NOTICE OF ACCEPTANCE (NOA) -NN-)v% tiiiaiiiid'ade.vol'/ec(itiottiv
Johns Manville Corporation
71717th Street
Denver,CO 80202
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction
materials. The documentation submitted has been reviewed and accepted by Miami-Dade County RER-
Product Control Section to be used in Miami Dade County and other areas where allowed by the Authority
Having Jurisdiction(AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami-Dade County Product
Coptrol. Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County)
reserve the right to have this product or material tested for quality assurance purposes. If this product
or material fails to perfonn in the accepted manner, the manufacturer will incur the expense of such
testing and the AHJ may immediately revoke, modify, or suspend the use of such product or material
within their jurisdiction. RER reserves the right to revoke this acceptance, if it is determined by
Miami-Dade County Product Control Section that this product or material fails to meet the
requirements of the applicable building code.
This product is approved as described herein,and has been designed to comply with the Florida Building
Code including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: Johns Manville APP Modified Bitumen Roofing Systems Over Wood Decks.
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo,city,state and
following statement: "Miami-Dade County Product Control Approved",unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been
no change in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change
in the materials, use,and/or manufacture of the product or process.Misuse of this NOA as an:ndorsemenf
of any product, for sales, advertising or any other purposes shall automatically terminate this-NOA.-Failure
to comply with any section of this NOA shall be cause for termination and removal of NQA. -
ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County,_"Flacida
followed by the expiration date may be displayed in advertising literature. If any portion 6f th--NOAi is
displayed,then it shall be done in its entirety. � J
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or,i'ts-------- �,•�
distributors and shall be available for inspection at the job site at the request of the Building Official.
This NOA renews and revises NOA No. 12-0123.06 and consists of pages 1 through 15.
The submitted documentation was reviewed by Jorge L. Acebo.
NOA No.: 13-0129.03
QMIAMMI-DAMDECOUiVTY Expiration Date: 06/14/16
�� Approval Date: 06/06/13
Page I of 15
ROOFING SYSTEM APPROVAL
Category Roofing
Sub-,Categyory: Modified Bitumen
Materials: APP
Deck Tvp-e: Wood
Maximum Design Pressure -52.5 psf
TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED By APPLICANT:
TABLE I
Test Product
Product Dimensions Specification Description
JM APP Base 39-3/8"x 48' ASTM D 6509 APP modified asphalt, fiberglass
reinforced,smooth surfaced base sheet.
APPeX 4S 339-3/8"x 34' ASTM D 6222 APP modified asphalt,polyester
Type I reinforced,smooth surfaced membrane
Grade S for use as a Base and/or Ply Sheet only.
APPeX 4.5M 39-3/8"x 34' ASTM D 6222 APP modified asphalt,polyester
Type [ reinforced,mineral surfaced membrane.
Grade G
APPeX 4.5\14 FR 39-3/8"x 34" ASTM D 6222 APP modified asphalt,polyester
TN-pel reinforced, fire-retardant,mineral surfaced
Grade G membrane.
Tricor MFR 39-3/8"x 34' ASTM D 6223 APP modified asphalt,polyester/glass
reinforced,granule surfaced membrane.
Tricor S 39-3/8"x 34' ASTM D 622') APP modified asphalt,polyester/glass
reinforced,smooth surfaced membrane
for use as a Base and/or Ply Sheet only.
PermaPly 28 36" x 106'; ASTM D 4601 Type 11 asphalt impregnated and coated
72 lb. roll glass fiber base sheet
Ventsulation 336" 136' ASTM D 4897 Heavy duty fiber glass base sheet
Type 11 impregnated and coated on both sides with
asphalt with or without fine mineral
stabilizer.
GlasBase Plus 36" x 106' ASTM D 4601 Type 11 SBS and asphalt blend
impregnated and coated glass fiber base
sheet with fine mineral stabilizer.
NOA No.: 13-0129.03
QMLARMI-DMADE CMOUNTY Expiration Date: 06114/16
VINVIYA)l Approval Date: 06/06/13
Page 2 of 15
Membrane Type: APP
Deck Type 11: Wood,Non-Insulated
Deck Description: 14/;2" or greater plywood or wood plank
System Type E: Base sheet mechanically fastened.
All General and System limitations apply.
Base Sheet: ( tion#1) One ply o P Base, P v 28,Glasbase Plus or
Vents tion me anically fasten to ze deck with Ultra F st,OM Roofgrip
or Tru-Fas Ital plates and fasten 5 t a 4" side lap 12' and two rows
staggered '1 tlt enter of the sl et 18" o. .
(III min Design re—45 psf,See imitation# .
(Option#2) klinimum two plies of JM PermaPly 28 or Ventsulation
simultaneously fastened to the deck lapped 4" and fastened with approved roofing
nails and tin caps 9" o.c. at the land two rows staggered in the center of the
sheet 12" o.c.
(Maximum Design Pressure—52.5 psf,See General Limitation#7.)
( tion 43) N 'm m two pl' s of J. PennaPlV or tsulati
simt taneo sly fasten to e deck with M trafast faster rs nd Metal Plates
space . ' o.c. in a #"Ia a d 12"o.c. in t staggered rows ' the center of the
sheet.
( nrincum Design Pressure—-2.5 f,See Gen L' citation 97.)
Ply beet: (Optional)One or more plies of JM APP Base or APPeX 4S heat welded to base
lied while maintaining 4"side laps and 6"end laps.
Membrane: lone or more plies of APPeX 4,5Nvl or APPeX 4.5M FR heat welded while
maintaining 4"side laps and~ "nd laps.
Surfacing: (Opt' nal)Install one of the following for all systems that do not achieve
accepta fire ratings through the use of FR membrane sheets. Any coa ' g, listed
below,use s a surfacing,must be listed within a current NOA.
1. 400 Ib./sq, grave or 300 lb./sq. slag in a flood coat of appr ' mopping asphalt at
a rate of 60 lb./sq.
2. Karnak 97,Karnak 9 . F,Monsey Premium g Life Aluminum Roof Coating
Asbestos Free or Monsey •ograde Alu um, Grundy AL MB aluminum coating
at a rate of 1-1/2 gal/sq. Mons abrite,Gardner asphalt emulsion, APOC
Sunbright 400 or Henry �_ Alun ' um Emulsion at 21/gal/sq. or APOC 212
Aluminum Roof ting at 3 gal/sq.
3. Grundy 2 asphalt emulsion, Endure As alt Emulsion,APOC 302 or 302 AF
applied at 21/gal/sq.with optional 60 Ibs./sq. oofing granules embedded in wet
coating.
Maximum Design
Pressure: See Fastening Options
NOA No.: 13-0129.03
MIAM!•DADE COUNTY Expiration Date: 06/14/16
■III '"'+ ' Approval Date: 06/06/13
Page 14 of 15
WOOD DECK SYSTEM LIMITATIONS:
I A slip sheet is required with Ply 4 and Ply 6 when used as a mechanically fastened base or anchor
sheet.
GENERAL LIMITATIONS:
1. Fire classification is not part of this acceptance; refer to a current Approved Roofing Materials
Directory for fire ratings
as of this product.
1 Insulation may be installed in multiple layers. The first layer shall be attached in compliance with
Product Control Approval guidelines. All other layers shall be adhered in a full mopping of
approved asphalt applied within the EVT range and at a rate of 20-40 lbs./sq.,or mechanically
attached using the fastening pattern of the top layer
3. All standard panel sizes are acceptable for mechanical attachment. When applied in approved
asphalt,panel size shall be 4'x 4'maximum.
4. An overlay and/or recovery board insulation panel is required on all applications over closed cell
foam insulations when the base sheet is fully mopped. If no recovery board is used the base sheet
shall be applied using spot mopping with approved asphalt, 12" diameter circles, 24" o.c.; or strip
mopped 8" ribbons in three rows,one at each side lap and one down the center of the sheet allowing
a continuous area of ventilation, Encircling of the strips is not acceptable. A 6" break shall be
placed every 12' in each ribbon to allow cross ventilation. Asphalt application of either system shall
be at a minimum rate of 12 lbs./sq.
Note: Spot attached systems shall be limited to a maximum design pressure of-45 psf.
5. Fastener spacing for insulation attachment is based on a Minimum Characteristic Force(F')value of
275 lbf., as tested in compliance with Testing Application Standard TAS 105. If the fastener value,
as field-tested, are below 275 lbf. insulation attachment shall not be acceptable.
6. Fastener spacing for mechanical attachment of anchorlbase sheet or membrane attachment is based
on a minimum fastener resistance value in conjunction with the maximum design value listed within
a specific system. Should the fastener resistance be less than that required, as jeten-nined by the
Building Official,a revised fastener spacing,prepared,signed and sealed by a Florida Registered
Engineer, Architect, or Registered Roof Consultant may be submitted. Said revised fastener spacing
shall utilize the withdrawal resistance value taken from Testing Application Standards TAS 105 and
calculations in compliance with Roofing Application Standard RAS 117.
7. Perimeter and corner areas shall comply with the enhanced uplift pressure requirements of these
areas. Fastener densities shall be increased for both insulation and base sheet as calculated in
compliance with Roofing Application Standard RAS 117. Calculations prepared, signed and sealed
by a Florida registered Professional Engineer, Registered Architect, or Registered Roof Consultant
C,
(When this limitation is specifically referred within this NOA, General Limitation #9 will not
be applicable.)
S. All attachment and sizing of perimeter nailers,metal profile, and/or flashing termination designs
shall conform to Roofing Application Standard RAS 111 and applicable wind load requirements.
9. The maximum designed pressure limitation listed shall be applicable to all roof pressure zones(i.e.
field,perimeters, and comers). Neither rational analysis,nor extrapolation shall be permitted for
enhanced fastening at enhanced pressure zones(i.e.perimeters,extended comers and comers).
(When this limitation is specifically referred within this NOA,General Limitation#7 will not
be applicable.)
10. All products listed herein shall have a quality assurance audit in accordance xvith the Florida
Building Code and Rule 9N-3 of the Florida Administrative Code.
END OF THIS ACCEPTANCE
NOA No.: 13-0129.03
19MIAMI-DADE C()=UNTY Expiration Date: 06/14/16