Structural Engineering, Design & Testing, CA#28948, NOA #13-0222.02
6915 Washington Rd,W Palm Beach, FL 33405/Ph. (561)804-9908/Fax(561)804-9907/e-mail:turginc@aol.com
April 29, 2015
TO: St Lucie County / Building Department
FROM: Riza N. ALTAN, P.E.
SUBJECT: Change in Roof Covering (Shingles to Metal Panels)
ADDRESS: HENDRIX Residence / 1395 S Jenkins Rd., Ft Pierce, FL 34947
CONTRACTOR: Larry Neese Roofing, LLC
Dear Sir:
The roof covering of subject residence is proposed to be changed from asphalt shingles
to 5V crimp metal panels. The purpose of this letter is to determine wind uplift forces
and specify fastening pattern of new plywood sheathing and metal roof panels.
The subject property is located in Exposure C area. The roof has 3/12 slope and mean
roof height is 14 ft. As per 2010 Florida Bldg. Code; ASCE 7-10, 165 MPH ultimate wind
speed for Risk Category II in Exposure C area, using Wind Load-Factor of 0.6 for ASD
the wind pressures are determined as follows:
Field Pi = -40 psf / Perimeter (4' wide) P2 = -70 psf / Corner (4'x4') P3 = -100 psf.
The installation of new roof panels consists of ASTM D 226 Type II, 30-lbs felt fastened
by using 11 ga 11/4' ring-shanked nails spaced at 6" o.c. along seams and 12" o.c.
staggered two rows in field and 4" o.c. in 5'-wide gable-end and 4'-wide, perimeter and
corner zones.
As per Gulf Coast Supply, 26 Ga., 24" wide 5V crimp Roof Panels on Wood Decks
(NOA #14-0520.02); the design pressures of -108.5 psf is achieved by fastening the
panels using #10-11/2" long hex-head screws with WSW washers spaced at 12" o.c. (see
Method 1). In perimeter and corner zones, the max. uplift resistance of -156.5 psf is
achieved by using #10-11/2" long hex-head screws spaced at 6" o.c. (Method 2).
As per Method 1; the 5V metal panels in field (P1 . 1 e will be fastened at 12" o.c.
along and across the panels. As per Method 2, two row Panels in perimeter (P2) and
corner zones (P3) are required to be secured at 6" o.c. s _ing and 12" o.c. across
the panels (see pg. 4&5/5).
Therefore, this letter is to certify that Gulf Coast Supply, 26 a., , Ide 5V crimp Roof
Panels on Wood Decks (NOA #14-0520.02), installed as sta'. d move, conform to
requirements of 2010 Florida Building Code, which specifies 1 AIVk ' Itimate wind
velocityfor Risk Category II in Exposure C area.
g rY p
If you have any questions re.garding.this'matter or I mybss %er
ease
do not hesitate to call me. N AN
Sincerely, - :`o. F �$ `SAY
�vo.335s1 ... 2fEg
° g� UJ
°
Riza N. ALTAN, P.E. 3 2`1. _ SY: o� A �e county-NTE FC
Consulting Engineer ` , y ~ t ;
G
MiAMra;e►r�
MIAMI-DADE COUNTY
0.1 PRODUCT CONTROL SECTION
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES(RER) 11805 SW 26 Street,Room 208
BOARD AND CODE ADMINISTRATION DIVISION Miami,Florida 33175-2474
T(786)315-2590 F(786)315-2599
NOTICE OF ACCEPTANCE (NOA) wnvw•miamidade.aov/economv
Gulf Coast Supply&Manufacturing,LLC.
4020 SW 449h Street
Horseshoe Beach,FL.32648
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami-Dade County RER-Product Control Section to be
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction(AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami-Dade County Product Control Section
(In Miami Dade County)and/or the AHJ(in areas other than Miami Dade County)reserve the right to have this product
or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner,the
manufacturer will incur the expense of such testing and the AHJ may immediately revoke,modify,or suspend the use
of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance,if it is
determined by Miami-Dade County Product Control Section that this product or material fails to meet the requirements
of the applicable building code.
This product is approved as described herein,and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: 26 ga.Coastal 5V Roof Panel
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo,city,state and following
statement: "Miami-Dade County Product Control Approved",unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials,use,and/or manufacture of the product or process.Misuse of this NOA as an endorsement of any product,for
sales,advertising or any other purposes shall automatically terminate this NOA.Failure to comply with any section of
this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed,then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA consists of pages 1 through 5.
The submitted documentation was reviewed by Alex Tigera.
NOA No.: 14-0520.02
MIAMI•DADE COUNTY Expiration Date:08/21/19
Approval Date: 08/21/14
Page 1 of 5
ROOFING SYSTEM APPROVAL:
Category: Roofing
Sub-Category: Metal,Panels(Non-Structural)
Material: Steel
Deck Type: Wood
Maximum Design Pressure -156.5 psf
TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT.-
Test
PPLICANT.Test Product
Product Dimensions Specifications Description
26 ga. Coastal 5V- 1=varies TAS 110 Corrosion resistant,galvanized,preformed,
Crimp Roof Panel w=26" Valspar coated,prefinished,metal panels.
(24"coverage)
h=3/8"
Min. Thickness 0.018"
(26ga.)
Min. Yield Strength: 67ksi
Trim Pieces 1=varies TAS 110 Standard flashing and trim pieces.
w=varies Manufactured for each panel width.
Min.Thickness 0.018"
(26ga.)
MANUFACTURING LOCATION:
1. Horseshoe Beach,FL.
2. Sebring,FL.
3. Stuart,FL.
EVIDENCE SUBMITTED:
Test Agency Test Identifier Test Name/Report Date
PRI Construction Materials VLS-004-02-01 ASTM G 155 02/22/13
Technologies VLS-005-02-01 ASTM G 23 02/22/13
Force Engineering&Testing Inc. 117-0065T-07A-C TAS 125 08/02/13
Farabaugh Engineering and T215-08A TAS 100 08/13/14
Testing,Inc.
NOA No.: 14-0520.02
MIAMI-DAD�KWIIW;COUNTY Expiration Date:08/21/19
Approval Date:08/21/14
Page 2 of 5
APPROVED ASSEMBLIES:
System A: 26 ga. Coastal 5V-Crimp Roof Panel
Deck Type: Wood,Non-insulated
Deck Description: New Construction 19/32"or greater plywood or wood plank,or for re-roofing 15/32"or greater
plywood.
Maximum Uplift See Table A below.
Pressure:
Deck Attachment: In accordance with applicable Building Code, but in no case shall it be less than 8d ring
shank nails spaced 6" o.c. In reroofing, where the deck is less than 19/32" thick (Minimum
15/32")the above attachment method must be in addition to existing attachment.
Underlayment: Minimum underlayment shall be an ASTM D 226 Type II installed with a minimum 4"side-
lap and 6"end-laps.Underlayment shall be fastened with corrosion resistant tin-caps and 12
gauge 1 '/4"annular ring-shank nails,spaced 6"o.c.at all laps and two staggered rows 12"
o.c. in the field of the roll. Or,any approved underlayment having a current NOA.
Fire Barrier: Any approved fire barrier having a current NOA. Refer to a current fire directory listing for
fire ratings of this roofing system assembly as well as the location of the fire barrier within
the assembly. See Limitation# 1.
Valleys: Valley construction shall be in compliance with Roofing Application Standard RAS 133 and
with Gulf Coast Supply&Manufacturing LLC's current published installation instructions.
Metal Panels and Install the"26 ga. Coastal 5V-Crimp Roof Panel" and accessories in compliance with Gulf
Accessories: Coast Supply&Manufacturing LLC's current,published installation instructions and details.
Flashing,penetrations,valley construction and other details shall be constructed in
compliance with the minimum requirements provided in Roofing Application Standards RAS
133.
Panel fasteners shall be#9-15 x 1-%"self drilling, self tapping,hex head screws with sealing
washer of sufficient length to penetrate through the sheathing a minimum of 3/16 inch.
Fasteners shall be installed at a maximum spacing as listed in Table A below parallel to the
slope. Fasteners shall be installed at a maximum of 12"o.c. at panel edge. See detail herein.
TABLE A
MAXIMUM DESIGN PRESSURES
Roof Areas Field Perimeter and Corner'
Maximum Design Pressures -108.5 psf -156.5 psf
Maximum Fastener Spacing 12"o.c. 6" o.c.
1.Extrapolation shall not be allowed
NOA No.: 14-0520.02
MI1•oAne courm Expiration Date: 08/21/19
Approval Date: 08/21/14
Page 3 of 5
LIMITATIONS
1. Fire classification is not part of this acceptance;refer to a current Approved Roofing Materials Directory for fire
ratings of this product.
2. The maximum designed pressure listed herein shall be applicable to all roof pressure zones(i.e. field,perimeters,
and corners).Neither rational analysis,nor extrapolation shall be permitted for enhanced fastening at enhanced
pressure zones(i.e. perimeters,extended corners and corners).
3. Panel shall be roll formed in continuous lengths from eave to ridge. Maximum lengths shall be described in the
Roofing Application Standard RAS 133.
4. All panels shall be permanently labeled with the manufacturer's name and/or logo, and the following statement:
"Miami-Dade County Product Control Approved" or with the Miami-Dade County Product Control Seal as seen
below. All clips shall be permanently labeled with the manufacturer's name and/or logo,and/or model.
MIAMI•DADE COUNTY
5. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 61 G20-3 of the Florida Administrative Code.
NOA No.: 14-0520.02
MIA PDADE COUNTY Expiration Date:08/21/19
Approval Date:08/21/14
Page 4 of 5
PROFILE DRAWINGS
DETAIL A
26 GA.COASTAL 5V-CRIMP ROOF PANEL
24"Coverage
#9-15 x 1 1/2"Woodgrip Screw #9-15 x 1 1/2"Woodgrip Screw
5V-Crimp Panel
ff
Moisture Barrier
Plywood Decking (By others)
(By others)
SeeTable A
Herein for Maximum
Fastening Spacing
5V Panel
END OF THIS ACCEPTANCE
NOA No.: 14-0520.02
MIAMI•DAD,COUNTY Expiration Date: 08/21/19
Approval Date:08/21/14
Page 5 of 5
TURQUOISE Engineering, LLC
Structural Engineering, Design & Testing, CA#28948, NOA#13-0222.02
6915 Washington Rd,West Palm Beach, FL 33405/Phone(561)804-9908/Fax(561)804-9907/e-mail:turginc@aol.com
April 29, 2015
TO: St. Lucie County / Building Department
FROM: Riza N. ALTAN, P.E.
SUBJECT: Flat Roof Uplift Pressures & Base Sheet Enhanced Fastening
ADDRESS: HENDRIX Residence / 1395 S Jenkins Rd., Ft Pierce, FL 34947
CONTRACTOR: Larry Neese Roofing, LLC
Dear Sir:
The re-roofing specifications for flat roof areas of the subject residence are reviewed by
myself. The purpose of this letter is to determine the wind uplift pressures and enhanced
spacing of the mechanical fasteners.
The one-story-high property is located in Exposure C area. The flat roof areas consist of 1x6
wood slats and 5/8" plywood decks with positive drainage. The roof mean height is 15 % As
per the 2010 Florida Building Code, ASCE 7-10, 170 MPH ultimate wind velocity for Risk
Category II in Exposure C area, using Wind Load Factor ofon" for ASD; the wind pressures
are determined as follows:
Field: P1 = - 44 Psf / Perimeter 4'wide : Pi = - 74 Psf / fforner,. 4'x4' : P3 = -111 PSf
The proposed CertainTeed Modified Bitumen Roof System overn° oecks (NOA #14-0224.03)
consists of mechanically attached 75-Ibs GlasBase base sheet, folio ed by torched-down
FlintLastic GTA modified bitumen cap sheet.
The system max. design pressure of -60 psf (Deck 1I, Syst.E(3), pa Limitation #7) is
specified by tin-tagging the base sheet with 11 ga., 1'/4" long ring-sh nke roofing nails,
spaced at 811o.c. along the laps and 8"o.c., three rows staggered in mid-s
It is required that, as per RAS 117 in order to meet the actual roof pressure , t se sheet
is tin-tagged to the existing wood decks in the following enhanced pattern:
Zone 1: Field (Intermediate areas): @ 8"o.c., staggered three rows in mid-sheet
Zone 2: Perimeter (4' from edges): @ 6"o.c., staggered three rows in mid-sheet
Zone 3: Corner (4' from ea. side): @ 4"o.c., staggered three rows in mid-sheet
Laps: Field (4"min.): @ 8"o.c., Perimeter @ 611o.c. & Corners: @ 411o.c.
Therefore, this letter is to certify that, installation of CertainTeed Modified torched-down
Bitumen Roof System (NOA #14-0224.03) conforms to the requirements of the 2010 Florida
Building Code which specifies 170 MPH ultimate wind speed for Risk Category II in Exposure
C area.
If you have any questions regarding-this=matter or I �y�e�o fl'% ,,assistance, please do
�. f
not hesitate to call me. �_ °• p `°° c�
Sincerely,
No • '�
.� .38�21 N
SiAT c OF
Riza N. ALTAN, P.a.21 38521 �.,` ' : Ao � ,,°
Consulting Engineer "=��, ",^�°6y""�••�����w�
MIAMI-RADE MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
11805 SW 26 Street,Room 208
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES(RER) Miami,Florida 33175-2474
BOARD AND CODE ADMINISTRATION DIVISION T(786)315-2590 F(786)31525-99
NOTICE OF ACCEPTANCE (NOA) www.miamidade.aov/economy
CertainTeed Corporation
1400 Union Meeting Road,P.O.Box 1100
Blue Bell,PA 19422-0761
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami-Dade County RER-Product Control Section to be
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction(AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami-Dade County Product Control
Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to
have this product or material tested for quality assurance purposes. If this product or material fails to perform in
the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately
revoke,modify,or suspend the use of such product or material within their jurisdiction. RER reserves the right to
revoke this acceptance, if it is determined by Miami-Dade County Product Control Section that this product or
material fails to meet the requirements of the applicable building code.
This product is approved as described herein,and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: CertainTeed Modified Bitumen Roofing Systems over Wood Decks.
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo,city,state and following
statement: "Miami-Dade County Product Control Approved",unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials,use,and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales,advertising or any other purposes shall automatically terminate this NOA.Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed,then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA renews NOA#13-0204.03 and consists of pages 1 through 16.
The submitted documentation was reviewed by Alex Tigera.
NOA No.: 14-0224.03
MIAM I-DADE coW Expiration Date: 06/19/18
Approval Date: 04/10/14
Page 1 of 16
ROOFING SYSTEM APPROVAL
Category Roofing
Sub-Category: Modified Bitumen
Material: APP/SBS
Deck Type: Wood
Maximum Design Pressure: -60 psf.
TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT:
TABLE 1
Test Product
Product Dimensions Specification Description
All Weather/Empire Base 36"x 65'10"; ASTM D 4601 Type Asphalt coated,fiberglass reinforced
Sheet Roll weight: 86 lbs. H base sheet
(2 squares) UL Type 15
Flex-I-G1aSTM Base Sheet 36" x 98'9';Roll ASTM D 4601,Type Modified Bitumen coated fiberglass
weight: 90 lbs. II base sheet.
(3 squares) UL Type G2
Flex-I-GlasTM FR Base Sheet 39 3/$" x 50;Roll ASTM D 6163, Modified Bitumen coated fiberglass
weight: 90 lbs. Grade S,Type I base sheet.
(1.5 squares)
Flintglas®Ply Sheet Type IV 36" x 1647";Roll ASTM D 2178 Type Fiberglass,asphalt impregnated ply
or V1 weight: 40/55 lbs. IV or VI sheet.
(5 squares) UL Type Gl
Flintlastic STA 393/8,, x 33;Roll ASTM D 6222, . Smooth surfaced APP Modified
weight: 90 lbs. Grade S,Type H Bitumen membrane with non-woven
(1 square) polyester mat reinforcement for torch
application.
Flintlastic GTA,GTA-FR 393/8,, x 33' 3"; Roll ASTM D 6222, Granule surfaced APP Modified
weight: 105 lbs. Grade G,Type II Bitumen membrane with non-woven
(1 square) polyester mat reinforcement for torch
application.
Flintlastic GMS, 393/8,, x 34'2";Roll ASTM D 6164, Granule surfaced SBS Modified
GMS Premium weight: 1001105 lbs. Grade G,Type 11 Bitumen membrane with non-woven
(1 square) polyester mat reinforcement for mop
application.
Flintlastic FR, 39 3/8" x 34'2";Roll ASTM D 6164, Fire resistant,granule surfaced SBS
FR-P Premium weight: 105 lbs. Grade G,Type I Modified Bitumen Membrane with
(1 square) non-woven polyester mat
reinforcement for mop application.
Flintlastic FR Cap Sheet 39 3/$"x 34'2";Roll ASTM D 6163, Fire resistant,granule surfaced SBS
weight: 90 lbs. Grade G,Type I Modified Bitumen membrane with
(1 square) fiberglass mat reinforcement for mop
applications.
NOA No.: 14-0224.03
MIAMI-pane c0uW Expiration Date: 06/19/18
Approval Date: 04/10/14
Page 2 of 16
TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT:
TABLE 1
Test Product
Product Dimensions Specification Description
Flintlastic FR Cap T 39-3/8"x 34'2";Roll ASTM D6163 Granule surfaced SBS Modified
weight: 81lbs. Bitumen membrane with fiberglass
(1 square) mat reinforcement for torch
application.
Flintlastic FR Base T 39-3/8"x 33';Roll ASTM D6163 Modified Bitumen,coated fiberglass
Weight: 81lbs. base sheet for torch application.
(1.0 squares)
Flintlastic FR Cap CoolStar 39 3/8"x 34'2"; Roll ASTM D 6163 Fire resistant,granule surfaced SBS
weight: 90 lbs. Modified Bitumen membrane with
(1 square) fiberglass mat reinforcement for mop
applications. Covered with reflective
CoolStar Coating.
Flintlastic FR Cap T CoolStar 39 3/8" x 34'2"; Roll ASTM D 6163 Fire resistant,granule surfaced SBS
weight: 90 lbs. Modified Bitumen membrane with
(1 square) fiberglass mat reinforcement for mop
applications. Covered with reflective
CoolStar Coating.
Flintlastic GTA,GTA-FR 393/8,, x 33' 3";Roll ASTM D 6222 Granule surfaced APP Modified
CoolStar weight: 105 lbs. Bitumen membrane with non-woven
(1 square) polyester mat reinforcement for torch
application. Covered with reflective
CoolStar Coating.
Flintlastic GMS/GMS 393/8,, x 34'2";Roll ASTM D 6164 Granule surfaced SBS Modified
Premium CoolStar weight: 100/105 lbs. Bitumen membrane with non-woven
(1 square) polyester mat reinforcement for mop
application. Covered with reflective
CoolStar Coating.
Flintlastic FR-P/FR-P Premium 39 3/8" x 34'2";Roll ASTM D 6164 Fire resistant,granule surfaced SBS
CoolStar weight: 105 lbs. Modified Bitumen Membrane with
(1 square) non-woven polyester mat
reinforcement for mop application.
Covered with reflective CoolStar
Coating. Covered with reflective
CoolStar Coating.
Ultra Poly SMS 36"x 64'4" ASTM D 6164, Smooth surfaced SBS Modified
(2 squares) Grade S,Type I Bitumen Membrane with non-woven
polyester mat reinforcement for mop
applications.
NOA No.: 14-0224.03
Mwr1�•DADE CO go
Expiration Date: 06/19/18
Approval Date: 04/10/14
Page 3 of 16
GlasBaseTM Base Sheet 36"x 98'9"; Roll ASTM D 4601 Asphalt coated,fiberglass base sheet.
weight: 69 lbs. UL Type G2
(3 squares)
PolySMS Base Sheet 393/8,, x 64'4"; Roll ASTM D 4601, Modified Bitumen coated polyester
weight: 901bs. Grade S,Type H base sheet.
(2 squares) UL Type G2
Yosemite®Buffer Base Sheet 36"x 32'10";Roll ASTM D 3909 Mineral Surfaced fiberglass reinforced
weight: 901bs. ASTM D 4897 buffer sheet.
(1 square) UL Type 30
Black DiamondTM Base Sheet 36"x 687';Roll ASTM D 1970 Self-adhering fiberglass reinforced
weight: 781bs. modified bitumen base sheet
(2 squares)
APPROVED INSULATIONS:
TABLE 2
Product Name Product Description Manufacturer
(With Current NOA)
FlintBoard ISO Polyisocyanurate foam insulation CertainTeed Corporation
ACFoam-H Polyisocyanurate foam insulation Atlas Roofing Corporation
High Density Wood Fiberboard Wood fiber insulation board Generic
Perlite Insulation Perlite insulation board Generic
DensDeck,DensDeck Prime Water resistant gypsum board Georgia Pacific Gypsum LLC
H-Shield Polyisocyanurate foam insulation Hunter Panels LLC
ENRGY 3,ENRGY 3 25 PSI Polyisocyanurate foam insulation Johns Manville Corp.
Multi-Max FA-3 Polyisocyanurate foam insulation RMax Operating,LLC
APPROVED FASTENERS:
TABLE 3
Fastener Product Product Manufacturer
Number Name Description Dimensions (With Current NOA)
1. None N/A None N/A
NOA No.: 14-0224.03
MIAMI•DADB COUNTY Expiration Date: 06/19/18
Approval Date: 04/10/14
Page 4 of 16
EVIDENCE SUBMITTED:
Test Agency/Identifier Name Report Date
Factory Mutual Research Corp. FMRC 4470 J.I. 3Y8A1.AM 03/23/96
FMRC 4470 J.I. OD3A3.AM 04/04/97
FMRC 4470 J.I. 2DOAO.AM 12/23/98
FMRC 4470 J.I. 1D7A4.AM 11/09/98
Underwriters Laboratories,Inc. UL 790 R11656 01/11/13
United States Testing Company ASTM D 5147 97457-4 06/03/88
ASTM D 5147 97-457-2R 12/02/87
Momentum Technologies,Inc. ASTM D 4601 AX31G8D 09/05/08
ASTM D6164 AX31G8F 06/05/09
ASTM D6222 AX31G8G 06/05/09
ASTM D 3909/D 4897 AX31G8C 09/05/08
TrinitylERD TAS 114(J) #3504.06.01-1 06/05/01
TAS 117(B) 3503.10.06 10/10/06
TAS 117(B) 06490.04.07-R1 06/27/07
TAS 114(H) Letter 04/05/06
TAS 114 3533.01.06 01/06/06
TAS 114 3521.07.04 07/29/04
TAS 117(B)/ASTM D 6862 C8500SC.11.07 11/30/07
TAS 114 C8370.08.08 08/19/08
ASTM Physical Properties C10080.09.08-R4 03/25/10
ASTM D6164/134798 C31410.01.11-2 01/10/11
ASTM D4601 C40050.09.12-1 09/28/12
ASTM D1970 C40050.09.12-2 09/28/12
ASTM 135147/134798 C31410.10.10-R1 11/01/12
ASTM 135147/134798 C31410.01.11-1-RI 11/01/12
ASTM D4798 C31410.01.11-2A-Rl 02/21/13
ASTM D4798 C31410.12.13 12/05/13
ASTM D6222 C40050.12.13 12/05/13
PRI Construction Materials ASTM D6163 CTC-032-02-01 01/22/08
Technologies LLC ASTM D6163 CTC-066-02-01 08/09/11
ASTM D6164 CTC-068-02-01 08/09/11
ASTM D6222 CTC-070-02-01 08/09/11
ASTM D6164/D4798 CTC-093-02-01 08/09/11
ASTM D2178 CTC-122-02-01 03/13/12
ASTM D2178 CTC-123-02-01 03/13/12
ASTM D4601 CTC-127-02-01 03/13/12
ASTM D6163 CTC-128-02-01 06/11/12
ASTM D6163 CTC-129-02-01 06/11/12
ASTM D6164 CTC-132-02-01 06/11/12
ASTM D6164 CTC-162-02-01 05/09/13
ASTM D6164 CTC-161-02-01 05/09/13
ASTM D6162 CTC-183-02-01 10/02/13
ASTM D6164 CTC-190-02-01 12/02/13
NOA No.: 14-0224.03
M"I-DAoe COuwrir Expiration Date: 06/19/18
Approval Date: 04/10/14
Page 5 of 16
APPROVED ASSEMBLIES:
Membrane Type: APP Modified
Deck Type 1I: Wood,Insulated
Deck Description: 19/3211 or greater plywood or wood plank
System Type A(1): Anchor sheet mechanically fastened; all layers of insulation adhered with approved asphalt.
All General and System Limitations apply.
Anchor Sheet: One ply of All Weather/Empire Base Sheet,Glas Base or Flintglas Premium Ply Sheet(Type
VI)mechanically attached as detailed below.
Fastening: Anchor sheet shall be lapped 4" and fastened with 11 ga. annular ring shank nails and approved
tin caps 8"o.c. in the lap and three rows staggered in the center of the sheet 8"o.c.
One or more layers of any of the following insulations.
Insulation Laver Insulation Fasteners Fastener
Table 3 Density/fe
ACFoam-II,Multi-Max FA-3,ENRGY 3,FlintBoard ISO,H-Shield
Minimum 1.5"thick N/A N/A
Note: All insulation shall be adhered to the anchor sheet in full mopping of approved hot asphalt within the
EVT range and at a rate of 20-40 lbs./100 W. Please refer to Roofing Application Standard RAS 117 for
insulation attachment. Insulation listed as base layer only shall be used only as base layers with a second layer
of approved top layer insulation installed as the final membrane substrate. Composite insulation panels may be
used as a top layer placed with the polyisocyanurate side facing down.
Base Sheet: One ply of Black Diamond Base Sheet self-adhered.
Ply Sheet: (Optional)One ply of All Weather/Empire Base Sheet,Ultra Poly SMS,Glas Base,Flex-I Glas
Base,Flex-I Glas FR Base or Poly SMS or one or more plies of Flintglas Ply Sheet(Type IV)or
Flintglas Premium Ply Sheet(Type VI)adhered in a full mopping of approved asphalt applied
within the EVT range and at a rate of 20-40 lbs./sq. or one ply of Black Diamond Base Sheet
self-adhered or Flintlastic STA torch adhered.
Membrane: Flintlastic GTA,Flintlastic GTA CoolStar,Flintlastic GTA-FR or GTA-FR CoolStar torch
adhered to base or ply sheet.
Surfacing: (Optional)Any coating,listed below,used as a surfacing,must be listed within a current NOA.
Install one of the following:
1. 400-1b./sq. gravel or 300-1b./sq. slag in a flood coat of approved
mopping asphalt at an application rate of 60 Ib./sq.
2. Karnak(#97 AF)Fibrated Aluminum Roof Coating,F1intCoat A-
150,APOC#212 Fibrated Aluminum Roof Coating at an application
rate of 1 %2 gal./sq.
Maximum Design -52.5 psf(See General Limitation#7)
Pressure:
NOA No.: 14-0224.03
MIAMIOAD;COUNTY�igzaiigel Expiration Date: 06/19/18
Approval Date: 04/10/14
Page 6 of 16
Membrane Type: SBS Modified
Deck Type 1I: Wood,Insulated
Deck Description: 19/3211 or greater plywood or wood plank
System Type A(2): Anchor sheet mechanically fastened;all layers of insulation adhered with approved asphalt.
All General and System Limitations apply.
Anchor Sheet: One ply of All Weather/Empire Base Sheet,Glas Base or Flintglas Premium Ply Sheet(Type
VI)mechanically attached as detailed below.
Fastening: Anchor sheet shall be lapped 4" and fastened with 11 ga. annular ring shank nails and approved
tin caps 8"o.c. in the lap and three rows staggered in the center of the sheet 8"o.c.
One or more layers of any of the following insulations.
Insulation Laver Insulation Fasteners Fastener
Table 3 Density/ft2
ACFoam-H,ENRGY 3,ENRGY 3 25 PSI,FlintBoard ISO,H-Shield
Minimum 1.5"thick N/A N/A
Approved Perlite
Minimum%"thick N/A N/A
Approved High Density Wood Fiberboard
Minimum Yz" thick N/A N/A
DensDeck,DensDeck Prime
Minimum V4" thick N/A N/A
Note: All insulation shall be adhered to the anchor sheet in full mopping of approved hot asphalt within the
EVT range and at a rate of 20-40 lbs./100 fe. Please refer to Roofing Application Standard RAS 117 for
insulation attachment. Insulation listed as base layer only shall be used only as base layers with a second layer
of approved top layer insulation installed as the final membrane substrate. Composite insulation panels may be
used as a top layer placed with the polyisocyanurate side facing down.
Base Sheet: One ply of All Weather/Empire Base Sheet,Ultra Poly SMS,Glas Base,Flex-I Glas Base,Flex-
I Glas FR Base or Poly SMS base adhered in a full mopping of approved asphalt applied within
the EVT range and at a rate of 20-40 lbs./sq
Ply Sheet: (Optional)One or more plies of Flintglas Ply Sheet(Type IV)or Flintglas Premium Ply Sheet
(Type VI)adhered in a full mopping of approved asphalt applied within the EVT range and at a
rate of 20-40 lbs./sq. or one ply of Black Diamond Base Sheet(for use with a torched cap sheet
only)self-adhered.
NOA No.: 14-0224.03
rtwrn•DanE COUNTY Expiration Date: 06/19/18
Approval Date: 04/10/14
Page 7 of 16
Membrane: One ply of Flintlastic GMS,Flintlastic GMS CoolStar,Flintlastic Premium GMS,Flintlastic
Premium GMS CoolStar, Flintlastic FR-P,Flintlastic FR-P CoolStar,Flintlastic Premium FR-
P,Flintlastic Premium FR-P CoolStar,Flintlastic FR Cap sheet,Flintlastic FR Cap Sheet
CoolStar adhered to base/ply sheet with approved mopping asphalt applied within the EVT
range and at a rate of 20 to 40 lbs./sq. or Flintlastic FR Cap T or Flintlastic FR Cap T CoolStar
torch adhered to base/ply sheet.
Surfacing: (Optional)Any coating,listed below,used as a surfacing,must be listed within a current NOA.
Install one of the following:
1. 400-1b./sq. gravel or 300-1b./sq. slag in a flood coat of approved mopping asphalt at an
application rate of 601b./sq.
2. Karnak(#97 AF)Fibrated Aluminum Roof Coating,F1intCoat A-150,APOC#212
Fibrated Aluminum Roof Coating at an application rate of 1 %Z gal./sq.
Maximum Design
Pressure: -52.5 psf(See General Limitation#7)
NOA No.: 14-0224.03
QM[AMI-DADECounirir Expiration Date: 06/19/18
Approval Date: 04/10/14
Page 8 of 16
Membrane Type: APP Modified
Deck Type 1I: Wood,Insulated
Deck Description: Minimum 19/32"thick plywood attached using approved nails spaced 4"o.c. at wood joists
spaced maximum 24"o. c.
System Type A(3): Anchor sheet mechanically fastened; all layers of insulation adhered with approved asphalt.
All General and System Limitations apply.
Anchor Sheet: One ply of All Weather/Empire Base Sheet,G1asBase or Flintglas Premium Ply Sheet(Type VI)
mechanically attached as detailed below.
Fastening: Anchor sheet shall be lapped 4" and fastened with 1 I ga. annular ring shank nails and approved
tin caps 8"o.c. in the lap and three rows staggered in the center of the sheet 8"o.c.
One or more layers of any of the following insulations.
Insulation Laver Insulation Fasteners Fastener
Table 3 Density/ft2
ACFoam-H,Multi-Max FA-3,ENRGY 3,FlintBoard ISO,H-Shield
Minimum 1.5"thick N/A N/A
Note: All insulation shall be adhered to the anchor sheet in full mopping of approved hot asphalt within the
EVT range and at a rate of 20-40 lbs./100 W. Please refer to Roofing Application Standard RAS 117 for
insulation attachment. Insulation listed as base layer only shall be used only as base layers with a second layer
of approved top layer insulation installed as the final membrane substrate. Composite insulation panels may be
used as a top layer placed with the polyisocyanurate side facing down.
Base: One ply of Black Diamond Base Sheet self-adhered.
Ply Sheet: (Optional)One ply of All Weather/Empire Base Sheet,Ultra Poly SMS,Glas Base,Flex-I Glas
Base,Flex-I Glas FR Base or Poly SMS base or one or more plies of Flintglas Ply Sheet(Type
IV)or Flintglas Premium Ply Sheet(Type VI)adhered in a full mopping of approved asphalt
applied within the EVT range and at a rate of 20-40 lbs./sq. or one ply of Black Diamond Base
Sheet self-adhered or Flintlastic STA torch adhered.
Membrane: Flintlastic GTA,Flintlastic GTA CoolStar,Flintlastic GTA-FR or GTA-FR CoolStar torch
adhered to base or ply sheet.
Surfacing: (Optional)Any coating,listed below,used as a surfacing,must be listed within a current NOA.
Install one of the following:
1. 400-Ib./sq. gravel or 300-1b./sq. slag in a flood coat of approved mopping asphalt at an
application rate of 60 lb./sq.
2. Karnak(#97 AF)Fibrated Aluminum Roof Coating,FlintCoat A-150,APOC#212
Fibrated Aluminum Roof Coating at an application rate of 1 %Z gal./sq.
Maximum Design
Pressure: -60 psf. (See General Limitation#7)
NOA No.: 14-0224.03
MIAMI•DAD,COUNTY Expiration Date: 06/19/18
Approval Date: 04/10/14
Page 9 of 16
Membrane Type: SBS Modified
Deck Type 1I: Wood,Insulated
Deck Description: Minimum 19/32"thick plywood attached using approved nails spaced 4"o.c. at wood joists
spaced maximum 24"o. c.
System Type A(4): Anchor sheet mechanically fastened;all layer of insulation adhered with approved asphalt.
All General and System Limitations apply.
Anchor Sheet: One ply of All Weather/Empire Base Sheet,G1asBase or Flintglas Premium Ply Sheet(Type VI)
mechanically attached as detailed below.
Fastening: Anchor sheet shall be lapped 4" and fastened with 11 ga. annular ring shank nails and approved
tin caps 8"o.c. in the lap and three rows staggered in the center of the sheet 8"o.c.
One or more layers of any of the following insulations.
Insulation Laver Insulation Fasteners Fastener
Table 3 Density/fe
ACFoam-II,ENRGY 3,ENRGY 3 25 PSI,FlintBoard ISO,H-Shield
Minimum 1.5" thick N/A N/A
Approved Perlite
Minimum%" thick N/A N/A
Approved High Density Wood Fiberboard
Minimum'/"thick N/A N/A
DensDeck,DensDeck Prime
Minimum'/4"thick N/A N/A
Note: All insulation shall be adhered to the anchor sheet in full mopping of approved hot asphalt within the
EVT range and at a rate of 20-40 lbs./100 W. Please refer to Roofing Application Standard RAS 117 for
insulation attachment. Insulation listed as base layer only shall be used only as base layers with a second layer
of approved top layer insulation installed as the final membrane substrate. Composite insulation panels may be
used as a top layer placed with the polyisocyanurate side facing down.
Base Sheet: One ply of All Weather/Empire Base Sheet,Ultra Poly SMS,Glas Base,Flex-I Glas Base,Flex-
I Glas FR Base or Poly SMS base adhered in a full mopping of approved asphalt applied within
the EVT range and at a rate of 20-40 lbs./sq
Ply Sheet: (Optional)One or more plies of Flintglas Ply Sheet(Type IV)or Flintglas Premium Ply Sheet
(Type VI)adhered in a full mopping of approved asphalt applied within the EVT range and at a
rate of 20-40 lbs./sq. or one ply of Black Diamond Base Sheet(for use with a torched cap sheet
only)self-adhered.
NOA No.: 14-0224.03
MIAMI•DAD'COUNTY�UzlgExpiration Date: 06/19/18
Approval Date: 04/10/14
Page 10 of 16
Membrane: One ply of Flintlastic GMS,Flintlastic GMS CoolStar,Flintlastic Premium GMS,Flintlastic
Premium GMS CoolStar, Flintlastic FR-P,Flintlastic FR-P CoolStar,Flintlastic Premium FR-
P,Flintlastic Premium FRP CoolStar,Flintlastic FR Cap sheet,Flintlastic FR Cap Sheet
CoolStar adhered to base/ply sheet with approved mopping asphalt applied within the EVT
range and at a rate of 20 to 401bs./sq. or Flintlastic FR Cap T or Flintlastic FR Cap T CoolStar
torch adhered to base/ply sheet.
Surfacing: (Optional)Any coating, listed below,used as a surfacing,must be listed within a current NOA.
Install one of the following:
1. 400-Ib./sq. gravel or 300-1b./sq. slag in a flood coat of approved mopping asphalt at an
application rate of 60 lb./sq.
2. Karnak(#97 AF)Fibrated Aluminum Roof Coating,FlintCoat A-150,APOC 9212
Fibrated Aluminum Roof Coating at an application rate of 1 %2 gal./sq.
Maximum Design
Pressure: -60 psf. (See General Limitation#7)
NOA No.: 14-0224.03
MIAMI•DAD;COUFlUaWNTY NIJ Expiration Date: 06/19/18
Approval Date: 04/10/14
Page 11 of 16
Membrane Type: APP Modified
Deck Type 1I: Wood,Non-Insulated
Deck Description: 19/32" or greater plywood or wood plank
System Type E(1): Base sheet mechanically fastened.
All General and System Limitations apply.
Base Sheet: One ply of All Weather/Empire Base Sheet,Glas Base or Flintglas Premium Ply Sheet(Type
VI)mechanically attached as detailed below.
Fastening: Base sheet shall be lapped 4" and fastened with 11 ga. annular ring shank nails and approved tin
caps 8"o.c. in the lap and three rows staggered in the center of the sheet 8"o.c.
Ply Sheet: (Optional)One ply of All Weather/Empire Base Sheet,Ultra Poly SMS,Glas Base,Flex-I Glas
Base,Flex-I Glas FR Base or Poly SMS or one or more plies of Flintglas Ply Sheet(Type IV)or
Flintglas Premium Ply Sheet(Type VI)adhered in a full mopping of approved asphalt applied
within the EVT range and at a rate of 20-40 lbs./sq. or one ply of Black Diamond Base Sheet
self-adhered or Flintlastic STA torch adhered.
Membrane: Flintlastic GTA,Flintlastic GTA CoolStar,Flintlastic GTA-FR or GTA-FR CoolStar torch
adhered to base/ply sheet.
Surfacing: (Optional)Any coating,listed below,used as a surfacing,must be listed within a current NOA.
Install one of the following:
1. 400-1b./sq. gravel or 300-1b./sq. slag in a flood coat of approved mopping asphalt at an
application rate of 60 lb./sq.
2. Karnak(497 AF)Fibrated Aluminum Roof Coating,FlintCoat A-150,APOC#212
Fibrated Aluminum Roof Coating at an application rate of 1 %2 gal./sq
Maximum Design
Pressure: -52.5 psf. (See General Limitation#7)
WMIAMIOADENOA No.: 14-0224.03
Fgjgxs courtr�r Expiration Date: 06/19/18
Approval Date: 04/10/14
Page 12 of 16
Membrane Type: SBS Modified
Deck Type 1I: Wood,Non-Insulated
Deck Description: 19/32" or greater plywood or wood plank
System Type E(2): Base sheet mechanically fastened.
All General and System Limitations apply.
Base Sheet: One ply of All Weather/Empire Base Sheet,Glas Base or Flintglas Premium Ply Sheet(Type
VI)mechanically attached as detailed below.
Fastening: Base sheet shall be lapped 4" and fastened with 11 ga. annular ring shank nails and approved tin
caps 8"o.c. in the lap and three rows staggered in the center of the sheet 8"o.c.
Ply Sheet: (Optional)One ply of All Weather/Empire Base Sheet,Ultra Poly SMS,Glas Base,Flex-I Glas
Base,Flex-I Glas FR Base or Poly SMS or one or more plies of Flintglas Ply Sheet(Type IV)or
Flintglas Premium Ply Sheet(Type VI)adhered in a full mopping of approved asphalt applied
within the EVT range and at a rate of 20-40 lbs./sq. or one ply of Black Diamond Base Sheet
self-adhered or Flintlastic STA torch adhered.
Membrane: One ply of Flintlastic GMS,Flintlastic GMS CoolStar,Flintlastic Premium GMS,Flintlastic
Premium GMS CoolStar,Flintlastic FR-P,Flintlastic FR-P CoolStar,Flintlastic Premium FR-P,
Flintlastic Premium FR-P CoolStar,Flintlastic FR Cap Sheet,Flintlastic FR Cap Sheet CoolStar
adhered to ply sheet with approved mopping asphalt applied within the EVT range and at a rate
of 20 to 40 lbs./sq. or Flintlastic FR Cap T or Flintlastic FR Cap T CoolStar torch adhered to
ply sheet.
Surfacing: (Optional)Any coating,listed below,used as a surfacing,must be listed within a current NOA.
Install one of the following:
1. 400-1b./sq. gravel or 300-1b./sq. slag in a flood coat of approved mopping asphalt at an
application rate of 601b./sq.
2. Karnak(#97 AF)Fibrated Aluminum Roof Coating,FlintCoat A-150,APOC#212
Fibrated Aluminum Roof Coating at an application rate of 1 %2 gal./sq
Maximum Design
Pressure: -52.5 psf. (See General Limitation#7)
NOA No.: 14-0224.03
Muu�i•oanE courrnr Expiration Date: 06/19/18
Approval Date: 04/10/14
Page 13 of 16
Membrane Type: APP Modified
Deck Type 1I: Wood,Non-Insulated
Deck Description: Minimum 19/32"thick plywood attached using approved nails spaced 4"o.c. at wood joists
spaced maximum 24"o. c
System Type E(3): Base sheet mechanically fastened.
All General and System Limitations apply.
Base Sheet: One ply of All Weather/Empire Base Sheet,G1asBase or Flintglas Premium Ply Sheet(Type VI)
mechanically attached as detailed below.
Fastening: Base sheet shall be lapped 4" and fastened with 11 ga. annular ring shank nails and approved tin
caps 8"o.c. in the lap and three rows staggered in the center of the sheet 8"o.c.
P1y'Sheet: (Optional)One ply of All Weather/Empire Base Sheet,Ultra Poly SMS,Glas Base,Flex-I Glas
Base,Flex-I Glas FR Base or Poly SMS or one or more Flintglas Ply Sheet(Type IV)or
Flintglas Premium Ply Sheet(Type VI)adhered in a full mopping of approved asphalt applied
within the EVT range and at a rate of 20-40 lbs./sq. or one ply of Black Diamond Base Sheet
self-adhered or Flintlastic STA torch adhered.
Membrane: Flintlastic GTA,Flintlastic GTA CoolStar,Flintlastic GTA-FR or GTA-FR CoolStar torch
adhered to base/ply sheet.
Surfacing: (Optional)Any coating,listed below,used as a surfacing,must be listed within a current NOA.
Install one of the following:
1. 400-Ib./sq. gravel or 300-Ib./sq. slag in a flood coat of approved mopping asphalt at an
application rate of 60 Ib./sq.
2. Karnak(#97 AF)Fibrated Aluminum Roof Coating,F1intCoat A-150,APOC#212
Fibrated Aluminum Roof Coating at an application rate of 1 %2 gal./sq
Maximum Design
Pressure: -60 psf. (See General Limitation#7)
NOA No.: 14-0224.03
QMMIAMI-DMADE COUNTY Expiration Date: 06/19/18
Approval Date: 04/10/14
Page 14 of 16
Membrane Type: SBS Modified
Deck Type 1I: Wood,Non-Insulated
Deck Description: Minimum 19/32"thick plywood attached using approved nails spaced 4"o.c. at wood joists
spaced maximum 24"o. c
System Type E(4): Base sheet mechanically fastened.
All General and System Limitations apply.
Base Sheet: One ply of All Weather/Empire Base Sheet,G1asBase or Flintglas Premium Ply Sheet(Type VI)
mechanically attached as detailed below.
Fastening: Base sheet shall be lapped 4" and fastened with 11 ga. annular ring shank nails and approved tin
caps 8"o.c. in the lap and three rows staggered in the center of the sheet 8"o.c.
Ply Sheet: (Optional)One ply of All Weather/Empire Base Sheet,Ultra Poly SMS,Glas Base,Flex-I Glas
Base,Flex-I Glas FR Base or Poly SMS or one or more plies of Flintglas Ply Sheet(Type IV)or
Flintglas Premium Ply Sheet(Type VI)adhered in a full mopping of approved asphalt applied
within the EVT range and at a rate of 20-40 lbs./sq. or one ply of Black Diamond Base Sheet
self-adhered or Flintlastic STA torch adhered.
Membrane: One ply of Flintlastic GMS,Flintlastic GMS CoolStar,Flintlastic Premium GMS,Flintlastic
Premium GMS CoolStar,Flintlastic FR-P,Flintlastic FR-P CoolStar,Flintlastic Premium FR-P,
Flintlastic Premium FRP CoolStar,Flintlastic FR Cap Sheet,Flintlastic FR Cap Sheet CoolStar
adhered to ply sheet with approved mopping asphalt applied within the EVT range and at a rate
of 20 to 401bs./sq. or Flintlastic FR Cap T or Flintlastic FR Cap T CoolStar torch adhered to
ply sheet.
Surfacing: (Optional)Any coating,listed below,used as a surfacing,must be listed within a current NOA.
Install one of the following:
1. 400-1b./sq. gravel or 300-1b./sq. slag in a flood coat of approved mopping asphalt at an
application rate of 60 lb./sq.
2. Karnak(#97 AF)Fibrated Aluminum Roof Coating,F1intCoat A-150,APOC#212
Fibrated Aluminum Roof Coating at an application rate of 1 %2 gal./sq
Maximum Design
Pressure: -60 psf. (See General Limitation#7)
NOA No.: 14-0224.03
MIAMI•DAD'COUNTY Expiration Date: 06/19/18
Approval Date: 04/10/14
Page 15 of 16
WOOD DECK SYSTEM LIMITATIONS:
1. A slip sheet is required with Ply 4 and Ply 6 when used as a mechanically fastened base or anchor sheet.
GENERAL LIMITATIONS:
1. Fire classification is not part of this acceptance; refer to a current Approved Roofing Materials Directory for fire
ratings of this product.
2. Insulation may be installed in multiple layers. The first layer shall be attached in compliance with Product Control
Approval guidelines. All other layers shall be adhered in a full mopping of approved asphalt applied within the
EVT range and at a rate of 20-40 lbs./sq.,or mechanically attached using the fastening pattern of the top layer
3. All standard panel sizes are acceptable for mechanical attachment. When applied in approved asphalt,panel size
shall be 4'x 4'maximum.
4. An overlay and/or recovery board insulation panel is required on all applications over closed cell foam insulations
when the base sheet is fully mopped. If no recovery board is used the base sheet shall be applied using spot
mopping with approved asphalt, 12" diameter circles, 24" o.c.; or strip mopped 8" ribbons in three rows, one at
each side lap and one down the center of the sheet allowing a continuous area of ventilation. Encircling of the
strips is not acceptable. A 6" break shall be placed every 12' in each ribbon to allow cross ventilation. Asphalt
application of either system shall be at a minimum rate of 12 lbs./sq.
Note: Spot attached systems shall be limited to a maximum design pressure of-45 psf.
5. Fastener spacing for insulation attachment is based on a Minimum Characteristic Force(F')value of 2751bf.,as
tested in compliance with Testing Application Standard TAS 105. If the fastener value,as field-tested,are below
2751bf. insulation attachment shall not be acceptable.
6. Fastener spacing for mechanical attachment of anchoribase sheet or membrane attachment is based on a minimum
fastener resistance value in conjunction with the maximum design value listed within a specific system. Should
the fastener resistance be less than that required,as determined by the Building Official,a revised fastener spacing,
prepared,signed and sealed by a Florida registered Professional Engineer,Registered Architect,or Registered
Roof Consultant may be submitted. Said revised fastener spacing shall utilize the withdrawal resistance value
taken from Testing Application Standards TAS 105 and calculations in compliance with Roofing Application
Standard RAS 117.
7. Perimeter and corner areas shall comply with the enhanced uplift pressure requirements of these areas. Fastener
densities shall be increased for both insulation and base sheet as calculated in compliance with Roofing
Application Standard RAS 117. Calculations prepared, signed and sealed by a Florida registered Professional
Engineer, Registered Architect, or Registered Roof Consultant (When this limitation is specifically referred
within this NOA,General Limitation#9 will not be applicable.)
8. All attachment and sizing of perimeter nailers,metal profile,and/or flashing termination designs shall conform to
Roofing Application Standard RAS 111 and applicable wind load requirements.
9. The maximum designed pressure limitation listed shall be applicable to all roof pressure zones(i.e. field,
perimeters,and corners).Neither rational analysis,nor extrapolation shall be permitted for enhanced fastening at
enhanced pressure zones(i.e.perimeters,extended corners and corners). (When this limitation is specifically
referred within this NOA,General Limitation 97 will not be applicable.)
10. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 61G20-3 of the Florida Administrative Code.
END OF THIS ACCEPTANCE
NOA No.: 14-0224.03
MIAMI-DAD�ffgam'COUNTY qli Expiration Date: 06/19/18
Approval Date: 04/10/14
Page 16 of 16
TIF-11) INVOICE
ROOFING SUPPLY GROUPI Invoice#: POL00067779-002
Invoice Date: 04/23/15
Account#: LARRY027
Roofing Supply Group of Polk County Branch : FLWINT00
3595 Recker Highway Phone#: (863)-293-1555
Winter Haven,FL 33880-
- Fax#: Fax:(863)293-1633
Delivery#: POL00067779-002
REMIT TO:
Roofing Supply Group of Polk County
3595 Recker Highway
Winter Haven,FL 33880-
BILL TO:
3376 1 MB 0.435 E0290X 10491 D1314400543 P2551634 0001:0002
���Il�����lf�lll�l�lll�fll�lllll'�������'ll'�'I'lll"III�IIIII�'I SHIP TO: 0001
LARRY NEESE 11 LARRY NEESE 11
2801 SUNRISE BLVD 115 SE SERENATA CT
FORT PIERCE FL 34982-3564 PORT ST LUCIE, FL 34982
-. PO#, -- - --=; RE6-# __..-.-- - . ,..JOB.# - - ORDER.DnTE SHIP-DATE SL u-AGENT ORDER.-TYPE-- ORDERED BY---
115 SE SERENATA 04/21/15 04/23/15 AKEEN WH-DEL
QTY QTY UOM ITEM/DESCRIPTION CONVERTED PRICE/UOM EXTENDED
ORDERED SHIPPED QTY AMOUNT
24 24 RL CRT CP FLNTLSTC GTA WHT 24.00/RL 64.22/RL 1541.28
CERTAINTEED CAP SHEET FLINTLASTIC GTA
WHITE 1SQ
12 12 RL CRT BS EMPR AL WTHR 12.00/RL 44.50/RL 534.00
CERTAINTEED BASE SHEET EMPIRE ALL
WEATHER 2SQ
1 1 BX NL TN CP 1.00/BX 48.00/BX 48.00
NAIL TIN CAP 50#
20 20 PC 3"x3"x10'MTL RF DG WHT 20.00/PC 5.95/PC 119.00
METAL ROOF EDGE WHITE 3"x3"x10'
1 1 CN TROP ASPHLT PRMR 410 QCK DRY SPRY BLK 1.00/CN 10.25/CN 10.25
TROPICAL ASPHALT PRIMER 410 QUICK DRY
SPRAY BLACK
2 2 PA 5GA PK BLDG 950 MDFD FLSHNG CMNT TRWL 2.00/PA 44.00/PA 88.00
GRD
PEAK BUILDING PRODUCTS 950 MODIFIED
FLASHING CEMENT TROWEL GRADE 5GA
******SUB-TOTAL****** 2340.53
Freight Charge 50.00
SALES TAX 152.13
All returned material is subject to a 25%restocking charge. All mE terial picked up is su ject to a 25%
restocking charge.$25.00 Service Charge or maximum allowed by state law on Return d Checks.No return after
30 days.Must have proof of purchase to return material. NO retuni on Special Order/N n Stock/Close Out
Mdse.TERMS:NET CASH unless credit approved at time order iE placed. OPEN ACCOUNTS DUE at Wint rhaven,FL.
PAST DUE and DELINQUENT thereafter subject to FINANCE CH ARGE at the rate of t le lesser of 1 1/2%p r month
(18%per year)or the maximum permitted by state law. Attorney es and court costsill be added if placed
for collection.Payable in Winterhaven,Polk County, Florida.
GO FROM GETTING A STATEMENT TO MAKING A STATEMENT
We offer three convenient ways for you to receive your invoices: email,fax or Invoice Gateway,our secure online site. With Invoice
Gateway,you are notified by email when new invoices are posted.
You can search,sort,view,print,download and even pay on this site. Save time and money.Save a tree.Go paperless by choosing one
of the options above and make a statement
Proceed to http://roofingsupplygroup.billtrust.com to get setup today!
TERMS: 1% 10TH,NET 25TH Due Date:05/25/15 BALANCE 2,542.66
You may deduct 23.41 if paid by 05/10/15
All returned material is subject to a 25%restocking charge. All material picked up is subject to a 25%restocking charge.$25.00 Service Charge or maximum allowed by state law on Returned
Checks.No returns after 30 days.Must have proof of purchase to return material.NO return on Special Order/Non Stock/Close Out Mdse.TERMS:NET CASH unless credit approved at time
order is placed. OPEN ACCOUNTS DUE at Winterhaven,FL.PAST DUE and DELINQUENT thereafter subject to FINANCE CHARGE at the rate of the lesser of 1 1/2%per month(18%per
year)or the maximum permitted by state law. Attorney fees and court costs will be added if placed for collection.Payable in Winterhaven,Polk County,Florida.
• • • • • http://roofingsupplygroup.billtrust.com • • SKB PMD KVP
oo0l:0002 Page 1 of 1