Product Evaluation Report
GULF COAST SUPPLY& MANUFACTURING, LLC.
26 Ga. GulfRibTm Roof Panel over 75132"Plywood
Florida Product Approval #11651.22 R2
Florida Building Code 2014
Per Rule 61 G20-3
Method: 1 -D
Category: Roofing
Subcategory: Metal Roofing
Compliance Method: 61 G20-3.005(1)(d)
NON HVHZ
Product Manufacturer:
Gulf Coast Supply & Manufacturing, LLC.
14429 SW 2nd Place, Suite G30
Newberry, FL 32669 OP• '• I G
�,\G E N,•s�
*; No, 7,519
Engineer Evaluator: • "
Dan Kuhn, P.E. #75519 "~ = — * �•
Florida Evaluation ANE ID: 10743 �0•, STATE OF
Validator: �'%S�ONAL ENC'a��.•�
Locke Bowden, P.E. #49704 r''''1 I' %%
9450 Alysbury Place 0.6130 y&s
Montgomery, AL 36117
Contents:
Evaluation Report Pages 1 - 5
FL#11651.22 R2•JUNE 15,2015
PRODUCT ® .
ENGINEERING,
11670 ISLAND LAKES LANE, BOCA RATON, • 430464
'F-1 1 PRODUCT.- APPROVAL Gull 'Cozk
SUPPLY & MANUFACTURING
ORJDA
LF-
26 GUAGE GULFRIBPANEL OVER PLYWOOD
FLORIDA PRODUCT APPROVAL NO. 11651.22 R2
TM
Compliance Statement: The product as described in this report has demonstrated compliance with the
Florida Building Code 2014, Sections 1504.3.2.
Product Description: GulfRibTM' 3/4" Rib Roof Panel, Minimum 26 Ga. Steel, 36" Coverage,
through fastened roof panel over minimum 15/32" Plywood Decking. Non
Structural application.
Panel Material/Standards: Material: Minimum 26 Ga. Steel, ASTM A792 or ASTM A653 G90 conforming to
Florida Building Code 2014 Section 1507.4.3.
Paint Finish Optional
Yield Strength: Min. 80.Oksi
Corrosion Resistance: Panel Material shall comp i II de
2014 Section 1507.4.3.
Panel Dimension(s): Thickness: 0.018" Minimum
Width: 36" Coverage
Rib Height: 3/4" Major Rib at 9" O.C.
Panel Fastener: #9-15x1.5" HWH with sealing washing or approved equal
'/4" minimum.penetration through plywood.
Corrosion Resistance: Per Florida Building Code 2014, Section 1506.6, 1507.4.4
Substrate Description: Minimum 15/32" thick, APA Rated plywood over supports at maximum 24" O.C.
Design of plywood and plywood supports are outside the scope of this evaluation.
Must be designed in accordance w/Florida Building Code 2014.
Design Uplift Pressures: Table"A"
Maximum Total Uplift Design Pressure�T ,'q 25 psf ; . 159.25 psf
Fastener Pattern 9"-9"-9"-9" 6.5"-2.5"-6.5"-
2.5"6.5"-2.5"-6.5"
Fastener Patt""',"S acrng ' r '.2°4�"
Design Pressure includes a Safety Factor=2.0.
FL#11651.22 R2•JUNE 15,2015
'PRODUCT e e .
KUHN ENGINEEWNG, LLC
• . , . • . • . G ulfCoast
SUPPLY & MANUFACTURING
I IV!
G U L F-- -5XN-�
26
GUAGE GULFRIB TM PANEL OVER • •D
FLORIDA PRODUCT APPROVAL NO 11651.22 I
TM
Code Compliance: The product described herein has demonstrated compliance with the
Florida Building Code 2014, Sections 1504.3.2.
Evaluation Report Scope: The product evaluation is limited to compliance with the structural wind load
requirements of the Florida Building Code 2014, as relates to Rule 61 G20-3.
Performance Standards: The product described herein has demonstrated compliance with:
• UL 580-06-Test for Uplift Resistance of Roof Assemblies
• UL 1897-04- Uplift Test for Roof Covering Systems.
Reference Data: 1. UL 580-94/1897-98 Uplift Test
Force Engineering &Testing, Inc. (FBC Organization #TST-5328)
Report No. 117-0062T-07A, B, Dated 02/19/2007
2. Certificate of Independence
By Dan Kuhn, P.E. (FL#75519)@ Kuhn Engineering, LLC
(FBC Organization #ANE ID: 10743)
Test Standard Equivalence: 1. The UL 580-94 test standard is equivalent to the UL 580-06 test standard.
2. The UL 1897-98 test standard is equivalent to the UL 1897-04 test
standard.
Quality Assurance Entity: The manufacturer has established compliance of roof panel products in
accordance with the Florida Building Code and Rule 61 G20-3.005(3)for
manufacturing under a quality assurance program audited by an approved quality
assurance entity.
Minimum Slope Range: Minimum Slope shall comply with Florida Building Code 2014, including
Section 1507.4.2 and in accordance with Manufacturers recommendations. For
slopes less than 3:12, lap sealant must be used in the panel side laps.
Installation: Install per Manufacturer's recommended details.
Underlayment: Shall comply with Florida Building Code 2014 section 1507.4.5.1 and 1507.4.5.2.
FL#11651.22 R2•JUNE 15,2015
PRODUCT EVAIUAT.110,11\11 REPORT
A :P-RODUCT APPROVAL GullCoast
SUPPLY & MA.NUFACTURIN-6
n�
GULF "-
26 GLIAGE GULFRIB TM PANEL OVER 15/32" PLYWOOD
FLORIDA PROD APPROVALNO 11651.22 r;:2
TNt
Roof Panel Fire Classification: Fire classification is not part of this acceptance.
Shear Diaphragm: Shear Diaphragm values are outside the scope of this report.
Design Procedure: For roofs within the parameters listed on the load table, fastening pattern must
at a minimum meet those listed for the applicable wind zone. For all roofs outside
the parameters listed on the load table, design wind loads shall be determined
for each project in accordance with FBC 2014 Section 1609 or ASCE 7-10
using allowable stress design.The maximum fastener spacing listed herein shall
not be exceeded. This evaluation report is not applicable in High Velocity
Hurricane Zone. Refer to current NOA or HVHZ evaluation report for use of this
product in High Velocity Hurricane Zone.
FL#11651.22 R2•JUNE 15,2015
p e
ISLAND11670 LAKES LANE, BOCA RATON, •
r
G61i�co St
SUPPLY & MANUFACTURING
G U L F lluro'\� ILI L-2-3
26 GUAGE
' PANEL OVER PLYWOOD
FLORIDA PRODUCT APPROVAL NO. 11651.22 R2
Tlvt
ENGINEER LOAD TABLE:26 Ga. GulfRibTM Panel over 15/32" Plywood
Buildings having a Roof Mean Height<—20'-0"; Roof Slope: 2"/12" - 12"/12``.Gable or Hip Roof; Wind Speeds 120-
180mph, Exposure C, Risk Category II, Enclosed Building, based on Florida Building Code
120 130 140 1500 180
WIIND FASTENER SUBSTRATE ,TU
SPEED (MIN.1/4" (MIN.15/32") ON CENTER ON CENTER ON CENTER ON CENTER ON CENTER ON CENTE CENTER
Penetration) SPACING SPACING SPACING SPACING SPACING SPACING SPACING
ZONE 1 #9-15x1.5" Plywood 24",TYPE 1 24",TYPE 1 24",TYPE 1 24",TYPE 1 24",TYPE 1 24",TYPE 1 '24",TYPE.1'
ZONE 2 #9-15x1.5" Plywood 24",TYPE 1 24",TYPE 1 24",TYPE 1 24",TYPE 1 24",TYPE 1 24",TYPE 1 12",TYPE 2
ZONE 3 #9-15X1.5 Plywood 24",TYPE 1 24",TYPE 1 24",TYPE 1 12",TYPE 2 12",TYPE 2 12"'TYPE 2. 12",TYPE 2
1.)PANEL DESCRIPTION:GULFRIBTM, MIN. 26 GA., GRADE 80,36"COVERAGE,3/4"TALL.
2.)PANEL FASTENER:#9-15X1.5" HWH WITH SEALING WASHER OR APPROVED EQUAL
3.)MAXIMUM ALLOWABLE PANEL UPLIFT PRESSURE:69.25 PSF @ 24" O.C. FASTENER SPACING TYPE I FASTENER PATTERN, 159.25
PSF @ 12" O.C. FASTENER SPACING TYPE 2 FASTENER PATTERN BASED ON TAS 125, UL 580/UL 1897 TESTING.
4.)PLYWOOD DECKING:MIN.15/32"THICK PLYWOOD MUST BE DESIGNED IN ACCORDANCE WITH FLORIDA BUILDING CODE 2014.
5.)ROOF SLOPE: ON ROOF SLOPES LESS THAN 3:12, LAP SEALANT MUST BE USED IN PANEL SIDE LAPS.
6.)LOAD TABLE BASED ON WIND PRESSURES CALCULATED PER ASCE 7-10(KD=0.85)MULTIPLIED BY 0.6 PER FLORIDA BUILDING
CODE 2014
ZONE 2 HIP ROOF a Note:Dimension(a)is defined as 10%of the minimum width of the building or
ZONE T 1 40%of the mean height of the roof,whichever is smaller,however,(a)cannot be
------------------ a less than either 4%of the minimum width of the building or 3 feet.
\ / TYPE 1 FASTENER PATTERN
I � � RIDGE i � I
i �g" 9 y99
At Panel Lep
ZONE 1 Cont.Tape Seal for use on Slopes less than 3:12
i \ ` (1)#9.15 x 1-1/2'w/Sealer Washer @ 24'O.C.Max.
-------------------
-EAVE
ZONE 2 TYPE 2 FASTENER PATTERN
GABLE ROOF Tal 6.5" 2.5" 6.5" 2.5' 6.5" 2.5" 6.5" 2.5'
—!— -----------------is
I I
RIDGE L Cont.Tape Seal for use on Slopes less than 3:12
I (1)#9.15 x 1-t/2'w/Sealer Washer @ 12'O.C.Max.
------ -- ------------- a
--
+----------------------+ a
ZONE 1
I I
.4----------------------
�ZONE3 -EAVE
FL#11651.22 R2•JUNE 15,2015
'PRODUCT
e , EVALUATION
ENGINEERING,KUHN
RECOMMENDED WASHERS&FASTENERS: FBC Approved Installation Instructions
Metal structures:Self-Drilling Tapping Screw �� To obtain FBC approval,certain installation
Wood structures:Tapping Screw +5 F� requirements must be met The icon show at left
is used within this guide to call out optional FBC- O
Side Stitching:Sharp Point Self-Tapping Screw REQUIREMENT
® approved installation methods and requirements.
Washer:Palram metal washer with EPDM gasket(see figures
15a,15b,and 15c;15crequiredfor FBC-approved installations) For information about Florida Building Code requirements, '' '
SUNSKY .
Grommet:Expanding rubber fastener visit the FBC web site at:http://www.floridabuilding.org.
Product approval numbers are 11238(roof decks)and 11240 Premium Corrugated Polycarbonate Panels
(see fig.15d&16b;required for FBC-approved installations) (structural walls).
Palram Metal Washers w/Concave EPDM Gasket
Authorized Palram Dealer -�
3/4"09 mm) 1"(25 mm)
t / i
Washer/gasket Washer/gasket
Figure 15a Figure 15b I
Metal Washer Grommet
w/EPDM Gasket Fastener
e
'RE
REVU(RElIENT
#12-140-1/4"HWH w/1-1/8"
Oversize Bonded Washer 1/4"x I"Grommet
(pre-drlllingw/oversizeholesrequired) (pre-drilling required)
Figure 15c Figure 15dInstallation
Stitch Screw Grommet Overview
PALRAM AMERICAS IMPORTANT
Zf 1— 9735 Commerce Circle,Kutztown,PA 19530
Phone:800-999-9459•Fax:610-285-9928 This is an abbreviated installation overview for
' Web Site:www.PalramAmericas.com SunSky Premium Polycarbonate Panels. F•
complete installationdetails, • 1
Figure 16a Figure 16b Inasmuch as Palram Americas has no control over the use to which others may put the -• • •e, , ,•
product,it does not guarantee that the same results as those described herein will be
obtained.Each user of the product should make his own tests to determine the product's www.P�lramAmericas.com, or by • •
suitability for his own particularuse Including the suitability of environmental conclitionsfor Palram Americas by• • 80 )999-9459.
SUGGESTED FASTENER TYPES AND PLACEMENT the product.Statements concerning possible or suggested uses of the products described
herein are not to be construed as constituting a license under any Palram Americas patent
SunSky 9" SunSky 12" covering such use or as recommendations for use of such products In the infringement of
any patent.Palram Americas or Its distributors cannot be held responsible for any losses
Fastening 1/4"X 2" 1/4"X 2-1/2" Incurred through Incorrect installation of the product In accordance with our company
g policy of continual product development you are advised to check with your local Palram
at crown with 3/4"washer with I"washer Americas supplier'to ensure that you have obtained the most up to date information.
Fastening 1/4"x1-1/2" 1/4"X1-1/2" Palram Americas reserves the right to change product specifications Build On.
atvalley with 1"washer with 1"washer and/or information contained in this brochure without notice.
Form#507 Revised 08.29.11 SCS
BEFORE YOU BEGIN INSTALLATION NOTES IMPORTANT INSTALLATION COMMENTS
Be sure to read these instructions completely before beginning. To Cut Panels:Use a circular saw with small teeth rotating at high Avoid overtightening the fasteners.Allow gaskets to squeeze
Before installation,check local building codes for relevant specifica- speed;advance saw slowly.A portable electric saw(jig saw)or sheet slightly until full contact with panel.Overtightening induces
tions and recommendations.Follow local codes at all times. metal shears can also be used.Support the sheet in the vicinity of the undue internal stresses,leading to premature failure.Regular
Transportation,Handling and Storage:Transport and store SunSky
cut;clean away debris after cutting. Washer/Gaskets(Tek Screws)for metal panels apply excessive
panels horizontally,on flat,sturdy pallets,equal or longer than the Drilling:Use a power drill with standard high speed bit intended for pressure,are inadequate for SunSky sealing,and cause undue
metal,rotating at about 1000 rpm. internal stresses in the panel.The stresses result in crazing,frac-
longestpanels.Short panels should be secured and fastened to the g P tures,and eventual failure.
pallet during transportation.Do not transport,leave or store panels Sealants:Use only Palram approved sealants.
in direct sun before installation.For outdoor storage,coverthe panels Visit www.Pairamamericas.com/sealants for the most up to date list. /� -IN
securely with a white opaque polyethylene sheet,corrugated card-
board,or other materials that do not absorb or conduct heat Sealing Tape:Side-laps and end-laps of any SunSky profile should
be treated with butyl rubber sealing strips,placed between the
INSTALLATION STEPS overlapping panels at all edges.In shallow pitch roofs(less than 5%) 90
Apply the sealing tape along the purlin line 2"to 4"above and below double(parallel)sealing strips are recommended at end-laps.
the SunSky panel.Apply the sealing tape to the corrugation crests Panel Orientation:SunSky's exterior surface is UV resistant,indi-
immediately adjacent to the opening as shown. cated by labeled strips on the protected side.Install panel with la- Never apply paints,shading compounds,paint thinners or any
beled side out.The protected side is up when panel edges are both material that may chemically attack SunSky,without first verifying
Place the SunSky panel exactly in place.Attach the SunSky panel pointing down.For multi-panel runs,begin installation of SunSky on compatibility to the panel by contacting Palram Americas or its
with 1"(25mm)fasteners with _ _ the side away from wind and rain direction. distributor,or refer to www.Pairamamericas.com/sealants for the
Palram-approved bonded washer/ z most up to date list.
Roof Pitch:SunSky performs best when installed at pitch rates of
gaskets.NEVER USE SOFT PVC 10%or more.When installed at a lower pitch,additional sealing Use only Palram approved sealants.Incompatible sealing or bonding
(vinyl)washer/gaskets.5oft PVC is - _'- should be applied to insure weather resistance.We recommend a material may damage the panels,causing failure that is not covered
totally incompatible with polycar- minimum 5%pitch rate. by the limited warranty.For the name of an approved sealing or bond-
bonate and will harm the panel. - ing product,consult your Dealer,Distributor,or Palram Americas.
NEVER USE NAILS to fasten SunSky _ -_- Safety Measures:Use ladders,crawling boards and other safety
anels.The use of nails can damage = - equipment required for safe installation.Use all safety measures re
P 9 Prior to installing clear SunSky,it is advisable to paint purlins using
theanel at the fastening point. quired according to local safety regulations.Do not step on installed
P 9 P white acrylic paint,or to to cover with aluminum tape,in order to
Usingnails will also prevent the _ _ __ .__ - panels between purlins.Never leave SunSky panels unattended
P prevent over-heating and/or charring of the purlins.
panel from properly expanding and on the roof until all the required fasteners have been appropriately
contracting with temperature change,thus resulting in buckling. For installed or the panels secured to the supporting structure. SunSky profiles were designed to closely match commonly used
panels longer than 12;pre-drill panels at all fastening points with Extra Fastening:On length runs,where SunSky overlaps metal metal profiles.Other panels,appearing to be similar,differ in small but
a 3/8"hole to allow for increased expansion and contraction due to panels on both sides,we recommend side stitching fasteners con- important ways and an exact match may be difficult to achieve. Slight
longer length.For panels 12'in length or less,pre-drill a hole 1/16" necting the SunSky to the frame.These should be spaced along the detail differences such as corrugation height,slant,wave distance etc.
larger than the diameter of the fastener shank.Palram recommends side-laps about 12"to 16"apart. will hinder exact matching of such a panel with a SunSky profile.This
that Sunsky panels are not installed below 40°F or above 80°F. may lead to insufficient sealing,water leakage and forced installation,
putting undue stresses on the SunSky panel while trying to adapt it to
POSITIONING OF FASTENERS I an"almost similar"metal profile.Undue stress may lead to premature
Install the fasteners along the purlin line as shown below. - failure,which is not covered by the limited warranty.
SunSky 12" Figure 14a I I I I I I I I I I MAXIMUM RECOMMENDED LOADS
At edge purlins I I I I I I I`I Panel
Panel Span Between Supports
Type Thickness
Inch mm 2 feet 3 feet 4 feet 5 feet
At internal purlins I A 031 0.8 50 psf 25 psf 10 psf
SunSky ,039 1.0 50 psf 30 psf 12.5 psf
ForFBC-approved installations,see SunSky Install Guide Form//505. .047 1 1.2 50 psf 35 psf 15 psf
031 0.8 50 psf 50 psf 35 psf 20 psf
SIDE LIGHT NOTES SunSky
rr Figure 14b .12rr .039 1.0 50 psf 50 psf 45 psf 25 psf
SunSky 9 Using SunSky in aside light application is similar to that of SunSky
At edge purlins
roof installation.This includes the selection and positioning of .063 1.5 50 psf 50 psf 1 50 psf 1 35 psf
fasteners. The dimensions specified do not supersede the requirements of local
construction codes.
Side light options include: Maximum recommended loads based on continuous beam setting,according
At internal purlins A.Multi-panel,single span D. Single panel,single span to allowed deflection of 1/20 of the span,and valid for mid span only.
sA _ _ _ �_ J►y_ B.Single panel,multi-span E. Framed side light,independent The mentioned load refers to both wind and snow loads and intended for
C.Multi-panel,multi-span on surrounding cladding type rooflights/wall lights only.
Force Engineering&Testing Inc.
19530 Ramblewood Drive
Humble,TX 77338
Product Evaluation Report
PALRAM AMERICAS, INC.
Sunsky 12"1.0 mm Polycarbonate Light Transmitting Roof Panel
Florida Product Approval # 11238.1 R3
Florida Building Code 2014
Per Rule 61G20-3
Method:2—B
Category:Structural Components
Subcategory:Roof Deck
Compliance Method:61G20-3.005(2)(b)
NON HVHZ
Product Manufacturer: FILA
COPY
Palram Americas,Inc.
9735 Commerce Circle
Kutztown,PA 19530
Engineer Evaluator:
Terrence E.Wolfe,P.E.
FBC ANE ID:1920
Validator:
Locke Bowden,P.E.,FL#49704
9450 Alysbury Place
Montgomery,AL 36117
Contents:
Evaluation Report Pages 1-4
C E N S_ �,o
�.
NO.47
STATE OF ;
FL#11238.1 R3 May 4, 2015
rForcengineering&Testing Inc.
19530 Ramblewood'Drive
Humble,TX 77338
Compliance Statement, The product as described in this report has demonstrated compliance with the
Florida Building Code 2014,Sections 1504.7,1709.2,2606,2609.
Product Description: Sunsky 12" Light Transmitting Roof Panel, 1.0 mm thick Polycarbonate, 1%"tall
ribs at 12" O.C., 36" Wide, through fastened structural roof panel. Structural
Application.
Panel Material/Standards: Material: Min.1.0 mm thick Polycarbonate.
Panel Dimension(s): Thickness: Min.1.0 mm
Width: 36"maximum coverage
Rib Height: 1-1/4"major rib at 12"O.C.
Panel Fastener: #12-14 x 1-1/4"HWH SD with 11/8"oversize bonded washer or approved equal
at 7"-5"-7"-5"-7" fastener pattern. Panel side laps fastened together w/%-x 1
%"Grommet at each support then 1'-3"O.C.
Corrosion Resistance:Per Florida Building Code 2014,Section 1506.6,1507.4.4
Substrate Description: Min.16 Ga.Steel Framing. Framing must be designed in accordance w/Florida
Building Code 2014.
Design Pressures:
Table"A"
Maximum Design Pressure: -27.5 psf +35.0 psf
Fastener Pattern: 7"-5"-7"-5"-7" 7--5"-7--5"-7-
Fastener Spacing: 5'-0"O.C. 5'-0"O.C.
'Design Pressure includes a Safety Factor=2.0.
N•C E, E.
D
C E N S�'!.t►,,i
No.4i
•a' STATE OF ;q
AZ 0 A 4,�.�
sur Armes i��E,s.• R
FL#11238.1 R3 May 4, 2015
rForceineering&Testing Inc.
19530 Ramblewood Drive.
Humble,TX 77338
Code Compliance: The product described herein has demonstrated compliance with
The Florida Building Code 2014,Section 1504.7,1709.2,2606,2609.
Evaluation Report Scope: The product evaluation is limited to compliance with the structural wind load
requirements of the Florida Building Code 2014,as relates to Rule 61G20-3.
Performance Standards: The product described herein has demonstrated compliance with:
■ ASTM E 1592-05
■ FM 4471-92
■ ASTM D 635-06
■ ASTM D 1929-96
■ ASTM E 84-09
Reference Data: 1. ASTM E 1592-01
Force Engineering&Testing,Inc.(FBC Organization#TST-5328)
Report No.273-0027T-08C,D
2. FM 4471-10,Section 4.4 Foot Traffic Resistance Test
Force Engineering&Testing,Inc.(FBC Organization#TST-5328)
Report No.273-0011T-12
3. ASTM D 635-98
SGS U.S.Testing Company Inc.
Report No.676900-02,Class CC2
4. ASTM D 1929-96
SGS U.S.Testing Company Inc.
Report No.528768,Flash Ignition 982°F,Self Ignition 1162°F
5. ASTM E 84-05
SGS U.S.Testing Company Inc.
Report No.676900-01,Smoke Developed Index 235,Flame Spread Index 15.
6. Certificate of Independence
By Terrence E.Wolfe,P.E.(No.44923)@ Force Engineering&Testing,Inc.
(FBC Organization#ANE ID:1920)
I
N•c E' Z.-W'p 410
CE iV
No.474 �=
a' STATE OF ;a
FL 4RI'D -4, -4*
sses,orpbda. 4%
VJ0A. 4e r 4r
mune '.4� 11 f 1 t���
FL#11238.1 R3
May 4, 2015
rFoorceineering&Testing Inc.
19530 Ramblewood Drive
Humble,TX 77338
Test Standard Equivalency: 1. The ASTM E 1592-01 test standard is equivalent to the ASTM E 1592-05 test
standard.
2. The FM 4471-10,Foot Traffic Resistance test standard is equivalent to the
FM 4471-92,Foot Traffic Resistance test standard.
3. See Letter of Equivalency for ASTM D635 from Architectural Testing,dated
March 14,2012.
4. See Letter of Equivalency for ASTM E84 from Architectural Testing,dated
May 4,2015.
Quality Assurance Entity: The manufacturer has established compliance of roof panel products in
accordance with the Florida Building Code and Rule 61G20-3.005(3)for
manufacturing under a quality assurance program audited by an approved
quality assurance entity.
Minimum Slope Range: Minimum Slope shall comply with Florida Building Code 2014,including Section
1507.4.2 and in accordance with Manufacturers recommendations. For slopes
less than 3:12,lap sealant must be used in the panel side laps.
Installation: Install per manufacturer's recommended details.
Panel Separation: Panels shall be separated from each other by a distance of not less than 4 ft.
measured in a horizontal plan unless the building meets one of the exceptions in
FBC 2014 Section 2609.2.
Area Limitations: See Table 2609.4(FBC 2014)
Panels Shall NOT be Installed in: Groups H,1-2,1-3(FBC 2014,Section 2609.1)
Shear Diaphragm: Shear diaphragm values are outside the scope of this report.
Design Procedure: Based on the dimensions of the structure,appropriate wind loads are
determined using Chapter 16 of the Florida Building Code 2014 for roof cladding
wind loads.These component wind loads for roof cladding are compared to the
allowable pressure listed above.The design professional shall select the
appropriate erection details to reference in his drawings for proper fastener
attachment to his structure and analyze the panel fasteners for pullout and
pullover.Support framing must be in compliance with Florida Building Code 2014
Chapter 22 for steel,and Chapter 16 for structural loading.
N•C E, .
D
•a' STATE OF :W
i
is. �.
saaar�a� ��E's•, ��'��
FU 11238.1 R3 May 4, 2015
SUNSKY 12" POLYCARBONATE PANEL.FASTENER LOCATIONS
1/4" x 1" GROMMET
® 1'-3". 2'-6..
BETWEEN SUPPORTS
#12-14,X 1 1/4" HWH
w/ 1 1/6" OVERSIZE BONDED-WASHER
CAT. ` aaeaaee+++i
+rye
L• V ♦�1 A
No 44923
E
C�
++,S/ONAL� ••'
DEC 06 2012
i •
Stock Profiles Basic Dlmenslons and Profile Illustrations
(IYPIC4NO*"Abld
+ —.36'Net Coverage Wtdth '
Sun5ky12" —t2'--' a
VAIJ
38'
$tme of Roadt
con. �,,•NCE F
A
No.44923 . •�
.0'
• S0 AN �
l`�tC
0
■■
40�00
■■
G U* 'Ifcoa t
SUPPLY & MANUFACTURING
Gulf Coast Supply & Mfg, LLC
4020 SW 449" St.
Horseshoe Beach, FL 32648
PH: (352) 498-0778
FX: (352) 498-7852
www.GulfCoastSupply.com
To Whom It May Concern:
Gulf Coast Supply & Mfg. LLC. approves the installation of Gulf Rib@ roofing
panels over one layer of shingles, as allowed for in "Florida Building Code
Section 1510 Reroofing, 1510.3 Recovering versus replacement".
Installation in this manner is approved by Gulf Coast Supply & Mfg as the
manufacturer, as required by the Florida Building Code. Decking must be
minimum 15/32" CDX plywood, and must be inspected to insure that it is
adequate as a base for additional roofing.
Jonathan Sherrill
President