HomeMy WebLinkAboutSUBMITTED PAPERSSummary for ENTIRE B
Project Name: 6186.1
f?,papared by: REI
,Air System Information.,,
System Name__ENTIRE BLOCK LOAD
Ecf spment Class:SPLT AHU
System Type _._—____SZCAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM
zone sensible load
Space CFM
Coincident space loads
Central Cooling Coil Sizing,,Data'
Total coil load_
5.5 Tons
Sensible coil load.�, ____-4.2
Tons
Coil CFM at Aug 1300____—____. __.___2352
CFM
Max possible CFM__T___._______2352
CFM
Design supply temp.
56.0 F
ft2/Ton ------___....-------405.4
BTU/hr/ft2
29.6
Water flow @ 10.0 F rise
Central Heating Coil Sizing Data
Max coil load ____22033
BTU/hr
Coil CFM at Des Htg___ _____
2352 CFM
Max possible CFM --___.___2352
CFM
Water flow @ 20.0 F drop _.—_ -.-_--
gpm
Supply Fan Sizing Data
Actual max CFM at Sep 1400_—_.2352
CFM
Standard CFM_-_-
2351 CFM
Actual max CFM/ft2
1.06 CFM/ft2
Outdoor Ventilation Air Data
Design airflow CFM—_._—_____300
CFM
CFM/ft2--_--___.._---.----_-0.14
CFM/ft2
r
��rrie Hourly Analysis f?rogrm v4.04
Number of Zones
Floor Area 2210.0 ft2
Calculation Months —_Jan to Dec
Sizing Data _:Calculated
Load occurs at
Aug 1300
OA DB / WB-.,
_
_. 89.6 / 77.6 F
Entering DBIWB
77.1 / 65.4 F
Leaving DB / WB
._-57.3 / 56.2 F
Coil ADP
55.1 F
Bypass factor
_
Resulting RH_52
%
Zone T-stat Check
1 of 1 OK
Load occurs at
--Des Htg
5TU/hr/ft2 _
_ .._ _ _.10.0
Ent. DB / Lvg DB
_ 66.1 / 74.8 F
Fan motor BHP
_0:49 BHP
Fan motor kW _
_ kW
Fan static . —
_0.37
1.00 in. wg.
CFM/person
09/28/07
02:15 PM
CFM/person
-- — _ --- -- -- ----- Page 1
. j �
Zone Sizing Summa
flame: 6186.1
IF,a ed bv: REI
Sizing Calculation Information
'one and Space Sizing Method:
Zone CFM Peak zone sensible load Calculation Months Jan to Dec
Space CFM Coincident space loads Sizing Data Calculated
. Zone Sizing Data
ti
Maximum
Design
Minimum
Time
Maximum
Cooling
Air
Air
of
Heating
Sensible
Flow
Flow
Peak
Load
Zone Name
MBH
CFM
CFM
Load
MBH
Zone 1
45.2
2329
2329
Sep 1400
14.5
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system
Q- i —4. —A Airfinwc
Zone Name /
Space Name
Mult
Cooling
Sensible
MBH
Time
of
Load
Air
Flow
CFM
Heating
Load
MBH
Zone 1
Z1-CUST SERVICE
1
11.8
Sep 1400
609
2.9
Z 2 OFFICE
1
5.2
Sep 1400
266
1.8
Z3-PARTS MANAGER
1
2.5
Sep 1400
127
0.3
Z4-BRANCH MANAGER
1
4.7
Sep 1400
242
1.9
Z5-SALES OFFICE
1
2.5
Sep 1400
126
0.3
Z6-HALLWAY
1
4.0
Sep 1400
205
2.3
Z7- BREAK RM
1
4.1
Se 1400
212
1.1
Z8-SERVER RM
1
6.9
Sep 1400
353
1.4
Z9-TOILET
1
1.5
Se 1400
78
1.4
Z10-TOILET/LOCKER
1
2.1
Sep 1400
1101
1.3
09/28/07
02:15 PM
Garrier Hourly Analysis Program v4.04 Page 2
09/28/07
02:15 PM
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1300
COOLING OA DB / WB 89.6 f / 77.6 F
HEATING DATA AT DES HTG
HEATINGOAD13 / WB 43.0 7 / 36.1 7
ZONE LOADS
Details
Sensible
BTU/hr
Latent
BTU/hr
Details
Sensible
BTU/hr
Latent
BTU/hr
Solar Loads
87 ft2
3361
-
87 ft2
-
Wall Transmission
1593 ft2
3712
-
1593 ft2
5791
-
Roof Transmission
2210 ft2
7672
-
2210 ft2
2899
-
Glass Transmission
87 ft2
1221
87 W.
2465
Skylight Transmission
0 ft2
0
-
0 ft2
0
-
Door Transmission
0 ft2
0
-
0 ft2
0
Floor Transmission -
2210 ft2
0
-
2210 ft2
2072
-
Partitions
550 ft2
275
-
550 ft2
0
-
Ceiling
0 ft2
0
-
0 ft2
0
Overhead Lighting
3226 W
11006
-
0
0
-
Task Lighting
0 W
0
-
0
0
-
Electric Equipment
1000 W
3412
-
0
0
People
14
3615
3265
0
0
0
Infiltration
-
0
0
0
0
0
Miscellaneous
-
6750
0
-
0
0
Safety Factor
10% / 10%
4102
327
10%
1323
0
>> Total Zone Loads
45126
3592
14549
0
Zone Conditioning
44086
3592
-
14554
0
Plenum Wall Load
0%
0
-
01
0
-
Plenum Roof Load
0%
0
-
01
0
-
Plenum Lighting Load
0%
0
0
0
Return Fan Load
2352 CFM
0
-
2329 CFIV
0
-
Ventilation Load
300 CFIV
4615
11415
300 CFIV
8589
0
Supply Fan Load
2352 CF1V
1256
2352 CF
-1256
Space Fan Coil Fans
0
+
-
-
0
-
Duct Heat Gain / Loss
1 %
451
-
1 %
145
-
>> Total System Loads
50407
15006
22033
0
Central Cooling Coil
-
50407
15009
-
0
0
Central Heating Coil
-
0
22033
-
Total Conditioning
cnAn'71
15009
22033
0
Key:
Positive values are clg loads
Ne alive values are ht loads
Positive values are htg loads
Negative values are cig loads
Project Name: 6186.1
Mepared by: RE[
M
'Carrier Hourly Analysis Program-v4.04
b
,r
r
9/28/2007 EnergyGauge Summit v3.10 incorporating Florida Energy Code Version - FLA/COM 2004 v2.5
w
Component
Gross Energy Use
Compliance Summary
Design
75,053.8
` . LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
Criteria Result
5,414.5 PASSES
PASSES
None Entered
PASSES
None Entered
PASSES
PASSES
Yes/No/NA
IMPORTANT NOTE: An input report of this design building must be submitted
along with this Compliance Report.
9/28/2007 EnergyGauge Summit v3.10 incorporating Florida Energy Code Version - FLA/COM 2004 v2.5 2
r�
CERTIFICATIONS
I hereby certify that the plans sp: ; ifi ations covered by this calculation are in compliance with the
Florida Energy Code
Prepared By _'+ Building Official:
Date: Date:
I certify that this building is in c pl'an with the FLorida Energy Efficiency Code
Owner Agent: Date: (/
If Required by Florida law, I hereby certify (*) that the system design is in compliance with the FLorida
Energy Efficiency Code
Architect: Reg No:
Electrical Designer: Reg No:
Lighting Designer: Reg No:
Mechanical Designer: RON RENNA, P.E. Reg No: 56067
Plumbing Designer: RON RENNA, P.E. Reg No: 56067
(*) Signature is required where Florida Law requires design to be performed by registered design
professionals. Typed names and registration numbers may be used where all relevant information is
contained on signed/sealed plans.
9/28/2007 EnergyGauge Summit v3.10 incorporating Florida Energy Code Version - FLA/COM 2004 v2.5 3
r
Project: 6186.01
Title: NEFF RENTAL
Type: Office
(WEA File: DAYTONABEACH.TMY)
Building End Uses
Design
Reference
Total
92.99
100.00
$5,054
$5,415
ELECTRICITY(MBtulk
92•99
100.00
Whl$)
99095
106585
$5,054
$5,415
AREA LIGHTS
32.36
34.84
34497
37119
$1, 759
$1, 886
MISC EQUIPMT
28.79
28.79
30684
30684
$1, 565
$1, 559
PUMPS & MISC
0.03
0.03
32
32
$2
$2
SPACE COOL
14.71
17.71
15671
18878
$799
$959
SPACE HEAT
1.32
0.88
1392
949
$71
$48
VENT FANS
15.78
17.76
16819
18923
$858
$961
Credits & Penalties (if any): Modified Points: = 92.99
PASSES
9/28/2007 EnergyGauge Summit v3.10 incorporating Florida Energy Code Version - FLA/COM 2004 v2.5
r
External Lighting Compliance
Description Category
Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (W)
(Sgft or ft)
None
Project: 6186.01
Title: NEFF RENTAL
Type: Office
(WEA File: DAYTONABEACH.TMY)
Lighting Controls Compliance
Acronym Ashrae Description
Area No. of Design Min Compli-
ID
(sq.ft) Tasks CP CP ance
RETAIL ,001 Sales Area
2,210 0 7 1 PASSES
REPAIR GARAGI ,001 Automotive Service/Repair
5,620 1 3 3 PASSES
PASSES
Project: 6186.01
Title: NEFF RENTAL
Type: Office
(WEA File: DAYTONABEACH.TMY)
System Report Compliance
AHU/CU 1 AHU/CU 1
Constant Volume Packaged No. of Units
System 1
Component Category Capacity
Design Eff Design IPLV Comp-
Eff Criteria IPLV Criteria liance
Cooling System Air Cooled 65000 to 135000
12.00 10.30 9.70 PASSES
Btu/h Cooling Capacity
Heating System Electric Furnace
1.00 1.00 PASSES
Air Handling Air Handler (Supply) -
0.80 0.90 PASSES
System -Supply Constant Volume
PASSES
9/28/2007 EnergyGauge Summit v3.10 incorporating Florida Energy Code Version - FLA/COM 2004 v2.5
Plant Compliance
Installed
No
L
Size Design Min Design Min Category Comp
Eff Eff IPLV IPLV Hance
None
Project: 6186.01
Title: NEFF RENTAL
Type: Office
(WEA File: DAYTONABEACH.TMY)
Water Heater Compliance
Description Type
Category Design Min
Eff Eff
Design Max Comp
Loss Loss liance
Water Heater 2 Electric water heater <= 12 [kW] 0.93 0.88
PASSES
PASSES
Project: 6186.01
Title: NEFF RENTAL
Type: Office
(WEA File: DAYTONABEACH.TMY)
Piping System Compliance
Category
Pipe Dia Is Operating Ins Cond Ins Req Ins Compliance
[inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in]
[F] .SF.F]
Heating System (Steam, Steam
Condensate, & Hot Water)
0.25 True 105.00 0.28
0.75 0.00 PASSES
PASSES
9/28/2007 EnergyGauge Summit v3.10 incorporating Florida Energy Code Version - FLA/COM 2004 v2.5 6
:t: 6186.01
NEFF RENTAL
Office
File: DAYTONABEACH.TMY)
Other Required Compliance
Category
Section
Requirement (write N/A in box if not applicable) e k
Infiltration
406.1
Infiltration Criteria have been met
System
407.1
HVAC Load sizing has been performed
Ventilation
409.1
Ventilation criteria have been met
ADS
410.1
Duct sizing and Design have been performed
T & B
410.1
Testing and Balancing will be performed
Motors
414.1
Motor efficiency criteria have been met
Lighting
415.1
Lighting criteria have been met
O & M
102.1
Operation/maintenance manual will be provided to owner
Roof/Ceil
404.1
R-19 for Roof Deck with supply plenums beneath it
Report
101
Input Report Print -Out from EnergyGauge F1aCom attached?
9/28/2007 EnergyGauge Summit v3.10 incorporating Florida Energy Code Version - FLA/COM 2004 v2.5 7
EnergyGauge Summit v3.10
INPUT DATA REPORT
Proiect
Information
Project Name:
6186.01
Orientation:
North
Project Title:
NEFF RENTAL
Building Type:
Office
Address:
7400 COMMERCIAL CIRCLE
Building Classification:
New Finished building
State:
FL
No.of Storeys:
1
Zip:
34951
GrossArea:
7830 SF
Owner:
Zones
No Acronym Description Type Area Multiplier Total Area
[sq [sf)
I ZONE 1 Zone 1 CONDITIONED 2210.0 1 2210.0
2 ZONE 2 Zone 2 UNCONDITIONED 5620.0 1 5620.0
9/28/2007 EnergyGauge Summit v3.10 1
Spaces
No Acronym Description
Type
Depth
Width
Height
Multi Total Area
Total Volume
IN
[ft]
[ft]
plier [sf]
[cf]
In Zone: ZONE 1
1 RETAIL Zo0Sp1
Sales Area
100.00
22.10
10.00
1 2210.0
22100.0
In Zone: ZONE 2
1 REPAIR GAR7-o0Sp1
Automotive Service/Repair 100.00
56.20
20.00
1 5620.0
112400.0
Lighting
No Type
Category
No. of
Watts per
Power
Control Type
No.of
Luminaires
Luminaire
[W]
Ctrl pts
In Zone: ZONE 1
In Space: RETAIL
1 Compact Fluorescent
General Lighting
23
128
2944
Manual On/Off
5
2 Incandescent
General Lighting
4
64
256
Manual On/Off
2
In Zone: ZONE 2
In Space: REPAIR GARAGE
1 Metal Halide
General Lighting
1
5620
5620
Manual On/Off
3
Walls
No Description Type
Width H (Effec) Multi
Area DirectionConductance Heat
Dens. R-Value
[ft]
[ft] plier
[sf]
[Btu/hr. sf. F] Capacity
[lb/cf] [h.sf.FBtu]
[Btu/sf.F]
In Zone: ZONE 1
1 PrOZo1Wa1 Metal
16.80
100.00 1
1680.0
North
0.0920 1.072
19.38 10.9
siding/2x4@24"+Rl
1Batt/5/8"Gyp
9/28/2007 EnergyGauge Summit v3.10
Windows
No Description Type
Shaded U SHGC
Vis.Tra
W H (Effec)
Multi Total Area
[Btu/hr sf F]
IN [ft]
plier [sf]
In Zone: ZONE 1
In Wall: PrOZo1Wa1
1 PrOZo1Wa1Wil User Defined
No 1.0000 1.15
0.90
10.88 8.00
1 87.0
Doors
No Description Type
Shaded? Width H (Effec) Multi
Area
Cond.
Dens. Heat Cap.
R-Value
IN [ft]
plier
[sf]
[Btu/hr. A. F] [lb/cf] [Btu/sf. F]
[h.sf.FBtu]
In Zone:
In Wall:
Roofs
No Description Type
Width H (Effec) Multi
Area
Tilt
Cond.
Heat Cap Dens.
R-Value
IN IN plier
[sf]
[deg]
[Btu/hr. Sf. F]
[Btu/sf. F] [lb/cf]
[h.sf.F/Btu]
In Zone: ZONE 1
1 PrOZo1Rf1 Mtl Bldg Roof/R-19
22.10 100.00 1
2210.0
0.00 0.0492
1.34 9.49
20.3
Batt
Skylights
No Description Type
U SHGC Vis.Trans
W
H (Effec) Multiplier Area
Total Area
[Btu/hr sf F]
[ft]
[ft]
[Sf]
[Sf]
In Zone:
In Roof:
9/28/2007 EnergyGauge Summit v3.10
Floors
No Description Type Width H (Effec) Multi Area Cond. Heat Cap. Dens. R-Value
IN [ft] plier [sf] [Btu/hr. sf. F] [Btu/sf. F] [lb/cf] [h.sf.FBtu]
In Zone: ZONE 1
1 PrOZo1F11 Concrete floor, 22.10 100.00 1 2210.0 0.5987 9.33 140.00 1.67
carpet and rubber
pad
Systems
AHU/CU 1 AHU/CU 1
Constant Volume Packaged System No. Of Units 1
Component Category
Capacity
Efficiency IPLV
1 Cooling System (Air Cooled 65000 to 135000 Btu/h
Cooling Capacity)
2 Heating System (Electric Furnace)
3 Air Handling System -Supply (Air Handler (Supply) -
Constant Volume)
71000.00
29522.00
2400.00
12.00 9.70
1.00
0.80
Plant
Equipment Category
Size
Inst.No Eff. IPLV
Water Beaters
W-Heater Description Capacit3Cap.Unit
I/P Rt.
Efficiency Loss
1 Electric water heater 40 [Gal]
3 [kW]
0.9300 [Eff [Btu/h]
9/28/2007 EnergyGauge Summit v3.10
Ext-Lighting
Description Category
No. of Watts per Area/Len/No. of units
Luminaires Luminaire [sf/ft/No]
Control Type
Wattage
[W]
Piping
No ,hype
Operating Insulation
Temperature Conductivity
[F] [ Btu-in/h.sf.F]
Nomonal pipe
Diameter
[in]
Insulation
Thickness
[in]
Is Runout?
1 Heating System (Steam, Steam Condensate, &
Hot Water)
105.00 0.28
0.25
0.75
Yes
Fenestration Used
Name Glass Type No. of Glass SHGC VLT
Panes Conductance
[Btu/h.sf.F]
ApLbWndl User Defined 1 1.0000 1.1494 0.9000
Materials Used
Mat No Acronym Description
Only R-Value RValue Thickness
Conductivity
Density
SpecificHeat
Used [h.sf.FBtu] IN
[Btu/h.ft.F]
[lb/cf]
[Btu/Ib.F]
94 Mat194 BUILT-UP ROOFING,
No 0.3366 0.0313
0.0930
70.00
0.3500
3/8IN
187 Mat1187 GYP OR PLAS
No 0.4533 0.0417
0.0920
50.00
0.2000
BOARD,1/2IN
9/28/2007 EnergyGauge Summit v3.10 5
r
151 Mat1151
178 Mat1178
23 Matl23
4 Mat14
271 Mat1271
No Name
CONC HW, DRD, 140LB,
41N
CARPET W/RUBBER PAD
6 in. Insulation
Steel siding
2x4@24" oc + RI 1 Batt
No 0.4403 0.3333 0.7570 140.00 0.2000
Yes 1.2300
No 20.0000 0.5000 0.0250 5.70 0.2000
No 0.0002 0.0050 26.0000 480.00 0.1000
No 10.4179 0.2917 0.0280 7.11 0.2000
Constructs Used
Simple Massless Conductance Heat Capacity Density RValue
Construct Construct [Btu/h.sf.Fl [Btu/sf.F] [lb/cfl [h.sf.F/Btul
1004 Concrete floor, carpet and rubber pad No
No 0.60
9.33
140.00
1.7
Layer Material Material
Thickness
Framing
No.
IN
Factor
1 151 CONC HW, DRD, 140LB, 41N
0.3333
0.000
2 178 CARPET W/RUBBER PAD
0.000
No Name Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/ct]
[h.sf.FBtul
1019 Metal siding/2x4@24"+R11Batt/5/8"Gyp No
No 0.09
1.07
19.38
10.9
Layer Material Material
Thickness
Framing
No.
1 4 Steel siding
IN
0.0050
Factor
0.000
2 271 2x4@24" oc + RI 1 Batt
0.2917
0.000
3 187 GYP OR PLAS BOARD,1/2IN
0.0417
0.000
aCC
9/28/2007 EnergyGauge Summit v3.10 6
t
No Name Simple
Massless
Conductance
Heat Capacity
Density
RValue
Construct
Construct
[Btu/h.sf.F]
[Btu/sf.F]
[Ib/cf]
[h.sf.FBtu]
1047 Mtl Bldg Roof/R-19 Batt No
No
0.05
1.34
9.49
20.3
Layer Material Material
No.
1 94 BUILT-UP ROOFING, 3/8IN
2 23 6 in. Insulation
Thickness
Framing
[ft]
Factor
0.0313
0.000
0.5000
0.000
9/28/2007 EnergyGauge Summit v3.10 7
ST LUCIE COUNTY FIRE DISTRICT
Office of the Fire Marshal
Plan Review
5160 N.W. Milner Drive Telephone: 772.621.3322
Port Saint Lucie, FL 34983 FAX: 772.621.3604
THE FLORIDA FIRE PREVENTION CODE, 2004 EDITION IS CURRENTLY ENFORCED.
The Code is based on NFPA 1 and NFPA 101, 2003 Florida Specific edition.
Jurisdiction: SLC
Project Name: Neff Rentals
Address: 7400 Commercial Circle
Contractor D S General Contractors
Contractor's Address: 2032 GE Giffen Ave
State: FI
Architect/Engineer: Faber Widdows Hiatt
Occupancy Type: Business/Industrial
Construction Type: 2B
Square feet: 7827
Number of stories: 1
Occupant Load:
FMO Permit #: B-07-543
Buildin Permit #• n71 n-0 7
9
Phone # 772-335-003
City: Port Saint Lucie
Zip Code: 34952
Phone # 727-815-3336
AS Permit:
FA Permit:
FFP Permit:
Access Box:
Access Key Switch:
NOTE
1. All revisions, including the electronic copy must be received prior to permitting.
2. The Fire Marshal requires 24 hour notice on all inspections.
3. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
4. Failed inspections require payment of fee prior to rescheduling of further inspections.
5. Penetrations through rated assemblies shall be of proper UL design. Design criteria shall be submitted
with the construction plans.
6. Fire alarm panels shall be located indoors within a controlled environment.
7. Plans and construction are subject to corrections in the field to maintain code compliance.
An electronic version of the construction plans on a CD is required. The file
format shall be .pdf only. The CD shall contain a sheet index file.
Files shall be separated by discipline. Files names shall match construction
documents sheet numbers.
Required Revisions
1. Read all notes above.
2007.12.03
08:29:21-05'00'