EVALUATION REPORT
Owens Corning Evaluation Report 037940.02.12-R5
One Owens Corning Parkway FL10674-R10
Toledo,OH 43659 Date of Issuance:02/06/2012
Revision 5: 04/22/2015
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida.The documentation submitted has been reviewed by Robert Nieminen,P.E.for
use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described
herein have been evaluated for compliance with the 5th Edition(2014)Florida Building Code sections noted herein.
DESCRIPTION: Owens Corning Asphalt Roof Shingles
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this
Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the
referenced Quality Assurance documentation changes. Trinity)ERD requires a complete review of this Evaluation Report
relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "TrinitylERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its
distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 6.
Prepared by:
(,�'�=C�; .���^;' The facsimile seal appearing was authorized by Robert Nleminen,
Robert J.M.Nieminen,P.E. '%S� """�2's•�` P.E.on 04222015.This does not serve as an signed
anis,. / / H g
Florida Registration No.59166,Florida DCA ANE1983 document.Signed,sealed hardcopies have been transmitted to the
Product Approval Administrator and to the named client
CERTIFICATION OF INDEPENDENCE:
1. TrinitylERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinity l ERD is not owned,operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way,the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof,is/was used for permitting or design guidance unless retained
specifically for that purpose.
TRIN,ITYIERD
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: Asphalt Shingles
Compliance Statement: Owens Corning Asphalt Roof Shingles,as produced by Owens Corning,have demonstrated compliance
with the following sections of the Florida Building Code and Florida Building Code, Residential Volume through testing in
accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations/Conditions of
Use set forth herein.
2. STANDARDS:
Section Property Standard Year
1507.2.5,R905.2.4 Physical Properties ASTM D3462 2009
1507.2.7.1,R905.2.6.1 Wind Resistance ASTM D3161 2009
1507.2.7.1,R905.2.6.1 Wind Resistance ASTM D7158 2008
3. REFERENCES:
Kn!itf Examination Reference Date
UL LLC(CER9626) Physicals&Wind Resistance File R2453,Vol.3 02/15/2007
UL LLC(CER9626) Physicals&Wind Resistance 20120516-112453 05/16/2012
UL LLC(TST9628) Physical Properties 06CA20263 04/18/2006
UL LLC(TST9628) Wind Resistance 11CA34308 02/18/2012
UL LLC(TST9628) Physicals&Wind Resistance 4786093137 02/01/2014
UL LLC(TST9628) Wind Resistance 4786126532 02/10/2014
UL LLC(TST9628) Physical Properties Classification letter 02/13/2014
Miami-Dade(CER1592) FBC HVHZ Compliance Various NOAs Various
UL LLC (QUA9625) Quality Control Service Confirmation,R2453 Exp.08/20/2017
4. PRODUCT DESCRIPTION:
4.1 Asphalt Shingles:
4.1.1 Classic and Supreme'are fiberglass reinforced,3-tab asphalt roof shingles.
4.1.2 Berkshire are fiberglass reinforced,4-tab asphalt roof shingles.
4.1.3 Devonshire—are fiberglass reinforced,5-tab asphalt roof shingles.
4.1.4 Duration', TruDefinition" Duration', Duration' Premium Cool, TruDefinition® Duration' Designer Color Collection,
TruDefinition Oakridge,Oakridge and WeatherGuard'HP are fiberglass reinforced,laminated asphalt roof shingles.
4.2 Berkshire Hip & Ridge Shingles, High Ridge, Hip & Ridge with Sealant, WeatherGuard� HP Hip & Ridge Shingles,
ProEdge Hip & Ridge Shingles and DuraRidge'" Hip & Ridge Shingles are fiberglass reinforced, hip and ridge asphalt
roof shingles.
4.3 Starter Strip Plus and Starter Shingle Roll are starter strips for asphalt roof shingles.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the Designer of
Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or
design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in the HVHZ.
5.3 Fire Classification is not part of this Evaluation Report;refer to current Approved Roofing Materials Directory for fire
ratings of this product.
5.4 Wind Classification:
5.4.1 All Owens Corning shingles noted herein are Classified in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to
ASTM D3161,Class F and/or ASTM D7158,Class H,indicating the shingles are acceptable for us in all wind zones up to
Vasd=150 mph(V„it=194 mph). Refer to Section 6 for installation requirements to meet this wind rating.
5.4.2 All Owens Corning hip&ridge shingles and Starter Strip Plus noted herein are Classified in accordance with FBC Tables
1507.2.7.1 and R905.2.6.1 to ASTM D3161,Class F,indicating the shingles are acceptable for us in all wind zones up to
Vasd=150 mph(V„it=194 mph). Refer to Section 6 for installation requirements to meet this wind rating.
Exterior Research and Design,I.I.C. Evaluation Report 037940.02.12-RS
Certificate o/Authorization 119503 FL10674-R10
Revision S:04/22/2015
Page 2 of 6
S
ati0
;X"I TRI 1CP
ER
5.4.3 Classification by ASTM D7158 applies to exposure category B or C and a building height of 60 feet or less. Calculations
by a qualified design professional are required for conditions outside these limitations. Contact the shingle
manufacturer for data specific to each shingle.
5.4.4 Refer to Owens Corning published information on wind resistance and installation limitations.
5.5 All products in the roof assembly shall have quality assurance audit in accordance with the Florida Building Code and
F.A.C.Rule 61G20-3.
6. INSTALLATION:
6.1 Underlayment:
6.1.1 Underlayment shall be acceptable to Owens Corning and shall hold current Florida Statewide Product Approval,or be
Locally Approved per Rule 61G20-3,per FBC Sections 1507.2.3,1507.2.4 or R905.2.3.
6.2 Asphalt Shingles:
6.2.1 Installation of asphalt shingles shall comply with the manufacturer's current published instructions, using minimum
four(4)nails per shingle in accordance with FBC Sections 1507.2 or R905.2,with the following exceptions:
Y Berkshire shingles require minimum five(5)nails per shingle.
➢ WeatherGuard'HP shingles require minimum six(6)nails per shingle.
➢ Devonshire'"shingles require minimum six(6)nails per shingle.
Y Starter Strip Plus requires minimum five(5)nails per strip.
Refer to Owens Corning published information on wind resistance and installation limitations.
6.2.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC 1507.2.6 or
R905.2.5. Staples are not permitted.
6.2.4 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are required.
Contact the shingle manufacturer for details.
6.2.5 Minimum Nailing—Classic®&Supreme:
� e
Normal: Mansard.ErA para- Normal Mansard or Area pare
Wind Areas High Windaos-y Wind Area9 High Wind darvanes y
Area pare vientoe norrnalea.:Areas ertes Area para vientas normales' Areas vientos fuertes:yr {A)—r �prye3" r I-
12 521
6,Exposure b 5/8"Exposure
Exposition Expo'sicidn
6.2.6 Minimum Nailing—Berkshire®:
Seakiiit_scrip:.. E,aai�ni strip
to t ra da'sepadar; to 1rra da seladx
$1" 9w fl yi 8 dt k.yf $.Yl' $yt' $V,
L.
� dsphali ropfingcemant
ceirmto a teebo da asfaffo
Exterior Research and Design,I.I.C. Evaluation Report 037940.02.12-RS
Certificate of Authorization 119503 FL10674-R10
Revision 5:04/22/2015
Page 3 of 6
TRI NIT' y ERP
6.2.7 Minimum Nailing—Devonshire'"':
Nails
a,
4—
S-_ yIII
t:� J_
s
Nails Ten 1"Spots of Asphalt Roof Cement
6.2.8 Minimum Nailing—Duration®,TruDefinition® Duration, Duration®Premium Cool&TruDefinition®Duration Designer
Color Collection:
4 wilfpaiiorn ii Nail 4 bf"WarMapswv
atto Www WOW
EspIrw d.0 4 claws Pattern tip d ml O-L
2 *
4 twig.
Z7
sur 14 IV _314 44�:_f Vit, Siff diale
LiE
tpmie
Naas SW 6ptire
!;6,pufg:doexposlomn 'VOYM 6UPUIO.da expaskim
v4v,
61A pufg.do exposid6n Clavas 54 paig.de exmsid&
6.2.9 Minimum Nailing—TruDefinition"Oakridgel,Oakridge®:
4'NaliPAt6rn 6"Nall all pattern
Esquom6,6a 4 elands Esouama Von G elavos
7
55fw�Fxposure
Nails S W Expo.!
Nailsi� de1'SigOk, Exposicoftde"JOU4 SSX,Exposue
clavos 6 5/9'Ekposum�
aqvS.1con dt 6 wpulg. Evpo.466ri do 55/e pufa
6.2.10 Minimum Nailing—WeatherGuard"HP:
In' SIOIOW
2"
mal
Fwati'm Twomb via Um
Exterior Research and Design,LLC. Evaluation Report 037940.02.12-RS
Certificate of Authorization#9503 FL10674-R10
Revision 5:04/22/2015
Page 4 of 6
' ERCP
I I
6.3 Hip&Ridge Shingles:
6.3.1 Installation of Berkshire® Hip and Ridge Shingles, High Ridge, Hip & Ridge with Sealant, WeatherGuard® HP Hip and
Ridge Shingles and ProEdge Hip&Ridge Shingles shall comply with the manufacturer's current published instructions,
using four(4)nails per shingle. Installation of DuraRidge'"Hip&Ridge Shingles shall comply with the manufacturer's
current published instructions,using two(2)nails per shingle. Refer to Owens Corning published information on wind
resistance and installation limitations,including the use of hand-sealing for wind warranties.
6.3.2 Fasteners shall be in accordance with the manufacturer's published requirements,but not less than FBC 1507.2.6 or
R905.2.5. Staples are not permitted.
6.3.3 Minimum Nailing—Berkshire®Hip&Ridge and High Ridge:
Fig;-1 v Fig.2
a—.PtevailMryWnd ——������--
.DlieGlan- � A TUUVfattl�. StdOViecti
halls --_.�— \YA=�—t Neils. NKIs i
o R+ ...._... 111111
� �2".......'� (±
Pi. j3
9" EI
6.3.4 Minimum Nailing—Hip&Ridge with Sealant:
ttem Fig.. s.l�i �Wind l"a`'6niti� P�Itturrrr
Marls). . .
rrim Shingle
and''DiscardIf
„
C" S S lanast rip 124,
Stoning.,&I I VEXP69ure
Drstanc�
6.3.5 Minimum Nailing—WeatherGuard®HP Hip and Ridge:
Fig.C Hip&Ridge Shingle Fastening.
Fig:A 4 4 Top vhvr
Pravapiny!nMtl �✓'� .
'�—Dlroctlen .l��� F\
Hells..`”—"'_"—_.
Naps Naha
2"
—
..._.___
A 1':
`............._.._ y r _
- E=paa'aro -
1
Exterior Research and Design,I.I.C. Evaluation Report 037940.02.12-115
Certificate of Authorization#9503 FL10674-R30
Revision 5:04/22/2015
Page 5 of 6
\4 TRINTY 1 ERD
i
6.3.6 Minimum Nailing-ProEdge Hip&Ridge Shingles:
Prevailing Standard
Wind DirectionFastening
Sealant Strip . Pattern
6'Exposure
12° Sealant
Fasten 7'h° 7'Jz" S„Expo r e
CoverExpasad l
F==ad
Rauf Cement
6.3.7 Minimum Nailing—DuraRidge'"Hip&Ridge Shingles:
Note: The drawings below pertain to minimum, as-tested attachment requirements. Refer to Owens Corning
published installation instructions for their minimum requirements.
Ftu�aiing Wud Dlraedm Top View
°—Direaiondxntranta iszvit Vista supporter I
Diracd&i dal vionCa pr,vio iiiranto
NA
t€aih---•--.,^m„--�� ,� `�� �,1 '� Ormns Gorrmreg Sar�dail � caw
I
i Er A
'_ f I• f + cla�
A;
UU
7. LABELING:
7.1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein.
7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC Table
1507.2.7.1/R905.2.6.1.
H. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product.
9. MANUFACTURING PLANTS:
Contact the named QA entity for information on which plants produce products covered by Florida Rule 9N-3 QA requirements.
10. QUALITY ASSURANCE ENTITY:
UL LLC–QUA9625;(414)248-6409;karen.buchmann@ul.com
END OF EVALUATION REPORT-