October 5,2015
Re: ' Window Replacement
10201) South Ocean Dr.
Jensen Beach,FL 34957
To Whom It May Concern:
Our office hr calculated �
thererequired design pressure in accordance with ASCE 7-10 for
q
a replacement of the roll up door at the above referenced address.
Wind speed: V,lt: 165mph,V.d: 124 mph
Exposure:. D
Enclosure T Enclosed
Window Size: Per Attached Schedule(same size as windows removed).
Quantity of Doors: 1
Location: I Zone 4 (Per Attached Sketch)
Required De ign Pressure(Zone 4): +48.8/-52.9 PSF
Windows to be installed shall be equal to,or exceed the required design pressures as
listed above. All installations shall be in accordance with FBC 2014 and manufacturer's
installation instructions.
Proposed Windows: PGT SH-200 NOA#15-0528.22 (+55.0/-63.8 PSF).
Thank you four your attention to this matter.
Submitted b :
PAUL WELCH INV.
i
0 Paul Welch,P.E
Reg.No 29945
Attached: -- I Product Approval'Affid.
Area of Work Plan
�OF ?7
PAUL WELCH INC.
Mechanical * Electrical * Civil Engineering
1984 S.W. Biltmore St. Suite#114
Port Saint Lucie,FL 34984
Phone(772)785 -9888
Email pwelchinc@uaol.com
Window Replacement
10200 South Ocean Dr.
Jensen Beach,FL 34957
13 Sm Area By calk
XOPR XBS1=1154
•i.
12 XOPR-96
W
I
4
CWRINDOW REPLACEMENT#1 WINDOW REPLACEMENT#2
(2)—36"WIDE X 38"HIGH (1)—36"WIDE X 38"HIGH
S.H. WINDOW S.H. WINDOW
i
AREA OF WORK PLAN nts... +—NORTH
i
NOTE:RE-USE EXISTING ACCORDIAN SMYITERS AT WINDOW
REPLACEMENT.
Paul Welch,P.E. I ��
Reg.No 29945 j
October 5,2415 1
Planning& Development Services Department
Building & Regulations Division
Product Review Affidavit
Building Permit# Owners NameApplicant:
Product Openingf Design Product Rated Manufacturer Model Number Product Approval Glass Method of Attachment
Pressures Design Pressure Number Tvue
Windows
Ns '14tt x Isle MSN.Et.^'c�EQ u�rtz.AcQ�.a
6AiiNlena
MEE.'[ttaL t--A.4 L, s6ND ttQC .
Fixed Glass
Block Glass
Skylights
Sliding Glass Doors
Swing Type Doors
French Doors
oarage Doors
Hurricane Protection
Root Ventilation r
Mut L►o+l 1rc x0.125 WcxA F -1SAv% Mites, Zv—kegEj> -&MC>P55
+48.8/-52,9 +/_84,aJ V6T �` �4 -fi e LI.tP
I have reviewed the above components or cladding and I have approved their use in this structure. These ptoducts provide adequate resistance to the
wind loads and forces specified by current code provisions.
Name:
PAUL WELCH P.E. , Signature: W44% fifi}
Design Profs PAUL WELCH P.E. . Cert.No. 29945 Date:
0
-n
W