . . . ... ..... Florida Steel. Corporation
Special Consultant
Armand H. Gustaferro, Consulting Engineer.
The Consulting Engineers Group, Inc.; Glenview, Iilinois
CONCRETE REINFORCING STEEL INSTITUTE
180 NORTH LA SALLE STREET, CHICAGO, ILLINOIS 60601
APPROVED BY - .
CHAPTER 3-FIRE ENDURANCE .DETERMINED
,BY HEAT TRANSMISSION REQUIREMENTS
OF ASTM E119
3.1 Introduction
The fire endurance of concrete floors, roofs, and walls is often governed
by the criteria for temperature rise of the unexposed surface rather than by
structural considerations. The ASTM El19 criteria for temperature rise of the
unexposed surface, referred to as "heat transmission" requirements, limit the
rise to an average of 250°F or a maximum at any one point of 325°F. The
purpose of these criteria is to guard against ignition of combustibles in contact
with the unexposed surface.
Some building codes waive or modify the heat transmission criteria for
certain conditions. For example, the Wisconsin Administrative Code modifies
the criteria in Section Ind 51.042—General Requiremen=
"(5) The heat transmission requirements of A=Vf E119 (25b). with the exception of high
hazard areas penal and health care facilities and warehouses for combustible materials. may
be reduced to one-half (�2) of the hourly rating ►equired by this code. but not less than one
hour.
(a) The fire -resistive rating for structural integrity required by this code shall be maintained
where the heat transmission criteria has been reduced "
For many years other codes have classified concrete floors with slab thick-
nesses of 2, 3, and 4 in., as 2, 3, and 4 hours, respectively. Even though such
requirements are more liberal than those of ASTM E 119, no known fire problems
have resulted.
3-2 Single Course SIabs
Fire ;tests of concrete slabs have shown that the temperature rise of the
unexposed surface is mainly a function of the slab thickness and the type of
aggregate, as shown in Fig. 3.1. The curves in Fig. 3.1 can be expressed approxi-
mately:
R = Ctn .
(3.1)
3-2
s
STRUCTURAL CONCRETES
4
LI 3HTWEIGHt
= 3: SANDED- IGRnYEIGH
w
Z
w AIR-COOL D 9LAG
w
U_ I CAR ONATE
ILICEO S
0' ,
2 3 �•8�� 4 S 6 7
S THICKNESS, IN.
Fig. 3.1 Fire Endurance of Concrete Slabs --Effect of Thickness and Type
of Aggregate —based on Heat Transmission
Where R = the fire endurance in minutes
C= a constant for a given concrete type; values as low as 6 have been
reported for siliceous aggregate concrete and as high as 11 for light-
weight concrete
t = the slab thickness in inches
n = an exponent, usually about 1.8, but values between 1.65 and 2.0
have been reported.
The data. in Fig. 3.1 represent concretes typical of those used in building construc-
tion. The data are based on fire tests of concrete slabs made with a variety of
aggregates as noted. For the normal weight concretes, the maximum aggregate
size was 3/4 in. and the air content was about 6%. For the structural lightweight
concretes, the maximum aggregate size was slightly less than 3/4 in. and the
air content was about 7%. In all cases, fire tests were conducted when the
mid -depth relative humidities of the slabs were 75%.
It was noted above that slab thickness and aggregate type are the main
factors affecting heat transmission. Other factors that affect fire endurance are
moisture. condition, unit weight, air content, and maximum aggregate size.
Within the usual ranges, water -cement ratio, strength, and age have only insignifi-
cant effects.
.3.2.1 Effect :of Moisture
The effect of moisture conditions on the fire endurance as determined by
heat transmission is illustrated in Fig. 3.2, which shows the temperature of
the unexposed surface of three hypothetical specimens during fire tests. All
specimens were made of the same concrete and were the same thickness. Speci-
APPROVED BY