HomeMy WebLinkAboutProduct Approval r ®IE 'o
r
Certificatoof Pr() Ratings
AHRI Certified Reference Number: 8047442 Date: 7/8/2015 tStatus: Active
Product: Split System: Air-Cooled Condensing Unit, Coil with Blower
Model Number: 38AUZ*25A0*(5,6,1)A*
Indoor Model Number: 40RUAA25A*A(5,6,1)A*
Manufacturer: CARRIER CORPORATION
Trade/Brand name: CARRIER CORPORATION
Series name: CARRIER GEMINI
Rated as follows in accordance with AHRI Standard 340/360-2007, Commercial and Industry Unitary
Air-Conditioning and Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored,
independent,third party testing:
Refrigerant Used: R-41 OA
..Hertz:.- 60
Cooling Capacity(Bfuh) 240000/240000
EER,Rating-(Cooling) "" 11 00/11 00"
LEER r 1
Heating Capacity at 47F(Bfuh)
.€
3
COP at47F
Heating Capacity at 17F(Bfuh)
`SCOP ..........at 17F
Full Load /-door Coil Av Quantity. 83017"
The AHRI 340/360 certified EER ratings in Btu/h/W are calculated under the same methodology as the EER ratings at T1 conditions of ISO 5151:2010 and ISO 13253:2011.
'Ratings followed by an asterisk(')indicate a voluntary rerate of previously published data,unless accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages of any kind arising out of.the use or performance of the product(s),or the
unauthorized alteration of data listed on this Certificate.Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI.This Certificate shall only be used for Individual,personal and
confidential reference purposes.The contents of this Certificate may not,in whole or In part,be reproduced;copied;disseminated;
entered into a computer database;or otherwise utilized,in any form or manner or by any means,except for the user's individual,
personal and confidential reference. AIR-CONDITIONING,HEATING,
CERTIFICATE VERIFICATION &REFRIGERATION INSTITUTE
The information for the model cited on this certificate can be verified at www.ahridirectory.org,dick on"Verify Certificate"link we make life better-
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above,and the Certificate No.,which Is listed at bottom right. " N
1308086861:42798310
@2014 Air-Conditioning, Heating,and Refrigeration Institute CERTIFICATE NO y
w
38AUZ / 38AUD
• Hz AirCooled • • • Unit
Puron@ ' Refrigerant
. to 20 Nominal Tons
Carrier
turn
to the experts
Product Data
Ge
FEATURES BENEFITS
® The Gemini 38AU series outdoor air cooled condensing
units matched with Carrier's 40RU series indoor air
handlers offer a wide variety of options for your HVAC
application needs. Whether it's first cost with the 38AU
M single compressor models or superior part load
performance from the two compressor models, this series
is designed for long, dependable operation as a rooftop or
on-the-ground installation. All Gemini 38AU and 40RU
° series units use environmentally sound Puron R-410A
refrigerant. Together, they create a reliable split system
that provides easy solutions to a wide range of
°0922' commercial HVAC needs.
38AUZ07-14 shown
Constructed for long life
The 38AUZ single circuit and 38AUD dual circuit, scroll
AR`NRA�
compressor models are designed and built to last. The
high efficient designed outdoor coil construction allows
.06MPLIAN?" ]Mron. for a more efficient design in a smaller cabinet size that
utilizes an overall reduction in refrigerant charge. Where
conditions require, special coil coating coil protection
Carrier's air-cooled air conditioning split systems: option is available. Cabinets are constructed of prepainted
•provide a logical solution for commercial needs galvanized steel, delivering unparalleled protection from
•have a rugged,dependable construction the environment. Inside and outside surfaces are protected
to ensure long life, good looks, and reliable operation.
•are available in single and circuit scroll compressor Safety controls are used for enhanced system protection
capacity control and reliability.
•have cooling capability up to 125°F(52°C)ambient Each unit utilizes the Comfort Alert diagnostic and
and down to 40°F(4°C)ambient standard troubleshoot control system. This protects the units
operation and provides valuable diagnostic information
when required.
ELECTRICAL DATA (cont.)
38AUZ25 COOLING WITHOUT POWERED CONVENIENCE OUTLET
V-Ph-Hz VOLTAGE RANGE COMP 1 COMP 2 OFM(ea) POWER SUPPLY
MIN MAX RLA LRA RLA LRA WATTS FLA MCA I Fuse
208/230-3-60 187 253 30.1 225 30.1 225 325 1.5 73.71- 100
460-3-60 414 506 16.7 114 16.7 114 325 0.8 40.8 1 50
575-3-60 1 518 633 12.2 80 12.2 80 325 0.7 30.3 1 40
38AUZ25 COOLING WITH POWERED CONVENIENCE OUTLET
V-Ph-Hz VOLTAGE RANGE COMP 1 COMP 2 OFM(ea) POWER SUPPLY
MIN MAX RLA LRA RLA LRA WATTS FLA MCA Fuse
208/230-3-60 187 253 30.1 225 30.1 225 325 1.5 78.5 100
460-3-60 414 506 16.7 114 16.7 114 325 0.8 43.0 50
575-3-60 518 633 12.2 80 12.2 80 325 0.7 32.0 40
38AUD25 COOLING WITHOUT POWERED CONVENIENCE OUTLET
V-Ph-Hz VOLTAGE RANGE COMP 1 COMP 2 OFM(ea) POWER SUPPLY
MIN MAX RLA LRA RLA LRA WATTS FLA MCA Fuse
208/230-3-60 187 253 30.1 225 30.1 225 325 1.5 73.7 100
460-3-60 414 506 16.7 114 16.7 114 325 0.8 40.8 50
575-3-60 518 633 12.2 80 12.2 80 325 0.7 30.3 40
38AUD25 COOLING WITH POWERED CONVENIENCE OUTLET
VOLTAGE RANGE COMP 1 COMP 2 OFM(ea) POWER SUPPLY
\V-Ph-Hz MIN MAX RLA LRA RLA LRA WATTS FLA MCA Fuse
208/230-3-60 187 253 30.1 225 30.1 225 325 1.5 78.5 100
460-3-60 414 506 16.7 114 16.7 114 325 0.8 43.0 50
575-3-60 518 633 12.2 80 12.2 80 325 0.7 32.0 40
46
• to Ton Direct Expansion
7.5 to Ton ChilledWater
• ' • Air—Handling � Turn to the Experts.
3 a
Product Data
Carrier's versatile packaged air-handling units satisfy
design requirements with:
•Multi-position design for horizontal or vertical
® installation without modification.
e
• Standard sloped drain pans and cleanable insulation
treated with Environmental Protection Agency(EPA)
registered antimicrobial agent improve indoor air
quality.
•High-static design meets a wider range of applications
than competitive packaged air handler lines.
e •Economizer accessory provides ventilation air and
"free"cooling.
® •Cooling coils with mechanically bonded fins provide
peak heat transfer.
•Hot water coil,steam coil,and electric heat accessories
°
are available.
•Standard factory-installed thereto-static expansion
009035 valves(TXT with removable power element on
40RU07 — 12 40RUA units.
•Die-formed galvanized steel casings provide durability
and structural integrity. Optional paint is available.
® FEATURES/BENEFITS
o Easy-to-install and economical 40RU units provide
reliable service.
The 40RU Series air-handling units are the best choice for
packaged air handlers. Model 40RUA units have
direct-expansion coils. All models offer excellent fan
° performance, a unique combination of indoor air quality
° features, easy installation, and affordable prices. Their
° versatility and state-of-the-art features will provide
economical performance now and in the future.
°
Indoor air quality features
The unique combination of features in the 40RU Series air
handlers ensures that clean, fresh, conditioned air is
cosoae
delivered to the occupied space.
40RU14—30 Cooling coils prevent the build-up of humidity in the
room, even during part-load conditions. Unit sizes of 10
tons and above feature dual-circuit face-split coils.
Peron- Two-inch (51-mm) disposable filters remove dust and
airborne particles from the occupied space.
PHYSICAL DATA
4ORUA- English
UNIT 40RUA 07 08 1214 16 2528 30
NOMINAL CAPACITY(Tons) 6 1 71/2 10 121/2 15 20 25 30
OPERATING WEIGHT(lb)
Base Unit with TXV(4 Row) 399 404 425 695 713 730 1050 1062
Plenum 175 175 175 225 225 225 325 325
Economizer 185 185 185 340 340 340 340 340
Hot Water Coil 195 195 195 285 285 285 345 345
Steam Coil 215 215 215 340 340 340 405 405
FANS
Qty...Diam.(in.) 1...15 1...15 1...15 2...15 2...15 2...15 2...18 2...18
Nominal Airflow,(cfm) 2400 3000 4000 5000 6000 8000 10,000 12,000
Airflow Range(cfm) 1800-3000 22503750 3000-5000 3750-6250 4500-7500 6000-10,000 7500-12,500 9000-15,000
Nom.Motor Hp(Standard Motor)*
208/230-1-60 1.3 2.4 - - - - - -
208/230-3-60 and 460-3-60 2.4 2.4 2.4 2.9 3.7 5.0 7.5 10.0
5753-60 1.0 2.0 2.0 3.0 3.0 5.0 7.5 10.0
230-3-50,400-3-50 2.4 2.4 2.9 2.9 2.9 5.0 7.5 10.0
Motor Speed(rpm)
206/230-1-60 1725 1725 - - - - - -
208/2303-60 and 4503-60 1725 1725 1725 1725 1725 1745 1745 1745
5753-60 1725 1725 1725 1725 1725 1745 1755 1755
2303-50,4003-50 1425
REFRIGERANT Puron(R-410A)
Operating charge(lb)
(approx per circuit)t 3.0 3.0 1.5/1.5 2.0/2.0 2.5/2.5 3.5/3.5 4.5/4.5 5.0/5.0
DIRECT-EXPANSION COIL Enhanced Copper Tubes,Aluminum Sine-Wave Fins
Max Working Pressure(psig) 435
Face Area(sq ft) 6.67 8.3310.01 13.25 17.67 19.88 I 24.86 29.83
No.of Splits 1 1 2 2 2 2 2 2
Split Type...Percentage - - Face...50/50
No.of Circuits per Split 12 15 9 12 16 18 20 24
Finsfin. 15 15 17 15 15 17 15 15
STEAM COIL
Max Working Press.(psig at 260°F) 20
Total Face Area(sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0
Rows...Fins/in. 1...9 1...9 1...9 1...10 1...10 1...10 1...10 1...10
HOT WATER COIL
Max Working Pressure(psig) 150
Total Face Area(sq ft) 6.67 I 6.67 6.67 13.33 13.33 13.33 15.0 15.0
Rows...Fins/in. 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...12.5 2...12.5
Water Volume
(gal) 8.3 13.9 14.3
(ft3) 1.1 1.85 1.90
PIPING CONNECTIONS**
Quantity...Size(in.)
DXCoil-Suction(ODF) 1...11/6 1...11/8 2...11/8 2...11/8 I 2...11/8 2...1 1/8 I 2...13/8 I 2...13/8
DX Coil-Liquid Refrig,(ODF) 1...5/8 2..5/8
Steam Coil,In(MPT) 1...21/2 1...21/2
Steam Coil,Out(MPT) 1...11/2 1...11/2
Hot Water Coil,In(MPT) 1...11/2 1...11/2 I 1...2
Hot Water Coil,Out(MPT) 1...11/2 1...11/2 1...2
Condensate(PVC) 1...11/4 ODM/1 IDF
FILTERS Throwaway-Factory-Supplied
Quantity...Size(in.) 4...16 x 24 x 2 4...16 x 20 x2 4...20 x24 x 2
4-16x24x2 4...20 x25 x2
Access Location Right or Left Side
* Refer to Alternate Fan Motor Data table,page 38,for alternate motor data.
t Units are shipped without refrigerant charge.
**All piping sizes are OD inches;equivalent sizes in millimeters follow:
in mm
/8 15.9
11/8 28.6
11/2 38.7
2 50.8
21/2 63.5
4