HomeMy WebLinkAboutEnergy Calculation Form & Manual J's 05/27/2015 08:42 7724662417
SEACOAST SHEET METAL PAGE 02
tleSt:riptldfk '
Stack flexible elast meric thermal pipe insulation
5'pactHcatinns Catnpl+iefttat r ..
ASTM C 534.Type I-Tubular Grade 1
Apipr4lrata,•06kifia atts„Cctmtfiattcii:
«Manufactured without CFCs,HFCs,HCFCsr PBOEs,or Formaldehyde. •All Atmacett facilities in North America are ISO 9001;2006 certified.
Sp lttartiot:s �y: Won 'Fest M'rrliitodt
Btu-in It� uc°F(WImK)
75aF Wan Temperature(260CJ 0.27(0.0391 ASTM C 177 or C 51R
90OF Mean Temperature(32�Ci 0,276/0.0401
WatorVapor Perrneatrilittr: 0.08(1.18 x ASTM E%,Procedure A
Perm-in,ftAs-m•Pall
Flame Spread and$make 25/50 rated ASTM E 84
aetretoped indAtt
Water Atrsarptlam 0.2% ASTM C209
%by Volume:
Meld Orowth; Passed UL181
F4ngi pteststanca: ASTM G211C1338
aucterisl Resistenem ASTM G22
Upper Use Limlte t 220°F 1105°C} ASTM 0534
Lower Use limit:t -297"F 1.183°CE a ASTM 0534
axone Resisttnce: GOOD
WE 318"1/2".3/4"and 1"110,13.1?hand 25mmJ
Inside Diameter,Tubular 3/8",10 to 4-1/8"10(10mtn Irl to 105mm l01
Langth of sections.Tubular 6'11.83ml
outdoor Use ' No painting is necessary for performance of the product,Woweverr alk eiastomeric-based cetluter
insulation Witt show surface defects after prolonged exposure to VV radiation.Painting will
minimize these defects it installed outdoors,
on the heating cyclo,AC Acedex piper insulation wiilwilbstand temperatures as high as 220°F 1105"C]_520,5209iack or S$0 BLV Adhesive may be used with pips insutadon
api ication8upto220'F(ia5°Cl•
'At temperatures betaw-20°F 1-29°Cl,etaistomeric fnsulation starts to become less firxibte.However,thla characteristic does opt affect thermal efficiency and reslsttinte to water
vapor permeabirdy of A40ftex insulation.
For applications of"40°Fto•297"F f"40"C to•183"01.contact ArmacclL
ARMACELL.LLC
TEL:800.866.5638
FAX:919.304.3847 a r vin a ve-- ell
info.usfaatmatefl.carrt
WWWarmaceLUS
7600 Oakwood Street Extension.Mebane,NC 27302 a d v etn o e d i n S u l a t i O M
Armacolt prvAdes this informatfon asa technlmA seMee.To the anent the tnfornnnion is deriv?d from sourr es otrwrthan Arenacea.Artnacelt le substaniialty,if nm wholly,FAW9 upon
the Other souratlsi to provide accurate roformaVon.information provided as a result of ArmaCeits own technical analysis and testing is accurate to iho extent of our knowledge end
abill%as of date of printing,using effect-1w standardized methods and procedures.Eich user of these products.Orfntorntoon,shout perform their own tests:to detertninc the safety,
titnass and suitability of the pproducts,or combination Of pmdtM for any foreseeable purposes,apDtiGa6ona and usn by the user and by a thud parry to which the our may carw+y
the products,Sim Armacettcarihot control the and use of this reduct,4rmatettdoes not guar4oteethat the user witi obt3m thq.am.res kl.as pubUihcd to 2htL sfOcumant,the data
andinto+Ynation arc provided as a technscQt serufcc and arc subject to change wttnaut notaec-
AGAccofto Submittal 00AAC EngtUSA btM4
,7!12014 Armacvll I.I.C.Printed in United Maws of America