Mechanical * Electrical * Civil Engineering
1984 S.W.Biltmore St. Suite#114
Port Saint Lucie,FL 34984
Phone(772)785 -9888
October 13 2015
Email pwelchinc@aol.com
ILE
O
Re: Door Replacement
3206 S Lakeview Cir. 1101
Fort Pierce,FL
To Whom It May Concern:
Our office has calculated the required design pressure in accordance with ASCE 7-10 for
a replacement of the doors at the above referenced address.
Wind speed: V,At: 165mph,Vim: 124 mph
Exposure: D
Enclosure Type: Enclosed
Door Size: 8' X 6'-8" Sliding Glass Door
Quantity of Doors: 5
Location: Zone 5 (Per Attached Sketch)
Required Design Pressure(Zone 5): +48.5/-64.8 PSF Worst Case
Doors to be installed shall be equal to,or exceed the required design pressures as listed
above. All installations shall be in accordance with FBC 2014 and manufacturer's
installation instructions.
Proposed Door: PGT SGD-2500 NOA#15-0609.10 (+65.0/-65.0 PSF).
Thank you for your attention to this matter.
Submitted by:
PAUL WELCH INC..
Paul Welch,P.E. i
Reg. No 29945
Attached: Product Approval Affid.
Area of Work Plan