HomeMy WebLinkAboutEvaluation Report Force Engineering&Testing Inc.
19530 Ramblewood Drive
Humble,TS 77338
Product Evaluation Report
GULF COAST SUPPLY& MANUFACTURING, LLC.
26 Ga. 5V Crimp Roof Panel over 15/32"Plywood
Florida Product Approval ## 11651.13 R1
Florida Building Code 2010
Per Rule 9N-3
Method:1—D
Category:Roofing
Subcategory:Metal Roofing
Compliance Method:9N-3.005(1)(d)
NON HVHZ
Product Manufacturer:
GULF COAST SUPPLY&MANUFACTURING, LLC.
4020 S.W.449th Street
Horseshoe Beach,Florida 32648
Engineer Evaluator:
Terrence E.Wolfe, P.E.#44923
Florida Evaluation ANE ID:1920
Validator:
Locke Bowden,P.E.,FL#49704
9450 Alysbury Place
Montgomery,AL 36117
Contents:
Evaluation Report Pages 1—4
,,l�1114111�I1�f!
0
x GE NSF <�f*
Na.4fi9�
STATE OF ;a
AaT. FLOp,-1 ID w�
2W ofykAb
Y2s71s o�f,s�ANAL• fix\
FL#11651.13 R1 February r+��1�, 2012
Force Engineering&Testing Inc.
19530 Ramblewood Drive
Humble,T%77338
Compliance Statement: The product as described in this report has demonstrated compliance with the
Florida Building Code 2010,Sections 1504.3.2.
Product Description: 5V Crimp Roof Panel, 26 Ga. Steel, 24" coverage, through fastened roof panel
with fasteners in the panel flat over Min. 15/32" Plywood decking. Non-
Structural Application.
Panel Material/Standards: Material: Min.26 Ga.Steel,ASTM A792 or ASTM A653 G90 conforming to
Florida Building Code 2010 Section 1507.4.3. Paint finish optional
Yield Strength: Min.80.0 ksi
Corrosion Resistance:Panel Material shall comply with Florida Building Code
2010 Section 1507.4.3.
Panel Dimension(s): Thickness: 0.018"min.
Width: 24"Coverage
Rib Height: 3/8"major rib
Panel Rollformer: Metal Rollforming Systems
Panel Fastener: #9-15 x 1-1/2" Woodgrip with sealing washing in the flat of the panel or
approved equal,V minimum penetration through plywood.
Corrosion Resistance:Per Florida Building Code 2010,Section 1506.6,1507.4.4
Substrate Description: Min.15/32"thick,APA Rated plywood over supports at maximum 24"O.C.
Design of plywood and plywood supports are outside the scope of this
evaluation. Must be designed in accordance w/Florida Building Code 2010.
Design Uplift Pressures:
Table"A"
Maximum Total Uplift Design Pressure: 94.25 psf 131.0 psf
Fastener Pattern: 12"-12" 9.5--2--9.5-
Fastener Pattern: 16"O.C. 16"O.C.
*Design Pressure includes a Safety Factor=2.0.
�`� •G E' ' •h'Q f'r
C
STATE OF
40
1Z ORI 4
MassrAas O'N A L.�`z`� *�
FL#11651.13 R1 February , L012
r��
Force Engineering&Testing Inc.
19530 Ramblewood Drive
Humble,T%77338
Compliance Statement: The product as described in this report has demonstrated compliance with the
Florida Building Code 2010,Sections 1504.3.2.
Product Description: 5V Crimp Roof Panel, 26 Ga. Steel, 24" coverage, through fastened roof panel
with fasteners in the panel flat over Min. 15/32" Plywood decking. Non-
Structural Application.
Panel Material/Standards: Material: Min.26 Ga.Steel,ASTM A792 or ASTM A653 G90 conforming to
Florida Building Code 2010 Section 1507.4.3. Paint finish optional
Yield Strength: Min.80.0 ksi
Corrosion Resistance:Panel Material shall comply with Florida Building Code
2010,Section 1507.4.3.
Panel Dimension(s): Thickness: 0.018"min.
Width: 24"Coverage
Rib Height: 3/8"major rib
Panel Rollformer: Metal Rollforming Systems
Panel Fastener: #9-15 x 1-1/2" Woodgrip with sealing washing in the flat of the panel or
approved equal,%"minimum penetration through plywood.
Corrosion Resistance:Per Florida Building Code 2010,Section 1506.6,1507.4.4
Substrate Description: Min.15/32"thick,APA Rated plywood over supports at maximum 24"O.C.
Design of plywood and plywood supports are outside the scope of this
evaluation. Must be designed in accordance w/Florida Building Code 2010.
Design Uplift Pressures:
Table"A".
Maximum Total Uplift Design Pressure: 94.25 psf 131.0 psf
Fastener Pattern: 12"-12" 9.5"-2--9.5-
Fastener Pattern: 16"O.C. 16"O.C.
*Design Pressure includes a Safety Factor=2.0.
�,1��{f1111f,1tf�t
�•C E, E.• I 41
<�,f'i
No.40
'a STATE OF :a
{ ���
FL#11651.13 R1 Februaryn','
Force Engineering&Testing Inc.
19530 Ramblewood Drive
Humble,T%77338
Code Compliance: The product described herein has demonstrated compliance with
The Florida Building Code 2010,Section 1504.3.2.
Evaluation Report Scope: The product evaluation is limited to compliance with the structural wind load
requirements of the Florida Building Code 2010,as relates to Rule 9N-3.
Performance Standards: The product described herein has demonstrated compliance with:
■ UL 580-06-Test for Uplift Resistance of Roof Assemblies
■ UL 1897-04-Uplift Test for Roof Covering Systems
Reference Data: 1. UL 580-94/1897-98 Uplift Test
Force Engineering&Testing,Inc.(FBC Organization#TST-5328)
Report No.117-0053T-05&117-0331T-08
2. Certificate of Independence
By Terrence E.Wolfe,P.E.(No.44923)@ Force Engineering&Testing,Inc.
(FBC Organization#ANE ID:1920)
Test Standard Equivalency: 1. The UL 580-94 test standard is equivalent to the UL 580-06 test standard.
2. The UL 1897-98 test standard is equivalent to the UL 1897-04 test standard.
Quality Assurance Entity: The manufacturer has established compliance of roof panel products in
accordance with the Florida Building Code and Rule 9N-3.005(3)for
manufacturing under a quality assurance program audited by an approved
quality assurance entity.
Minimum Slope Range: Minimum Slope shall comply with Florida Building Code 2010,including Section
1507.4.2 and in accordance with Manufacturers recommendations. For slopes
less than 3:12,lap sealant must be used in the panel side laps.
Installation: Install per manufacturer's recommended details.
Underlayment: Per Manufacturer's installation guidelines per Florida Building Code 2010 Section
1507.4.5.
Roof Panel Fire Classification: Fire classification is not part of this acceptance.
Shear Diaphragm: Shear diaphragm values are outside the scope of this report.
CG E.Z.
h1O.449�
�°• STATE OF :a
FI,#11651.13 R1 February 22, 2012
Force Engineering&'Testing Inc.
19530 Ramblewood Drive
Humble,T%77338
Design Procedure: Based on the dimensions of the structure,appropriate wind loads are
determined using Chapter 16 of the Florida Building Code 2010 for roof cladding
wind loads.These component wind loads for roof cladding are compared to the
allowable pressure listed above.The design professional shall select the
appropriate erection details to reference in his drawings for proper fastener
attachment to his structure and analyze the panel fasteners for pullout and
pullover.Support framing must be in compliance with Florida Building Code 2010
Chapter 22 for steel,Chapter 23 for wood and Chapter 16 for structural loading.
,; f.'• IVB.473
a• 5TATE OF
* 0�, 'r~ 0 R.,ID , 4.t �
FL#11651.13 R1 February 22, 2012