PAUL WELCH INC.
Mechanical * Electrical * Civil Engineering
1984 S.W. Biltmore St. Suite#114
Port Saint Lucie,FL 34984
Phone (772)785 -9888
Email pwelchinc@aol.com
s
June 17, 2015
Re: Golden Shutter Installation
9650 S. Ocean Dr. (#409)
Jensen Beach,FL 34957
To Whom It May Concern:
Our office has calculated the required design pressures in accordance with ASCE 7-10
and Florida Building Code 2010 for the installation of accordion shutters at the above
referenced address.
Wind speed: Vult: 165 mph, Vasd: 128 mph
Exposure: D
Enclosure Type: Enclosed
Shutter Size: 96"Maximum Height
Shutter Location: Covered Porch(See Attached Sketch)
Required Design Pressure: +29.3 /-39.2 PSF
Shutters to be installed shall be equal to, or exceed the required design pressures as listed
above"Required Design Pressure".
Accordion Shutters shall be installed in accordance with the shutter manufacturer's
installation instructions and Florida Product Approval and Florida Building Code 2010.
Accordion Shutters shall be FL# 389.1.
Thank you for your attention to this matter.
Submitted by:
PA WELCH INC.
-Paul elch,P.E.
Reg. No 29945 =